NATIONAL INSTRUMENTS SCC-RLY01 Relay Module User Guide
- June 16, 2024
- NATIONAL INSTRUMENTS
Table of Contents
USER GUIDE
SCC-RLY01 Relay Module
SCC-RLY01 Relay Module
The SCC-RLY01 contains one single-pole double-throw (SPDT) nonlatching relay
capable of switching 5 A at 30 VDC when using an SC-2345 or SC-2350, or 250
VAC when using an SCC-68. Any single E/M Series DAQ device digital
input/output (P0) line 0 to 7 can control the SCC-RLY01.
The SCC-RLY01 uses positive logic. A digital high sets the relay, and a
digital low resets it. In the set state, the common (COM) contact is connected
to the normally open (NO) contact. In the reset state, the common (COM)
contact is connected to the normally closed (NC) contact.
Conventions
The following conventions are used in this guide:
| Angle brackets that contain numbers separated by an ellipsis represent a
range of values associated with a bit or signal name—for example, P0 <3..0>.
---|---
| The » symbol leads you through nested menu items and dialog box options to a
final action. The sequence File»Page Setup»Options directs you to pull down
the File menu, select the Page Setup item, and select Options from the last
dialog box.
| This icon denotes a note, which alerts you to important information.
| This icon denotes a caution, which advises you of precautions to take to
avoid injury, data loss, or a system crash. When this symbol is marked on the
product, refer to the Read Me First: Safety and Radio- Frequency Interference
document, shipped with the product, for precautions to take.
| When symbol is marked on a product, it denotes a warning advising you to
take precautions to avoid electrical shock.
| When symbol is marked on a product, it denotes a component that may be hot.
Touching this component may result in bodily injury.
bold
Bold text denotes items that you must select or click in the software, such as
menu items and dialog box options. Bold text also denotes parameter names.
italic
Italic text denotes variables, emphasis, a cross-reference, or an introduction
to a key concept. Italic text also denotes text that is a placeholder for a
word or value that you must supply.
monospace
Text in this font denotes text or characters that you should enter from the
keyboard, sections of code, programming examples, and syntax examples.
This font is also used for the proper names of disk drives, paths,
directories, programs, subprograms, subroutines, device names, functions,
operations, variables, filenames, and extensions.
SC-2345
SC-2345 refers to both the SC-2345 connector block and SC-2345 with
configurable connectors.
SCC
SCC refers to any SCC Series signal-conditioning module.
What You Need to Get Started
To set up and use the SCC-RLY01, you need the following items:
❑ Hardware
– SCC-68 or SC-2345 with one of the following:
• SCC-PWR01
• SCC-PWR02 and the PS01 power supply
• SCC-PWR03 (requires a 7 to 42 VDC power supply, not included)
– One or more SCC-RLY01 modules
– 68-pin E/M Series DAQ device
– 68-pin cable
– Quick Reference Label
❑ Software
– The latest version of NI-DAQmx
❑ Documentation
– SCC-RLY01 Relay Module User Guide
– SC-2345/2350 User Manual or SCC-68 User Guide
– SCC Quick Start Guide
– Read Me First: Safety and Radio-Frequency Interference
– Documentation for your hardware
– Documentation for your software
❑ Tools
– 1/8 in. flathead screwdriver
– Numbers 1 and 2 Phillips screwdrivers
– Wire insulation stripper
You can download NI documents from ni.com/manuals. To download the latest version of NI-DAQ, click Download Software at ni.com.
Note Configuring the SCC system using Measurement & Automation Explorer (MAX) is not supported on the Macintosh operating system.
Device Specific Information
Note For general SCC module installation and signal connection information, and information about the SCC-68 or SC-2345 carrier, refer to the SCC Quick Start Guide, available for download at ni.com/manuals.
Installing the Module
Caution Refer to the Read Me First: Safety and Radio-Frequency
Interference document before removing equipment covers or
connecting/disconnecting any signal wires.
Plug the SCC-RLY01 into any DIO socket J(X+9), where X is 0 to 7, on the
SC-2345, or into any of the four slots that correspond to P0.0 to P0.3 on the
SCC-68.
Connecting the Input Signals
Note The signal names have changed. Refer to ni.com/info and enter rdtntg
to confirm the signal names.
Each screw terminal is labeled by pin number <1..3>. Pin 1 is the NC terminal,
pin 2 is the COM terminal, and pin 3 is the NO terminal.
The SCC-RLY01 contains one SPDT relay controlled by the digital line of an E/M
Series DAQ device P0. line X. The value of X is determined by the number of
the DIO socket, J(X+9) on the SC-2345 or SCC Mod (X + 1) on the SCC-68, where
you plug in the SCC-RLY01. Figure 1 shows a circuit diagram of the SCC-RLY01.
Caution When connecting signals >60 VDC to the SCC-RLY01 module in the SCC-68, you must use the high-voltage backshell. Figure 2 shows the high- voltage backshell.
For information about how to configure the SCC-RLY01 module with NI-DAQmx, refer to the SCC Quick Start Guide.
Specifications
These ratings are typical at 25 °C unless otherwise stated.
Electrical
Contact type……………………………………..SPDT (Form C), nonlatching Nominal switching
capacity
SCC-68 ……………………………………..5 A at 250 VAC 5 A at 30 VDC
SC-2345…………………………………….5 A at 30 VAC 5 A at 30 VDC
Caution The SCC-RLY01 module is derated to 30 V maximum switching voltage in the SC-2345 carrier regardless of any other voltage markings found on the SCC-RLY01 module case.
