LENNOX COMMERCIAL EDA-036C EDA Ton Whole Home Dehumidification System
MODEL NUMBER IDENTIFICATION
- EDA letter designation in the model number will physically match gas furnaces with the same letter designation in their model number.
FEATURE HIGHLIGHTS
- Heavy Gauge Steel Cabinet
- Low Voltage Electrical Inlet
- Fully Insulated Cabinet
- Dehumidification Coil
- Sweat Connections
- Dual Refrigerant Diverter Valves
- 3-Way Diverter Valve Actuator
APPROVALS AND WARRANTY
APPROVALS
- Units are CSA certified according to UL-207 and CSA C22.2 No. 14.3 standards
- ISO 9001 Registered Manufacturing Quality System
WARRANTY
- All covered components:
- Limited five years in residential installations
- Limited one year in non-residential installations
NOTE – Refer to Lennox® Basic Limited Warranty at www.Lennox.com for additional details.
NOTE – Lennox warranties do not cover damage or defect resulting from operation with system components (indoor unit, outdoor unit and refrigerant control devices) which do not match or meet the specifications recommended by Lennox. This unit is intended to operate with specific furnaces and air handlers only.
FEATURES
APPLICATIONS
NOTE – The Humiditrol® Whole Home Dehumidification System is not applicable to variable-capacity outdoor units.
- The Humiditrol® Whole Home Dehumidification System is designed for use with Lennox R-410A outdoor unit expansion valve systems only that are matched with specific furnaces or air handlers
- See System Decision Tree on page 13 for available matches
- For indoor installations in either upflow or horizontal applications only
- Height, space and air flow restrictions or the unit’s stability in a stacked configuration will limit the use of downflow applications
NOTE – Refer to Installation Instructions supplement “Installing
Humiditrol® EDA Unit in Downflow Configuration” for more details
NOTE – Sensible to Total Ratios are not available for downflow
applications.
OVERVIEW
- The EDA unit is installed in an HVAC system downstream from the indoor coil or air handler
- In dehumidification mode, the coil becomes an extension of the outdoor coil and rejects heat into the indoor air stream
- This dehumidification mode allows significantly improved control of the humidity in the conditioned space without overcooling the space
- The EDA unit includes a set of 3-way diverter valves which route refrigerant through the EDA coil (Dehumidification ON), or which cause the refrigerant to bypass the EDA coil (Dehumidification OFF)
-
CABINET
- Low-profile allows easy installation in up flow or horizontal applications
- Heavy-gauge, cold rolled steel construction
- Pre-painted cabinet finish
- Flanges provided on supply air opening for ease of plenum connection
- Slots on perimeter of inlet opening help facilitate secure connection to indoor coil / air handler flanges
-
Low voltage electrical inlet (for refrigerant valve actuator) provided on front of cabinet
-
Fully insulated with foil faced insulation
COMPONENTS -
Dehumidification Coil
- Durable copper tubing
- Ripple-edged aluminum fins
- Lanced fins provide maximum exposure of fin surface to air stream
- Rifled tubing provides superior refrigerant heat transfer
- Twin coil construction assembled in an A” configuration for large surface area (036C and 060D models)
- Single slab coil construction (024B model)
-
Sweat connections
-
High pressure testing insures leak-proof construction
Combination Check/Flow Limiting Piston -
Furnished with unit for field installation on the EDA unit
-
See dimension drawing
-
Prevents refrigerant from flowing into the inactive components when the EDA coil is inactive
-
-
Dual Refrigerant Diverter Valves
- Heavy duty valves control refrigerant flow depending on mode
-
3-Way Diverter Valve Actuator
- Controls operation of refrigerant valves during EDA operation
- 24VAC
- Three position actuator shaft for maintenance – Cooling, Evacuate or Bypass
Outdoor Fan Relay and Wiring Harness
- Required when EDA is used with outdoor units with multi-speed outdoor fans.
OPTIONAL ACCESSORIES
REQUIRED CONTROLS
NOTE – Third-party thermostats are not compatible with the EDA Dehumidification System. One of these Lennox thermostats with integrated EDA control logic is required for proper operation.
S40 Smart Wi-Fi Thermostat (part of the Lennox® Residential Communicating Control System)
- Recognizes and connects to all Lennox® Communicating products to automatically configure and control the heating/cooling system (based on user specified settings) for the highest level of comfort, performance and efficiency.
