MIGHTY THERM2 MT2V Volume Water Heater Instruction Manual
- June 17, 2024
- MIGHTY THERM2
Table of Contents
- MIGHTY THERM2 MT2V Volume Water Heater
- Specifications
- Product Usage Instructions
- FAQs
- General Information
- Venting and Combustion Air
- Gas Supply and Piping
- Water Connections
- Electrical Connections
- 1 6
- Operating Instructions
- Maintenance
- Trouble Shooting
- Replacement Parts
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
MIGHTY THERM2 MT2V Volume Water Heater
Specifications
- Model: Hydronic Boiler MT2H, Volume Water Heater MT2V
- Manufacturer: LAARS Heating Systems
- Document: 1211M
Product Usage Instructions
Section 1: General Information
This manual provides information necessary for the installation, operation,
and maintenance of the Laars Heating Systems Mighty
Therm2 commercial hydronic boilers and volume water heaters. Read this manual
carefully before installation.
All application and installation procedures should be reviewed completely before proceeding with the installation. Consult the factory, or local factory representative, with any issues or questions regarding this equipment. Experience has shown that most operating issues are caused by improper installation.
1.A Introduction
In the Commonwealth of Massachusetts, this unit must be installed by a licensed plumber or gas fitter.
Section 3: Gas Supply and Piping
Ensure proper gas supply and piping according to the guidelines provided in section 3.A of the manual.
Section 4: Water Connections
For boilers, follow the instructions for heating system piping, cold water make-up, water flow requirements, and freeze protection as outlined in section 4.A of the manual.
Section 5: Electrical Connections
Connect the main power following the instructions in section 5.A. If needed, change from a single circuit to two circuits as described in section 5.A.1. Ensure proper field wiring and external staging control wiring as per sections 5.B and 5.C.
FAQs
- Q: What should I do if I encounter operating issues with the Mighty Therm2?
- A: Operating issues are often caused by improper installation. Ensure that all installation procedures are followed correctly and consult the factory or local representative for assistance if needed.
“`
Installation and Operation Instructions
Document 1211M
Installation and Operation Instructions for
MIGHTY THERM2®
Hydronic Boiler
Model MT2H
Volume Water Heater
Model MT2V
Sizes 5002000 MBTU/h
FOR YOUR SAFETY: This product must be installed and serviced by a professional service technician, qualified in hot water boiler installation and maintenance. Improper installation and/or operation could create carbon monoxide gas in flue gases which could cause serious injury, property damage, or death. Improper installation and/or operation will void the warranty. For indoor installations, as an additional measure of safety, Laars strongly recommends installation of suitable Carbon Monoxide detectors in the vicinity of this appliance and in any adjacent occupied spaces.
WARNING
If the information in this manual is not followed exactly, a fire or explosion
may result causing property damage, personal injury or loss of life.
Do not store or use gasoline or other flammable vapors and liquids in the
vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS · Do not try to light any appliance. · Do not
touch any electrical switch; do not use
any phone in your building. · Immediately call your gas supplier from a
nearby phone. Follow the gas supplier’s instructions. · If you cannot reach
your gas supplier, call the fire department. Installation and service must be
performed by a qualified installer, service agency, or gas supplier.
LAARS Heating Systems
General Information
USING THIS MANUAL Because these Boilers and Water Heaters are identical
appliances, with the exception of materials of manufacture, labels and
ultimate use and application, this manual provides information for the proper
installation, operation and maintenance of both products. Where differences
exist between their application and their operation, the sections pertinent to
only one or the other will be so identified.
In the Commonwealth of Massachusetts, this unit must be installed by a
licensed plumber or gas fitter.
1.A Introduction
This manual provides information necessary for the installation, operation,
and maintenance of the Laars Heating Systems Mighty Therm2 commercial hydronic
boilers and volume water heaters. Read this manual carefully before
installation.
All application and installation procedures should be reviewed completely
before proceeding with the installation. Consult the factory, or local factory
representative, with any issues or questions regarding this equipment.
Experience has shown that most operating issues are caused by improper
installation.
The Mighty Therm2 is protected against over pressurization. A pressure relief
valve is fitted to all units. It is installed on the outlet header, at the
water outlet of the unit
NOTE: Throughout the content of this
manual, the Mighty Therm2 will be referred to
as a `unit’.
unit = MightyTherm2
1.B Warranty
Laars Heating Systems Mighty Therm2s are covered by a limited warranty. Owners
should submit online warranty registration at www.Laars.com.
All warranty claims must be made to an authorized Laars Heating Systems
representative, directly to Customer Service, or online at www.Laars.com.
Claims must include the serial number and model number (this information can
be found on the rating plate), installation date, and name of the installer.
Shipping costs are not included in the warranty
coverage.
Some accessory items are shipped in separate packages. Verify receipt of all
packages listed on
the packing slip. Inspect everything for damage immediately upon delivery, and
advise the carrier of any shortages or damage. Any such claims should be filed
with the carrier. The carrier, not the shipper, is responsible for shortages
and damage to the shipment whether visible or concealed.
GAS
INLET
VENT
GAS
PUMP
The Pump and the Hydronic Supply/Return are reversible.
HYDRONIC SUPPLY AND RETURN
Page 6
1.C Model Identification (Model Nomenclature)
Consult the rating plate on the unit. The following information describes the
model number structure.
1-3 Model Series Designation M T 2 = Mighty Therm2
4 Usage H = Hydronic V = Volume Water
5-8 Size 0 5 0 0 = 500,000 BTU/h input 0 7 5 0 = 750,000 BTU/h input 1 0 0 0 =
999,000 BTU/h input 1 2 5 0 = 1,250,000 BTU/h input 1 5 0 0 = 1,500,000 BTU/h
input 1 7 5 0 = 1,750,000 BTU/h input 2 0 0 0 = 1,999,000 BTU/h input
9 Fuel N = Natural Gas P = Propane
10 Altitude A = 010,000 feet
11 Location C = Indoor and Outdoor
LAARS Heating Systems
12 Firing Mode K = Two-stage
13 Revision 1 = First version of design
14 Heat Exchanger B = Glass-lined cast iron / copper / bronze trim (std. on
water heaters) C = Glass-lined cast iron / copper (std. on boilers, n/a on
water heaters) N = Glass-lined cast iron / cupro-nickel (n/a on water heaters)
P = Glass-lined cast iron / cu-nickel / bronze trim
15 Option Code X = Standard unit J = CSD-1, FM, IRI, IL
16 Pump Options X = No Pump H = Pump mounted MT2V, TACO, hard water pump N =
Pump mounted (any), TACO, normal water pump S = Pump mounted MT2V, TACO, soft
water pump
1 2 3
4
5 67 8
9
10
11
12
13
14
MT 2
A
C
K
1
15
16
SERIES M T 2
USAGE H – HYDRONIC V – VOLUME WATER
SIZE 0 5 0 0 0 7 5 0 1 0 0 0 1 2 5 0 1 5 0 0 1 7 5 0 2 0 0 0
ALTITUDE A – 0′ 10,000′
FIRING MODE
K – 2-Stage
FUEL N – NATURAL P – PROPANE
LOCATION
C – INDOOR/ OUTDOOR
REVISION
1 – FIRST REV
HEAT EXCHANGER
B – GLASS-LINED CAST IRON/ COPP/BRZ TRIM (std.MT2V)
C – GLASS-LINED CASTIRON/ COPP. (std.MT2H, n/a MT2V)
N – GLASS-LINED CAST IRON/ CU-NICKEL (n/a MT2V)
P – GLASS-LINED CAST IRON / CU-NICKEL, BRZ TRIM
HLW STAMP (MT2V only) 2 – GLASS-LINED CAST IRON/
COPPER / BRZ TRIM
5 – GLASS-LINED CAST IRON/ CU-NICKEL / BRZ TRIM
OPTIONS CODE
X – STD
J – CSD-1, GAP, FM
PUMP OPTIONS
X – NO PUMP
H – PUMP MOUNTED TACO, HARD WATER (MT2V)
N – PUMP MOUNTED, TACO, NORMAL WATER (MT2V, MT2H)
S – PUMP MTD, TACO SOFT WATER PUMP (MT2V)
MIGHTY THERM2 Commercial Boilers and Volume Water Heaters
Page 7
1.D Safety Notes
Safety notes are used throughout this manual to bring attention to the
presence of hazards with various risk levels and to offer important
information concerning the life of this product. There are 3 basic types.
1
WARNING
Indicates an imminently hazardous situation which, if not
avoided, can or will result in death or serious injury and can
or will result in catastrophic property damage.
2
CAUTION
Indicates a potentially hazardous situation which, if not avoided, may result in moderate injury and/or property damage.
3 NOTE:
Indicates instructions that are important to that topic but not related to personal injury or property damage.
WARNING
· Water temperature over 125°F (52°C) can cause severe burns instantly or
death from scalds.
· Children, disabled and elderly are at highest risk of being scalded.
· See instruction manual before setting temperature at the unit.
· Feel water before bathing or showering.
· If this unit is used to produce water that could scald if too hot, such as
domestic hot water use, adjust the outlet control (limit) or use temperature
limiting valves to obtain a maximum water temperature of 125°F (52°C).
WARNING
Fire or Explosion Hazard Improper configuration can cause fuel buildup and
explosion. Improper user operation may result in property loss, severe
physical injury, or death.
Any change to safety-related configuration parameters must only be done by
experienced and/or licensed burner/boiler operators and mechanics. Should
overheating occur or the gas supply fails to shut off, turn off the manual gas
control valve to the appliance.
If any odor of gas is detected, or if the gas burner does not appear to be
functioning in a normal manner, close the main gas shutoff valve. Do not shut
off the power switch. Contact your heating contractor, gas company, or factory
representative.
AVERTISSEMENT
En cas de surchauffe ou si I’alimentation en gaz ne s’arrête pas, fermez.
WARNING
This unit must be installed in accordance with the procedures detailed in this
manual, or the manufacturers warranty will be voided. The installation must
conform to the requirements of the local jurisdiction having authority, and,
in the United States, to the latest edition of the National Fuel Gas Code,
ANSI Z223.1/NFPA54. In Canada, the installation must conform to the latest
edition of CSA B149.1 Natural Gas and Propane Gas Installation Code, and/or
local codes. Where required by the authority having jurisdiction, the
installation of these units must conform to the Standard for Controls and
Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1. Any
modifications to the boiler, its gas controls, or wiring may void the
warranty. If field conditions require modifications, consult the factory
representative before initiating such modifications.
WARNING
Carbon Monoxide Hazard
This product burns gas to produce heat. The appliance must be properly
installed, operated, and maintained to avoid exposure to appreciable levels of
carbon monoxide.
The installer must verify that at least one carbon monoxide alarm has been
installed within a residential living space or home following the alarm
manufacturer’s instructions and applicable local codes before putting the
appliance into operation. It is important for carbon monoxide alarms to be
installed, maintained, and replaced following the alarm manufacturer’s
instructions and applicable local codes.
AVERTISSEMENT
L’installateur est tenu de vérifier qu’au moins une alarme de détection de
monoxyde de carbone soit installée dans un espace résidentiel ou dans un
domicile conformément aux directives du fabricant de l’alarme et aux codes
locaux applicables avant de mettre l’appareil en service.
Page 8
LAARS Heating Systems
WARNING
Electrical Shock Hazard
Electrical shock can cause severe injury, death or property damage. Disconnect
the power supply before beginning installation or changing the wiring to
prevent electrical shock or damage to the equipment. It may be necessary to
turn off more than one power supply to disconnect.
All electrical wiring is to be done in accordance with local codes, or in the
absence of local codes, with: 1) The National Electrical Code ANSI/NFPA No. 70
– latest Edition, or 2) CSA STD. C22.1 “Canadian Electrical Code – Part 1.”
This appliance must be electrically grounded in accordance with these codes.
WARNING
The Repair Parts list designates parts that contain refractory ceramic fibers
(RCF). RCF has been classified as a possible human carcinogen. When exposed to
temperatures above 180ºF, such as during direct flame contact, RCF changes
into crystalline silica, a known carcinogen. When disturbed as a result of
servicing or repair, these substances become airborne and, if inhaled, may be
hazardous to your health.
Do not remove or replace RCF parts or attempt any service or repair work
involving RCF without wearing the following protective gear:
1. A National Institute for Occupational Safety and Health (NIOSH) approved
respirator.
2. Long sleeved, loose fitting clothing.
3. Gloves.
4. Eye Protection.
CAUTION
CO needs to be less than 150 ppm.
ATTENTION Le CO doit être inférieur à 150 ppm.
NOTE: All installations must be made in accordance with 1) American National
Standard Z223.1/NFPA54-Latest Edition “National Fuel Gas Code” or 2) CSA
B149.1 “Natural Gas and Propane Installation Code” or in Canada reference the
B149.1 latest edition and with the requirement of the local utility or other
authorities having jurisdiction. Such applicable requirements take precedence
over the general instructions contained herein. All electrical wiring is to be
done in accordance with the local codes, or in the absence of local codes,
with: 1) The National Electrical Code ANSI/NFPA No. 70-latest Edition, or 2)
CSA STD. C22.1 “Canadian Electrical Code – Part 1”. This appliance must be
electrically grounded in accordance with these codes.
NOTE: A pressure relief valve is included with each unit and must be installed
prior to filling the system.
WARNING
CANCER AND REPRODUCTIVE HARM. WWW.P65WARNINGS.CA.GOV.
AS REQUIRED BY THE STATE OF CALIFORNIA PROPOSITION 65.
CAUTION
The supply voltage to this unit must not be disengaged, except for service or
isolation, or unless otherwise instructed by procedures outlined in this
manual. To signal a call for heat, use the correct terminals as instructed in
the Electrical Connections Section of this manual.
MIGHTY THERM2 Commercial Boilers and Volume Water Heaters
Page 9
1.E Locating the unit
This unit should be located to provide clearances on all sides for maintenance
and inspection. It should not be located in an area where leakage of any
connections will result in damage to the area adjacent to the unit or to lower
floors of the structure.
When such a location is not available, it is recommended that a suitable drain
pan, adequately drained, be installed under the unit.
This unit is design certified by CSA-International for installation on
combustible flooring; in basements; in closets, utility rooms or alcoves.
These units must never be installed on carpeting. The location for the unit
should be chosen with regard to the vent pipe lengths and external plumbing.
The unit shall be installed such that the gas ignition system components are
protected from water (dripping, spraying, rain, etc.) during operation and
service (circulator replacement, control replacement, etc.). When vented
vertically, this unit must be located as close as practical to a chimney or
outside wall. If the vent terminal and/or combustion air terminal terminate
through a wall, and there is potential for snow accumulation in the local
area, both terminals should be installed at an appropriate level above grade.
