Taco 0034ePlus ECM High Efficiency Circulator with Digital Display Controller Instruction Manual
- June 17, 2024
- TACO
Table of Contents
Taco 0034ePlus ECM High Efficiency Circulator with Digital Display
Controller
Product Information
Specifications:
- Model: ECM High-Efficiency Circulator with Digital Display Controller
- Model Numbers: 0034eP-F2 (Cast Iron), 0034eP-SF2 (StainlessSteel)
- Part Number: 102-544
- Plant ID No.: 001-5063
- Energy Efficiency: Up to 85% compared to equivalent AC permanent split capacitor circulators
- Conforms to: UL STD. 778
- Certified to: CAN/CSA STD. C22.2 NO. 108, NSF/ANSI/CAN 61 & 372
Installation:
Before installing the ECM High-Efficiency Circulator, please read and
understand the following instructions:
Fluid Compatibility
CAUTION: The addition of petroleum-based fluids or certain chemical additives to systems using TACO equipment voids the warranty. Consult the factory for fluid compatibility.
Elevation Considerations
CAUTION: Installations at elevations over 5000 feet must have a higher fill pressure of at least 20 psi to prevent pump cavitation and flashing. Premature failure may result. Adjust the expansion tank pressure to equal the fill pressure. A larger size expansion tank may be required.
Piping Diagrams
The circulator can be installed on the supply or return side of the boiler,
but for best system performance, it should always pump away from the expansion
tank. Refer to Figure 2 and Figure 3 for preferred piping diagrams.
Figure 2: Preferred Piping for Circulators on Boiler Supply
Figure 3: Preferred Piping for Circulators on Boiler Return
Figure 4: Preferred Primary/Secondary Piping for Circulators on Boiler Supply
Mounting Position
The circulator must be mounted with the motor in the horizontal position.
Refer to Figure 4 and Figure 5 for acceptable and unacceptable motor mounting
orientations. See Figure 6 for the Rotating Control Cover.
Figure 4 : Acceptable Mounting Positions
Figure 5: Unacceptable Mounting Positions
Figure 6: Rotating Control Cover
The 0034ePlus is equipped with a symmetrical control cover connected to the pump with a ribbon cable. The cover can be removed, rotated, and repositioned for best viewing and user operation. It allows the installer to mount the circulator casing in any flow direction, then rotate the cover accordingly.
FAQ:
Q: Can I use flat rubber gaskets?
A: No, flat rubber gaskets should not be used. Only use the O-ring
gaskets provided to prevent leaks and avoid voiding the warranty.
Q: What should I do if I need to install the circulator at an elevation
over 5000 feet?
A: For installations at elevations over 5000 feet, ensure that the fill
pressure is at least 20 psi to prevent pump cavitation and flashing. Adjust
the expansion tank pressure to match the fill pressure, and consider using a
larger size expansion tank if necessary.
Q: Where can I find the preferred piping diagrams for the circulator?
A: The preferred piping diagrams can be found in the user manual under
the “Piping Diagrams” section. Refer to Figure 2 for preferred piping on the
boiler supply side, Figure 3 for preferred piping on the boiler return side,
and Figure 4 for preferred primary/secondary piping on the boiler supply side.
DESCRIPTION
The 0034ePlus is a high performance, variable speed, high-efficiency, wet-
rotor
circulator with an ECM, permanent magnet motor and an advanced digital LED
display controller for easy programming and diagnostic feedback. With 5
operating modes and simple keypad programming, its variable speed performance
curves are equivalent to the Taco 009, 0010, 0011, 0012, 0012 3-Speed, 0013,
0013 3-Speed & 0014. Ideal for large residential and light commercial
hydronic heating, chilled water cooling and domestic hot water systems. The
0034ePlus reduces power consumption by up to 85% compared to equivalent AC
permanent split capacitor circulators.