- Recognizes model and serial number information for Lennox® Communicating products to simplify system setup
- Lennox Smart Room Sensors, Lennox Wireless Extenders and Lennox Smart Air Quality Monitor can be added to the system
- Smart home automation compatible with Amazon Alexa®, Google Assistant, Control4® and Building36®
- Sends service alerts and reminders
- Lennox Smart Thermostat App features Wi-Fi remote temperature monitoring and adjustment through a home wireless network apps for smartphones or tablets
- Lennox Smart Technician App allows installer to manage systems in the home
- Service Dashboard features online real-time monitoring and advanced diagnostics of installed Lennox® Communicating systems
- Simple easy-to-use touchscreen allows complete system configuration
- Scheduled maintenance alerts, system warnings and troubleshooting are also displayed on thermostat screen
- Easy to read 7 inch high definition color display (measured diagonally)
- Conventional outdoor units (not Lennox® Communicating) can easily be added and controlled by the S40 Thermostat
- Installer setup screens allow quick and simple system configuration without a manual, Installer can also run tests on complete system or individual components for easy maintenance and troubleshooting
- Serial communications bus (RSB us), with less wiring than a conventional heating/cooling system, allows system communication
- Uses standard 4-wire unshielded thermostat wiring
- High Definition Color Display with Subbase and wall plate furnished for easy installation
NOTE – See the Lennox® S40 Thermostat Product Specifications bulletin for more information.
Units only)
NOTE – A Lennox® Communicating indoor unit (furnace or air handler) is
required for proper operation of the Lennox® Communicating Thermostat with a
conventional outdoor unit.
NOTE – The Humiditrol® Enhanced Dehumidification Accessory is not Lennox®
Communicating but can easily be added and controlled by the Lennox®
Thermostat. Dehumidify settings are adjustable from 40 to 60% relative
humidity (RH).
E30 Smart Wi-Fi Thermostat
- Wi-Fi enabled, electronic 7-day, universal, multi-stage, programmable, touchscreen thermostat
- 3 Heat/2 Cool
- Auto-changeover
- Controls dehumidification during cooling mode and humidification during heating mode
- Offers enhanced capabilities including humidification / dehumidification / dewpoint measurement and control, Humiditrol® control, and equipment maintenance reminders
- Easy to read 7 in. color touchscreen (measured diagonally)
- LCD display with backlight shows the current and set temperature, time, inside relative humidity, system status (operating mode and schedules) and outside temperature (optional outdoor sensor required)
- Smooth Setback Recovery starts system early to achieve setpoint at start of program period
- Compressor short-cycle protection (5 minutes)
- Up to four separate schedules are available plus Schedule IQ™
- One-Touch Away Mode – A quick and easy way to set the cooling and heating setpoints while away
- Smart Away™ – Uses geo-fencing technology to determine when the homeowner is within a predetermined distance from the home to operate the system when leaving, away and arriving
- Wi-Fi remote monitoring and adjustment through a home wireless network for desktop PCs, laptops and apps for smartphones or tablets
- Smart home automation compatible with Apple HomeKit™, Amazon Alexa®, Google Assistant and IFTTT
- Service Dashboard features online real-time monitoring of installed Lennox® thermostats
- High Definition Color Display with Subbase, Smart Hub Controller, wallplate (for retrofit installations) furnished for easy installation
- See the E30 Smart Wi-Fi Thermostat Product Specifications bulletin for more information.
NOTE – Third-party thermostats are not compatible with the EDA Dehumidification System. One of these Lennox thermostats with integrated EDA control logic is required for proper operation.
CS7500 Touchscreen Thermostat
- Electronic 7-day, universal, multi-stage, programmable, touchscreen thermostat
- 4 Heat/2 Cool
- Auto-changeover.
- Dual-fuel control with optional outdoor sensor
- Controls dehumidification during cooling mode and humidification during heating mode
- Offers enhanced capabilities including humidification / dehumidification / dewpoint measurement and control, Humiditrol® control, and equipment maintenance reminders
- Easy-to-use, menu driven thermostat with a back-lit, LCD touchscreen
- See the CS7500 Thermostat Product Specifications bulletin for more information
CS7500 Commercial 7-Day Programmable Thermostat
- Electronic 7-day, universal, multi-stage, programmable, touchscreen thermostat
- 4 Heat/3 Cool
- Remote Indoor Temperature Sensing with Averaging
- Outside or Discharge Air Temperature Display
- Occupancy Scheduling with Economizer Relay Control
- Away mode
- Offers enhanced capabilities including humidification / dehumidification / dewpoint measurement and control, Humiditrol® control, and notifications/reminders
- Performance reports
- Economizer relay control
- Easy-to-use, menu driven thermostat with a back-lit, LCD touchscreen
- See the CS7500 Commercial Thermostat Product Specifications bulletin more information.
