Service and Troubleshooting

GSXV9 4 Ton 22.3 SEER2 Variable Speed Air Conditioner

*SXV9 Inverter Air Conditioner Condenser Units with R-410A Refrigerant
Pride and workmanship go into every product to provide our customers with quality products. It is possible, however, that during its lifetime a product may require service. Products should be serviced only by a qualified service technician who is familiar with the safety procedures required in the repair and who is equipped with the proper tools, parts, testing instruments and the appropriate service manual. REVIEW ALL SERVICE INFORMATION IN THE APPROPRIATE SERVICE MANUAL BEFORE BEGINNING REPAIRS.

WARNING
ONLY PERSONNEL THAT HAVE BEEN TRAINED TO INSTALL, ADJUST, SERVICE, MAINTENANCE OR REPAIR (HEREINAFTER, “SERVICE”) THE EQUIPMENT SPECIFIED IN THIS MANUAL SHOULD SERVICE THE EQUIPMENT. THIS EQUIPMENT IS NOT INTENDED FOR USE BY PERSONS (INCLUDING CHILDREN) WITH REDUCED PHYSICAL, SENSORY OR MENTAL CAPABILITIES, OR LACK OF EXPERIENCE AND KNOWLEDGE, UNLESS THEY HAVE BEEN GIVEN SUPERVISION OR INSTRUCTION CONCERNING USE OF THE APPLIANCE BY A PERSON RESPONSIBLE FOR THEIR SAFETY.
CHILDREN SHOULD BE SUPERVISED TO ENSURE THAT THEY DO NOT PLAY WITH THE EQUIPMENT.
THE MANUFACTURER WILL NOT BE RESPONSIBLE FOR ANY INJURY OR PROPERTY DAMAGE ARISING FROM IMPROPER SUPERVISION, SERVICE OR SERVICE PROCEDURES. IF YOU SERVICE THIS UNIT, YOU ASSUME RESPONSIBILITY FOR ANY INJURY OR PROPERTY DAMAGE WHICH MAY RESULT. IN ADDITION, IN JURISDICTIONS THAT REQUIRE ONE OR MORE LICENSES TO SERVICE THE EQUIPMENT SPECIFIED IN THIS MANUAL, ONLY LICENSED PERSONNEL SHOULD SERVICE THE EQUIPMENT. IMPROPER SUPERVISION, INSTALLATION, ADJUSTMENT, SERVICING, MAINTENANCE OR REPAIR OF THE EQUIPMENT SPECIFIED IN THIS MANUAL, OR ATTEMPTING TO INSTALL, ADJUST, SERVICE OR REPAIR THE EQUIPMENT SPECIFIED IN THIS MANUAL WITHOUT PROPER SUPERVISION OR TRAINING MAY RESULT IN PRODUCT DAMAGE, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
For service information related to the Bluetooth® Shared Data Loader BTSDL01 referenced in this manual, please refer to the installation instructions for the BTSDL01 at www.coolcloudhvac.com/loaderuserguide

RS6115001r13
March 2023
© 2019-2023 Daikin Comfort Technologies Manufacturing, L.P.
is a registered trademark of Maytag Corporation or its related companies and is used under license.
All rights reserved.

IMPORTANT INFORMATION

IMPORTANT NOTICES
RECOGNIZE SAFETY SYMBOLS, WORDS AND LABELS
Pride and workmanship go into every product to provide our customers with quality products. It is possible, however, that during its lifetime a product may require service. Products should be serviced only by a qualified service technician who is familiar with the safety procedures required in the repair and who is equipped with the proper tools, parts, testing instruments and the appropriate service manual.
REVIEW ALL SERVICE INFORMATION IN THE APPROPRIATE SERVICE MANUAL BEFORE BEGINNING REPAIRS.

WARNING
HIGH VOLTAGE Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death.

WARNING
Do not connect to or use any device that is not design certified by the manufacturer for use with this unit. Serious property damage, personal injury, reduced unit performance and/or hazardous conditions may result from the use of such non-approved devices.

WARNING
To prevent the risk of property damage, personal injury, or death, do not store combustible materials or use gasoline or other flammable liquids or vapors in the vicinity of this appliance.
NOTICE: Inverter air conditioner models can only be matched with an AMVE air handler or TXV-V expansion valve kit. Damage resulting from operation with any other combination is not covered by our warranties.

SAFE REFRIGERANT HANDLING
While these items will not cover every conceivable situation, they should serve as a useful guide.

WARNING
Refrigerants are heavier than air. They can “push out” the oxygen in your lungs or in any enclosed space. To avoid possible difficulty in breathing or death:

  • Never purge refrigerant into an enclosed room or space. By law, all refrigerants must be reclaimed.
  • If an indoor leak is suspected, thoroughly ventilate the area before beginning work.
  • Liquid refrigerant can be very cold. To avoid possible frost bite or blindness, avoid contact and wear gloves and goggles. If liquid refrigerant does contact your skin or eyes, seek medical help immediately.
  • If refrigerant gas leaks during installation, ventilate the area immediately. Refrigerant gas will result in producing toxic gas if it comes into contact with fire. Exposure to this gas will result in severe injury or death.
  • After completing the installation work, check that the refrigerant gas does not leak throughout the system.
  • Do not install unit in an area where flammable materials are present due to risk of explosions that will result in serious injury or death.
  • When installing the unit in a small room, take measures to keep the refrigerant concentration from exceeding allowable safety limits. Excessive refrigerant leaks, in the event of an accident in a closed ambient space, could result in oxygen deficiency.
  • Always follow EPA regulations. Never burn refrigerant, as Poisonous gas will be produced.

WARNING
The United States Environmental Protection Agency (“EPA”) has issued various regulations regarding the introduction and disposal of refrigerants introduced into this unit. Failure to follow these regulations may harm the environment and can lead to the imposition of substantial fines. These regulations may vary by jurisdiction. Should questions arise, contact your local EPA office.

OUTSIDE THE U.S., call 1-713-861-2500.
(Not a technical assistance line for dealers.) Your telephone company will bill you for the call.

WARNING
To avoid possible explosion:

  • Never apply flame or steam to a refrigerant cylinder. If you must heat a cylinder for faster charging, partially immerse it in warm water.
  • Never fill a cylinder more than 80% full of liquid refrigerant.
  • Never add anything other than R-22 to an R-22 cylinder or R-410A to an R-410A cylinder. The service equipment used must be listed or certified for the type of refrigerant used.
  • Store cylinders in a cool, dry place. Never use a cylinder as a platform or a roller.

WARNING

  • To avoid possible explosion:
  • Use only returnable (not disposable) service cylinders when removing refrigerant from a system.
  • Ensure the cylinder is free of damage which could lead to a leak or explosion.
  • Ensure the hydrostatic test date does not exceed 5 years.
  • Ensure the pressure rating meets or exceeds 400 lbs. When in doubt, do not use cylinder.

WARNING
To avoid possible injury, explosion or death, practice safe handling of refrigerants.