The dimensions and requirements that are shown in Table 1 should be met when
choosing the locations for the unit.
1.F Locating Pump-Mounted Water Heater with Respect to Storage Tank(s)
For best results, a pump-mounted water heating unit should be located within
15 feet (4.6m) of the storage tank(s). The pump is sized for 30 feet (9.1m) of
piping.
If the unit must be installed with longer piping runs, then larger diameter
pipe or tubing shall be used. Consult the factory for assistance.
1.G Locating Pump-Mounted Boiler with Respect to Return/Supply Header
For the best results, a pump-mounted boiler should be located within 15 feet
(4.6m) of the supply and return headers. The pump is sized for 30 feet (9.1m)
of piping.
If the unit must be installed with longer piping runs, then larger diameter
tubing shall be used. Consult the factory for assistance.
1.H Locating the Unit for Correct Horizontal Vent/Ducted Air Distance from
Outside Wall
The forced draft combustion air blower/blowers in the unit has/have sufficient
power to pull air and vent properly when the following guidelines for
horizontal air and vent are followed (see Table 2).
SURFACE
REQUIRED
CLEARANCE FROM
COMBUSTIBLE MATERIAL
inches
cm
RECOMMENDED
SERVICE ACCESS
CLEARANCE
inches
cm
Left Side Right Side
1
2.5
1
2.5
24
61
24
61
Top
1
2.5
12
30
Back
1
2.5
12 30**
Front
1
2.5
36
91
Vertical
(Category 1)
6*
15.2*
Vent Horizontal
(Category 3)
per UL1738 venting system supplier’s
Vent
instructions
*1″ (2.5cm) when b-vent is used. **When vent and/or combustion air connects to the back, recommended clearance is 36″ (91cm).
Table 1. Clearances
NOTE: The vent collar size is larger than the size of the vent pipe that can
be used. Vent collar size and horizontal pipe diameters can be found in Table
2. The larger vent collar size is to accommodate Category I
(vertical) vent systems.
NOTE: When located on the same wall, the combustion air intake terminal must
be installed a minimum of 12″ (30cm) below the exhaust vent terminal and
separated by a minimum of 36 inches
(91cm) horizontally.
The air intake terminal must be installed high enough to avoid blockage from
snow, leaves and other debris.
Page 10
1.I Dimensions
GAS
LAARS Heating Systems
Unit
Size
A
B
C
500
33¾ 85
16¾ 43
6½ 17
750
45¾ 116
22¾ 53
6½ 17
1000 57¾ 147
28¾ 73
6½ 17
1250 68¼ 173
34 87 10¼ 26
1500 78¾ 200
39½ 100 10¼ 26
1750 89¼ 227
44¾ 113 10¼ 26
2000 99¾ 253
49¾ 127 10¼ 26
NOTES: 1. Add 55 lbs (25kg) for pump-mounted units. Dimensions in inches cm.
Figure 1. Dimensional Data (standard units).
D 10 25 10 25 10 25 10 25 10 25 10 25 10 25
E 8 20 9½ 24 9½ 24 9 23 9 23 9 23 9 23
Air Conn.
W 6 15 8 20 8 20 12 30 12 30 12 30 12 30
Vent Conn.
V 8 20 10 25 10 25 12 30 12 30 14 36 14 36
Shipping Weight1
lbs kg 425 193 505 229 615 279 675 306 760 345 825 375 955 434
MIGHTY THERM2 Commercial Boilers and Volume Water Heaters
Page 11
GAS
Size 500 750 1000 1250 1500 1750 2000
A 33¾ 86 45¾ 116 57¾ 147 68¼ 173 78¾ 200 89¼ 227 99¾ 253
B 16¾ 43 22¾ 58 28¾ 73 34¼ 87 39½ 100 44¾ 113 49¾ 127
C 6½ 17 6½ 17 6½ 17 10¼ 26 10¼ 26 10¼ 26 10¼ 26
D 10 25 10 25 10 25 10 25 10 25 10 25 10 25
Figure 2. Dimensional Data (pump-mounted models).
E 8 20 9½ 24 9½ 24 9 23 9 23 9 23 9 23
F 46¼ 117 58¼ 148 70¼ 178 80¾ 205 91¼ 232 101¾ 258 112¼ 285
Air Conn.
W 6 15 8 20 8 20 12 30 12 30 12 30 12 30
Vent Conn.
V 8 20 10 25 10 25 12 30 12 30 14 36 14 36
HORIZONTAL
VENT COLLAR VENT PIPE
SIZE
SIZE
DIAMETER
500 750 1000 1250 1500 1750 2000
in. cm 8 20 10 25 10 25 12 30 12 30 14 36 14 36
in. cm 6 15 8 20 8 20 10 25 10 25 12 30 12 30
INTAKE AIR PIPE
DIAMETER
in. cm 6 15 8 20 8 20 12 30 12 30 12 30 12 30
MIN. INTAKE MIN. VENT AIR PIPE LENGTH PIPE LENGTH
ft. m 0 0
0 0 0 0 0 0 0 0 0 0 0* 0
ft. m 3 1 3 1 3 1 3 1 3 1 3 1 3 1
MAX. PIPE MAX. NO. SIDE WALL
LENGTH OF ELBOWS
VENT
TERMINAL
ft. m
PART NUMBER
50 15
3
CA001406
50 15
3
CA001407
50 15
3
CA001407
50 15
3
CA001408
50 15
3
CA001408
50 15
3
CA001409
50 15
3
CA001409
SIDE WALL COMBUSTION AIR TERMINAL
PART NUMBER
CA20260701 CA20260703 CA20260703 CA20260706 CA20260706 CA20260706 CA20260706
*Appliance needs to vent outdoors using approved vent caps and following all guidelines as noted in our IO manual. Proper protection
against debris in the air intake (through using a downward spout and/or
screen) to avoid debris pick-up / falling into the appliance is required.
Table 2. Horizontal Vent / Combustion Air Parameters.
Page 12
LAARS Heating Systems
Venting and Combustion Air
2.A Combustion Air
These boilers and water heaters must have provisions for combustion and
ventilation air in accordance with section 5.3, Air for Combustion and
Ventilation, of the National Fuel Gas Code, ANSI Z223.1, or Sections 7.2, 7.3
or 7.4 of CSA B149.1, Installation Codes, or applicable provisions of the
local building codes.
This unit may receive combustion air from the space in which it is installed,
or it can be ducted directly to the unit from the outside. Ventilation air
must be provided in either case.
2.A.1 Combustion Air From Room In the United States, the most common
requirements specify that the space shall communicate with the outdoors in
accordance with method 1 or 2, which follow. Where ducts are used, they shall
be of the same cross-sectional area as the free area of the openings to which
they connect.
Method 1: Two permanent openings, one commencing within 12 inches (30 cm) of
the top and one commencing within 12 inches (30 cm) of the bottom, of the
enclosure shall be provided. The openings shall communicate directly, or by
ducts, with the outdoors or spaces that freely communicate with the outdoors.
When directly communicating with the outdoors, or when communicating to the
outdoors through vertical ducts, each opening shall have a minimum free area
of 1 square inch per 4000 BTU/hr (5.5 square cm/kW) of total input rating of
all equipment in the enclosure. When communicating to the outdoors through
horizontal ducts, each opening shall have a minimum free area of not less than
1 square inch per 2000 BTU/hr (11 square cm/kW) of total input rating of all
equipment in the enclosure. Table 3 shows data for this sizing method, and for
each model.
Method 2: One permanent opening, commencing within 12 inches (30 cm) of the
top of the enclosure, shall be permitted. The opening shall directly
communicate with the outdoors or shall communicate through a vertical or
horizontal duct to the outdoors or spaces that
directly communicate with the outdoors and shall have a minimum free area of 1
square inch per 3000 BTU/hr (7 square cm/kW) of the total input rating of all
equipment located in the enclosure. This opening must not be less than the sum
of the areas of all vent connectors in the confined space.
Other methods of introducing combustion and ventilation air are acceptable,
providing they conform to the requirements in the applicable codes listed
above.
In Canada, consult local building and safety codes or, in absence of such
requirements, follow CSA B149.1.
2.A.2 Intake Combustion Air The combustion air can be taken through the wall,
or through the roof. When taken from the wall, it must be taken from out-of-
doors by means of the Manufacturers horizontal wall terminal (see Table 2).
When taken from the roof, a field-supplied rain cap or an elbow arrangement
must be used to prevent entry of rain water (see Figure 3).
Use single-wall galvanized pipe, per Table 4, for the combustion air intake
(see Table 2 for appropriate size). Route the intake to the heater as directly
as possible. Seal all joints with tape. Provide adequate hangers. The unit
must not support the weight of the combustion air intake pipe. Maximum linear
pipe length allowed is 50 feet (15.2m). Three elbows have been calculated into
the 50-foot (15.2m) linear run. Subtract 10 allowable linear feet (3.0m) for
every additional elbow used (see Table 2). When fewer than 3 elbows are used,
the maximum linear pipe length allowed is still 50 feet (15.2m).
The connection for the intake air pipe is on the filter box. This unit has
venting and combustion air ducting attached to the top.
In addition to air needed for combustion, air shall also be supplied for
ventilation, including all air required for comfort and proper working
conditions for personnel. This unit loses less than 1 percent of its input
rating to the room, but other heat sources may be present.
2.B Venting
2.B.1 Vent Categories Depending upon desired venting for this unit, it may
be considered a Category I or a Category III appliance. In general, a vertical
vent system will be a Category I system. However, in rare instances, a
vertical vent system may be considered Category III. In the U.S., the National
Fuel Gas Code (ANSI Z223.1-Latest Edition),
UNIT
SIZE
500 750 1000 1250 1500 1750 2000
EACH OPENING*
SQUARE INCHES
SQUARE CM
125
807
188
1213
250
1613
313
2020
375
2420
438
2826
500
3226
*Net Free Area in Square Inches / Square cm Area indicated is for one of two openings; one at floor level and one at the ceiling, so the total net free area could be double the figures indicated.
This chart is for use when communicating directly with the outdoors. For
special conditions and alternate methods, refer to the latest edition of ANSI
Z223.1.
Note: Check with louver manufacturers for net free area of louvers. Correct
for screen resistance to the net free area if a screen is installed. Check all
local codes applicable to combustion air.
Table 3. Combustion Air Openings.
MIGHTY THERM2 Commercial Boilers and Volume Water Heaters
Page 13
or in Canada the CSA B149.1 (latest edition), defines a Category I vent
system, and includes rules and tables to size these vent systems. If this
units vertical vent system does not satisfy the criteria for Category I
venting, it must be vented as a Category III system.
All vent systems which discharge horizontally (without the use of a power
venter) are considered Category III vent systems.
2.B.2 Category I Vent When vented as a category I appliance, the vent
system must conform to the National Fuel Gas Code (ANSI Z223.1-Latest Edition)
in the U.S., or in Canada, to CSA B149.1 (latest edition). The vent system
must be sized and installed for a Category I Fan-Assisted Appliance.
If chimney height is greater than 25 feet, or if multiple units are vented
into the same vertical vent, a barometric damper must be installed on each
unit, such that the flue draft does not exceed (negative) 0.1″ w.c.
If using a power venter for any type of Category I venting, the draft should
be set between (negative) 0.01 and 0.10″ w.c.
2.B.3 Common Venting Systems These units are Category I fan-assisted when
vented vertically and adhering to all applicable codes. When common venting a
fan-assisted unit with
other other appliances through one shared vertical duct called a “common
vent”, special care must be taken by the installer to ensure safe operation.
In the event that the common vent is blocked, it is possible, especially for
fan-assisted devices, to vent backwards through non-operating appliances
sharing the vent, allowing combustion products to infiltrate occupied spaces.
If the appliances are allowed to operate in this condition, serious injury or
death may occur.
Proper vent sizing, construction and safety requirements from the National
Fuel Gas Code, ANSI Z223.1 or in Canada, from CSA B149.1 as well as all
applicable local codes must be followed.
As an additional precaution, it is recommended that a Carbon Monoxide (CO)
alarm be installed in all enclosed spaces containing combustion appliances.
These units are not allowed to be vented into a common horizontal Cat III vent
system (horizontal discharge or other configuration for Cat III), unless a
properly sized vent fan is used, and the common vent system is properly
designed by the vent fan manufacturer or a qualified engineer.
Refer to the installation and operating instructions on all appliances to be
common vented for instructions, warnings, restrictions and safety
requirements. If safe operation of all appliances connected to a common vent
cannot be assured, including prevention of spillage of flue gasses into living
spaces, common venting should not be applied, and appliances should each be
vented separately.
WARNING
When an existing Cat I appliance is removed or replaced, the original venting
system may no longer be sized to properly vent the attached appliances. Under
no circumstances should an improperly sized vent be used. An improperly sized
vent may cause operational and safety problems,and could result in
serious injury, death, or property damage.
WARNING
Operation of appliances with a blocked common vent may lead to serious injury
or death. If safe operation of all appliances connected to a common vent
cannot be assured, including prevention of spillage of flue gasses into living
spaces, common venting should not be applied, and appliances
should each be vented separately.
TERM Pipe
Joint Sealing
DESCRIPTION Single-wall galvanized steel pipe, 24 gauge minimum (either
insulated or non-insulated)
Permanent duct tape or aluminum tape
Table 4. Required Combustion Air Piping Material.
Figure 3. Combustion Air and Vent Through Roof.
Page 14
LAARS Heating Systems
2.B.4 Category III Vent When this unit is vented with horizontal discharge,
it must be installed per this installation manual and the venting system
manufacturer’s installation instructions. The vent system must be sealed
stainless steel (see Table 5).
Route the vent pipe to the heater as directly
as possible. Seal all joints and provide adequate hangers every 4′ or as
required in the venting system manufacturer’s Installation Instructions.
Horizontal portions of the venting system must be supported to prevent sagging
and may not have any low sections that could trap condensate. The unit must
not support the weight of the vent pipe. Horizontal runs must slope downwards
not less than ¼ inch per foot (2 cm/m) from the unit to the vent terminal.
Reference Table 2 for the size of the Category III vent system. Up to three
elbows can be used with 50 linear feet (15.2m) of pipe. Subtract 10 allowable
linear feet (3.0m) for every additional elbow used.
4. Locate the vent terminal so that vent gases cannot enter the building
through doors, windows, gravity inlets or other openings. When possible,
locations under windows or near doors should be avoided.
