ADC 181B Air Duct and Air Connector Nonmetallic with Plain Instruction Manual

June 17, 2024
ADC

INSTALLATION INSTRUCTIONS
Air Ducts and Air Connectors
Nonmetallic with Plain Ends

Connections – Using Tape & Fasteners

  1. After desired length is determined, cut completely around and through duct with knife or scissors. Cut wire with wire cutters. Fold back jacket and insulation.
  2. Slide at least 1″ [25 mm] of core over fitting and past the bead. Seal core to collar with at least 2 wraps of duct tape. Secure connection with clamp placed over the core and tape and past the bead.
  3. Pull jacket and insulation back over core. Tape jacket with at least 2 wraps of duct tape. A clamp may be used in place of or in combination with the duct

Splices – Using Tape & Fasteners

  1. Fold back jacket and insulation from core. Butt two cores together on a 4” [100 mm] min. length metal sleeve.
  2. Tape cores together with at least 2 wraps of duct tape. Secure connection with 2 clamps placed over the taped core ends and past the beads.
  3. Pull jacket and insulation back over cores. Tape

Connections & Splices – Using Mastic & Fasteners

Step 1
After desired length is determined, cut completely around and through duct with knife or scissors. Cut wire with wire cutters. Pull back jacket and insulation from core.

Step 2
Apply mastic approximately 2″ [50 mm] wide uniformly around the collar of the metal fitting or over the ends of a 4″ [100 mm] min. length metal sleeve. Reference data on mastic container for application rate, application thickness, cure times and handling information. Step 3
Slide at least 2″ [50 mm] of core over the fitting or sleeve ends and past the bead.

Step 4
Secure core to collar with a clamp applied past the bead. secure cores to sleeve ends with 2 clamps applied past the beads.

Step 5
Pull jacket and insulation back over core ends. Tape jacket(s) with at least 2 wraps of duct tape. A clamp may be used in place of or in combination with the duct tape.

NOTES:

  1. For uninsulated air ducts and air connectors, disregard references to insulation and jacket.
  2. Use beaded sheet metal fittings and sleeves when using nonmetallic clamps.
  3. Use mastics listed and labeled in accordance with Standard UL 181B and marked “181B-M” on container.
  4. Use tapes listed and labeled in accordance with Standard UL 181B and marked “181B-FX’.
  5. Nonmetallic clamps shall be listed and labeled in accordance with standard UL 181B and marked “181B-C”.

Use of nonmetallic clamps shall be limited to 6 in. w.g. [1500 Pa] positive pressure.

Copyright 2021, Air Duct Council AIR DUCT COUNCIL
1300 Summer Ave.
Cleveland, OH 44115-2851
Tel. 216-241-7333
Fax 216-241-0105
www.flexibleduct.org

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals