OONO F-1063 Automatic Transfer Switch AC 120V Instruction Manual

May 15, 2024
OONO

OONO logoCZH-LABS.com OONO F-1063 Automatic Transfer Switch
AC 120VManual and Automatic Transfer Switch
AC 120V 15 Amp
Model: F-1063

FEATURES:

  • OONO F-1063 Manual and automatic transfer switch, an easy to mount 15 Amp inline transfer module provides switching between AC IN1 (Inverter or Generator) and AC IN2 (Utility or Shore Power) AC source. With input and output and switch status indicators. It has a manual power switch function, which can quickly control the on and off of the output. With the function of automatic and manual working mode, the product can work in automatic mode, and the input source can also be selected manually.
  • Automatic mode (MODE switch set to AUTO): when AC IN2 (Utility or Shore Power) is powered, the load power will be switched to AC IN2, when AC IN2 is powered off, the load power will be switched to AC IN1 (Inverter or Generator). Manual mode (MODE switch set to SW1 or SW2): You can manually select AC IN1 (Inverter or Generator) or AC IN2 (Utility or Shore Power) as the input source according to your needs.
  • Operating voltage AC 90 to 135V 50/60Hz. Maximum current 15 Amp. Transfer time less than 30mS (0.03 second), for most smart devices or computers, the switching action of 30mS time will not affect their normal operation.
  • Internal four high power SPST relays switch design, effectively avoid the problem of DPDT relay high inductive load arcing. Live and Neutral wire are switched at the same time. The Ground wires of the two inputs and output are connected together  internally and will not follow the switch on and off .
  • IP66 waterproof level design, suitable for indoor or outdoor use. AC IN1, AC IN2 and AC OUT cables: Length 19 inches (0.5 meter), 14AWG (2.08 square millimeter) x 3 cores.

SPECIFICATIONS:

  • Input or Output Voltage: ………………………… AC 90 – 135V 50/60Hz.
  • Maximum Current: ……………………………….. 15 Amp.
  • Transfer Time: …………………………………….. 30 millisecond.
  • Input / Output Cable Length: …………………… 19 inches (0.5 meter).
  • Enclosure Waterproof Rating: …………………. IP66.

INPUT / OUTPUT SWITCH STATUS:

MODE| AC IN1
(Inverter or Generator)| AC 1N2
(Utility or Shore Power)| AC OUTPUT
---|---|---|---
AUTO| Powered| Powered| Powered from AC IN2
Powered| No Powered| Powered from AC IN1
No Powered| Powered| Powered from AC 1N2
No Powered| No Powered| Output No Powered
Manual Mode – SW 1| Powered| Powered| Powered from AC IN1
Powered| No Powered| Powered from AC IN1
No Powered| Powered| Output No Powered
No Powered| No Powered| Output No Powered
Manual Mode – SW 2| Powered| Powered| Powered from AC 1N2
Powered| No Powered| Output No Powered
No Powered| Powered| Powered from AC IN2
No Powered| No Powered| Output No Powered

CABLE CONNECTS:

OONO F-1063 Automatic Transfer Switch AC 120V - CABLE
CONNECTS

AC IN1: 14AWG (2.08 square millimeter) x 3 cores, recommended connect Inverter or Generator.
AC IN2: 14AWG (2.08 square millimeter) x 3 cores, recommended connect Utility or Shore Power.
AC OUT: 14AWG (2.08 square millimeter) x 3 cores, power output, connect to Load.
Cables Color: Black – AC Live Wire, White – AC Neutral Wire, Green – Ground Wire

INTERNAL SIMPLE SCHEMATIC:

OONO F-1063 Automatic Transfer Switch AC 120V - INTERNAL SIMPLE
SCHEMATIC

DIMENSIONS:

OONO F-1063 Automatic Transfer Switch AC 120V -
DIMENSIONS IMPORTANT

  • THIS MODULE OPERATES ON A HAZARDOUS VOLTAGE !
  • DISCONNECT AC POWER DURING INSTALLATION !
  • Installation must be done according to local regulations and standards. If any doubt, consult a licensed technician.
  • This module is not suited for portable applications.

DANGER !!!

  • Do not open the housing in order to avoid the risk of electroshocks.
  • This module operates on a dangerous AC voltage !
  • All repairs should be executed by qualified technicians.

SAFETY INSTRUCTIONS !!!

  • Do not attempt to disassemble the unit as it does not contain any parts that are to be serviced by the user. (Tampering voids warranty)
  • Do not touch unused terminals when the module is connected to the AC power.
  • Handle the module gently and carefully. Dropping it can damage the circuit board and case.
  • Never exceed the protection limit values indicated in the specifications.
  • As safety requirement vary, please check with your local authorities.
  • Disconnect the module from the AC power before connecting new devices.
  • Wipe the device with a dry and clean cloth. Do not use detergents or other liquids that may damage the housing.
  • Keep the device away from children.
  • Facilitate the operation of the device by familiarising yourself with its adjustments and indications.
  • CZH-LABS and Eelectronics-Salon modules are not suitable for use or as part of life support systems, or systems that might create hazardous situations of kind.