Remote Outdoor Temperature Sensor
- Used with the Lennox® Communicating Thermostats, Lennox E30, Lennox M30 and CS7500 thermostats
- When installed outdoors, sensor allows thermostat to display outdoor temperature.
NOTE – Sensor is required for Humiditrol® applications.
NOTE – The outdoor sensor is furnished as standard with Lennox®
Communicating outdoor units, optional for conventional units.
REQUIRED COMPONENTS
Insulation and Piping Kit
-
Kit includes all necessary piping, fittings and insulation required for EDA installation
NOTE – Some model match-ups require a charge compensator to maintain the proper amount of refrigerant circulating in the system. The compensator stores excess refrigerant when the EDA coil is active and returns it to the system during normal cooling or heating operations. When the EDA coil is active, less charge is required to obtain the proper amount of subcooling because of the additional coil surface and the cooler air which passes over the EDA. -
Charge compensator and related piping and insulation is furnished with certain Insulation and Piping Kits depending on the system match-up
Relay Kit
- Required when use with CBA27UHE air handlers
Transformer
- 75VA, 24VAC indoor unit transformer is required when EDA unit is installed with a two-stage heat pump system
SEQUENCE OF OPERATION
Cooling Cycle With EDA Active
- Dehumidification mode begins when the room thermostat cooling demand has been satisfied but the dehumidification setting has not been satisfied
- The room thermostat sends a signal to the EDA unit’s diverter valve actuator to begin operating in the dehumidification mode
- Refrigerant from the outdoor unit enters the EDA unit, passes through the first 3-way diverter valve and then enters the EDA coil
- There, heat from the warm refrigerant is rejected into the indoor air stream
- The refrigerant leaves the coil, passes through the second 3-way diverter valve and into the indoor coil expansion valve in a highly subcooled state
- During dehumidification, the indoor air blower (and multi-speed outdoor fan, if used) operate at a lower air volume
- The warm refrigerant entering the EDA unit from the outdoor unit will be subcooled in the EDA coil and enter the expansion valve at a lower-than-normal temperature
- Liquid temperatures can be in the 65 to 70°F range, with a 10 to 40°F temperature drop through the EDA coil
- The air temperature leaving the indoor coil and entering the EDA coil will be normal for the reduced airflow, but will be warmed as it passes over the EDA coil
- Air temperature rise across the EDA can be from 10 to 25°F, depending on the operating ambient and airconditioned space conditions
- If the cooling demand has been satisfied, but a dehumidify demand still exists and the room temperature is not more than 2° below the setpoint, the blower will operate at reduced airflow while the compressor operates on 2nd stage cooling (two-stage systems only)
- When outdoor ambient temperatures reach 95º, the system runtime requirements are high and dehumidification requirements are met without activating the dehumidification mode
- By design the system, which is controlled by a CS7500 thermostat or a Lennox® Communicating thermostat, will not allow operation in the dehumidification mode when outdoor temperatures exceed 95º
- The system will operate more efficiently and will avoid unfavorable operating conditions
- When operating in normal cooling (or heat pump heating) mode, all temperatures and pressures will be the same as a standard heating/cooling system
Cooling Cycle With EDA Active
NOTE 1 − With EDA coil active, expect a 3 to 8°F air temperature rise
across EDA coil.
NOTE 2 − With EDA coil active, expect a 10 to 25°F liquid line
temperature drop through EDA coil.
NOTE 3 − Charge compensator and 1/4 in. line may not be required on some
single−stage systems.
Cooling Cycle With EDA Inactive
- In normal cooling mode (dehumidification mode OFF), the liquid refrigerant from the outdoor unit enters the first 3-way diverter valve
- The diverter valve actuator directs the refrigerant flow to bypass the EDA coil and flow directly to the indoor unit expansion valve
Heat Pump Heating Cycle With EDA Inactive
- In heat pump heating mode, a system that includes an EDA unit will operate as a conventional heat pump; there is no requirement for EDA unit operation in heat pump heating mode
SPECIFICATIONS
General Data | Model No. | EDA-024B | EDA-036C | EDA-060D |
---|---|---|---|---|
Line Connections in. (sweat) | Liquid to Indoor TXV o.d. Liquid from |
Outdoor Unit o.d. Check/Flow Restrictor to Vapor Line Tee o.d. Charge
Compensator o.d.| 3/8| 3/8| 3/8
3/8 (9.5)| 3/8| 3/8
3/8| 3/8| 3/8
1/4| 1/4| 1/4
EDA Coil| Net face area – sq. ft.| 2.0| 3.0| 4.0
Tube diameter – in.| 3/8| 3/8| 3/8
Fins per inch| 20| 20| 14
Number of rows| 1| 1| 1
Shipping Data| lbs. – 1 package| 35| 39| 47
CONTROLS – ORDER SEPARATELY
NOTE – Third-party thermostats are not compatible with the EDA
Dehumidification System.