APPLICATION
- Maximum operating pressure: 150 psi (10.3 bar)
- Minimum NPSHR: 18 psi at 203˚F (95˚C)
- Maximum fluid temperature: 230°F (110˚C)
- Minimum fluid temperature: 14°F (-10˚C)
- Electrical specifications:
- Voltage: 115/208/230V, 50/60 Hz, single phase
- Maximum operating power: 170W
- Maximum amp rating: 1.48 (115V) / .70 (230V)
- Equipped with a cast iron or stainless steel casing
- SS Model suitable for open loop potable water systems
- Taco circulator pumps are for indoor use only – employer uniquement a l’interieur
- Acceptable for use with water or maximum of 50% water/glycol solution
FEATURES
- Simple keypad programming
- Digital LED screen display (Watts, GPM, Head, RPM and diagnostic error codes)
- Five operating modes to match any system requirements – TacoAdapt™, Constant Pressure, Proportional Pressure, Variable Fixed Speed or 0-10V DC input
- Replaces all single-speed and 3-speed circulators in its class
- ECM performance equivalent to Taco’s 009, 0010, 0011, 0012, 0013 & 0014 circulators
- Multi-color LED display showing power on, mode setting and error code diagnostics
- Use with a Taco ZVC Zone Valve Control or SR Switching Relay for ON/OFF operation
- Nut-capture feature on flanges for easier fit-up
- Dual electrical knockouts and removable quick-connect terminal strip for easy wiring
- Whisper quiet operation
- BIO Barrier® protects the pump from system contaminants
- SureStart® automatic unblocking and air purging mode
- Rotatable control cover to allow any pump body orientation
INSTALLATION
WARNING: Do not use in swimming pool or spa areas. Pump has not been investigated for these applications.
CAUTION: The addition of petroleum-based fluids or certain chemical additives to systems using TACO equipment voids the warranty. Consult factory for fluid compatibility.
-
Location: The circulator can be installed on the supply or return side of the boiler but for best system performance, it should always pump away from the expansion tank. See piping diagrams in Figure 2 & Figure 3.
NOTE: Two shorter 1-1/4” x 7/16” flange bolts are provided with the circulator to use on the discharge flange to prevent interference with the circulator casing.
CAUTION: Do not use flat rubber gaskets. Only use O-ring gaskets provided or leaks may result. Warranty will be void. -
Mounting position: Circulator must be mounted with the motor in the horizontal position. See Figure 4 & Figure 5 below for acceptable and unacceptable motor mounting orientations. See Figure 6 for Rotating Control Cover.
The 0034ePlus is equipped with a symmetrical control cover connected to the pump with a ribbon cable. The cover can be removed, rotated and repositioned for best viewing and user operation. It allows the installer to mount the circulator casing in any flow direction, then rotate the cover to the upright position. Remove the 4 cover screws, rotate cover to upright position, reattach cover with 4 screws.
CAUTION: To reduce the possibility of noise transmission, be sure to add vibration dampeners to piping when mounting circulator to wall or floor joists. -
Filling the system: Fill the system with tap water or a maximum of 50% propylene-glycol and water solution. The system must be filled before operating the circulator. The bearings are water lubricated and should not be allowed to operate dry. Filling the system will result in immediate lubrication of the bearings. It is always good practice to flush a new system of foreign matter before starting the circulator.
WARNING: Risk of electric shock. To reduce the risk of electric shock, be certain that it is connected only to a properly grounded, grounding-type receptacle. Follow all local electrical and plumbing codes.
WARNING:- Use supply wires suitable for 90°C.
- Disconnect power when servicing.
CAUTION: Use flexible conduit only. Not for use with rigid conduit.
Wiring Diagram
-
Wiring the circulator: Disconnect AC power supply. Remove terminal box cover. Attach a wiring connector into knockout hole. Use flexible conduit only. The green terminal plug may be removed to simplify wiring, then snapped back in place. Connect Line/Hot power to the L terminal, Neutral to the N terminal and Ground to the G terminal. See wiring diagram above. Replace terminal box cover. Insert rubber cap plug provided to cover unused knockout hole.
-
Wiring the circulator for 0-10V DC Operation: (See Page 10)
-
Start the circulator: When purging the system, it is recommended to run the circulator at full speed long enough to remove all remaining air from the bearing chamber. This is especially important when installing the circulator in the off-season. Set operating mode to Fixed Speed on 100% HIGH setting for maximum fixed speed. A blue LED will illuminate when the 0034ePlus is powered on.
CAUTION: Never run the circulator dry or permanent damage may result.
