Lennox Commercial HVAC Blower Housing Replacement Kit Instruction Manual

June 10, 2024
Lennox Commercial

Lennox-Commercial-logo

Lennox Commercial HVAC Blower Housing Replacement Kit

Lennox-Commercial-HVAC-Blower-Housing-Replacement-Kit-
product

Product Information

Blower Housing Replacement Kit

The Blower Housing Replacement Kit (part no. E2022) is designed for use with LG/LC/LH/LD 024-060 unit direct drive blowers. The kit contains a blower housing that can replace the existing housing on the unit. The kit comes in one package and includes one blower housing.

The Blower Housing Replacement Kit is available in two variants, 21P18 (621654-05) and 21P20 (621654-06). The 21P18 variant does not have corrosion protection, while the 21P20 variant has corrosion protection.

The installation of the Blower Housing Replacement Kit requires caution and should only be performed by a licensed professional HVAC installer or equivalent service agency, or the gas supplier. Improper installation, adjustment, alteration, service, or maintenance can cause property damage, personal injury, or loss of life.

Product Usage Instructions

Blower Housing Replacement Kit

To install the Blower Housing Replacement Kit, follow the below steps:

  1. Disconnect electrical power to the unit. Wait for five minutes before continuing service procedures to avoid electrical shock.
    This will allow internal capacitors time to fully discharge.

  2. Open access panels as shown in figure 1.

  3. Disconnect J48 from P48 in the blower area and unscrew the ground terminal from the blower deck.

  4. Disconnect the Modbus 9-pin blower control plug located in the blower area.

  5. Remove four screws securing blower assembly to the unit. See figure 2.

  6. If the unit was equipped with an optional blower proving switch, remove the switch from the existing blower housing.

  7. Remove PT6 pressure transducer bracket and silicone tubing from the housing. See figure 2. If needed, remove the inlet ring to disconnect the tubing from the inlet ring barb. See figure 3.
    Disconnect the pressure transducer wire connector.

  8. Use the handle on the blower assembly to slide the assembly out of the unit.

  9. Turn the blower assembly upside down. See figure 4.

  10. Remove the inlet grill, orifice, and the side of the housing shown in figure 3.

  11. Remove the motor/impeller secured to the existing housing. See figures 3 and 4.

  12. Discard the existing housing.

  13. Remove one side of the replacement housing. See figures 3 and 4.

  14. Install existing motor/impeller on replacement blower housing in the same manner the motor/impeller was removed from the discarded housing. Secure with six bolts provided in this kit. Tighten to 21.7 ft.-lbs.

  15. Attach the pressure transducer bracket, wire connector, and silicone tubing to the housing in reverse order of removal.

  16. Install blower assembly flanges into rails on the blower deck in the same manner the discarded housing was removed. Secure into place using four screws shown in figure 2.

  17. Connect P48 to J48 in blower compartment. Screw the ground terminal back onto the blower deck. Reconnect Modbus 9-pin blower control plug located in the blower area.

Note: Take care while handling this equipment, and wear gloves and protective clothing. Contact with sharp sheet metal edges can result in personal injury.

By following the above steps, the Blower Housing Replacement Kit can be installed successfully.

Shipping and Packing List

Package 1 of 1 contains:

  1. Blower housing

WARNING

Improper installation, adjustment, alteration, ser­vice or maintenance can cause property damage, personal injury or loss of life. Installation and ser­vice must be performed by a licensed professional HVAC installer or equivalent, service agency, or the gas supplier

CAUTION

As with any mechanical equipment, contact with sharp sheet metal edges can result in personal in­jury. Take care while handling this equipment and wear gloves and protective clothing.

Application

The blower housing replacement kit is used on LG/LC/LH/LD 024 – 060 unit direct drive blowers. 21P18 (621654-05) does not have corrosion protection. 21P20 (621654-06) has corrosion protection.

Remove Housing

  1. Disconnect electrical power to unit. Wait five minutes before continuing service procedures to avoid electrical shock. This will allow internal capacitors time to fully discharge.

  2. Open access panels as shown in figure 1.

  3. Disconnect J48 from P48 in the blower area and unscrew the ground terminal from the blower deck.Lennox-Commercial-HVAC-Blower-Housing-Replacement-Kit-fig 1
    FIGURE 1

  4. Disconnect the Modbus 9-pin blower control plug located in the blower area.

  5. Remove four screws securing blower assembly to unit. See figure 2.

  6. If unit was equipped with an optional blower proving switch, remove switch from existing blower housing.

  7. Remove PT6 pressure transducer bracket and silicone tubing from housing. See figure 2. If needed, remove the inlet ring to disconnect the tubing from the inlet ring barb. See figure 3. Disconnect the pressure transducer wire connector.

  8. Use the handle on the blower assembly to slide the assembly out of unit.

  9. Turn the blower assembly upside down. See figure 4.

  10. Remove the inlet grill, orifice and the side of the housing shown in figure 3.

  11. Remove the motor / impeller secured to the existing housing. See figures 3 and 4.

  12. Discard existing housing.

SLIDE BLOWER ASSEMBLY OUT OF UNITLennox-Commercial-HVAC-Blower-Housing-
Replacement-Kit-fig 2

FIGURE 2

Install Replacement Housing

  1. Remove one side of the replacement housing. See figures 3 and 4.
  2. Install existing motor / impeller on replacement blower housing in the same manner the motor / impeller was removed from the discarded housing. Secure with 6 bolts provided in this kit. Tighten to 21.7 ft.-lbs.
  3. Replace the blower housing side, orifice and inlet grill which was previously disassembled. Tighten orifice screws to 10.8 ft.-lbs. Tighten inlet grill screws to 3.7 ft.-lbs.
  4. If previously removed, attach the optional blower proving switch to replacement housing in the same manner it was removed.
  5. Attach the pressure transducer bracket, wire connector, and silicone tubing to the housing in reverse order of removal.
  6. Install blower assembly flanges into rails on the blower deck in the same manner the discarded housing was removed. Secure into place using four screws shown in figure 2.
  7. Connect P48 to J48 in blower compartment. Screw GND terminal to blower deck in the same manner it was removed.
  8. Connect the Modbus plug in the blower area to the replacement blower motor 9-pin control plug.
  9. Bundle harnesses and use wire ties to secure kit harnesses to unit harnesses in the same manner they were removed.

BLOWER ASSEMBLY

Lennox-Commercial-HVAC-Blower-Housing-Replacement-Kit-
fig 3

FIGURE 3 Lennox-Commercial-HVAC-Blower-Housing-Replacement-Kit-fig
4

FIGURE 4

Documents / Resources

| Lennox Commercial HVAC Blower Housing Replacement Kit [pdf] Instruction Manual
HVAC Blower Housing Replacement Kit, HVAC, Blower Housing Replacement Kit, Housing Replacement Kit, Replacement Kit
---|---

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Lennox Commercial User Manuals

Related Manuals