CAUTION
The compressor PVE oil for R-410A units is extremely susceptible to moisture absorption and could cause compressor failure. Do not leave system open to atmosphere any longer than necessary for installation.
NOTICE: The entire system (combination of indoor and outdoor sections) must be manufacturer approved and Air-Conditioning, Heating and Refrigerant Institute (AHRI) listed.
NOTE: Installation of unmatched systems is not permitted. Damage or repairs due to installation of unmatched systems is not covered under the warranty.
NOTICE: Approved systems are combination of ComfortBridge compatible indoor unit and single-stage thermostat (with dehumidification function).

WARNING
System contaminants, improper service procedure and/or physical abuse affecting hermetic compressor electrical terminals may cause dangerous system venting.
NOTICE: When the outdoor unit is connected to main power, the inverter board has a small current flowing into it to be prepared for operation when needed. Due to this, the Control Board components have to be cooled even when the unit is not running. For this cooling operation, the condenser fan may come on at any time, including in the winter months. Any obstruction to the outdoor fan should be avoided at all times when the unit is powered to prevent damage.
The successful development of hermetically sealed refrigeration compressors has completely sealed the compressor’s moving parts and electric motor inside a common housing, minimizing refrigerant leaks and the hazards sometimes associated with moving belts, pulleys or couplings.
Fundamental to the design of hermetic compressors is a method whereby electrical current is transmitted to the compressor motor through terminal conductors which pass through the compressor housing wall. These terminals are sealed in a dielectric material which insulates them from the housing and maintains the pressure tight integrity of the hermetic compressor. The terminals and their dielectric embedment are strongly constructed, but are vulnerable to careless compressor installation or maintenance procedures and equally vulnerable to internal electrical short circuits caused by excessive system contaminants.
In either of these instances, an electrical short between the terminal and the compressor housing may result in the loss of integrity between the terminal and its dielectric embedment.
This loss may cause the terminals to be expelled, thereby venting the vaporous and liquid contents of the compressor housing and system.
A venting compressor terminal normally presents no danger to anyone, providing the terminal protective cover is properly in place.
If, however, the terminal protective cover is not properly in place, a venting terminal may discharge a combination of (a) hot lubricating oil and refrigerant (b) flammable mixture (if system is contaminated with air) in a stream of spray which may be dangerous to anyone in the vicinity. Death or serious bodily injury could occur. Under no circumstances is a hermetic compressor to be electrically energized and/or operated without having the terminal protective cover properly in place. See Service Section for proper servicing.

PRODUCT IDENTIFICATION

NOMENCLATURES

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner - PRODUCT
IDENTIFICATION 1

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner - PRODUCT
IDENTIFICATION 2

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner - PRODUCT
IDENTIFICATION 3

SYSTEM OPERATION

This section gives a basic description of Air Conditioner condenser unit operation, its various components and their basic operation. Ensure your system is properly sized for heat gain and loss according to methods of the Air Conditioning Contractors Association (ACCA) or equivalent.

CONDENSING UNIT
The ambient air is pulled through the Air Conditioner condenser coil by a direct drive propeller fan. This air is then discharged out of the top of the cabinet. These units are designed for free air discharge, so no additional resistance, like duct work, shall be attached.
The gas and liquid line connections on present models are of the sweat type for field piping with refrigerant type copper. Front seating valves are factory installed to accept the field run copper. The total refrigerant charge for a normal installation is factory installed in the Air Conditioner condenser unit.
SXV9 models are available in 2 through 5 ton sizes and use R-410A refrigerant. They are designed for 208/230 volt single phase applications. SXV9 R-410A model units use a Daikin rotary compressor. These models are ComfortBridge™ and ComfortNet™ ready. There are a number of design characteristics which are different from the traditional compressors.
*SXV9 models use “FVC50K” which is NOT compatible with mineral oil based lubricants like 3GS. “FVC50K” oil (required by the manufacturer) must be used if additional oil is required.

COOLING

The refrigerant used in the system is R-410A. It is a clear, colorless, non- toxic and non-irritating liquid. R-410A is a 50:50 blend of R-32 and R-125. The boiling point at atmospheric pressure is -62.9°F.
A few of the important principles that make the refrigeration cycle possible are: heat always flows from a warmer to a cooler body. Under lower pressure, a refrigerant will absorb heat and vaporize at a low temperature. The vapors may be drawn off and condensed at a higher pressure and temperature to be used again.
The indoor evaporator coil functions to cool and dehumidify the air conditioned spaces through the evaporative process taking place within the coil tubes.
NOTE: The pressures and temperatures shown in the refrigerant cycle illustrations on the following pages are for demonstration purposes only. Actual temperatures and pressures are to be obtained from the “Expanded Performance Chart”.
Liquid refrigerant at condensing pressure and temperatures leaves the outdoor condensing coil through the drier and is metered into the indoor coil through the metering device. As the cool, low pressure, saturated refrigerant enters the tubes of the indoor coil, a portion of the liquid immediately vaporizes. It continues to soak up heat and vaporizes as it proceeds through the coil, cooling the indoor coil down to about 48°F.
Heat is continually being transferred to the cool fins and tubes of the indoor evaporator coil by the warm system air. This warming process causes the refrigerant to boil. The heat removed from the air is carried off by the vapor. As the vapor passes through the last tubes of the coil, it becomes superheated. That is, it absorbs more heat than is necessary to vaporize it. This is assurance that only dry gas will reach the compressor. Liquid reaching the compressor can weaken or break compressor valves.
The compressor increases the pressure of the gas, thus adding more heat, and discharges hot, high pressure superheated gas into the outdoor condenser coil. In the condenser coil, the hot refrigerant gas, being warmer than the outdoor air, first loses its superheat by heat transferred from the gas through the tubes and fins of the coil. The refrigerant now becomes saturated, part liquid, part vapor and then continues to give up heat until it condenses to a liquid alone. Once the vapor is fully liquefied, it continues to give up heat which subcools the liquid, and it is ready to repeat the cycle.
The inverter system can stop the compressor or outdoor fan to protect the unit. The inverter system can run higher compressor speed than required from thermostat to recover compressor oil that flows.

SYSTEM STARTUP TEST
NOTICE: On initial power start-up, the outdoor unit will display code E11, signaling that initial SYSTEM test must be run. Follow the instructions BELOW to initiate and complete the testing.
A system verification test is now required to check the equipment settings and functionality.
Inverter units are tested by any of the following methods:

  • Setting the “SUt” menu (System verification test) to ON through the indoor unit control board push buttons.
  • Setting the System verification test menu of mode display screen-4 to ON through the outdoor unit control board push buttons.
  • Through the CoolCloud HVAC phone application.

Once selected, it checks the equipment for approximately 5 – 15 minutes. System test may exceed 15 minutes if there is an error. Refer to the Troubleshooting section, if error code appears.
Before starting the SYSTEM TEST, turn off the electric heater and gas furnace.
NOTE: If the unit is attempting to run SYSTEM TEST in under 20°F ambient temperature, the unit may not be able to complete the test due to low suction pressure. In such a case, re-run the SYSTEM TEST when the ambient temperature exceeds 20°F.