5. Locate the vent terminal so that it cannot be blocked by snow. The
National Fuel gas code requires that it be at a minimum of 12″ above grade. In
a location that has the possibility of snow accumulation, it is critical the
installer places the vent at least 12″ higher than the maximum potential snow
line. Seek local municipalities and their codes for appropriate installation
techniques.
6. Locate the terminal so the vent exhaust does not settle on building
surfaces or other nearby objects. Vent products may damage such surfaces or
objects.
7. If the boiler or water heater uses ducted combustion air from an intake
terminal located on the same wall, locate the vent terminal at least 3 feet
(0.9m) horizontally from the combustion air terminal, and locate the vent
terminal at least 1 foot
(0.3m) above the combustion air terminal.
WARNING
The outdoor vent terminal gets hot. This unit must be installed in such a way
as to reduce the risk of
burns from contact with the vent terminal.
2.C Locating Vent & Combustion Air Terminals
2.C.1 Side Wall Vent Terminal The appropriate manufacturers side wall vent
hood must be used, and is listed in the installation and operation manual. The
terminal provides a means of installing the vent piping through the building
wall, and must be located in accordance with ANSI Z223.1/ NFPA 54 and
applicable local codes. In Canada, the installation must be in accordance with
CSA B149.1 or .2 and local applicable codes. Consider the following when
installing the terminal: 1. Figure 4 shows the requirements for mechanical
vent
terminal clearances for the U.S. and Canada. 2. Vent terminals for condensing
appliances or
appliances with condensing vents are not permitted to terminate above a public
walkway, or over an area where condensate or vapor could create a nuisance or
hazard. 3. Locate the vent terminal so that vent gases cannot be drawn into
air conditioning system inlets.
TERM
Pipe
Joint Sealing
DESCRIPTION
Must comply with UL Standard 1738 such as Type 29-4C Stainless Steel (either
insulated or non-insulated). Follow vent manufacturer’s instructions
Table 5. Required Horizontal Venting Material.
2.C.2 Side Wall Combustion Air Terminal The manufacturers side wall combustion
air
terminal (see Table 2) must be used when the unit takes its combustion air
through a duct from a side wall. Consider the following when installing the
terminal: 1. Do not locate the air inlet terminal near a source
of corrosive chemical fumes (e.g., cleaning fluid, chlorinated compounds,
etc.) 2. Locate the terminal so that it will not be subject to damage by
accident or vandalism. 3. Locate the combustion air terminal so that it cannot
be blocked by snow. The National Fuel gas code requires that it be at a
minimum of 12″ above grade. Depending on local conditions, the installer
should ensure that it remains at least 12″ above the maximum potential snow
line. Seek local municipalities and their codes for appropriate installation
techniques.
WARNING
It is critical that the combustion air intake and the vent terminals remain at
least 12″ above the maximum potential snow line. If either the vent terminal
or the
air terminal is blocked by snow, there may be potential for the unit to
produce excess carbon monoxide and or recirculate flue gasses into the
building/dwelling. Personal injury or DEATH may occur. Natural snowfall,
drifting, and banking should all be taken into account
when locating the terminals in a potential snow environment.
4. If this unit is side-wall vented to the same wall, locate the vent
terminal at least 3 feet (0.9m) horizontally from the combustion air terminal,
and locate the vent terminal at least 1 foot (0.3m) above the combustion air
terminal (see Figure 4).
MIGHTY THERM2 Commercial Boilers and Volume Water Heaters
Page 15
Canadian Installations1
A = Clearance above grade, veranda, porch, deck, or balcony
12 in (30 cm)
B = Clearance to window or door that may be opened
6 in (15 cm) for appliances 10,000 Btuh (3 kW) 12 in (30 cm) for appliances >
10,000 Btuh (3 kW) and
100,000 Btuh (30 kW) 36 in (91 cm) for appliances >100,000 Btuh (30 kW)
C = Clearance to permanently closed window
See Note 4
D = Vertical clearance to ventilated soffit located See Note 4 above the terminal within a horizontal
distance of 2 ft (61 cm) from the center line of the terminal
E = Clearance to unventilated soffit
See Note 4
F = Clearance to outside corner
See Note 4
G = Clearance to inside corner
See Note 4
H = Clearance to each side of centerline extended above meter / regulator assy
3 ft (91 cm) within a height of 15 ft (4.6 m)
I = Clearance to service regulator vent outlet 3 ft (91 cm)
J = Clearance to nonmechanical air supply inlet to building or the combustion air inlet to any other appliance
6 in (15 cm) for appliances 10,000 Btuh (3 kW) 12 in (30cm) for appliances >
10,000 Btuh (3 kW) and
100,000 Btuh (30 kW) 36 in (91 cm) for appliances > 100,000 Btuh (30 kW)
K = Clearance to a mechanical air
6 ft (1.83 m)
supply inlet L = Clearance above paved sidewalk or paved 7 ft (2.13 m)
driveway located on public property
M = Clearance under veranda, porch, deck, or 12 in (30 cm) balcony
U.S. Installations2
12 in (30 cm)
6 in (15 cm) for appliances 10,000 Btuh (3 kW) 9 in (23 cm) for appliances >
10,000 Btuh (3 kW) and
50,000 Btuh (15 kW) 12 in (30 cm) for appliances >50,000 Btuh (15 kW)
See Note 5 See Note 5
See Note 5 See Note 5 See Note 5 See Note 5
See Note 5 6 in (15 cm) for appliances 10,000 Btuh (3 kW) 9 in (23cm) for
appliances > 10,000 Btuh (3 kW) and
50,000 Btuh (15 kW) 12 in (30 cm) for appliances > 50,000 Btuh (15 kW) 3 ft
(91 cm) above if within 10 ft (3 m) horizontally 7 ft (2.13 m) for mechanical
draft systems (Category I appliances). Vents for Category II and IV appliances
cannot be located above public walkways or other areas where condensate or
vapor can cause a nuisance or hazard*
See Note 5
A vent shall not terminate directly above a sidewalk or paved driveway that is
located between two single family dwellings and serves both dwellings.
Permitted only if veranda, porch, deck, or balcony is fully open on a minimum
of two sides beneath the floor.
Notes: 1) In accordance with the current CSA B149.1, Natural Gas and Propane
Installation Code. 2) In accordance with the current ANSI Z223.1/NFPA 54,
Natural Fuel Gas Code. 3) If locally adopted installation codes specify
clearances different than those illustrated, then the most stringent clearance
shall prevail. 4) For clearances not specified in CAN/CSA-B149, clearance is
in accordance with local installation codes and the requirements of the gas
supplier. 5) For clearances not specified in ANSI Z223.1/ NFPA 54, clearance
is in accordance with local installation codes and the requirements of the gas
supplier. 6) IMPORTANT: Terminal must be placed such that it remains a minimum
of 12″ above maximum expected snow line. Local codes may have more specific
requirements, and must be consulted.
*When vent terminal is less than 10 feet (3m) horizontally from a forced air inlet, the terminal must be at least 3 feet (0.9m) above the air inlet. (US only)
Figure 4. Combustion Air and Vent Through Side Wall.
Page 16
LAARS Heating Systems
2.C.3 Vertical Vent Terminal When the unit is vented through the roof, the
vent
must extend at least 3 feet (0.9m) above the point at
which it penetrates the roof. It must extend at least 2
feet (0.6m) higher than any portion of a building within a
horizontal distance of 10 feet (3.0m), and high enough
above the roof line to prevent blockage from snow. When
the combustion air is taken from the roof, the combustion
air must terminate at least 12″ (30cm) below the vent
terminal (see Figure 3). Seek local municipalities and
their codes for appropriate installation techniques.
From Massachusetts Rules and Regulations 248 CMR 5.08: (a) For all side wall
horizontally vented gas fueled equip-
ment installed in every dwelling, building or structure used in whole or
inpart for residential purposes, including those owned or operated by the
Commonwealth and where the side wall exhaust vent termination is less than
seven (7) feet above finished grade in the area of the venting, including but
not limited to decks and porches, the following requirements shall be
satisfied: 1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of
installation of the side wall horizontal vented gas fueled equipment, the
installing plumber or gasfitter shall observe that a hard-wired carbon
monoxide detector with an alarm and battery back-up is installed on the floor
level where the gas equipment is to be installed. In addition, the installing
plumber or gasfitter shall observe that a battery operated or hard-wired
carbon monoxide detector with an alarm is installed on each additional level
of the dwelling, building or structure served by the side wall horizontal
vented gas fueled equipment. It shall be the responsibility of the property
owner to secure the services of qualified licensed professionals for the
installation of hard-wired carbon monoxide detectors.
a. In the event that the side wall horizontally vented gas
fueled equipment is installed in a crawl space or an attic, the hard-wired
carbon monoxide detector with alarm and battery back-up may be installed on
the next adjacent floor level. b. In the event that the requirements of this
subdivision cannot be met at the time of completion of installation, the owner
shall have a period of thirty (30) days to comply with the above requirements;
provided, however, that during said thirty (30) day period, a battery operated
carbon monoxide detector with an alarm shall be installed. 2. APPROVED CARBON
MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance
with the above provisions shall comply with NFPA 720 and be ANSI/ UL 2034
listed and IAS certified. 3. SIGNAGE. A metal or plastic identification plate
shall be permanently mounted to the exterior of the building at a minimum
height of eight (8) feet above grade directly in line with the exhaust vent
terminal for the horizontally vented gas fueled heating appliance or
equipment. The sign shall read, in print size no less than one-half (½) inch
in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”. 4.
INSPECTION. The state or local gas inspector of the side wall horizontally
vented gas fueled equipment shall not approve the installation unless, upon
inspection, the inspector
observes carbon monoxide detectors and signage installed in accordance with
the provisions of 248 CMR 5.08(2)(a) 1 through 4. (b) EXEMPTIONS: The
following equipment is exempt from 248 CMR 5.08(2)(a) 1 through 4: 1. The
equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented”
in the most current edition of NFPA 54 as adopted by the Board; and 2. Product
Approved side wall horizontal vented gas fueled
equipment installed in a room or structure separate from the dwelling,
building or structure used in whole or in part for residential purposes. (c)
MANUFACTURER REQUIREMENTS – GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the
manufacturer of Product Approved side wall horizontally vented gas equipment
provides a venting system design or venting system components with the
equipment, the instructions provided by the manufacturer for installation of
the equipment and the venting system shall include: 1. Detailed instructions
for the installation of the venting system design or the venting system
components; and 2. A complete parts list for the venting system design or
venting system. (d) MANUFACTURER REQUIREMENTS – GAS EQUIPMENT VENTING
SYSTEMNOT PROVIDED. When the manufacturer of a Product Approved side wall
horizontally vented gas fueled equipment does not provide the parts for
venting the fuel gases, but identifies “special venting systems”, the
following requirements shall be satisfied by the manufacturer: 1. The
identification of each “special venting system” shall include either the
listing of the website, phone number or manufacturer’s address where the
venting system installation instructions can be obtained; and 2. The “special
venting systems” shall be Product Approved by the Board, and the instructions
provided with that system shall include a parts list and detailed installation
instructions. (e) A copy of all installation instructions for the Product
Approved side wall horizontally vented gas fueled equipment, and all the
venting instructions, parts lists, and/or design instructions for the venting
system shall remain with the appliance or equipment at the completion of the
installation. Manufacturers’ websites where venting system installation
instructions may be obtained is located on the manufacturers website (see back
cover).
2.C.4 Vertical Combustion Air Terminal When combustion air is taken from the
roof, a
field-supplied rain cap or an elbow arrangement must be used to prevent entry
of rain water (see Figure 3). The opening on the end of the terminal must be
at least 12″ (30cm) above the point at which it penetrates the roof, and high
enough above the roof line to prevent blockage from snow. When the vent
terminates on the roof, the combustion air must terminate at least 12″ (30cm)
below the vent terminal.
2.D Common Vent Test — Boilers
When an existing boiler is removed from a common venting system, the common
venting system is likely to be too large for proper venting of the appliances
remaining connected to it.
At the time of removal of an existing boiler, the following steps shall be
followed with each appliance remaining connected to the common venting system
placed in operation, while the other appliances remaining connected to the
common venting system are not in operation.
1. Seal any unused openings in the common venting system.
2. Visually inspect the venting system for proper size and horizontal pitch
and determine there is
MIGHTY THERM2 Commercial Boilers and Volume Water Heaters
Page 17
no blockage or restriction, leakage, corrosion and other deficiencies which
could cause an unsafe condition.
3. Insofar as it is practical, close all building doors and windows and all
doors between the space in which the appliances remaining connected to the
common venting system are located and other spaces of the building. Turn on
clothes dryers and any appliance not connected to the common venting system.
Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they
will operate at maximum speed. Do not operate a summer exhaust fan. Close
fireplace dampers.
4. Place in operation the appliance being inspected. Follow the lighting
instructions. Adjust thermostat so that the heating unit will operate
continuously.
5. Test for spillage at the draft hood relief opening
after 5 minutes of main burner operation. Use the flame of a match or candle,
or smoke from a cigarette, cigar or pipe.
6. After it has been determined that each appliance remaining connected to
the common venting system properly vents when tested as outlined above, return
doors, windows, exhaust fans, fireplace dampers and any other gas burning
appliance to their previous conditions of use.
7. Any improper operation of the common venting system should be corrected so
that the installation conforms to the National Fuel Gas Code, ANSI Z223.1/NFPA
54 and/or CSA B149.1, Installation Codes. When resizing any portion of the
common venting system, the common venting system should be resized to approach
the minimum size as determined using the appropriate tables in Part II of the
National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CSA B149.1, Installation
Codes.
- 2.E Vent Terminals for Outdoor Units For outdoor applications, the vent and combustion air openings must be covered with proper terminals to prevent rain, snow and other objects from falling into the unit.
If local codes allow, outdoor installations may use 1′ of appropriately sized galvanized single wall or B-Vent and a rain cap for exhaust vent termination in the default configuration (venting out of the top). Note that some local codes may require a higher vertical vent height, extending above any perimeter fencing, etc. In installations where the appearance of the vent is
objectionable, the low profile vent terminals in Table 6 may be used.
Combustion air inlets consist of appropriately sized galvanized pipe and elbows to allow the open end to face down aside the boiler. This is available as a Commercial Kit from the manufacturer.
Part numbers for the low profile terminals to cover the vent and combustion air openings are shown in Table 6.
SIZE
500 750 1000 1250 1500 1750 2000
OUTDOOR VENT TERMINAL
20254703 20254705 20254705 D2007700 D2007700 D2007800 D2007800
OUTDOOR
COMBUSTION AIR TERMINAL
CA014701 CA014702 CA014702 CA014704 CA014704 CA014704 CA014704
Table 6. Vent Terminals for Outdoor Units.