Signal bandwidth……………………………… DC to 400 Hz
Contact resistance ……………………………. 30 mΩ max Switching time
Operate time (NC to NO)……………. 5 ms (10 ms max)
Release time (NO to NC)……………. 4 ms (5 ms max)1
Maximum operating speed………………… 30 cps at rated load
Contact lifetime……………………………….. 5 × 107 operations at 180 cpm (minimum)
Power Requirement
Digital power…………………………………… 300 mW max
+5 V……………………………………………….. 60 mA max
Physical
Weight……………………………………………. 37 g (1.3 oz)
I/O connectors…………………………………..One 20-pin right-angle male connector One 3-pin
screw-terminal block
Field-wiring diameter ………………………..28 to 16 AWG
Maximum Working Voltage
Maximum working voltage refers to the signal voltage plus the common-mode
voltage.
When used with an SCC-2345
Channel-to-earth (inputs)……………..±60 VDC, Measurement Category I
Caution Do not use for connection to signals in Measurement Category II,
III, or IV.
Do not connect to MAINS.
When used with an SCC-68
Channel-to-earth (inputs)……………..±300 VDC, Measurement Category II1
Caution Do not use for connection to signals in Measurement Category III, or IV.
Isolation Voltage
Channel-to-channel, channel-to-earth isolation
Continuous…………………………………60 VDC, Measurement Category I
Withstand…………………………………..2300 Vrms verified by a 5 s dielectric withstand type
test
Environmental
Operating temperature ……………………….0 to 50 °C
Storage temperature …………………………..–20 to 65 °C
Humidity ………………………………………….10 to 90% RH, noncondensing
Maximum altitude……………………………..2,000 m
Pollution Degree (indoor use only) ……..2
Safety
This product meets the requirements of the following standards of safety for
electrical equipment for measurement, control, and laboratory use:
- IEC 61010-1, EN 61010-1
- UL 61010-1, CSA 61010-1
Note For UL and other safety certifications, refer to the product label or the Online Product Certification section.
Electromagnetic Compatibility
This product meets the requirements of the following EMC standards for
electrical equipment for measurement, control, and laboratory use:
- EN 61326 (IEC 61326): Class A emissions; Basic immunity
- EN 55011 (CISPR 11): Group 1, Class A emissions
- AS/NZS CISPR 11: Group 1, Class A emissions
- FCC 47 CFR Part 15B: Class A emissions
- ICES-001: Class A emissions
Note For the standards applied to assess the EMC of this product, refer
to the Online Product Certification section.
Note For EMC compliance, operate this product according to the
documentation.
Note For EMC compliance, operate this device with shielded cables.
CE Compliance
This product meets the essential requirements of applicable European
Directives as follows:
- 2006/95/EC; Low-Voltage Directive (safety)
- 2004/108/EC; Electromagnetic Compatibility Directive (EMC)
Online Product Certification
Refer to the product Declaration of Conformity (DoC) for additional regulatory
compliance information. To obtain product certifications and the DoC for this
product, visit ni.com/certification, search by model number or product line,
and click the appropriate link in the Certification column.
Environmental Management
NI is committed to designing and manufacturing products in an environmentally
responsible manner. NI recognizes that eliminating certain hazardous
substances from our products is beneficial to the environment and to NI
customers.
For additional environmental information, refer to the NI and the Environment
Web page at ni.com/environment. This page contains the environmental
regulations and directives with which NI complies, as well as other
environmental information not included in this document.
Waste Electrical and Electronic Equipment (WEEE)
EU Customers
At the end of the life cycle, all products must be sent to a WEEE recycling
center. For more information about WEEE recycling centers and National
Instruments WEEE initiatives, visit
ni.com/environment/weee.
SCC-RLY01 Module Pin Assignments
Figure 4 shows the I/O connector pins on the bottom of the module.
Table 1 lists the signal connection corresponding to each pin. GND is the reference for the +5 V supply.
Table 1. SCC-RLY01 Pin Signal Connections
Pin Number | Signal |
---|---|
1 | — |
2 | — |
3 | — |
4 | — |
5 | — |
6 | — |
7 | P0.(X) |
8 | — |
9 | +5 V |
10 | GND |
11 | — |
12 | — |
13 | — |
14 | — |
15 | — |
16 | — |
17 | — |
18 | — |
19 | — |
20 | — |
National Instruments, NI, ni.com, and LabVIEW are trademarks of National
Instruments Corporation.
Refer to the Terms of Use section on ni.com/legal for more information about
National Instruments trademarks. Other product and company names mentioned
herein are trademarks or trade names of their respective companies. For
patents covering National Instruments products/technology, refer to the
appropriate location: Help»Patents in your software, the
patents.txt file on your media, or the National
Instruments Patent Notice at ni.com/patents.
© 2001–2008 National Instruments Corporation. All rights reserved.
371079D-01
Aug08
Documents / Resources
|
NATIONAL INSTRUMENTS SCC-RLY01 Relay
Module
[pdf] User Guide
SCC-2345, SC-2350, SCC-68, SCC-RLY01, SCC-RLY01 Relay Module, Relay Module,
Module
---|---
References
- Test and Measurement Systems, a part of Emerson - NI
- Product Certifications - NI
- Engineering a Healthy Planet - NI
- Product Take-Back Program and Recycling - NI
- Using Info Codes - NI
- Product Documentation - NI
- Manual-Hub.com – Free PDF manuals!
Read User Manual Online (PDF format)