COOLCLOUD™ HVAC PHONE APPLICATION
The CoolCloud HVAC phone application designed to improve the contractor’s setup /diagnostic experience. This application can only use with the ComfortBridge compatible indoor unit and can download through CoolCloud website at https://www.coolcloudhvac.com, Google Play or the Apple App Store.
Users can see specific model information, review active diagnostic error codes, observe system status during operation, make system menu adjustments, add site visit notes and run system testing of all operational modes (heat / cool / fan) directly from the phone.
The phone application is also capable of directly updating the ComfortBridge compatible indoor unit software anytime updates are available.
The application will automatically notify the user if updates are available.
NOTE: The software update may take up to 20 minutes to complete.

CHARGE MODE
CHARGE mode allows for charging of the system.
System operates for a duration of approximately one hour while the equipment runs at full capacity.
After one hour, the CHARGE MODE ends and the system resumes normal operation.
Before starting the CHARGE MODE, turn off the Cool or Heat mode and electric heater or gas furnace.
a. Inverter units are charged by any of the following methods:

  • Setting the “CR9” menu (Charge Mode) to ON through the indoor unit control board push buttons.
  • Setting the Charge mode menu of mode display screen-4 to ON through the outdoor unit control board push buttons.
  • Through the CoolCloud HVAC phone application.
    b. The System will remain in charge mode (high speed) for 60 minutes before timing out.
    c. When charge mode once complete, the installer must manually shut off.

NOTE: Charge mode is for validating sub cooling. To ensure a proper initial charge, the amount of refrigerant added must be weighed in after measuring the line set and calculating additional charge.
NOTICE: When put into CHARGE MODE the 7-segment display will begin blinking “cha” lights. Once the system is stable the “cha” lights will stop blinking and stay solid (will take around 30 minutes). Using service equipment, add or recover refrigerant according to the calculation in Step 1.
Do not adjust refrigerant level if the “cha” lights are not solid.

BOOST MODE
BOOST MODE can be enabled or disabled through the control board push buttons or through the CoolCloud app.
BOOST MODE allows the system to operate at increased compressor speed to satisfy unusual high loads. BOOST MODE is initiated by an outdoor temperature sensor located in the outdoor unit.
Please note that outdoor equipment operational sound levels may increase while the equipment is running in BOOST MODE. Disabling BOOST MODE will provide the quietest and most efficient operation.
BOOST MODE is ON by default and is activated when the outdoor temperature reaches 105°F. BOOST MODE can be disabled and enabled and the activation temperature adjusted in the Settings menu of the CoolCloud app or through the indoor / outdoor push button menus.

DEHUMIDIFICATION
The thermostat reads the indoor humidity level and allows the user to set a dehumidification target based on these settings. The thermostat controls the humidity level of the conditioned space using the cooling system. Dehumidification is engaged whenever a cooling demand is present and structural humidity levels are above the target level. When this condition exists, the circulating fan output is reduced, increasing system run time, over cooling the evaporator coil and ultimately removing more humidity from the structure than if only in cooling mode. The thermostat also allows for an additional overcooling limit setting from 0°F to 3°F setup. This allows the cooling system to further reduce humidity by lowering the temperature up to 3°F below the cooling setpoint in an attempt to better achieve desired humidity levels.

*DEHUMIDIFICATION TIPS (ComfortNet Systems Only)**
For effective dehumidification operation:

  • Ensure “Dehumidification” is not set to “OFF”

  • Verify the cooling airflow profile (cool profiles) is set to “Profile D”.
    – See the Cool Set-up section of the Installation
    Manual for complete airflow profile details.
    – By default, “dehumidification selection” is standard and the cooling airflow profile is set to “Profile D”.

  • For additional dehumidification control, airflow settings are field adjustable and can be fine-tuned to a value that is comfortable for the application from a range of Cool Airflow Trim.

  • In addition, the system can have Enhanced Dehumidification operation in setting “A”, “B”, or “C” of dehumidification based on dehumidification demand.

  • See the Dehumidification Select section for more detail.

COMFORTBRIDGE™ SYSTEM OVERVIEW

The Comfort Bridge based inverter heating and air conditioning system uses an indoor unit and outdoor unit digitally communicating with one another via a two-way communications path. The 24 VAC single-stage thermostat sends commands to the indoor and outdoor units.
The indoor and outdoor units interacting with one another directly while taking simple analog commands from the thermostat are the core of unlocking the benefits and features of the ComfortBridge control system.
NOTE: It is strongly recommend the use of thermostat with humidity sensor and dehumidification terminal. Without these functions, dehumidification operation does not work.

COMFORTBRIDGE SYSTEM ADVANCED FEATURES
The Comfort Bridge system permits access to additional system information, advanced set-up features, and advanced diagnostic/troubleshooting features via the control board push buttons or the Cool Cloud mobile app.

FAULT CODE HISTORY
The Air Conditioner’s diagnostics menu provides access to the most recent faults. The six most recent faults can be accessed through the control board seven segment displays or the Cool Cloud mobile app.
Any consecutively repeated fault is stored a maximum of three times.
EXAMPLE: A leak in the system, low refrigerant charge or an incompletely open stop valve can cause the unit to flash error code E15. This error code suggests that the unit is experiencing operation at low pressure. The control will only store this fault the first three consecutive times the fault occurs.
NOTE: The fault list can be cleared after performing maintenance or servicing the system to assist in the troubleshooting process.

DEVICE STATUS
This menu displays information about the systems current status. This menu can be utilized to confirm correct functionality of the equipment and for troubleshooting purposes.
The following items will be displayed:

  • Heat Capacity Request Percentage
  • Cool Capacity Request Percentage
  • Heat Capacity Request During Defrost Percentage
  • Dehumidification Request Percentage
  • Reversing Valve Status
  • Reported Airflow by Indoor Unit
  • Boost Mode
  • Previous Defrost Run Time

SENSOR DATA
The following sensor items will be displayed:

  • Outdoor Temperature
  • Coil Temperature
  • Liquid Line Temperature
  • Discharge Temperature
  • Defrost Sensor
  • Suction Pressure

PUMP DOWN
This function can be enabled this menu.
SET 7-SEGMENT MODE DISPLAY TO PUMP DOWN
Please follow the following sequence to enter PUMP DOWN to accumulate the refrigerant to outdoor unit by 7 Segment Mode. Do not operate COOL ON or HEAT ON mode to enter PUMP DOWN.
Before starting the PUMP DOWN operation, change indoor fan trim, delay and profile back to default and stop electric heater and gas furnace. Remove if no trim feature. In this operation, the gas and liquid service valve should be opened.

  1. Set 7-segment display to SCREEN 4 (SETTING MODE 2) Setting No. 8 and change the display from “-01” to “-00” System will then automatically start PUMP DOWN operation. For information on how to set 7-segment display, see the section SETTING THE MODE DISPLAY in this manual.
  2. Approximately one minute later, the compressor should start operating. Check the amperage at the compressor wiring to see the compressor operation status. Unit display error code E11 (System verification Test) once the PUMP DOWN operations starts.
  3. Close liquid service valve approximately two minutes after compressor has come on.
  4. Compressor will come to a stop automatically. Close the suction service valve immediately after the compressor stops. After completion of PUMP DOWN, unit shows error code“E11”.