Full Speed Operation:
To run the pump at full speed during the fast fill, start-up and purge process, set operating mode to Fixed Speed on 100% HIGH setting. (See “Programming your 0034ePlus Circulator”). The LED will change to blue. To return to the normal operating mode, reset operating mode to desired TacoAdapt™, Constant Pressure, Proportional Pressure,Fixed Speed or 0-10V setting. -
Programming your 0034ePlus circulator: Modify the performance of the circulator as needed by changing the operating mode using the easy programming button keypad. When the circulator is powered on, the LED will illuminate and change color based on the operating mode selected. The LED will flash each time a setting is changed. See diagram below to set pump for desired operating mode. The selection of the right operating curve depends on
the characteristics of the system and the actual flow/head requirements. See Pump Curves on pages 7, 8, 9 & 12 to determine the best operating mode for the system. See cross-reference replacement chart on the back page.
The 0034ePlus has 5 Operating Modes:
- TacoAdapt™ — Automatic, self-adjusting, proportional pressure, variable speed (Violet LED)
- Constant Pressure — 5 curve settings of constant pressure, variable speed (Orange LED)
- Proportional Pressure — 5 curve settings of proportional pressure, variable speed (Green LED)
- Fixed Speed — Variable fixed speed settings (1 – 100%) (Blue LED)
- 0-10V DC — Analog external input or PWM pulse width modulation input from building control system, variable speed (Yellow LED)
Change the performance of the circulator according to the need, using “SET”, DOWN and UP buttons.
TacoAdapt™ Mode:
TacoAdapt™ is an operating mode designed for constant circulation systems.
On this setting, the circulator will sense changes in system flow and head
conditions and adjust the operating curve automatically. See TacoAdapt™
operating range in the chart to the right.
Constant Pressure Mode:
Circulator will vary speed to maintain desired feet of head constant pressure
curve. There are 5 setting options: 6 – 30 feet.
Proportional Pressure Mode:
Circulator will vary speed to maintain desired feet of head proportional
pressure curve.
There are 5 setting options:
8.2 – 28.6 ft.
Fixed Speed Mode:
External connection for 0-10V DC / PWM signal
WARNING: If there is a need to make external connection (PLC / Pump
Controller) it is mandatory to perform the following operations.
Variable fixed speed operation. Setting from 1 – 100% speed.
- Remove the four screws (Figure 8 – Ref. 1) attaching the control cover (Figure 8 – Ref. 2).
- Unscrew a signal input / output cap (Figure 8 – Ref. 3).
- Remove the green terminal plug (Figure 8 – Ref. 4) from the electronic board (Figure 8 – Ref. 5).
- Insert the cable (Figure 8 – Ref. 6) in the cable strain relief gland M12x1.5 (Figure 8 – Ref. 7) provided in carton and screw it to the cover.
- Strip (Minimum .25”) the ends of the wires, insert them into the connector as shown (Figure 8 – Ref. 4) and fix them with screws (Figure 8 – Ref. 8).
- Re-connect the terminal plug to the electronic board, replace the control cover and secure it with the screws.
Analog Input
In the “external input” mode, the circulator accepts either a 0-10VDC voltage
signal or a PWM signal. The selection of the signal type is automatically made
by the circulator without operator intervention.
Input 0-10V DC
The circulator operates at variable speed depending on the DC input voltage.
At voltages below 1.5 V, the circulator is in “standby” mode. LED will be
flashing yellow in “standby” mode.
At voltages between 2 V and 10 V, the circulator operates at a variable speed
depending on the voltage:
- 0% for a voltage not exceeding or equal to 2 V
- 50% at 7 V
- 100% for voltages greater than or equal to 10 V
Between 1.5 V and 2 V the circulator can be in “standby” or at minimum speed depending on the previous state (hysteresis). See diagram.
PWM Input
Circulator operates at variable speed according to digital input duty cycle.
PWM digital input is shared with 0-10V DC analog input, the pump will
automatically switch between different input protocols when it detects a
constant frequency input signal. 0% and 100% PWM inputs are not valid and will
be treated as an analog input.
PWM amplitude must be from 5 to 12V, frequency between 200Hz to 5kHz
Operations based on PWM input:
- Standby for PWM below 5%
- Min speed for PWM between 9-16%
- Half speed for 50% PWM
- Max speed for PWM in over 90%
Between 5% to 9% PWM the circulator remainsin standby or run mode according to minimum threshold.
IMPORTANT: If the input remains disconnected, the circulator goes into Standby Mode.
In the operating mode with external connection for 0-10V, the “Standby” mode is indicated by the Yellow LED (flashing slowly) and the word “Stb” on the display.