*Outdoor installation of volume water heaters is not permitted in Canada.
Page 18
LAARS Heating Systems
Gas Supply and Piping
3.A Gas Supply and Piping
Gas piping should be supported by suitable hangers or floor stands, not by the
boiler or water heater.
This units gas train allows the user to pipe the gas
from either the right side or the left side of the unit. As shipped, the right
side of the gas train is capped off, and there is a manual valve on the left
side. If desired, the manual valve on the left side of the gas train may be
moved to the right side, and the cap on the right side may be moved to the
left.
Review the following instructions before proceeding with the installation.
1. Verify that the unit is fitted for the proper type of gas by checking the
rating plate. These units are equipped to operate at elevations up to 10,000
feet (3050m) and may be adjusted to operate properly at altitudes above 2500
feet (see Section 6.F.2) and the input will be reduced if the heating value of
the gas supply is below sea level values.
2. Verify the inlet gas supply pressure.
Min
Max
Natural Gas
4″ W.C.
10.5″ W.C.
Propane
8″ W.C.
13″ W.C.
3. Refer to Table 7, size supply. 4. Run gas supply line in accordance with
all applicable
codes.
5. Locate and install manual shutoff valves in accordance with state and
local requirements.
6. A sediment trap must be provided upstream of the gas controls.
7. All threaded joints should be coated with piping compound resistant to
action of liquefied petroleum gas.
8. The unit and its individual shutoff valve must be disconnected from the
gas supply piping during any pressure testing of that system at test pressures
in excess of 1/2 PSIG (3.45kpa).
9. The unit must be isolated from the gas supply system by closing its
individual manual shutoff valve during any pressure testing of the gas supply
piping system at test pressures equal to or less than 1/2 PSIG (3.45kpa). 10.
The unit and its gas connection must be leak tested before placing it in
operation. 11. Purge all air from gas lines.
NOTE: This unit and all other gas appliances sharing
the gas supply line must be firing at maximum capacity to properly measure the
inlet supply pressure. The pressure can be measured at the supply pressure
port on the gas valve. Low gas pressure could be an
indication of an undersized gas meter, undersized gas supply lines and/or an
obstructed gas supply line.
WARNING
If an inline high gas pressure regulator is used, it must be of the lockup
type and located a minimum of 10 feet from the unit. Failure to do so may
result in
insufficient gas volume supplied to the unit.
WARNING
Do not use open flame to check for leaks. An open flame could lead to
explosion, which could result
in property damage, serious injury or death.
SIZE AND GAS TYPE
500 natural 500 propane 750 natural 750 propane 1000 natural 1000 propane 1250
natural 1250 propane 1500 natural 1500 propane 1750 natural 1750 propane 2000
natural 2000 propane
DISTANCE FROM GAS METER OR LAST STAGE REGULATOR
0-100′
100-200′
200-300′
1½”
2″
2″
1″
1½”
1½”
2″
2″
2½”
1½”
1½”
2″
2″
2½”
3″
1½”
2″
2½”
2½”
2½”
3″
2″
2″
2½”
2½”
3″
3″
2″
2½”
2½”
2½”
3″
3″
2″
2½”
2½”
3″
3″
3½”
2½”
2½”
3″
Metric Equivalent
SIZE AND GAS TYPE
500 natural 500 propane 750 natural 750 propane 1000 natural 1000 propane 1250
natural 1250 propane 1500 natural 1500 propane 1750 natural 1750 propane 2000
natural 2000 propane
DISTANCE FROM GAS METER OR LAST STAGE REGULATOR
0-31m
31-61m
61-91m
3.8cm 2.5cm
5.1cm 3.8cm
5.1cm 3.8cm
5.1cm 3.8cm
5.1cm 3.8cm
6.4cm 5.1cm
5.1cm 3.8cm 6.4cm 5.1cm
6.4cm 5.1cm 6.4cm 5.1cm
7.6cm 6.4cm 7.6cm 6.4cm
6.4cm 5.1cm 6.4cm 5.1cm
7.6cm 6.4cm 7.6cm 6.4cm
7.6cm 6.4cm 7.6cm 6.4cm
7.6cm 6.4cm
7.6cm 6.4cm
8.9cm 7.6cm
NOTES: 1. These figures are based on 1/2″ (0.12kPa) water column pressure
drop. 2. Check supply pressure and local code requirements before proceeding
with work. 3. Pipe fittings must be considered when determining gas
pipe sizing.
Table 7. Gas Piping Sizes.
MIGHTY THERM2 Commercial Boilers and Volume Water Heaters
Page 19
SECTION 4
Water Connections
4.A Boilers. 4.A.1 Heating System Piping:
Hot Supply Connections — Boiler NOTE: This unit must be installed in a closed
pressure
system with a minimum of 12 psi (82.7kPa) static pressure at the boiler.
Hot water piping should be supported by suitable hangers or floor stands. Do
not support piping with this unit. Due to expansion and contraction of copper
pipe, consideration should be given to the type of hangers used. Rigid hangers
may transmit noise through the system resulting from the piping sliding in the
hangers. It is recommended that padding be used when rigid hangers are
installed. Maintain 1″ clearance to combustibles for hot water pipes.
Pipe the discharge of the relief valve (full size) to a drain or in a manner
to prevent injury in the event of pressure relief. Install an air purger, an
air vent, a diaphragm-type expansion tank, and a hydronic flow check in the
system supply loop. Minimum fill pressure must be 12psig (82.7kPa). Install
shutoff valves where required by code.
Suggested piping diagrams are shown (see Figures 6 through 10 on page 22).
These diagrams are meant only as a guide. Components required by local codes
must be properly installed.
4.A.2 Cold Water Make-Up — Boiler 1. Connect the cold water supply to the
inlet
connection of an automatic fill valve. 2. Install a suitable back flow
preventer between the
Figure 5. Typical Gas Train Configuration.
automatic fill valve and the cold water supply. 3. Install shut off valves
where required.
NOTE: This boiler, when used in connection with a refrigeration system, must
be installed so the chilled
medium is piped in parallel with the boiler with appropriate valves to prevent
the chilled medium from
entering the boiler.
The boiler piping system of a hot water heating boiler connected to heating
coils located in air handling appliances where they may be exposed to
refrigerated air circulation must be equipped with flow control valves or
other automatic means to prevent gravity circulation of the boiler water
during the cooling cycle.
A boiler installed above radiation level, or as required by the authority
having jurisdiction, must be provided with a low water cutoff device either as
a part of the boiler or at the time of boiler installation.
4.A.3 Water Flow Requirements — Boiler A hydronic heating (closed loop)
application
re-circulates the same fluid in the piping system. As a result, no new
minerals or oxygen is introduced into the system. To ensure a proper operating
temperature leading to long boiler life, a flow rate has been established
based on the fluid temperature rise for this specific size boiler.
Pump-mounted boilers can be ordered for use in primary secondary piping
systems. The pumps used are sized for the headloss through the heater, plus 30
feet (9.1m) of full-sized piping (same size as boiler outlet) and a normal
number of fittings.
Unit
20°F
Size
flow H/L
500 750 1000 1250 1500 1750
gpm feet
43 1.7 64 3.3 85 5.0 106 8.1 128 10.0 N/R N/R
2000 N/R N/R
Metric Equivalent
Unit
11°C
Size
flow H/L
lpm
m
500 161 0.5
750 241 1.0
1000 321 1.5
1250 401 2.5
1500 483 3.0
1750 N/R N/R
2000 N/R N/R
25°F
flow H/L
gpm feet
34 1.1 51 2.3 68 3.6 85 6.1 102 7.2 119 10.5 136 12.5
30°F
flow H/L
gpm feet
28 0.9 43 1.7 57 3.1 71 4.7 85 5.5 99 8.4 113 10.4
35°F
flow H/L
gpm feet
24 0.7 36 1.2 49 2.2 61 3.4 73 4.2 85 5.8 97 8.3
14°C
flow H/L
lpm m
129 0.3 193 0.7 257 1.1 322 1.9 386 2.2 451 3.2 515 3.8
17°C
flow H/L
lpm m
107 0.3 161 0.5 214 0.9 269 1.4 322 1.7 375 2.6 429 3.2
19°C
flow H/L
lpm m
92 0.2 138 0.4 184 0.7 231 1.0 276 1.3 322 1.8 368 2.5
Notes: gpm = gallons per minute, lpm = liters per minute, H/L = headloss, ft = headloss in feet, m = headloss in meters. Maximum temperature rise is 35°F (19°C), as shown. Headloss is for boiler’s heat exchanger only. N/R = not recommended.
Table 8. Water Flow Requirements — Boilers.
Page 20
LAARS Heating Systems
Table 8 specifies water flow rates for boilers, which will enable the user to
size a pump. The headloss shown is for the heater only, and the user will need
to add the headloss of the system piping to properly size the pump.
The minimum inlet water temperature for the this unit is 120°F (49°C) to avoid
condensing on the copper coils.
4.A.4 Freeze Protection — Boiler Boiler installations are not recommended in
areas
where the danger of freezing exists unless proper precautions are made for
freeze protection. A non toxic, heating system, anti-freeze may be added to
the hydronic system provided that the concentration does not exceed 50% and
the anti freeze contains an anti foamant. When a 50/50 mixture is used,
increase the water flow requirements by 15%, and increase the headloss
requirements by 20%.
Power outage, interruption of gas supply, failure of system components,
activation of safety devices, etc., may prevent a boiler from firing. Any time
a boiler is subjected to freezing conditions, and the boiler is not able to
fire, and/or the water is not able to circulate, there is a risk of freezing
in the boiler or in the pipes in the system. When water freezes, it expands.
This can result in bursting of pipes in the system, or damage to the boiler,
which could result in leaking or flooding conditions.
NOTE: Different glycol products may provide varying degrees of protection.
Glycol products must be
maintained properly in a heating system, or they may become ineffective.
Consult the glycol specifications,
or the glycol manufacturer, for information about specific products,
maintenance of solutions, and set up
according to your particular conditions.
30 feet (9.1m) of full-sized piping (same size as boiler outlet) and a normal
number of fittings. Pumps used on pump-mounted unit are sized for soft/normal
or hard water, so make sure a pump-mounted unit matches the water quality of
the installation.
Pipe the outlet from the heater’s relief valve such that any discharge from
the relief valve will be conducted to a suitable place for disposal when
relief occurs. Do not reduce line size or install any valves in this line. The
line must be installed to allow complete drainage of both the valve and the
line.
Suggested piping diagrams are shown in Figures 11 through 14 on page 24. These
diagrams are meant only as a guide. Components required by local codes must be
properly installed.
The minimum inlet water temperature for this unit is 120°F (49°C) to avoid
condensing on the copper coils.
4.B.2 Hot Water Supply Piping — Water Heater Follow the tank manufacturer’s
guidelines for
completion of the hot water system connections.
NOTE: A temperature and pressure relief valve, listed as complying with the
Standard for Relief Valves and Automatic Gas Shutoff Devices for Hot Water
Supply Systems (ANSI Z21.22 / CSA 4.4) of suitable discharge capacity, must be
installed in the separate
storage tank system.
If this water heater is installed in a closed water supply system, such as one
having a backflow preventer in the cold water supply line, the relief valve
may discharge periodically, due to thermal expansion. A properly-sized
expansion tank (or other means) must be provided to control thermal expansion.
Contact the water supplier or local plumbing inspector on how to control this
situation.
4.B Water Connections — Water Heaters
4.B.1 Water System Piping — Water Heater Hot water piping should be supported
by suitable
hangers or floor stands. Do not support piping with this unit. Due to
expansion and contraction of copper pipe, consideration should be given to the
type of hangers used. Rigid hangers may transmit noise through the system
resulting from the piping sliding in the hangers. It is recommended that
padding be used when rigid hangers are installed.
This unit can be used with several different types of readily available
storage tanks. A pump draws water from the storage tank and pumps the water
through the heater and back into the tank. Pump-mounted units have a
circulating pump built into the water heater. The pumps used are sized for the
headloss through the heater, plus
4.B.3 Water Flow Requirements — Water Heater In a water heating application
(an open system),
new water is constantly being introduced. With the new water comes a fresh
supply of minerals that can be deposited on the units heat exchanger. This is
commonly known as scaling. The amount of minerals will depend upon the
hardness of the water. Water can
also be aggressive, and can erode metals, including copper, if the water is
moved too quickly. The water flow requirements for this units water heater are
based upon the hardness of the water. The water flow is kept high enough to
prevent scaling, but low enough to prevent tube erosion. For extremely soft or
hard water, cupronickel tubes are available. Contact a manufacturers
representative if you have questions or concerns about water quality.
Pump-mounted water heaters can be ordered with standard pumps for soft or
normal water or with pumps for hard water. The pumps used are sized for the
headloss through the heater, plus 30 feet (9.1m) of full-
MIGHTY THERM2 Commercial Boilers and Volume Water Heaters
sized piping (same size as heater outlet) and a normal number of fittings.
Table 9 specifies water flow rates for water heaters, which will enable the
user to size a pump. The headloss shown is for the heater only, and the user
will need to add the headloss of the piping system to properly size the pump.
4.B.4 Combined Water Heating (potable) and Space Heating — Water Heater
NOTE: These systems are not allowed in the Commonwealth of Massachusetts.
Piping and components connected to this water heater for the space heating
application shall be suitable for use with potable water.
Toxic chemicals, such as used for boiler treatment, shall not be introduced
into the potable water used for space heating.
This water heater when used to supply potable water shall not be connected to
any heating system or component(s) previously used with a non-potable water
heating appliance.
When the system requires water for heating at temperatures higher than
required for other uses, an anti-scald mixing or tempering valve shall be
installed to temper the water for those uses in order to reduce scald hazard
potential.
4.B.5 Freeze Protection Water Heater Although these water heaters are
design-certified
- for outdoor installations such installations are not
recommended in areas subject to freezing temperatures, unless proper precautions are taken.
Power outage, interruption of gas supply, failure of system components, activation of safety devices, etc., may prevent a heater from firing. Any time a heater is subjected to freezing conditions, and the heater is not able to fire, and/or the water is not able to circulate, there is a risk of freezing in the heater or in the pipes in the system. When water freezes, it expands. This can result in bursting of pipes in the system, or damage to the heater, which could result in leaking or flooding conditions.
Contact your manufacturer’s representative for additional information.
*Outdoor installation of volume water heaters is not permitted in Canada.
Page 21
Page 22 4.B.6 Suggested Piping Diagrams
LAARS Heating Systems
Figure 6. Hydronic Piping — Multiple Boilers, Primary Secondary System.