NOTE: Refrigerant cannot be collected to the outdoor unit completely if the system is overcharged or if there is a delay in closing the liquid service valve and suction service valve.
Evacuate the left over refrigerant from the system using a recovery machine.

SYSTEM VERIFICATION TEST
The mandatory system verification test is enabled from this menu, which enables a functional check of the equipment, in addition to ensuring proper stop valve position.

COOL SET-UP
The system allows for the adjustment of several cooling performance variables. Cool Airflow Trim (*1), Cool Airflow Profiles, Cool Fan ON Delay, Cool Fan OFF Delay and Dehumidification Select (some enable option or off ) can be adjusted in this menu. You can also reset this entire menu to factory default settings.
See the following images showing the four cooling airflow profiles.

COOLING AIRFLOW PROFILE

  • Profile A provides only an OFF delay of one (1) minute at 100% of the cooling demand airflow.
    Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner - SYSTEM
OPERATION 1

  • Profile B ramps up to full cooling demand airflow by first stepping up to 50% of the full demand for 30 seconds. The motor then ramps to 100% of the required airflow. A one (1) minute OFF delay at 100% of the cooling airflow.
    Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner - SYSTEM
OPERATION 2

  • Profile C ramps up to 82% of the full cooling demand airflow and operates there for approximately 7 1/2 minutes. The motor then steps up to the full demand airflow. Profile C also has a one (1) minute 100% OFF delay.
    Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner - SYSTEM
OPERATION 3

  • Profile D (default) ramps up to 50% of the demand for 1/2 minute, then ramps to 82% of the full cooling demand airflow and operates there for approximately 7 1/2 minutes. The motor then steps up to the full demand airflow. Profile D has a 1/2 minute at 50% airflow OFF delay.
    Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner - SYSTEM
OPERATION 4

HEAT SET-UP
This menu allows for the adjustment of several heating performance variables. Heat Airflow trim (*1), Heat Fan ON Delay, Heat Fan OFF Delay and timed Defrost interval can be adjusted in this menu. Time interval of 30, 60, 90 and 120 minutes between two defrost cycles can be set to suit the weather conditions and performance of the unit.

*SET THERMOSTAT TO ADJUST INDOOR AIR CFM TRIM¹
User can change the airflow trim at high, intermediate and low for cooling.
Select: Cool/Heat Airflow Trim (High): high speed cooling/heating Cool/Heat Airflow Trim (Int): intermediate speed cooling/ heating Cool/Heat Airflow Trim (Low): low speed cooling/ heating Under each trim setting, the airflow can be increased or decreased by a certain percentage.
1 1) At Cool and Heat Hi speed trim, SXV906010
with VC960804C, VM970804C and *MVC800804C combination trim more than 5% settings are invalid. Trimmed up CFM makes miss matching error.
2) At Cool Hi speed trim, Other than the above, depending on the connected indoor unit, there are restrictions on the positive side Trim setting.
If you want to change the Cool Airflow Trim to positive side, be sure to confirm the Airflow Trim restrictions in the latest indoor unit installation manual. The latest manual can be obtained from the website “PartnerLink(InfoFinderPlus/ Literature)”. [PartnerLink URL] https://partnerlinkmarketing.goodmanmfg.com/goodman/info-finder-plus
3) At Cool Intermediate and Low speed trim, The Inverter system uses lower compressor speed and lower indoor unit CFM to optimize system performance. To obtain 100% CFM for home circulation, use full Trim setting instead of Int/Low speed. This is recommended for applications with unusually cold return temperatures such as basements.

**DEHUMIDIFICATION SELECT***
When Dehumidification mode exists, the circulating fan output is reduced, increasing system run time, over cooling the evaporator coil and ultimately removing more humidity from the structure than if only in cooling mode.
The system can have Dehumidification operation in setting “Standard”, “A”, “B” or “C” of “dehumidify with cooling” menu based on dehumidification demand.
Setting “Standard” allows for the widest compressor operation range with lower CFM than Cooling mode.
In the Enhanced Dehumidification (setting A, B and C) the indoor airflow is lower than Standard Dehumidification (Standard).
Setting “A” allows for the same compressor operation range in Dehumidification operation with lower CFM than standard dehumidification (Standard).
Setting “B” limits compressor operation range and keeps high dehumidification capacity.
In setting “C” the system runs fixed at 100% compressor and airflow. See Figure 1.
NOTE: In high humidity environments, sweating on supply ducts, cased coils or air handler cabinets can become an issue in Enhanced Dehumidification operation. It is strongly recommended covering then with 2” fiberglass insulation for these installations.
For details, see the Installation Manual or Service Manual that matches the Major and Minor revision of model name.

MAX COMPRESSOR RPS FOR COOLING/HEATING (SELECTED RPS/ RPS range)
Max compressor speed at which the outdoor unit will operate can be changed through the control board seven segment displays or the CoolCloud mobile app. Max compressor speed can be changed to get the required capacity or efficiency.
Once the maximum speed is set, the system operates between the set maximum speed and default low speed. When determining the appropriate compressor speed for cooling and heating, in the “RPS Range For Cooling/ Heating” menu select the range that contains the desired value. (Then, after pressing the Apply Changes button, leave the Device setting menu and enter this menu again. Otherwise, the changed settings will not be reflected.) Next, in the “Selected RPS for Cooling/Heating” menu, select the desired RPS within the displayed range.

COOLING CYCLE

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner - SYSTEM
OPERATION 6

LEGEND:

Tl =Thermistor( Outdoor Liquid Temperature)
Td =Thermistor(Discharge Temperature )
Ta =Thermistor( Outdoor Air Temperature)| HP/LP sensor= High/Low Pressure Sensor
HPS= High Pressure Switch
Tm =Thermistor(Outdoor Coil Temperature )
---|---

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner - SYSTEM
OPERATION 7

LEGEND:

Tl = Thermistor (Outdoor Liquid Temperature)
Td = Thermistor (Discharge Temperature)
Ta = Thermistor (Outdoor Air Temperature)
Tm = Thermistor (Outdoor Coil Temperature)| Tli =Thermistor (Indoor Liquid Temperature)
Tgi =Thermistor (Indoor Gas Temperature)
ID HP/LP sensor =Indoor High/Low Pressure Sensor
OD HP/LP sensor =Outdoor High/Low Pressure Sensor
HPS =High Pressure Switch
---|---

SERVICING

CHECKING VOLTAGE

  1. Remove outer case, control panel cover, etc., from unit being tested.
    With power ON:
    WARNING Line voltage now present.

  2. Using a voltmeter, measure the voltage across terminals L1 and L2 of the contactor for the Air Conditioner condenser unit or at the field connections for the air handler or  eaters. ComfortNet™ Ready Air Conditioner Condenser Units: Measure the voltage across the L1 and L2 lugs on the unitary (UC) control.