Analog Output 0-10V DC
The circulator has an analog output signal feature to indicate the operating
status
0 V | Circulator off, not powered |
---|---|
2 V | Circulator powered in standby |
4 V | Circulator on and running |
6 V | Warning presence (overheating, air) |
10 V | Alarm presence (Circulator blocked, under voltage, over |
temperature)
Errors List
The presence of errors is indicated by a Red LED and by the “Error Code” on
the display.
E1 | Pump locked / Loss of step | Stop |
---|---|---|
E2 | Under Voltage | Stop |
E3 | Overheating Warning | It operates in limited power |
E4 | Overheating Alarm | Stop |
E5 | Communication with inverter card is interrupted | It works in recover |
mode
E6| SW cards error. Pumps are incompatible with each other.| It works in
recover mode
0-10V DC Input Mode:
The circulator will vary its speed and performance based on a 0-10V DC analog
signal external input.
Troubleshooting the error codes
Listed below are potential diagnostic error codes which will appear on the LED display in case of a malfunction.
FAULTS | CONTROL PANEL | CAUSES | REMEDIES |
---|
The circulator is noisy
|
LED on
| Suction pressure is insufficient – cavitation|
Increase the system suction pressure within the permissible range.
LED on| Presence of foreign bodies in the impeller| Disassemble the motor and clean the impeller.
Loud noises of water circulation
|
Flashing white LED
|
Air in the system. Circulator may be air-bound.
| Vent the system.
Repeat fill and purge steps.
Circulator is not running although the electrical power supply is switched on
|
LED off
|
Lack of power supply
|
Verify voltage value of the electric plant. Verify the connection of the motor.
Circuit breaker might be tripped| Check circuit breaker at panel and reset if
necessary.
The circulator is defective| Replace the circulator.
Overheating
|
Let the circulator cool down for some minutes.
Then try to restart it. Verify that the water and ambient temperature are within the indicated temperature ranges.
LED red
|
The rotor is blocked
| Disassemble the motor and clean the impeller. See unlocking procedure below.
Insufficient supply voltage
|
Verify that the power supply matches the data on the name plate.
Building does not get warm
| LED on|
System may be air-bound
| Vent system.
Repeat fill and purge steps.
Unlocking Procedure: A red LED indicates the circulator is locked or
sticking. Disconnect and connect
power supply to start the automatic release process. The circulator makes 100
attempts to restart (process lasts approximately 15 minutes). Every restart is
signaled by a short white flash of the LED. If the locking is not removed
through the automatic release process after 100 attempts to restart the
circulator, it goes into standby and the LED remains red. In this case follow
the manual procedure described in the next steps: during any attempt, the red
LED keeps blinking; after that the circulator tries again to start. If the
locking is not removed through the automatic release process (the warning
light returns to red), perform the manual steps described below.
- Disconnect power supply – the warning light switches off.
- Close both isolating valves and allow cooling. If there are no shut-off devices,drain the system so that the fluid level is beneath that of the circulator.
- Loosen 4 motor bolts. Remove motor from casing. Carefully pull the rotor/impeller from the motor.
- Remove impurities and deposits from the impeller and casing.
- Reinsert the rotor/impeller into the motor.
- Connect power supply. Check for impeller rotation.
- If the circulator still doesn’t run it will need to be replaced.
Technical Menu
Proceed as follows to access the technical menu:
- Press the UP and DOWN buttons simultaneously for 5s, the message “tECH” will appear in the display.
- Press the “SET” button and select the parameter to be displayed by pressing the UP or DOWN buttons. (See below).
- Press the “SET” button and select the desired parameter.
IMPORTANT: After 10 seconds of inactivity, the circulator leaves the technical menu and returns to normal operation.