Figure 7. Hydronic Piping — Multiple Boilers, Low Temperature System.
MIGHTY THERM2 Commercial Boilers and Volume Water Heaters
Page 23
Figure 8. Hydronic Piping — One Boiler, Multi-Temperature System. Figure 9. Hydronic Piping – Primary-Secondary, Reverse-Return.
Page 24
LAARS Heating Systems
Figure 10. Hydronic Piping – Primary-Secondary, Reverse-Return, Low Temperature. Figure 11. Water Heater Piping — One Heater, One Tank.
MIGHTY THERM2 Commercial Boilers and Volume Water Heaters
Page 25
Figure 12. Water Heater Piping — Multiple Heaters, One Tank. Figure 13. Water Heater Piping — One Heater, Multiple Tanks.
Page 26
LAARS Heating Systems
Figure 14. Water Heater Piping — Multiple Heaters, Multiple Tanks.
Unit Size 500 750 1000 1250 1500 1750 2000
gpm S N H 45 68 90 45 68 90 45 68 90 68 68 90 68 68 90 68 68 90 112 112 112
ft SN H 1.8 2.3 3.5 2.1 3.0 6.0 2.3 3.6 6.1 3.8 3.8 6.3 3.9 3.9 6.5 4.0 4.0 6.7 10.0 10.0 10.0
Temp Rise °F S NH 19 13 9 28 19 14 38 25 19 31 31 24 38 38 28 44 44 33 30 30 30
lpm SN H 170 257 341 170 257 341 170 257 341 257 257 341 257 257 341 257 257 341 424 424 424
m S N H 0.5 0.7 1.1 0.6 0.9 1.8 0.6 1.1 1.9 1.2 1.2 1.9 1.2 1.2 2.0 1.2 1.2 2.0 3.0 3.0 3.0
NOTES:
S = soft water (1 to 7.5 grains hardness). N = normal water (7.6 to 17 grains hardness). H = hard water (more than 17 grains hardness). gpm = gallons per minute; lpm = liters per minute; ft = headloss in feet; m = headloss in meters. Headloss is for heater’s heat exchanger only.
Table 9. Water Flow Requirements — Water heaters.
Temp Rise °C SN H 10 7 5 16 10 8 21 14 10 17 17 13 21 21 16 24 24 18 17 17 17
MIGHTY THERM2 Commercial Boilers and Volume Water Heaters
Page 27
SECTION 5
Electrical Connections
WARNING
This unit must be electrically grounded in accordance with the requirements of
the authority having jurisdiction or, in the absence of such requirements,
with the latest edition of the National Electrical Code, ANSI/NFPA 70, in the
U.S.
and with latest edition of CSA C22.1 Canadian Electrical Code, Part 1, in
Canada. Do not rely on the gas or water piping to ground the metal parts of
the boiler. Plastic pipe
or dielectric unions may isolate the boiler electrically. Service and
maintenance personnel, who work on or around the boiler, may be standing on
wet floors and could
be electrocuted by an ungrounded boiler.
Single pole switches, including those of safety controls and protective
devices must not be wired in a grounded line.
All electrical connections are made in the field wiring terminal strip, which
is located at the right side of the unit.
Pump-mounted models 1750 and 2000 require two 120-volt fused supplies. See
Figure 15 for over current protection ratings.
5.A.1 Changing Single Circuit to Two Circuits Sizes 500 to 1500 will be
shipped from the factory
for a single 120-volt power supply. To use a separate circuit for the pump:
1. Ensure power is disabled to the unit. 2. Remove the three jumper wires
that connect the
L2, N2 and GROUND wires on terminal block 1 to the main distribution terminal
block. These wires will be black/white, white and green respectively.
NOTE: All internal electrical components have been pre-wired. No attempt should be made to connect electrical wires to any other location except the wiring box
5.A Main Power
Non-pump-mounted heaters require a single 120-volt fused supply. See Figure 15
for over current protection ratings.
Pump-mounted models 500 to 1500 use a single 120-volt fused supply. The
installer can change these units to use a separate circuit for the pump, if
desired. Instructions to make this change are found in Section 5.A.1.
SIZE
500 750 1000 1250 1500 1750 2000
SINGLE CIRCUIT CONNECTION. HEATER
W/O PUMP
15 15 20 25 25 25 25
W / PUMP
20 20 25 30 30 — —
PUMP ONLY
15 15 15 15 15 15 20
Figure 15. Field Wiring.
Figure 16. Models 500 – 750 Wiring Diagram.
Page 28 Figure 17. Model 1000 Wiring Diagram.
LAARS Heating Systems
TB1-1
MAIN POWER SWITCH DPDT
IGN BD #1
35 67 L1
JUMPER
L1
N1
120 VAC
IGN BD #1 35 67
S1
HSI #1
IGN BD #1 35 67 S2
IGN BD #1 35 67
L2
IGN BD #2 35 67
L1
IGN BD #2 35 67
S1
HSI #2
IGN BD #2 35 67
S2
IGN BD #2 35 67
L2
BLOWER 1
K1
HIGH
K1 LOW
HIGH BLOWER2 K2
K2 LOW
PUMP K3
120 VAC
2 1 P1 P2
24 VAC
1
IGN
IGN
BD #1 35 67
35 67 BD #1
24V
GND
TO PUMP
10
IGN BD #1 35 67
F1
IGN BD #1 35 67
F2
35 67 IGN 24V BD #2
K1
35 67 GND IGN
BD #2
STAGE 1
35 67 35 67
F1
F2
K2
IGN
IGN
BD #2 BD #2
INPUT STAGE 1
STAGE 1
INPUT STAGE 2
STAGE 2
LOW GAS
AUTO RESET
HIGH GAS
HIGH LIMIT OPTIONAL
BLOCK FLUE
MANUAL RESET HIGH LIMIT
2
STAGE 2
STAGE 1
LOCAL/REMOTE DPDT SWITCH
STAGE 1
STAGE 2
T’stat 35 67
35 67 8
T’stat
STAGE 2
Field Interlock
34 PUMP
SELECT SWITCH
FLOW SWITCH
5
Proof of Fan
1 6
Proof of Fan #2
Initiate K3 Relay Delay on Break
Press 35 67
IGN BD #1
Press 35 67
IGN BD #2
IGN BD #1 IGN BD #1
35 67 35 67
L.O.(G)
L.O.
IGN BD #2 35 67
L.O.(G)
IGN BD #2 35 67
L.O.
ALARM SILENCE
BELL
R
ALARM DRY CONTACT
TERMINAL BLOCK 1
POLE 5
POLE 6
Gas 35 67 IGN BD #1
Gas 35 67
IGN BD #2
Gas Valve stage 1
7 LIGHT
Gas Valve stage 2 9
LIGHT
H2329000D
Figure 18. Models 12502000 Wiring Diagram.
MIGHTY THERM2 Commercial Boilers and Volume Water Heaters
Page 29
Figure 19. Models 500750 Connection Diagram.
Page 30
LAARS Heating Systems
Figure 20. Size 1000 Connection Diagram.
Figure 21. Sizes 12502000 Connection Diagram.
COLOUR LEGEND
BK-BLACK W-WHITE R-RED Y-YELLOW BL-BLUE BR-BROWN O-ORANGE G-GREEN P-PURPLE GR-
GREY
WIRING
24V
120V
OPTIONAL WIRING
24V
W IRES NO T INSTA LLED O N PUM P M O UNTED UNITS.
BK/W
PUMP BK/W
TERMINAL BLOCK 1
ALARM ALARM
G W
6
5
4 L2 LOAD 3G 2 N2 1 L2
OPTIONAL LWCO 2 1 P1 P2
BL 1 2 Y
3
4
RELAY, DELAY ON BREAK
6
R
SWITCH P/W
BK/W
MAIN POWER
BK/W
YY BL
HIGH BL GAS BL
LOW GAS
AUTO RESET HIGH LIMIT OPTIONAL
BLOCK FLUE
MANUAL RESET HIGH LIMIT
BL
BL
BL/W R/BK
YY BK/W
FLOW SWITCH
Gas Valve 1
Gas Valve 2
Y/R Y/BK
P PROOF OF FAN LIG HT BL/BK
Y/BK STAGE 1
DPDT SWITCH
LOCAL/REMOTE
STAGE 2
R/W
BL BL BL/W BL P/W GR/P P/W BR/BK
BR/R
BK R/BK
R
Fuse
P BL BL
1
P/BK
1
2
3
FIELD
INTERLOCK 4
5
GR
6
GR/BK
7
BR/BK
8R 9 BR/R 10 Y 10
INPUT STAGE 1 G STAGE 1
INPUT STAGE 2 STAGE 2
TRANSFORMER BK
24V 120V W
R/BK
PROOF OF FAN #2
GR/R (GR/W)
BL/W
AQUASTAT BL/BK
STAGE 1 R/BK
BL/R
STAGE 2
ALARM
DRY
CONTACT
Y
O
Y
BELL
Y
LIGHT
BL
BL
BL
ALARM SILENCE BL
O
O/BK O/R
BL/BK BL/R
JUM PER O NLY INSTA LLED O N PUM P M O UNTED UNITS (1250 & 1500). REM O VE JUM PERS FO R SEPA RA TE PUM P PO W ER SO URC E (L2/ N2)
BK/W BK BK
W W W G
G W BK
1 BK
2 BK 3 BK/W 4 BK 5W 6 W/BK 7 W/BK 8W 9G
10 FIELD G 11 FIELD N 12
FIELD L1
GR/BK
S1 L1
Fenwal
F1
L2
GR
S2
F2
G BL/BK
O/BK
Remote Sense
Ground
24V Gas Valve Pressure Switch lockout indicator (G) T-stat lockout indicator
GR/BK S1 L1 L2
GR S2
Fenwal
F1 F2 BL/R
G
BL/R BR/R GR/R P/R
R O/R
Remote Sense
Ground 24V Gas Valve Pressure Switch lockout indicator (G) T-stat lockout
indicator
G W/BK N
BL/BK LOW
BR/BLK
HIGH
BLO W ER 1
RELAY 1 2 43
BK 6 5
87
BR/R
BL/BK
Y
BR/BK
G W N
BL/R LOW
BR/R
HIGH
BLO W ER 2
RELAY 2
2 BR/R 4
BK 6
3 5 BR/BK
87
BL/R
Y
H2329000F
Page 31
MIGHTY THERM2 Commercial Boilers and Volume Water Heaters
Page 32
LAARS Heating Systems
5.B Field Wiring
Main Power: The main field wiring connection points are located inside the
line voltage connection/ field wire area. Single circuit 120-volt units will
be field connected at the main terminal block labeled “120V (L1)”, “NEUTRAL”
and “GROUND”. See Figure 15 for over current protection ratings.
Sizes 1750, 2000 (and those which have been field retrofitted to electrically
separate the pump and heater) require two 120-volt circuits. The heater
circuit is found on the main terminal block and denoted as “120V (L1)”,
“NEUTRAL” and “GROUND”. The pump circuit is located on terminal block 1 and is
denoted as “120V (L2)”, “N2 (PUMP MTD)”, “GROUND 2 (PUMP MTD)”. See Figure 15
for over current protection ratings.
External Pumps: All non-pump-mounted MT2 units have an internal (dry) contact
rated for 20Amps. A fieldsupplied pump can be connected directly to this
contact if it does not draw more than 20 Amps. If more current is required, a
separate pump contactor must be installed.
To utilize this internal pump contact, supply 120 volt single-phase power to
the terminal marked “120V (L2)” and supply the pump using the terminal marked
“L2 LOAD (EXT. PUMP)”.
NOTE: This pump control is equipped with a delay on break typically set for 3
minutes, but can be adjusted between 0.1 and 10 minutes.
Field Interlocks: To install other field-wired devices to interlock with the
boiler (tank stats, louver switches, flow switches, etc.), remove the jumper
between terminals 3 and 4 and wire the device in series across these
terminals. These terminals are located in the upper main control panel.
External Control Wiring: These terminals are located in the upper main control
panel.
Optional Alarm Contacts: As an option, this unit is available with an alarm
kit. This alarm kit contains a dry contact for up to 120V which is available
within the 120V field wiring panel. These terminals will be clearly labeled
“Alarm” and are rated up to 10 amps.
5.C External Staging Control Wiring
WARNING
Improper field wiring may result in fire or explosion which can cause property
damage, severe injury, or
death. Make only wiring connections which are in accordance with the
Installation and Operation manual.
AVERTISSEMENT
Un câblage incorrect lors de l’installation peut causer un incendie ou une
explosion pouvant entraîner des dommages matériels, de graves blessures ou la
mort. Ne faire seulement que les connexions
conformes au Manuel d’installation et d’exploitation.
If controlling the stages of the MT2 from an external
source (multiple boiler control, BAS, etc.), wire Stage 1 to the terminals
marked “Input Stage 1” and “Stage 1”, and wire Stage 2 to the terminals marked
“Input Stage 2” and “Stage 2”. The “Local/Remote” selector switch above the
terminal strip must be placed in the “Remote” position for the external
controller to manage the staging.
If it is intended to use the MT2’s on-board 2- stage controller, no extra
wiring is necessary. Ensure the Local/ Remote selector switch is in the
“Local” position.
SECTION 6
Operating Instructions
6.A Sequence of Operation Upon initiation of the main power switch, 120V will
be sent to multiple items. Among these are the open contact fan relays, open
contact ignitor relay, open contact pump relay, ignition control module(s) and
open contact lock out indicators (the optional alarm package uses this). In
addition to these, 24V will travel through the optional gas pressure switches
and optional auto reset high limit and boiler control relays. The 24V will
then travel through the block flue switch and the manual reset high limit to
the temperature controller.
Upon a call for heat from the MT2’s internal control or an external staging
control, 24V travels through the field interlock (if closed) and then to the
ignition control(s) “T-stat” terminal (500-750 models are equipped with one
ignition control and models 10002000 are equipped with two ignition controls).
When “T-stat” on an ignition control is energized, its fan will energize and
the ignition control will seek signal from the “pressure circuit”. The
pressure circuits consist of the flow switch and proof of fan.
Models 500-1,000 calls for fan, fan prove, initiate pump then prove flow,
after which “pressure circuit” has been satisfied.
Models 1250-2000 calls for pump, proof of flow, initiate fan then prove fan,
after which “pressure circuit” has been satisfied. The fan prove will only
occur for the active stage that has been called.
When pressure circuit has been satisfied, proving combustion air and adequate
water flow, the hot surface igniter will initiate. The ignition control checks
that the igniter current reached a predetermined level then will dwell
momentarily. When dwell time is complete the gas valve will open.