  3. No reading – indicates open wiring, open fuse(s) no power or etc., from unit to fused disconnect service. Repair as needed.

  4. With ample voltage at line voltage connectors, energize the unit.

Unit Type Unit Supply Voltage (VAC)
voltage min.

Outdoor Unit, Air Handler,
Modular Blower, Heater Kit| 208/230| 197| 253
Gas Furnaces| 115| 103| 126

NOTE: When operating electric heaters on voltages other than 240 volt, refer to the System Operation section on electric heaters to calculate temperature rise and air flow.
Low voltage may cause insufficient heating.

CHECKING WIRING
WARNING

HIGH VOLTAGE
Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death.

  1. Check wiring visually for signs of overheating, damaged insulation and loose connections.
  2. Use an ohmmeter to check continuity of any suspected open wires.
  3. If any wires must be replaced, replace with comparable gauge and insulation thickness.

CHECKING THERMOSTAT AND WIRING
Communicating Thermostat Wiring: The maximum wire length for 18 AWG thermostat wire is 250 feet.

THERMOSTAT AND WIRING
WARNING
Line voltage now present.
With power ON, thermostat calling for cooling/heating.

  1. Use a voltmeter to check for 24 volt at thermostat wires C and R in the indoor unit control panel.
  2. No voltage indicates trouble in the thermostat, wiring or transformer source.
  3. Check the continuity of the thermostat and wiring. Repair or replace as necessary.

WARNING
Line voltage now present.

RESISTANCE HEATERS
With power ON:

  1. Set room thermostat to a higher setting than room temperature so both stages call for heat.
  2. With voltmeter, check for 24 volt at each heater relay.
  3. No voltage indicates the trouble is in the thermostat or wiring.
  4. Check the continuity of the thermostat and wiring. Repair or replace as necessary.

NOTE: Consideration must be given to how the heaters are wired (O.D.T. and etc.). Also safety devices must be checked for continuity.

THERMOSTAT COMFORTBRIDGE™ SYSTEM
OVERVIEW
The ComfortBridge based inverter heating and air conditioning system uses an indoor unit and outdoor unit digitally communicating with one another via a two-way communications path.
The 24 VAC single-stage thermostat sends commands to the indoor and outdoor units.
The indoor and outdoor units interacting with one another directly while taking simple analog commands from the thermostat are the core of unlocking the benefits and features of the ComfortBridge control system.
NOTE: It is strongly recommend the use of thermostat with humidity sensor and dehumidification terminal. Without these functions, Dehumidification operation does not work.

COMFORTBRIDGE™ SYSTEM WIRING
ComfortBridge™ control system is low voltage wiring consists of two wires between the indoor unit and outdoor unit.
The required wires are data lines 1 and 2.
The thermostat needs 4 wires between the indoor unit and thermostat or 5 wires if the thermostat requires a Common wire.
NOTE: Regarding the wiring of the indoor unit to the thermostat, also refer to ComfortBridge™ compatible indoor unit’s install manual (in case of communicating inverter system).

CHECKING TRANSFORMER AND CONTROL CIRCUIT
WARNING
HIGH VOLTAGE
Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death.
A step-down transformer (208/230 volt primary to 24 volt secondary) is provided with each indoor unit. This allows ample capacity for use with resistance heaters. The outdoor sections do not contain a transformer (see note below). (see indoor unit WIRING DIAGRAM)

WARNING
Disconnect ALL power before servicing.

  1. Remove control panel cover, or etc., to gain access to transformer.
    With power ON:
    WARNING
    Line voltage now present.

  2. Using a voltmeter, check voltage across secondary voltage side of transformer (R to C).

  3. No voltage indicates faulty transformer, bad wiring, or bad splices.

  4. Check transformer primary voltage at incoming line voltage connections and/or splices.

  5. If line voltage available at primary voltage side of transformer and wiring and splices good, transformer is inoperative. Replace.

CHECKING HIGH PRESSURE SWITCH
WARNING
HIGH VOLTAGE
Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death.
The high pressure switch senses the pressure in the compressor discharge line. If abnormally high condensing pressures develop, the contacts of the control open, breaking the control circuit before the compressor motor overloads. This control is automatically reset.

  1. Using an ohmmeter, check across the X32A connection on outdoor unit PCB high pressure control, with wire removed. If not continuous, the contacts are open.

  2. Attach a gauge to the dill valve port on the base valve.
    With power ON:
    WARNING
    Line voltage now present.

  3. Start the system in charge mode and place a piece of cardboard in front of the outdoor coil, raising the condensing pressure.

  4. Check pressure at which the high pressure control cutsout. If it cuts-out at 605 PSIG to -17 PSIG, it is operating normally (See causes for high head pressure in Service Problem Analysis Guide). If it cuts out below this pressure range, replace the control.

CHECKING OUTDOOR HI/LOW PRESSURE SENSOR
WARNING
Line voltage now present.
The HI/LOW pressure sensor senses the suction pressure in cooling mode, and the discharge pressure in heating mode. Follow the following sequence to check the pressure sensor.

  1. Connect manifold gauge to the air conditioner unit
  2. Connect a pair of extended Molex probe tips to your voltmeter test leads.
  3. Find the suction pressure in the cool mode, or discharge pressure in the heat mode. Locate (X17A) connection and connect a DC voltmeter across sensor terminals 1 and 3, (black and white wires) and record the DC voltage.
  4. Compare your readings to the detected pressure vs output voltage in the following table. Replace the sensor if the sensor is open, shorted, or outside of the voltage range.

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner - SERVICING
2

VOLTAGE AND PRESSURE CHARACTERISTICS
RESISTANCE CHECK (5 TON ONLY)
WARNING
HIGH VOLTAGE
Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death.

  1. Discharge capacitor and remove wire leads.
    WARNING
    Discharge capacitor through a 20 to 30 OHM resistor before handling.

  2. Set an ohmmeter on its highest ohm scale and connect the leads to the capacitor.
    A. Good Condition – indicator swings to zero and slowly returns to infinity. (Start capacitor with bleed resistor will not return to infinity. It will still read the resistance of the resistor).
    B. Shorted – indicator swings to zero and stops there – replace.
    C. Open – no reading – replace. (Start capacitor would read resistor resistance.)

CAPACITANCE CHECK (5 TON ONLY)
Using a hookup as shown below, take the amperage and voltage readings and use them in the formula:
Capacitance (MFD) = 2650 X Amperage Voltage
WARNING
Discharge capacitor through a 20 to 30 OHM resistor before handling.

