UniPOS 7000-1MC Addressable-Conventional Modular System Panel Owner’s Manual
- July 22, 2024
- Unipos
Table of Contents
UniPOS 7000-1MC Addressable-Conventional Modular System Panel
Specifications
- Model: 7000-1MC
- Certification: Certified to EN54-2/4/13
- Power Supply Unit:
- Current Consumption at 230V AC: 150 devices, 1,500m distance
- Current Consumption at 120V AC: 300mA / 24V DC
- Cable Connection: DIN Rail two-wire shielded
- Mains Power Fuse: 27.6 +1/-8V DC
- User Output: 1 pcs
- Battery Capacity: Not specified
- Loop Module Connecting Type: Base-Loop DIN module is mandatory for panel 7000-1MC
- Connecting Line to Loop: RS485 for connection with panel repeater
- Maximum Resistance of a Loop: Not specified
- Maximum Loop Consumption Power Supply: Not specified
- Number of Modules per Panel: Not specified
Product Usage Instructions
Panel Information
- The Addressable-Conventional Modular System Panel 7000-1MC is a non-networkable/stand-alone panel that is auto-configuring and easy to use. The Base-Loop DIN module is mandatory for the panel’s operation.
Connector Information
- The module includes detachable and standard connectors for interface connection. Use RS485 for connection with the panel repeater.
USB Host
- You can upload/download panel configuration and update panel firmware using the USB host. This functionality requires access to level 3.
FAQ
Q: What certification standards does the 7000-1MC panel meet?
A: The panel is certified to EN54-2/4/13 standards.
Q: Can I connect multiple modules to the panel?
A: The number of modules per panel is not specified in the manual. Please consult the manufacturer for further information.
Q: How do I update the panel firmware?
A: You can update the panel firmware by using the USB host with access level 3 permissions.
- The Addressable-Conventional Modular System Panel 7000-1MC is designed to satisfy a professional solution enhancement.
- Installation Procedure with set-up flexibility
- One Loop Addressable
- Fully Compatible with the EN54 Standard
- Up to 40 Zone Conventional Detection
- Using DIN8CL 8 Zone Modules
- Up to 3 repeater panels
- Certified to EN54-2/4/13
Technical Features
Power Supply Unit
Current Consumption at 230V AC| 0.8A
Current Consumption at 120V AC| 1.6A
Cable Connection| min 1.5mm²
Mains Power Fuse| 4A
User Output| 2 x 700mA at 24V DC (max)
Battery Capacity| 2 x 12AH at 12V
Loop Module
Connecting Type| DIN Rail
Connecting Line to Loop| two-wire shielded
Maximum Resistance of a Loop| 20Ω (-wire)
| 150 devices, 1,500m distance – 40Ω (+wire)
Maximum Loop Consumption| 300mA / 24V DC
Power Supply (ensured PSU Module)| 27.6 +1/-8V DC
Number of Modules per Panel| 1 pcs
Panel Information
- Non-networkable / stand-alone
- Auto configuring, easy to use
- Base-Loop DIN module is mandatory for panel 7000-1MC
- The module includes a detachable and standard connector for interface connection
- RS485 for connection with panel repeater
- USB host – upload/download panel configuration (and update panel firmware) (requires access level 3)
- 1 Efr. Nikola Paskalev Str, Mladost 1
- Sofia 1748, Bulgaria
- Telephone: +359 2 97 439 25
- Email: sales@unipos-bg.com
- Website:www.unipos-bg.com