After a 4-second trial for ignition, the igniter switches off. Unless a flame
is detected by the flame sensor (a minimum value of 0.4µA), the gas valve will
close and The ignition module will either attempt ignition again (up to three
times) or will lock out if the optional lockout ignition module is used.
If flame is sensed, the burner will continue to fire as long as there is a
call for heat and adequate flame signal. If there is a subsequent loss of
flame signal, the
MIGHTY THERM2 Commercial Boilers and Volume Water Heaters
Page 33
burner will attempt re-ignition up to three times (only once if optional
lockout ignition is used.) When the call for heat is satisfied, the gas
valves(s) close and the blowers continues to run for 30 seconds.
The pump will continue to run for 0.1 to 10 minutes, depending on what the
pump time delay has been set to. Model sizes 1,000-2,000 have two ignition
controls that control the individual stages. If one ignition control should
fail for any reason, the remaining module can operate its burners
independently. (Note that if a single blower is disabled on units 1250-2000,
the other fan will
continue to operate and safely allow the boiler to run
with a single stage.)
6.B Filling the System
1. Ensure the system is fully connected. Close all bleeding devices and open
make-up water valve. Allow system to fill slowly.
2. If make-up water pump is employed, adjust pressure switch on pumping
system to provide a minimum of 12 psi (81.8 kPa) at the highest point in the
heating loop.
3. If a water pressure regulator is provided on the make-up water line,
adjust the pressure regulator to provide at least 12 psi (81.8 kPa) at the
highest point in the heating loop.
4. Open bleeding devices on all radiation units at the high points in the
piping throughout the system, unless automatic air bleeders are provided at
such points.
5. Run system circulating pump for a minimum of 30 minutes with the boiler
shut off.
6. Open all strainers in the circulating system, check flow switch operation,
and check for debris. If debris is present, clean out to ensure proper
circulation.
7. Recheck all air bleeders as described in Step 4. 8. Check liquid level in
expansion tank. With the
system full of water and under normal operating pressure, the level of water
in the expansion tank should not exceed ¼ of the total, with the balance
filled with air. 9. Start up system according to the procedure in this manual.
Operate the entire system, including the pump, boiler, and radiation units for
one (1) hour. 10. Recheck the water level in the expansion tank. If the water
level exceeds ¼ of the volume of the expansion tank, open the tank drain, and
drain to that level.
11. Shut down the entire system and vent all radiation units and high points
in the system piping, as described in Step 4.
12. Close make-up water valve and check strainer in pressure reducing valve
for sediment or debris from the make-up water line. Reopen make-up water
valve.
13. Check gauge for correct water pressure and also check water level in the
system. If the height
indicated above the boiler insures that water is at the highest point in the
circulating loop, then the system is ready for operation. 14. Refer to local
codes and the make-up water valve manufacturer’s instructions as to whether
the make-up water valve should be left open or closed. 15. After placing the
unit in operation, the ignition system safety shutoff device must be tested.
First, shut off the manual gas valve, and call the unit for heat. After the
pre-purge and ignitor heat-up time, the main gas terminals will be energized,
attempting to light, for four (4) seconds, and then will de-energize. The unit
will go into lockout mode. Second, turn the power off and then on again, open
the manual gas valve and allow the unit to light. While the unit is operating,
close the manual gas valve and ensure that power to the main gas valve has
been cut. 16. Within three (3) days of start-up, recheck all air bleeders and
the expansion tank as described in Steps 4 and 8 above. Important: The
installer is responsible for identifying to the owner/operator the location of
all emergency shutoff devices.
1 Difference between the temperatures at which the two switch-
es make R-W. Adjustable from 3°F to 10°F (1.7°C to 5.6°C) on standard models,
or from 3.6°F to 12°F (2.0°C to 6.7°C); 55°F to 175°F (13°C to 79°C) models.
2 Two DPDT switches operate in sequence. Each switch differ-
ential is fixed at approximately 3°F (1.7°C) on standard models, or 3.6°F
(2.0°C); 55°F to 175°F (13°C to 79°C) models.
Figure 22. Honeywell L8008G.
Page 34
LAARS Heating Systems
WARNING
Do not use this unit if any part has been under water. Immediately call a
qualified service technician to inspect the unit and to replace any part of
the control
system and any gas control that may have been under water.
6.C Operating Temperature Control
All of these units are equipped with a two-stage aquastat. To utilize this
mounted controller be sure to have the “Local/Remote” selector switch to
“Local”. Set the controller to the desired operating set point. The controller
has an interstage differential that can be adjusted from 3°F to 10°F. This
allows the user to have some control over how stage 2 and stage 1 call for
heat (see Figure 22).
Because the controller senses inlet water and the manual reset high limit
senses outlet water, the high limit should be set 40-50°F higher than the
controller, to avoid nuisance lockout of the manual reset high limit.
6.D External Boiler Operations
If controlling the stages of the MT2 from an external source (multiple boiler
control, BAS, etc) the “Local/Remote” selector switch above the terminal strip
must be placed in the “Remote” position. In this mode, the controller that is
mounted on the MT2 will no longer have control of the unit. The 24V from the
unit waits at the input terminal, and the external control switches this 24V
from the input terminal to the stage terminal.
6.E Limit Controls
The manual reset high limit control is provided as standard equipment on all
heaters. An additional automatic reset switch is optional.A high limit
temperature-sensing bulb is always located in the heater outlet. Burners will
automatically shut down whenever overheating occurs.
4. Switch on the power switch located on the right side of the unit.
5. This unit will enter the start sequence, as long as
there is a call for heat. The blower and pump come on for pre-purge, then the
ignitor warm-up sequence starts and after the ignitor warm-up is complete and
all safety devices are verified, the gas valves open. If ignition doesn’t
occur, check
that there is proper gas supply. Wait 5 minutes and start the unit again.
During initial start up, air in the
gas line may cause this unit to “lock out” during the first few trials for
ignition. Depending on the ignition modules installed, the manual reset button
on the ignition modules may need to be depressed to restart the unit.
6. When the unit is running, the supply gas pressure
must be checked. Inlet gas pressure must not exceed 13″ W.C. (3.2kPa). The
minimum inlet gas pressure is 5″ W.C. (1.2kPa). 7. Once the inlet gas pressure
is verified, the outlet gas pressure from each valve (manifold gas pressure)
must be checked, and adjusted, if necessary. The manifold gas pressure must be
2.5″ W.C. (0.62kPa). 8. Complete the setup by checking the CO2 at the outlet
of the unit. The CO2 should be 8% for natural gas, or 9.2% for propane. 9.
After placing the unit in operation, the Burner Safety Shutoff Device must be
tested. (a) Close gas shutoff valve with burner operating. (b) The flame will
go out and blower will continue to
run for the post purge cycle. One additional
attempt to light will follow. Ignition will not occur as the gas is off. The
ignition control will lockout, and will have to be reset before the unit will
operate.
(c) Open gas shutoff valve. Restart the unit. The ignition sequence will start
again and the
burner will start. The unit will return to its previous mode of operation.
6.F Operating the Burner and Set Up
6.F.1 Set Up for 0 to 2500 Feet Altitude This unit utilizes a modular design
to achieve its
stage-firing. The setup must be checked before the unit is put in operation.
Problems such as failure to start, rough ignition, strong exhaust odors, etc.
can be due to improper setup. Damage to this unit resulting from improper
setup is not covered by the limited warranty. 1. Using this manual, make sure
the installation
is complete and fully in compliance with the instructions.
2. Determine that the unit and system are filled with water and all air has
been bled from both. Open all valves.
3. Observe all warnings on the Operating Instructions label and turn on gas
and electrical power to unit.
NOTE: Model sizes 10002000 have two ignition controls and two ignitors, which
work independently
of one another. If the ignition control for stage 1 fails to properly light
the main burners for that stage, the second ignition control will still be
active, and will be able to energize stage 2. This, of course, will only occur
upon call for stage 2 and if all other safety devices
confirm that the unit will run in a safe condition.
MIGHTY THERM2 Commercial Boilers and Volume Water Heaters
Page 35
6.F.2 High Altitude Adjustment and Set Up These units may be operated at high
altitude (7700
ft., 2347 m) with a reduction in output of approximately 10%. At altitudes of
less than or more than 7700 ft. (2347 m) the unit will perform equally as
well, but with differing reductions in output. At elevations higher than 7700
ft. (2347 m) the reduction in output will exceed 10% and at elevations below
7700 ft. (2347 m) it will be less than 10%. High altitude adjustment must not
be made on units operating at elevations below 2500 ft. (762 m).
No orifice changes are required to adjust this unit for high altitude. High
altitude adjustment is accomplished by adjustment of the gas valve manifold
pressure and the air shutter(s). The required instruments used to assist in
these adjustments are a CO2 or O2 Analyzer and a U-Tube Manometer or other
device capable of reading a pressure of 2.5-3.0 inches W.C. (0.62-0.75 kPa).
Start the adjustment process by checking the CO2 in the “as installed”
condition. Adjust the air shutter(s) so that the CO2 is about 8% or the O2 is
about 6.8% for units operating on Natural Gas. For units operating on LP Gas
adjust the air shutter(s) so that the CO2 is about 9.2% or the O2 is about
6.8%. Units with two blowers should be adjusted so that the air shutters below
each blower are open the same amount.
Once the CO2 or O2 has been set, the manifold pressure may be adjusted. Remove
the 1/8 NPT plug from the lower side of the gas valve that is to be set and
install a fitting, hose and manometer. Start the unit and observe the manifold
pressure. Manifold pressure must be adjusted to 3.0 in. W.C. (0.75 kPa) (for
high altitude only, standard operating pressure is 2.5 in. W.C. (0.62 kPa)).
It is adjusted by removing the slotted cap on the gas valve and turning the
adjustment screw (beneath the cap) clockwise to increase pressure and replaced
after
the adjustments have been completed and the fitting, hose and manometer have
been removed and the 1/8″ plug has been replaced. Repeat this process until
all gas valves have been set. Note: The pressure can be set only when the unit
is operating and only when the particular
gas valve being adjusted is energized by a call for heat from the staging
control.
After all of the gas valve manifold pressures have been set, the CO2 or O2
must be reset. CO2 or O2 will have changed when the manifold pressure was
adjusted. Open the air shutter(s) to reduce the CO2 or O2 to the values
achieved previously.
The procedure is complete when all gas valves are adjusted to a manifold
pressure of 3.0 in. W.C. (0.75 kPa) and the CO2 is adjusted to 8.0% for
Natural Gas units or 9.2% for LP units (to be checked only at full fire). When
using an O2 analyzer, the correct O2 is 6.8% for both Natural Gas and LP
units.
CAUTION
Should any odor of gas be detected, or if the gas burner does not appear to be
functioning in a normal
manner, close main shutoff valve, do not shut off switch, and contact your
heating contractor, gas
company, or factory representative.
6.G Shutting Down the Unit
1. Switch off the main electrical disconnect switch. 2. Close all manual gas
valves. 3. If freezing is anticipated, drain this unit and be sure
to also protect building piping from freezing. This step to be performed by a
qualified service person.
6.H To Restart the Unit
If drained, follow Section 6.B in this manual for proper filling and purging.
- Switch off the main electrical disconnect switch. 2. Close all manual gas valves. 3. WAIT FIVE (5) MINUTES. 4. Set the aquastat or thermostat to its lowest setting. 5. Open all manual gas valves. 6. Reset all safety switches (pressure switch, manual reset high limit, etc.). 7. Set the temperature controller to the desired temperature setting and switch on electrical power.
- Burner will go through a prepurge period and ignitor warm-up period, followed by ignition.
Page 36
LAARS Heating Systems
SECTION 7
Maintenance
7.A System Maintenance
1. Lubricate the system water-circulating pump, if required, per the
instructions on the pump.
2. If a strainer is employed in a pressure reducing valve or the piping,
clean it every six months.
3. Inspect the venting system for obstruction or leakage at least once a
year. Periodically clean the screens in the vent terminal and combustion air
terminal (when used).
4. Keep the unit area clear and free from combustible materials, gasoline,
and other flammable vapors and liquids.
5. If the unit is not going to be used for extended periods in locations
where freezing normally occurs, it should be isolated from the system and
completely drained of all water. All systems connected to it should also be
drained or protected from freezing.
6. Low water cutoffs, if installed, should be checked every 6 months. Float
type low water cutoff should be flushed periodically.
7. Inspect flue passages, and clean with brushes/ vacuums, if necessary.
Sooting in flue passages indicates improper combustion. Determine the cause
and correct.
8. Inspect the vent system and air intake system, and if the vent system is
Category III, ensure that all joints are sealed properly. If joints need to be
resealed, completely remove existing sealing material, and clean with alcohol.
Apply new sealing material, and re-assemble.
7.B Maintenance and Component Description
Only genuine OEM replacement parts should be used.
CAUTION
Label all wires prior to disconnection when servicing controls. Wiring errors
can cause improper and dangerous
operation. Verify proper operation after servicing.
See Figure 5 for location of gas train components. The gas and electric
controls on the unit are engineered for long life and dependable operation,
but the safety of the equipment depends on their proper functioning. It is
strongly recommended that a qualified service technician inspect the basic
items listed below every year. a. Ignition controls b. Ignitors c. Water
temperature control d. Automatic gas valve e. Pressure switches f. Blowers
7.B.1 Burners Close main manual gas valve before proceeding.
Checking the burners for debris – Remove the ignitor inspection panels(s) and
ignitor(s) and inspect the burners through the ignitor hole(s) using a
flashlight to illuminate. If there is any indication of debris on the burners
that are visible, all the burners will need to be inspected more thoroughly.
Remove the screws from around the front of the air box (large panel from which
the ignitor inspection panel(s) were removed), and remove the large panel.
Remove the gas manifold assemblies and the burner panels. Inspect the burners.
Clean burners, if necessary, by blowing compressed air from the outside of the
burners into the center of the burner. A dirty burner may be an indication of
improper combustion or dirty combustion air. Determine the cause, and correct.
Replace the burners in the reverse order
7.B.2 Filter The filter used in the this unit is washable with an
83% arrestance. Since the filter is washable, it will only need replacement
when unwashable, deteriorated or damaged. If filter replacement is needed, it
should only be replaced with a factory part. Inspect the air filter. If there
is debris on the air filter, remove it from the filter box, and wash it with
mild soap and water. Ensure that the filter is completely dry before re-
installing, in reverse order.