CHECKING COMPRESSOR
WARNING
Hermetic compressor electrical terminal venting can be dangerous. When insulating material which supports a hermetic compressor or electrical terminal suddenly disintegrates due to physical abuse or as a result of an electrical short between the terminal and the compressor housing, the terminal may be expelled, venting the vapor and liquid contents of the compressor housing and system.
If the compressor terminal PROTECTIVE COVER and gasket (if required) are not properly in place and secured, there is a remote possibility if a terminal vents, that the vaporous and liquid discharge can be ignited, spouting flames several feet, causing potentially severe or fatal injury to anyone in its path.
This discharge can be ignited external to the compressor if the terminal cover is not properly in place and if the discharge impinges on a sufficient heat source.
Ignition of the discharge can also occur at the venting terminal or inside the compressor, if there is sufficient contaminant air present in the system and an electrical arc occurs as the terminal vents.
Ignition cannot occur at the venting terminal without the presence of contaminant air, and cannot occur externally from the venting terminal without the presence of an external ignition source.
Therefore, proper evacuation of a hermetic system is essential at the time of manufacture and during servicing. To reduce the possibility of external ignition, all open flame, electrical power, and other heat sources should be extinguished or turned off prior to servicing a system.

COMPRESSOR WINDING INSULATION TEST
The Inverter on the outdoor control board takes the position signal from the UVW line, connected with the compressor. If the system detects a malfunction on the compressor, check the insulation resistance in accordance with the following procedure.
WARNING
HIGH VOLTAGE
Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death.

  1. Remove the leads from the compressor terminals.
  2. Using a Megometer, attach one lead to ground.
  3. Using the other lead of the Megometer, check the insulation between U to ground, V to ground, W to ground.

TESTING COMPRESSOR WINDINGS INSULATION

NOTE: The 2, 3, and 4 ton compressor has a terminal on the top. The 5 ton compressor has the terminals on the side. If the insulation resistance of the compressor is less than 100k Ohms between U to ground, V to ground, W to ground, replace the compressor.
GROUND TEST
If fuse, circuit breaker, ground fault protective device, etc., has tripped, this is a strong indication that an electrical problem exists and must be found and corrected. The circuit protective device rating must be checked, and its maximum rating should coincide with that marked on the equipment nameplate.
With the terminal protective cover in place, it is acceptable to replace the fuse or reset the circuit breaker ONE TIME ONLY to see if it was just a nuisance opening. If it opens again, DO NOT continue to reset.
Disconnect all power to unit, making sure that all power legs are open.

  1. DO NOT remove protective terminal cover. Disconnect the three leads going to the compressor terminals at the nearest point to the compressor.
  2. Identify the leads and using an ohmmeter on the R x 10,000 scale or the highest resistance scale on your ohmmeter check the resistance between each of the three leads separately to ground (such as an unpainted tube on the compressor).
  3. If a ground is indicated, then carefully remove the compressor terminal protective cover and inspect for loose leads or insulation breaks in the lead wires.
  4. If no visual problems indicated, carefully remove the leads at the compressor terminals.
  5. Carefully retest for ground, directly between compressor terminals and ground.
  6. If ground is indicated, replace the compressor. The resistance reading should be infinity. If there is any reading on meter, there is some continuity to ground and compressor should be considered defective.

WARNING
Damage can occur to the glass embedded terminals if the leads are not properly removed. This can result in terminal and hot oil discharging.
TESTING CRANKCASE HEATER (5 TON ONLY)
The crankcase heater must be energized a minimum of 2 hours before the unit is operated. Crankcase heaters are used to prevent migration or accumulation of refrigerant in the compressor crankcase during the off cycles and prevents liquid slugging or oil pumping on start up. A crankcase heater will not prevent compressor damage due to a floodback or over charge condition.
WARNING
Disconnect ALL power before servicing.

  1. Disconnect the heater lead in wires.
  2. Using an ohmmeter, check heater continuity – should test continuous. If not, replace.

NOTE: The positive temperature coefficient crankcase heater is a 33 watt 240 voltage heater. The cool resistance of the heater will be approximately 1745 ohms. The resistance will become greater as the temperature of the compressor shell increases.
TESTING TEMPERATURE SENSORS AND EEV COIL RESISTANCE
The *SXV9 outdoor units and AMVE** indoor units are factory equipped with:

  • (Ta) an outdoor air temperature sensor
  • (Tm) an outdoor coil temperature sensor
  • (TI) an outdoor liquid temperature sensor
  • (Td) a discharge temperature sensor
  • (Tgi) an indoor gas temperature sensor
  • (Tli) an indoor liquid temperature sensor

To check above sensors:
WARNING
HIGH VOLTAGE
Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death.

  1. Disconnect power to the Air Conditioner condensor.
  2. Disconnect the sensor from the electric board.
  3. Connect an ohmmeter across the sensor terminals. The ohmmeter should read be the resistance shown in the table THERMISTOR RESISTANCE AND TEMPERATURE CHARACTERISTICS CHART (page 31). Replace the sensor if the sensor is open, shorted, or outside the valid resistance range.

TESTING EEV COIL RESISTANCE
To check the resistance of the EEV coil, first disconnect EEV cable from the PCB board. Make measurements of resistance between the connector pins, and then make sure the resistance falls in the range of 40 to 50 Ʊ.

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner - SERVICING
7

AMVE HEATER CONTROL (OPTIONAL)
DESCRIPTION
The AMVE models utilize an electronic control that provides ECM blower motor control and control of up to two electric heat sequencers. The control has thermostat inputs for up to two stages of cooling, two stages of electric heat, reversing valve, and dehumidification. Control input is 24VAC.

TROUBLESHOOTING
MOTOR CONTROL CIRCUITS
WARNING
HIGH VOLTAGE
Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death.

  1. Turn on power to air handler or modular.
    WARNING
    Line voltage now present.

  2. Check voltage between pins 1 and 4 at the 4-wire motor connector on the control board. Voltage should be between 9 and 15 VDC. Replace control if voltage is not as specified.

ELECTRIC HEAT SEQUENCER OUTPUTS
WARNING
HIGH VOLTAGE
Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death.

  1. Turn on power to air handler or modular blower.
    WARNING
    Line voltage now present.

  2. Disconnect the 4-circuit harness connecting the control to the electric heater kit.

  3. Provide a thermostat demand for low stage auxiliary heat. Measure the voltage between pins 1 and 3 at the onboard electric heat connector. Voltage should measure 24VAC.
    Replace control if no voltage is present.
    NOTE: Allow for any built-in time delays before making voltage measurements. Any electric heater faults that are present may prevent the heater output from energizing. Verify that no heater faults are present before making voltage measurements.

  4. Provide a thermostat demand for high stage auxiliary heat (W1 + W2). Measure the voltage between pins 1 and 3 at the on-board electric heat connector. Measure the voltage between pins 2 and 3 at the on-board electric heat connector. Voltage should measure 24VAC. Replace control if no voltage is present.

The integrated air handler control has some on-board tools that may be used to troubleshoot the network. These tools are: red communications LED, green receive (Rx) LED, and learn button. These are described below
a. Red communications LED – Indicates the status of the network. Refer to the Network Troubleshooting Chart for the LED status and the corresponding potential problem.
b. Green receive LED – Indicates network traffic. Refer to the Network Troubleshooting Chart for the LED status and the corresponding potential problem.
c. Learn button – Used to reset the network. Depress the button for approximately 2 seconds to reset the network.
For details, see NETWORK TROUBLESHOOTING section.
WARNING
Disconnect ALL power before servicing.
REFRIGERATION REPAIR PRACTICE
DANGER
Always remove the refrigerant charge in a proper manner before applying heat to the system.
When repairing the refrigeration system:
WARNING
HIGH VOLTAGE
Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death.