Parameters | Meaning |
---|---|
T 0 | Display Firmware version |
T 1 | Inverter Firmware version |
T 2
| Unit of measurement shown on the display:
• SI = System International (European)
• IU = Imperial units
T 3| Maximum pump head
T 4| Analog input voltage 0-10V
T 5| “Duty Cycle” PWM input
T 6| Mains voltage
T 7| Internal inverter voltage
T 8
| Pump working hours
(in thousands, 0.010 = 10 hours, 101.0 = 101,000 hours)
T 9| Ignitions counter
T 10| Standby counter
T 11| Rotor blocks counter
T 12| Step losses counter
T 13| Under voltages counter
T 14| Over voltages counter
T 15| Counter for missing internal cards communications
Replacement Parts List
007-007RP | Flange Gasket set |
---|---|
198-213RP | Casing ‘O’ Ring |
198-3251RP | Control Panel Cover (0034ePlus Digital Display) |
198-3247RP | Terminal Box Cover |
198-3185RP | Wiring Connector (Green) |
198-217RP | Terminal Box cover screws (5 per bag) |
0034ePlus Pump Replacement Cross Reference (6-1/2” Flange to Flange Dimension)
Taco | Bell & Gossett | Armstrong | Grundfos | Wilo |
---|
2400-10
2400-20
2400-30
2400-40
110
111
112
113
009
0010
0011
0012
0013
0014
| PL 50
PL 45
PL 36
PL 30 E90 1AAB
Series 60 (601) Series HV Series PR Series HV Series 100
NRF 45
NRF 36
ECOCirc XL 36-45
| E 11
E 10
E 8
E 7
S 25
H 63
H 52
H 51
Astro 290
Astro 280
Astro 210
1050 1B
1050 1 1/4B
Compass ECM
| TP(E) 32-40
UP 50-75
UPS 43-100
UPS 50-44
UP 43-75
UP(S) 43-44
UP 26-116
UP(S) 26-99
UP 26-96
UP 26-64
UPS 32-40
UPS 32-80
Magna 32-100
Magna 32-60
Alpha2 26-99
| Stratos: 1.25 x 3 – 35
1.25 x 3 – 30
1.25 x 3 – 25
1.25 x 3 – 20
Top S:
1.25 x 15
1.25 x 25
1.25 x 35
1.50 x 20
Top Z:
1.5 x 15
1.5 x 20
NOTE: Flange size and flange to flange dimensions will vary by competitive model and may require some piping changes.
LIMITED WARRANTY STATEMENT
Taco, Inc. will repair or replace without charge (at the company’s option) any
Taco product which is proven defective under normal use within three (3) years
from the date code.
In order to obtain service under this warranty, it is the responsibility of
the purchaser to promptly notify the local Taco stocking distributor or Taco
in writing and promptly deliver the subject product or part, delivery prepaid,
to the stocking distribu-tor. For assistance on warranty returns, the pur-
chaser may either contact the local Taco stock-ing distributor or Taco. If the
subject product or part contains no defect as covered in this war-ranty, the
purchaser will be billed for parts and labor charges in effect at time of
factory exami-nation and repair.
Any Taco product or part not installed or operated in conformity with Taco
instructions or which has been subject to misuse, misapplication, the addi-
tion of petroleum-based fluids or certain chemical additives to the systems,
or other abuse, will not be covered by this warranty.
If in doubt as to whether a particular substance is suitable for use with a
Taco product or part, or for any application restrictions, consult the
applicable Taco instruction sheets or contact Taco at
(401-942-8000).
Taco reserves the right to provide replacement products and parts which are
substantially similar in design and functionally equivalent to the defective
product or part. Taco reserves the right to make changes in details of design,
construc-tion, or arrangement of materials of its products without
notification.
TACO OFFERS THIS WARRANTY IN LIEU OF ALL OTHER EXPRESS WARRANTIES. ANY
WARRANTY IMPLIED BY LAW INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS IS
IN EFFECT ONLY FOR THE DURA-TION OF THE EXPRESS WARRANTY SET FORTH IN THE
FIRST PARAGRAPH ABOVE.
THE ABOVE WARRANTIES ARE IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR
STATUTORY, OR ANY OTHER WARRANTY OBLIGATION ON THE PART OF TACO.
TACO WILL NOT BE LIABLE FOR ANY SPECIAL INCIDENTAL, INDIRECT OR CONSEQUENTIAL
DAMAGES RESULTING FROM THE USE OF ITS PRODUCTS OR ANY INCIDENTAL COSTS OF
REMOVING OR REPLACING DEFECTIVE PRODUCTS.
This warranty gives the purchaser specific rights, and the purchaser may have
other rights which vary from state to state. Some states do not allow
limitations on how long an implied warranty lasts or on the exclusion of
incidental or conse-quential damages, so these limitations or exclu-sions may
not apply to you.
Taco, Inc., 1160 Cranston Street, Cranston, RI 02920| Tel:
401-942-8000
Taco (Canada), Ltd., 8450 Lawson Road, Suite #3, Milton, Ontario L9T 0J8
Visit our web site: www.TacoComfort.com / ©2023
Taco, Inc.
Tel: 905-564-9422
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>