7.B.3 Gas Valves The gas valves are designed to operate with supply
pressures of 4-13 inches w.c. (1.0 to 3.2 kPa). To remove a valve, shut off
120-volt power and the
manual gas shutoff valve. Remove the top front panel from the unit. Disconnect
the wires to the valve. Disengage the flanged fitting before and after the
valve, and remove the valve. Re-install in reverse order. Ensure o-rings are
properly installed for both inlet and outlet. Turn on manual gas shutoff valve
and 120 volt power and check operation and tightness of gas valve connections.
7.B.4 Manual Reset High Limit Control The high limit switch is manual reset
switch with
an adjustable set point, up to 240°F (116°C) on boiler models and 200°F (93°C)
on water heater models and boilers ordered with low temperature controls. To
replace the switch, shut off the 120-volt power to the unit. Remove the cover
from the switch to access the mounting screws. Remove the screws, and pull the
switch off the control panel. Remove the capilliary and bulb from the thermal
well located in the header. Replace in reverse order.
MIGHTY THERM2 Commercial Boilers and Volume Water Heaters
Page 37
7.B.5 Temperature Control The temperature control is a Honeywell L6008.
To replace the control, shut off the 120-volt power to the unit. Remove the
cover from the control panel, and remove the mounting screws to remove the
controller. Replace in reverse order.
7.B.6 Ignition Controls The ignition controls ensure the proved interrupted-
type ignition system. They control the hot surface ignitors and prove that the
flame signal is appropriate for powering the gas valves. It also controls the
blower’s pre-purge and post-purge. Model sizes 500 and 750 have one ignition
control. Sizes 1000 to 2000 have two ignition controls. On sizes up to 750,
one ignition control controls stages 1 and 2. On unit sizes 10002000, one
ignition control is for stage 1, and the other is for stage 2.
To replace a control, shut off the 120-volt power to the unit. Remove the
cover from the control panel. Remove the electrical connectors from the
ignition control. Take out the controller’s mounting screws, and pull the
controller out. Replace in reverse order.
change is required, turn off the 120-volt power and gas supply to the unit.
Remove the front panel. Disconnect the blower’s wire harness. Remove the
screws at the blower flange, and pull the blower out. Replace blower in
reverse order, ensuring that all joints are made correctly. After replacement,
ensure that the unit operates properly, by following the set-up procedure in
this manual.
7.B.10 Flow Switch This unit uses a paddle-type flow switch to ensure
that the unit has water flow before ignition is allowed.
7.B.11 Heat Exchanger Coil
WARNING
Black carbon soot buildup on a dirty heat exchanger can be ignited by a random
spark or flame, thereby creating a risk of fire or explosion.. To prevent this
from happening, dampen the soot deposits with a wet brush or fine water spray
before servicing the heat exchanger.
7.B.7 Ignitors/Sensor The ignitor/sensor used are 120v “hot surface”
type. They are energized whenever there is a call for heat and switched off
when ignition is established and flame has been sensed. Model sizes 500 and
750 have one ignitor/sensor. Sizes 1000 to 2000 have two ignitor/ sensors. To
replace the ignitor/sensor, shut off the 120-volt power to the unit, remove
the ignitor access panel, disconnect the Molex connector, remove the two
mounting screws on the ignitor/sensor flange and pull the ignitor out. ((Hot
Surface) Ignitor and the Flame Sensor are the same items). Install in reverse
order, always using a new ignitor gasket with the replacement ignitor.
CAUTION
Ignitor gets hot.
7.B.8 Transformer The transformer is not capable of supplying control
voltage for external devices such as zone valves, which must have their own
separate power supply. Should a transformer need replacing, shut off the
120volt power. Unplug the transformer wires, remove the mounting screws and
remove the transformer. Replace transformer in the reverse order.
7.B.9 Blowers The combustion air blowers bring the combustion
air for the this unit from the upper chamber to the lower chamber. Mixing of
the gas and air occurs in the burners. Sizes 500, 750 and 1000 each have one
blower, and sizes 1250 to 2000 each have two blowers. If a blower
This unit has a pre-mixed burner system. These systems provide the burners
with sufficient air for complete combustion, and black carbon sooting is
seldom experienced. If sooting is suspected, view ports for inspection of the
heat exchanger are provided on the right side of the boiler. They are located
below the headers, and are accessed by opening the small round cover that is
attached by one screw. In the unlikely event that there is a buildup of black
carbon soot or other debris on the heat exchanger, clean per the following:
1. Disconnect the electrical supply to the unit.
2. Turn off the gas supply by closing the manual gas valve on the heater.
3. Disconnect and remove the wires, conduit and sensors from all components
that are attached to the inlet/outlet header.
4. Isolate the heat exchanger from the water supply.
5. Disconnect the header flanges from the inlet and outlet.
6. Allow the heat exchanger to drain. Remove the front cover(s) by removing
the rubber access strip(s) and the retaining screws. Remove the venting and
remove the top, by removing the screws that attach the top to the side panels.
Remove the side panels. Remove the front lower panels sealing the combustion
area. To remove the gas train, disconnect the unions located below the
intermediate pan and the field installed union located outside the cabinet,
and pull up, bringing the union end connectors through the grommets in the
intermediate pan. To remove the intermediate pan, remove the slide out control
assembly and blower(s) to reveal the screws. Remove the screws holding the
intermediate pan, and lift up to remove it. The heat exchanger has integral
metal sections attached,
Page 38
LAARS Heating Systems
SECTION 8
Trouble Shooting
which connect to the frame of the boiler. Locate and remove the screws along
the front, rear and bottom of the integral metal sections, and remove the heat
exchanger and metal sections by lifting up. On the larger units, a center heat
exchanger support must be unbolted before it can be removed.
7. Remove the heat exchanger from the unit. Note: The heat exchangers are
heavy and may require two people to remove to avoid personal injury.
8. Clean the heat exchanger: A light accumulation of soot or corrosion on the
outside of the heat exchanger can be easily removed. Use a wire brush to
remove loose soot and scale from the heat exchanger. Do not use water or
compressed air for cleaning.
9. Note: While the heat exchanger is out of the unit, inspect the firewall
refractory insulation. Replace if necessary.
10. Inspect the inside of the copper tubes for scale buildup. Scale can build
up on the inner surface of the heat exchanger tubes, which can restrict water
flow. If the tubes show signs of scaling, clean the internal surface. The
manufacturer offers a tube cleaning kit, part number R0010000.
11. Reassemble in the reverse order, and check the units operation after
start-up.
NOTE: The Warranty does not cover damage caused by lack of required
maintenance, lack of water flow,
or improper operating practices.
8.A Resolving Lockouts
There are many causes of lockouts. The three most common causes are: (1)
inadequate gas supply, (2) poor combustion, (3) ignitor failure. 1. Inadequate
gas supply: Before proceeding, ensure
that the gas supply has not been shutoff or the LP tank (LP boilers) is not
empty.
If your boiler is equipped with the optional gas pressure switches, then the
Low Pressure switch might have tripped and will need to be reset.
Then, restart the boiler and observe the operational cycle. After a 15-second
fan pre-purge, the ignitor will heat up for 20 seconds, and then the unit will
light. If it does not, check the gas supply pressure to the unit, after
resetting the unit and attempting another start-up. The gas pressure to the
unit must be above 5″ W.C. (1.2kPa) throughout the entire start-up cycle. If
it is not, correct the supply problem (check gas valves or supply piping). If
the supply pressure is adequate, consult the factory for assistance. 2. Poor
combustion: Poor combustion should be suspected if there is a strong flue gas
odor. The odor may result from an improper gas/air ratio (high or low O2 or
CO2). These units operate best with 45% excess air (8% CO2 on natural gas,
9.2% CO2 on LP). Check the CO2 of the unit and adjust if necessary. 3. Ignitor
failure: If the boiler goes through a normal start cycle but combustion does
not occur, ignitor failure should be suspected. Check the ignitor by
unplugging the ignitor plug and measuring the ignitor resistance. It should be
50-80 ohms at room temperature. If the resistance is not 50-80 ohms, replace
the ignitor. If the resistance is correct, reset the boiler and check for 120
VAC at the ignitor plug during the start cycle. If there is no voltage,
replace the faulty ignitor wire harness or the ignition control.
8.B Delayed Ignition — Possible Causes
A defective burner can cause a delayed ignition. If the gas supply pressure is
proper and the gas valves are
functioning properly, then burners should be inspected. There should be no
distortion or perforations in the burners outside of the active burner port
area. Replace if indicated.
MIGHTY THERM2 Commercial Boilers and Volume Water Heaters
Page 39
8.C Short Cycling — Boiler
Because this unit is a stage-fired boiler, and its input will decrease when
there is a reduction in heating load, short cycling is greatly reduced. If the
heating load drops below the minimum input of the boiler for an extended
period, the boiler will have a tendency to short cycle. This can be a symptom
of improper control strategy or setpoints, or a load distribution problem.
Contact your manufacturers representative to discuss possible remedies.
8.D Short Cycling — Water Heater
Short cycling will generally occur only in combination space heating and water
heating applications when the water heater is operating in the space-heating
mode. Because the unit is a stage-fired water heater and its input will reduce
when there is a reduction in heating load, short cycling is greatly reduced.
If the heating load drops below the minimum input of the water heater for an
extended period, the water heater will have a tendency to short cycle. If
short cycling is frequently experienced, regardless of the control’s attempt
to limit it, the heating load should be redistributed to control it.
If short cycling occurs in a water heater application, it is probably caused
by undersized piping between the water heater and the storage tank or by some
other factor that restricts proper water flow through the water heater. The
cause should be determined and corrected.
8.E High Gas Consumption
Units operating with an improper air/fuel ratio are very inefficient and
consequently, have very high gas consumption. Because efficiency is high when
the CO2 is high (or O2 is low), units operating with low CO2 or high O2
(especially LP units) consume more gas. Adjust the CO2 or O2 for optimum
efficiency. If no combustion analyzing equipment (CO2 or O2) is available then
a proper adjustment of the air/fuel ratio (CO2 or O2) cannot be accomplished.
However, by briefly sniffing the flue gases it is possible to determine if the
CO2 or O2 is within the proper range. No significant flue gas odor should be
detected when combustion is proper. A strong piercing smell indicates poor
combustion and generally a lean mixture – low CO2 or high O2 . The CO2 should
be 8% at high fire. To check the CO2, first verify that the supply gas
pressure is within 5″ to 13″ w.c. (1.2 to 3.2 kPa) With the unit running with
all stages firing, set the air box pressure to 1.5″ w.c. (0.37 kPa) (as a
starting point), by adjusting the air shutter(s) at the bottom of the fan(s).
Check the CO2, and adjust the air shutters if further adjustment to the CO2 is
needed. Sizes 1250 to 2000 have two blowers and two air chambers (boxes). The
pressure of each air box must be equal when the final adjustment is made.
SECTION 9
Replacement Parts
Only genuine OEM replacement parts should be used.
9.A General Information
To order or purchase parts for this unit, contact your nearest Manufacturers
Representative or Distributor. See back cover for website.
9.B Parts List – see next pages.