  1. Never open a system that is under vacuum. Air and moisture will be drawn in.
  2. Plug or cap all openings.
  3. Remove all burrs and clean the brazing surfaces of the tubing with sand cloth or paper. Brazing materials do not flow well on oxidized or oily surfaces.
  4. Clean the inside of all new tubing to remove oils and pipe chips.
  5. When brazing, sweep the tubing with dry nitrogen to prevent the formation of oxides on the inside surfaces.
  6. Complete any repair by replacing the liquid line drier in the system, evacuate and charge.

BRAZING MATERIALS
IMPORTANT NOTE: Torch heat required to braze tubes of various sizes is proportional to the size of the tube. Tubes of smaller size require less heat to bring the tube to brazing temperature before adding brazing alloy. Applying too much heat to any tube can melt the tube. Service personnel must use the appropriate heat level for the size of the tube being brazed.
NOTE: The use of a heat shield when brazing is recommended to avoid burning the serial plate or the finish on the unit. Heat trap or wet rags should be used to protect heat sensitive components such as stop valves, EEV, TXV and filters.
Copper to Copper Joints – Sil-Fos used without flux (alloy of 15% silver, 80% copper, and 5% phosphorous). Recommended heat 1400°F.
Copper to Steel Joints – Silver Solder used without a flux (alloy of 30% silver, 38% copper, 32% zinc). Recommended heat – 1200°F.
LEAK TESTING (NITROGEN OR NITROGEN-TRACED)
WARNING
To avoid the risk of fire or explosion, never use oxygen, high pressure air or flammable gases for leak testing of a refrigeration system.
WARNING
To avoid possible explosion, the line from the nitrogen cylinder must include a pressure regulator and a pressure relief valve. The pressure relief valve must be set to open at no more than 450 psig.
LEAK TESTING
Leak test the system using dry nitrogen and soapy water to identify leaks. If you prefer to use an electronic leak detector, charge the system to 10 PSIG with the appropriate system refrigerant (see Serial Data Plate for refrigerant identification). Do not use an alternative refrigerant. Using dry nitrogen finish charging the system to 450 PSIG. Apply the leak detector to all suspect areas. When leaks are discovered, repair the leaks, and repeat the pressure test. If leaks have been eliminated proceed to system evacuation.
STANDING PRESSURE TEST
Using dry nitrogen, pressurize the system to 450 PSIG. Allow the pressure to stabilize and hold for 15 minutes (min- imum). If the pressure does not drop below 450 PSIG the system is considered leak free. Proceed to system evacuation using the Deep Vacuum Method. If after 15 minutes the pressure drops below 450 PSIG follow the procedure outlined below to identify system leaks. Repeat the Standing Pressure Test.
SYSTEM EVACUATION
WARNING
REFRIGERANT UNDER PRESSURE!
Failure to follow proper procedures may cause property damage, personal injury or death.
IMPORTANT NOTE: Because of the potential damage to compressors, do not allow suction pressure at service valve to drop below 5 PSIG when pumping unit system down for repair. Outdoor section, depending on line set length and amount of charge in system, may not be able to hold the entire system charge.
This is the most important part of the entire service procedure. The life and efficiency of the equipment is dependent upon the thoroughness exercised by the serviceman when evacuating air (non-condensables) and moisture from the system.
Air in a system causes high condensing temperature and pressure, resulting in increased power input and reduced performance.
Moisture chemically reacts with the refrigerant oil to form corrosive acids. These acids attack motor windings and parts, causing breakdown.
The equipment required to thoroughly evacuate the system is a vacuum pump, capable of producing a vacuum equivalent to 500 microns absolute and a micron gauge to give a true reading of the vacuum in the system
NOTE: Never use the system compressor as a vacuum pump or run when under a high vacuum. Motor damage could occur.
Condensing unit liquid and suction valves are closed to contain the charge within the unit. The unit is shipped with the valve stems closed and caps installed. Do not open valves until the system is evacuated.
DEEP VACUUM METHOD
The Deep Vacuum Method requires a vacuum pump rated for 500 microns or less. This method is an effective and efficient way of assuring the system is free of non-condensable air and moisture. As an alternative, the Triple Evacuation Method may be used.
It is recommended to remove the Schrader Cores from the service valves using a core-removal tool to expedite the evacuation procedure.
Connect the vacuum pump, micron gauge, and vacuum rated hoses to both service valves. Evacuation must use both service valves to eliminate system mechanical seals. Evacuate the system to less than 500 microns.
Isolate the pump from the system and hold vacuum for 10 minutes (minimum). Typically, pressure will rise slowly during this period. If the pressure rises to less than 1000 microns and remains steady, the system is considered leakfree; proceed to system charging and startup.
If pressure rises above 1000 microns but holds steady below 2000 microns, non- condensable air or moisture may remain or a small leak is present. Return to step 2: If the same result is achieved check for leaks and repair. Repeat the evacuation procedure.
If pressure rises above 2000 microns, a leak is present. Check for leaks and repair. Repeat the evacuation procedure
TRIPLE EVACUATION METHOD (ALTERNATE TO DEEP VACUUM METHOD)

  1. Evacuate the system to 4000 microns and hold for 15 minutes. Then, break the vacuum with dry nitrogen, bring the system pressure up to 2-3 PSIG, and hold for 20 minutes. Release the nitrogen.
  2. Evacuate to 1500 microns and hold for 20 minutes. Break the vacuum with dry nitrogen again, bring the system pressure back up to 2-3 PSIG, and hold for 20 minutes.
  3. Then, evacuate the system until it is below 500 microns and hold for 60 minutes.

WARNING
Do not front seat the service valve(s) with the compressor open, with the suction line of the compressor closed or severely restricted.

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner - SERVICING
8

CHARGING
WARNING
REFRIGERANT UNDER PRESSURE!

  • Do not overcharge system with refrigerant.
  • Do not operate unit in a vacuum or at negative pressure.

Failure to follow proper procedures may cause property damage, personal injury or death.
CAUTION
Use refrigerant certified to AHRI standards. Used refrigerant may cause compressor damage and is not covered by the warranty. Most portable machines cannot clean used refrigerant to meet AHRI standards.
CAUTION
Damage to the unit caused by operating the compressor with the suction valve closed is not covered under the warranty and may cause serious compressor damage.
Charge the system with the exact amount of refrigerant. See the Installation Manual for the correct refrigerant charge.
An inaccurately charged system will cause future problems.

  1. When using an ambient compensated calibrated charging cylinder, allow liquid refrigerant only to enter the high side.

  2. Once the system stops taking refrigerant, close the valve on the high side of the charging manifold.

  3. Start the system and charge the balance of the refrigerant through the low side.
    NOTE: R410A should be drawn out of the storage container or drum in liquid form due to its fractionation properties, but should be “Flashed” to its gas state before entering the system. There are commercially available restriction devices that fit into the system charging hose set to accomplish this. DO NOT charge liquid R410A into the compressor.