One of these Lennox thermostats with integrated EDA control logic is required
for proper operation.
Model No. | EDA-024B | EDA-036C | EDA-060D |
---|---|---|---|
S40 Smart Wi-Fi Thermostat (4 heat / 2 cool) | 22V24 | 22V24 |
22V24
E30 Smart Wi-Fi Thermostat (3 heat / 2 cool)
1 Discharge Air Temperature Sensor (for E30/S40)
| 15S63| 15S63| 15S63
88K38| 88K38| 88K38
M30 Smart Wi-Fi Thermostat (4 heat / 2 cool)| 15Z69| 15Z69|
15Z69
CS7500 Thermostat (4 heat / 2 cool)| 13H14| 13H14| 13H14
CS7500 Commercial Thermostat (4 heat / 3 cool)| 24K41| 24K41|
24K41
2 Remote Outdoor Temperature Sensor (all thermostats) (for dual fuel,
Humiditrol® and outdoor temperature display)| X2658| X2658|
X2658
Dehumidification Relay Kit (for CBA27UHE air handlers)| 26W62|
26W62| 26W62
- Optional for service diagnostics.
- Remote Outdoor Temperature Sensor is used with conventional (non-Lennox® Communicating) outdoor units (sensor is furnished with Lennox® Communicating outdoor units). Allows the thermostat to display outdoor temperature. Required in dual-fuel and Humiditrol® applications.
REQUIRED COMPONENTS – ORDER SEPARATELY
IRED COMPONENTS – ORDER SEPARATELY
Model No.| EDA-024B| EDA-036C| EDA-060D
| | |
** ELECTRICAL
Transformer| 12P61 – 75VA, 120/208/240V primary, 24VAC secondary
** REFRIGERATION
Insulation and Piping Kits| See System Decision Tree on page 13 for
usage
Required when EDA unit is installed with two-stage heat pump system.
AIR RESISTANCE
Model No.| Air Volume (cfm)| Total Air Resistance ( in. w.g.
)
---|---|---
EDA-024B| 400| 0.05
600| 0.10
800| 0.15
1000| 0.22
EDA-036C| 600| 0.05
800| 0.08
1000| 0.11
1200| 0.15
1400| 0.20
EDA-060D| 1000| 0.05
1200| 0.06
1400| 0.08
1600| 0.10
1800| 0.11
2000| 0.13
2200| 0.15
DIMENSIONS
Model No. | A | B | C | D | E | F | G |
---|---|---|---|---|---|---|---|
in. | mm | in. | mm | in. | mm | in. | mm |
in. | mm | in. | mm | in. | mm | ||
EDA-024B | 17-1/2 | 445 | 12-1/4 | 311 | 16-1/8 | 422 | 1-3/8 |
3 | 76 | ||||||
EDA-036C | 21 | 533 | 12-1/4 | 311 | 19-5/8 | 498 | 3-1/8 |
3-1/4 | 83 | ||||||
EDA-060D | 24-1/2 | 622 | 14 | 356 | 23-1/8 | 587 | 4-7/8 |
121 | 4-3/4 | 121 |
TYPICAL INSTALLATION
Typical Installation (Horizontal Air Handler shown)
INSTALLATION CONFIGURATIONS
NOTES:
Transition is not furnished and must be field fabricated.
- Transition is required for all air handlers. Transition dimension width and depth is dependent upon the air handler and the model of EDA used.
- Transition is required between indoor coil and EDA if EDA-060D model is used with small profile furnace.
Alternate installation position information – The EDA coil is not position
sensitive as long as the correct air flow direction through the coil is
maintained. See Dimension Drawing on page 8 for correct air flow.
SYSTEM DECISION TREE
PERFORMANCE
NOTE- Data varies ± 3% for all unit matches.
NOTE- Data varies ± 3% for all unit matches.
NOTE- Data varies ± 3% for all unit matches.
REVISIONS
Sections | Description of Change |
---|---|
Performance | Performance data updated. |
Customer Support
Visit us at www.Lennox.com
For the latest technical information,
www.LennoxCommercial.com
Contact us at 1-800-4-LENNOX
NOTE – Due to Lennox’ ongoing commitment to quality, Specifications,
Ratings and Dimensions subject to change without notice and without incurring
liability.
Improper installation, adjustment, alteration, service or maintenance can
cause property damage or personal injury.
Installation and service must be performed by a qualified installer and
servicing agency.