IItem
1 2A 2B 3A 3B 4 5 6 7 8 9 10 11
12A 12B 12C 14
16 17 18 19 20 21 22
23 24 25 26 27
28 29 30 31
Description
Sheet Metal Components See Figure 23 Panel, Jacket, Front Panel, Jacket,
Side, Lower Left Panel, Jacket, Side, Lower Right Panel, Jacket, Side, Lower
Left Panel, Jacket, Side, Lower Right Panel, Side, Top Left, Jacket Panel,
Side, Top Right, Jacket Panel, Rear, Jacket Panel, Top, Jacket Weldment, Vent
Plate Weldment, Housing, Air Inlet/Filter Panel, Access, Filter Filter,
Combustion Air
Pump Housing Right Side Pump Housing Left Side Pump Housing Cover Cover, Pipe,
Gas Manifold
Size 500
5F3320 5F3420 5F3421 5F3520 5F3521 5F3400 5F3501 5F3220 5F3021 5F3100 5F3800
5F3701 A2088700
(1)
5C3018 5C3019 5C3020 5F3304
(2)
Internal Components See Figure 24 Assembly, Base Panel, Front, Combustion
Chamber Panel, Rear, Combustion Chamber Panel, Top, Combustion Chamber
Weldment, Chamber, Left Side, Bottom Weldment, Chamber, Right Side. Bottom
Panel, Chamber, Left/Right Side, Top
Assembly, Sight Glass Panel, Left Side, Air Box Panel, Right Side, Air Box
Panel, Access, Air Box Cover, Access Panel, Air Box
Divider, Chamber, Upper, Air Box Divider, Chamber, Lower, Air Box Divider,
Front Chamber, Combustion Chamber Assembly, Exhaust Stack
5F1020 5F2003 5F2006 5F2001 5C2602 5C2202 5C2002
(2) 10956000
5F2015 5F2016 5F2004 5F2005
(1)
5F2027
Size 750
7F3320 5F3420 5F3421 5F3520 5F3521 5F3400 5F3501 7F3220 7F3021 7F3100 5F3800
5F3701 A2088700
(1) 5C3018 5C3019 5C3020 5F3304
(2)
7F1020 7F2003 7F2006 7F2001 5C2602 5C2202 5C2002
(2) 10956000
5F2015 5F2016 7F2004 5F2005
(1)
7F2027
Size 1000
10F3320 5F3420 5F3421 5F3520 5F3521 5F3400 5F3501 10F3220 10F3021 7F3100
10F3800 5F3701 A2088700
(1) 5C3018 5C3019 5C3020 10F3304
(2)
10F1020 10F2003 10F2006 10F2001 5C2602 5C2202 5C2002
(2) 10956000
5F2015 5F2016 10F2004 5F2005
(1)
7F2027
Size 1250
12F3320 5F3420 5F3421 5F3520 5F3521 5F3400 5F3501 12F3220 12F3021 12F3100
12F3800 12F3701 A2088700
(2) 5C3018 5C3019 5C3020 20F3304
(2)
12F1020 12F2003 12F2006 12F2001 5C2602 5C2202 5C2002
(2) 10956000
5F2015 5F2016 12F2004 5F2005
(2) 15F2005 15F2002
12F2027
Size 1500
15F3320 5F3420 5F3421 5F3520 5F3521 5F3400 5F3501 15F3220 15F3021 12F3100
12F3800 12F3701 A2088700
(2) 5C3018 5C3019 5C3020 20F3304
(2)
15F1020 15F2003 15F2006 15F2001 5C2602 5C2202 5C2002
(2) 10956000
5F2015 5F2016 15F2004 5F2005
(2) 15F2005 15F2002
12F2027
Size 1750
17F3320 5F3420 5F3421 5F3520 5F3521 5F3400 5F3501 17F3220 17F3021 12F3100
12F3800 12F3701 A2088700
(2) 5C3018 5C3019 5C3020 20F3304
(2)
17F1020 17F2003 17F2006 17F2001 5C2602 5C2202 5C2002
(2) 10956000
5F2015 5F2016 17F2004 5F2005
(2)
20F2002 12F2027
Size 2000
20F3320 5F3420 5F3421 5F3520 5F3521 5F3400 5F3501 20F3220 20F3021 20F3100
20F3800 12F3701 A2088700
(2) 5C3018 5C3019 5C3020 20F3304
(2)
20F1020 20F2003 20F2006 20F2001 5C2602 5C2202 5C2002
(2) 10956000
5F2015 5F2016 20F2004 5F2005
(2)
20F2002 12F2027
LAARS Heating Systems
Page 40
Item Description
32
Assembly, Copper Tube, Heat Exchanger
Assembly, Cupro-Nickel, Heat Exchanger
33
Tile, Side (Left and Right)
34
Tile, Front
35
Tile, Front, Left Side
36
Tile, Front, Right Side
37
Tile, Front, Center
38
Tile, Rear
39
Tile, Rear, Left Side
40
Tile, Rear, Right Side
41
Tile, Rear, Center
42
Tile, Bottom
43
Tile, Bottom, Left Side
44
Tile, Bottom, Right Side
45
Tile, Bottom, Center
Gas Train Components See Figure 24
46
Blower
47
Weldment, Blower Mount
47A Assembly, Blower Damper
48
Manifold, Gas Supply
49
Valve, Ball, Manual Shutoff
50
Valve, Gas, Combination
50A O-Ring
51A Weldment, Pipe, Gas Valve/Ball Valve
51B 4″ Nipple, black
51C Union
52
Valve, Ball, Manual Shutoff, Secondary
53
Manifold, 3 Burner/Orifice, Left
Size 500 5C4000 5C4020 T2015600 (2) T2017300 T2016200
T2015700
T2015500
Size 750 7C4000 7C4020 T2015600 (2)
T2016800 T2016300
T2017500 T2016600
T2017400 T2016500
Size 1000 10C4000 10C4020 T2015600
(2)
T2016800 T2017100
T2016600 T2016600
T2017400 T2017400
Size 1250 12C4000 12C4020 T2015600
(2)
T2016800 T2017900 T2016900
(1)
T2016600 T2018100 T2017200
(1)
T2017400 T2018000 T2015900
(1)
Size 1500 15C4000 15C4020 T2015600
(2)
T2016800 T2017100 T2016900
(1)
T2016600 T2016600 T2017200
(1)
T2017400 T2017400 T2015900
(1)
Size 1750 17C4000 17C4020 T2015600
(2)
T2016800 T2017900 T2016900
(2)
T2016600 T2018100 T2017200
(2)
T2017400 T2018000 T2015900
(2)
Size 2000 20C4000 20C4020 T2015600
(2)
T2016800 T2017100 T2016900
(2)
T2016600 T2016600 T2017200
(2)
T2017400 T2017400 T2015900
(2)
A2111900 (1)
5C5300 (1)
5C6100 V2003100 V2017600
(2) V2017500
(4) P2073600 (2) P0014700 (2) P0030400 (2)
V2000200 (2)
L2012800 (1)
A2111900 (1)
5C5300 (1)
7C6100 V2003100 V2017600
(3) V2017500
(6) P2073600 (3) P0014700 (3) P0030400 (3)
V2000200 (3)
L2012800 (2)
A2111900 (1)
5C5300 (1)
10C6100 V2003200 V2017600
(3) V2017500
(6) P2073600 (3) P0014700 (3) P0030400 (3)
V2000200 (3)
A2111900 (2)
5C5300 (2)
15C5400 (2)
12C6100 V2003300 V2017600
(5) V2017500
(10) P2073600 (5) P0014700 (5) P0030400 (5)
V2000200 (5)
L2012800 (3)
A2111900 (2)
5C5300 (2)
15C5400 (2)
15C6100 V2003300 V2017600
(5) V2017500
(10) P2073600 (5) P0014700 (5) P0030400 (5)
V2000200 (5)
L2012800 (1)
A2111900 (2)
5C5300 (2)
15C5400 (2)
17C6100 V2003300 V2017600
(6) V2017500
(12) P2073600 (6) P0014700 (6) P0030400 (6)
V2000200 (6)
L2012800 (2)
A2111900 (2)
5C5300 (2)
15C5400 (2)
20C6100 V2003300 V2017600
(6) V2017500
(12) P2073600 (6) P0014700 (6) P0030400 (6)
V2000200 (6)
Page 41
MIGHTY THERM2 Commercial Boilers and Volume Water Heaters
Item Description Manifold, 3 Burner/Orifice, Right Manifold, 4 Burner/Orifice, Left
Size 500
L2012900 (1)
Manifold, 4 Burner/Orifice, Right
54
Assembly, 3 Burner
Assembly, 4 Burner
L2012200 (2)
55
Orifice, Gas, Natural
Orifice, Gas, Propane
56
Gasket, 3 Burner
Gasket, 4 Burner
L2013000 (6)
L2012400 (6)
S2012700 (2)
57
Ignitor, Hot Surface with Gasket
2400-286 (1)
Heat Exchanger Components See Figure 25
58
Flow Switch
E0013000
59
Low Water Cutoff (optional)
E2076500
60
Gauge, Temperature/Pressure
A0079000
62
Tee, Adapter, Outlet, Cast Iron
20130001
Tee, Adapter, Outlet, Cast Iron (boiler)
Tee, Adapter, Outlet, Bronze
20150302
63
Relief Valve, Hydronic, 75 Psi
RA2138800
Relief Valve, Water Heater, 125 Psi
RA2138900
64
Flange, Connection, Cast Iron
10391302
Flange, Connection, Bronze
20255401
65
Gasket, Connection Flange
S0063700
(2)
66
Cover, In/Out, Glass-Lined Cast Iron
10364504
Cover, In/Out, Bronze
10364501
67
Gasket, Header/Cover
S0095100
(2)
68
Water Barrier, Inlet/Outlet
20230101
Size 750 L2012900 (1)
L2012200 (3)
L2013000 (9)
L2012400 (9)
S2012700 (3)
2400-286 (1)
E0013000 E2076500 A0079000 20130001
20150302 RA2138800 RA2138900 10391302 20255401 S0063700
(2) 10364504 10364501 S0095100
(2) 20230101
Size 1000
L2012600 (2)
L2012700 (1)
L2012500 (3)
L2013000 (12)
L2012400 (12)
S2012500 (3)
2400-286 (2)
E0013000 E2076500 A0079000 20130002
20150303 RA2138801 RA2138900 10391303 10391304 S0063700
(2) 10364504 10364501 S0095100
(2) 20230101
Size 1250 L2012900
(2)
L2012200 (5)
L2013000 (15)
L2012400 (15)
S2012700 (5)
2400-286 (2)
E0013000 E2076500 A0079000 20130002
20150303 RA2138801 RA2138900 10391303 10391304 S0063700
(2) 10364504 10364501 S0095100
(2) 20230101
Size 1500 L2012900
(1) L2012600
(2) L2012700
(1) L2012200
(2) L2012500
(3) L2013000
(18) L2012400
(18) S2012700
(2) S2012500
(3) 2400-286
(2)
E0013000 E2076500 A0079000 20130002
20150303 RA2138802 RA2138900 10391303 10391304 S0063700
(2) 10364504 10364501 S0095100
(2) 20230101
Size 1750
L2012900 (1)
L2012600 (2)
L2012700 (1)
L2012200 (3)
L2012500 (3)
L2013000 (21)
L2012400 (21)
S2012700 (3)
S2012500 (3)
2400-286 (2)
E0013000 E2076500 A0079000 20130002 20130009 20150303 RA2138802 RA2138900
10391303 10391304 S0063700
(2) 10364504 10364501 S0095100
(2) 20230101
Size 2000
L2012600 (4)
L2012700 (2)
L2012500 (6)
L2013000 (24)
L2012400 (24)
S2012500 (6)
2400-286 (2)
E0013000 E2076500 A0079000 20130002 20130009 20150303 RA2138802 RA2138900
10391303 10391304 S0063700
(2) 10364504 10364501 S0095100
(2) 20230101
LAARS Heating Systems
Page 42
Item Description
69
Baffle, Water Deflector, Inlet
70
Well, Immersion, Temperature Control
71
Cover, Return, Glass-Lined Cast Iron
Cover, Return, Bronze
72
Pump Housing, Glass-Lined Cast Iron
73
Baffle, Diffuser, Pump Housing Inlet
Size 500 10338300 E2058300 10364300 10364301 S2056900 10338400
Electrical Components See Figure 26
74
Control, Gas Ignition, Three-Try (standard)
E2313900
(1)
Control, Gas Ignition, Single-Try (CSD-1 option) E2107300
(1)
75
SPDT, Toggle Switch
E0109200
75A DPDT Switch
E2056300
76
Terminal Block, 16-Position, Dual Row
E2327500
77
Switch, Hi-Limit Manual Reset (boiler)
E0015900
Controller, Temperature, 100° to 200°F,
E2217800
Manual Reset
78
Thermostat, 2-Stage, 130° to 230°F
E0093200
79
Panel, Mounting, Limits/Ignition Control
5F7001
80
Panel, Cover, High Limit/Ignition Control
5F7003
81
Panel, Access, Terminal
5F7006
82
Switch, Rocker, 30A, 125 VAC
E2343300
83
Terminal Block, 6-Position, Dual Row
E2327700
84
Terminal Block, 12-Position, Dual Row
E2342500
85
Switch, Pressure, Diaphragm, SPDT
E0240900
(2)
86
Bracket, Pressure Switch
5F7007
87
Transformer, 150 VA, 120/24V
E2310400
88
Relay, Time Delay (24 VAC)
E2077700
Delay on Break, Adj.
89
Relay, 24VAC, DPDT
E2327800
90
Panel, Mounting, LWCO Switch (optional)
91
Wire Harness #1, Fenwal
92
Wire Harness #2, Control Panel
93
Wire Harness #3, Main
94
Wire Harness #4, Local Remote SW
5F7005 E2328800 E2328900 E2329000 E2328700
NOTE: Quantity is one (1) unless otherwise indicated.
Size 750 10338300 E2058300 10364300 10364301 S2056900 10338400
E2313900 (1)
E2107300 (1)
E0109200 E2056300 E2327500 E0015900 E2217800
E0093200 5F7001 5F7003 5F7006
E2343300 E2327700 E2342500 E0240900
(2) 5F7007 E2310400 E2077700
E2327800
5F7005 E2328800 E2328900 E2329000 E2328700
Size 1000 10338300 E2058300 10364300 10364301 S2056900 10338400
E2313900 (2)
E2317300 (2)
E0109200 E2056300 E2327500 E0015900 E2217800
E0093200 5F7001 5F7003 5F7006
E2343300 E2327700 E2342500 E0240900
(2) 5F7007 E2310400 E2077700
5F7005 E2328400 E2328500 E2329100 E2328700
Size 1250 10338300 E2058300 10364300 10364301 S2056900 10338400
E2313900 (2)
E2317300 (2)
E0109200 E2056300 E2327500 E0015900 E2217800
E0093200 5F7001 5F7003 5F7006
E2343300 E2327700 E2342500 E0240900
(3) 5F7007 E2310400 E2077700
E2327800 (2)
5F7005 E2328400 E2330100 E2328600 E2328700
Size 1500 10338300 E2058300 10364300 10364301 S2056900 10338400
E2313900 (2)
E2317300 (2)
E0109200 E2056300 E2327500 E0015900 E2217800
E0093200 5F7001 5F7003 5F7006
E2343300 E2327700 E2342500 E0240900
(3) 5F7007 E2310400 E2077700
E2327800 (2)
5F7005 E2328400 E2330100 E2328600 E2328700
Size 1750 10338300 E2058300 10364300 10364301 S2056900 10338400
E2313900 (2)
E2317300 (2)
E0109200 E2056300 E2327500 E0015900 E2217800
E0093200 5F7001 5F7003 5F7006
E2343300 E2327700 E2342500 E0240900
(3) 5F7007 E2310400 E2077700
E2327800 (2)
5F7005 E2328400 E2330100 E2328600 E2328700
Size 2000 10338300 E2058300 10364300 10364301 S2056900 10338400
E2313900 (2)
E2317300 (2)
E0109200 E2056300 E2327500 E0015900 E2217800
E0093200 5F7001 5F7003 5F7006
E2343300 E2327700 E2342500 E0240900
(3) 5F7007 E2310400 E2077700
E2327800 (2)
5F7005 E2328400 E2330100 E2328600 E2328700
Page 43
MIGHTY THERM2 Commercial Boilers and Volume Water Heaters
Page 44
12C
12B
12A
LAARS Heating Systems
Figure 23. Sheet Metal Components.
MIGHTY THERM2 Commercial Boilers and Volume Water Heaters
Page 45
Figure 24. Internal Components
Page 46
LAARS Heating Systems
Size Size 500 750 1000 1250 1500 1750 2000
Hydronic Boiler Pump p/n A2001700 A2001700 A2001800 A2001800 A2001900 A2001900 A2109700
Figure 25. Heat Exchanger Components.
Size
500 750 1000 1250 1500 1750 2000
Soft Water A2001700 A2001700 A2001700 A2001700 A2001700 A2001900 A2109700
Water Heater Pump p/n
Normal Water A2001700 A2001700 A2001800 A2001800 A2001900 A2001900 A2109700
Hard Water A2001900 A2001900 A2001900 A2001900 A2001900 A2001900 A2109700
MIGHTY THERM2 Commercial Boilers and Volume Water Heaters
Page 47
Figure 26. Electrical Components.
MIGHTY THERM2 Commercial Boilers and Volume Water Heaters
Notes:
All Manuals (Install & Operate, Start Up, and Service Manuals) can be downloaded at
For LAARS Product and Service VIDEOS
www.laars.com
https://www.youtube. com/user/LaarsHeating
H2329100M
Laars Heating Systems Company reserves the right to change specifications, components, features, or to discontinue products without notice.
Customer Service and Product Support: 800.900.9276 · Fax 800.559.1583
Headquarters: 20 Industrial Way, Rochester, NH, USA 03867 · 603.335.6300 · Fax 603.335.3355
9 Brigden Gate, Halton Hills, Ontario, Canada L7G 0A3 · 905.203.0600 · Fax 905.636.0666
www.Laars.com
Litho in U.S.A. © Laars Heating Systems 23-06 Document 1211M
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>