  4. With the system still running, close the valve on the charging cylinder. At this time, you may still have some liquid refrigerant in the charging cylinder hose and will definitely have liquid in the liquid hose. Reseat the liquid line core. Slowly open the high side manifold valve and transfer the liquid refrigerant from the liquid line hose and charging cylinder hose into the suction service valve port. CAREFUL: Watch so that liquid refrigerant does not enter the compressor.
    FINAL CHARGE ADJUSTMENT
    The outdoor temperature must be 65°F to 105°F. If outdoor ambient temperature is out of range, charge defined amount and don’t adjust subcooling. Set the room thermostat to CHARGE mode.
    After system has stabilized per startup instructions, check subcooling as detailed in the following section. In the event of system overcharge or undercharge, refrigerant in the system must be adjusted to the appropriate subcooling and superheat as specified in the following sections. Refrigerant amount should be adjusted within +/- 0.5 lb. if the outdoor ambient temperature is greater than 65°F and less than 105°F. Manufacturer recommends that the system should be evacuated and should be charged the initial efrigerant for given line length when the ambient temperature is less than 65°F and more than 105°F. Refer to the Installation Manual to calculate refrigerant amount.

  5. With the system still running, remove hose and reinstall both valve caps.

  6. Check system for leaks.

NOTE: Subcooling information is valid only while the unit is operating at 100% capacity or 100% of compressor speed in CHARGE MODE. Compressor speed is displayed under STATUS menu in the thermostat.
CHECKING COMPRESSOR EFFICIENCY
The reason for compressor inefficiency is that the compressor is broken or damaged, reducing the ability of the compressor to pump refrigerant vapor. The condition of the compressor is checked in the following manner.

  1. Attach gauges to the high and low side of the system.
  2. Start the system and run CHARGE MODE.

If the test shows:
a. Below normal high side pressure.
b. Above normal low side pressure.
c. Low temperature difference across coil.
d. Low amp draw at compressor.
And the charge is correct. The compressor is faulty – re- place the compressor.
THERMOSTATIC EXPANSION VALVE
The expansion valve is designed to control the rate of liquid refrigerant flow into an evaporator coil in exact proportion to the rate of evaporation of the refrigerant in the coil. The amount of refrigerant entering the coil is regulated since the valve responds to temperature of the refrigerant gas leaving the coil (feeler bulb contact) and the pressure of the refrigerant in the coil. This regulation of the flow prevents the return of liquid refrigerant to the compressor.
Some TXV valves contain an internal check valve thus eliminating the need for an external check valve and bypass loop. The three forces which govern the operation of the valve are: (1) the pressure created in the power assembly by the feeler bulb, (2) evaporator pressure, and (3) the equivalent pressure of the superheat spring in the valve. 0% bleed type expansion valves are used on indoor and outdoor coils. The 0% bleed valve will not allow the system pressures (High and Low side) to equalize during the shut down period. The valve will shut off completely at approximately 100 PSIG.
30% bleed valves used on some other models will continue to allow some equalization even though the valve has shutoff completely because of the bleed holes within the valve. This type of valve should not be used as a replacement for a 0% bleed valve, due to the resulting drop in performance.
The bulb must be securely fastened with two straps to a clean straight section of the suction line. Application of the bulb to a horizontal run of line is preferred. If a vertical installation cannot be avoided, the bulb must be mounted so that the capillary tubing comes out at the top.
THE VALVES PROVIDED BY THE MANUFACTURER ARE DESIGNED TO MEET THE SPECIFICATION REQUIREMENTS FOR OPTIMUM PRODUCT OPERATION. DO NOT USE SUBSTITUTES.
OVERFEEDING
Overfeeding by the thermostatic expansion valve results in high suction pressure, cold suction line, and possible liquid slugging of the compressor.
If these symptoms are observed:

  1. Check for an overcharged unit by referring to the cooling performance charts in the servicing section.
  2. Check the operation of the power element in the valve as explained in S-110 Checking Thermostatic Expansion Valve.
  3. Check for restricted or plugged equalizer tube.

UNDERFEEDING
Underfeeding by the thermostatic expansion valve results in low system capacity and low suction pressures.
If these symptoms are observed:

  1. Check for a restricted liquid line or drier. A restriction will be indicated by a temperature drop across the drier.
  2. Check the operation of the power element of the valve as described in S-110 Checking Thermostatic Expansion Valve Operation.

SUPERHEAT
The thermostatic expansion valve is factory adjusted to maintain 8°F ± 1°F degrees superheat of the suction gas. Before checking the superheat or replacing the valve, perform all the procedures outlined under Air Flow, Refrigerant Charge, Thermostatic Expansion Valve – Overfeeding, Underfeeding. These are the most common causes for evaporator malfunction.
CHECKING SUPERHEAT
Refrigerant gas is considered superheated when its temperature is higher than the saturation temperature corresponding to its pressure. The degree of superheat equals the degrees of temperature increase above the saturation temperature at existing pressure. See Temperature – Pressure Chart on following pages.

  1. Run system at least 10 minutes to allow pressure to stabilize.

  2. For best results, temporarily install a thermometer on the liquid line at the liquid line service valve and 4-6” from the compressor on the suction line. Ensure the thermometer makes adequate contact and is insulated for best possible readings. Use liquid line temperature to determine sub-cooling and vapor temperature to determine superheat.
    NOTE: An optional method is to locate the thermometer at the suction line service valve. Ensure the thermometer makes adequate contact and is insulated for best possible readings.

  3. Refer to the superheat table provided for proper system superheat. Add charge to lower superheat or recover charge to raise superheat.

Superheat Formula = Suct. Line Temp. – Sat. Suct.Temp.
EXAMPLE:
a. Suction Pressure = 143 PSIG
b. Corresponding Temp. = 50°F.
c. Thermometer on Suction Line = 58°F.
To obtain the degrees temperature of superheat, subtract 50.0 from 58.0°F.
The difference is 8° Superheat. The 8° Superheat would fall in the ± range of allowable superheat.
CHECKING SUBCOOLING
Refrigerant liquid is considered subcooled when its temperature is lower than the saturation temperature corresponding to its pressure. The degree of subcooling equals the degrees of temperature decrease below the saturation temperature at the existing pressure.

  1. Attach an accurate thermometer or preferably a thermocouple type temperature tester to the liquid service valve as it leaves the condensing unit.
  2. Install a high side pressure gauge on the high side (liquid) service valve at the front of the unit.
  3. Record the gauge pressure and the temperature of the line.
  4. Review the technical information manual or specification sheet for the model being serviced to obtain the design subcooling.
  5. Compare the hi-pressure reading to the “Required Liquid Line Temperature” chart. Find the hi-pressure value on the left column. Follow that line right to the column under the design subcooling value. Where the two intersect is the required liquid line temperature. Alternately you can convert the liquid line pressure gauge reading to temperature by finding the gauge reading in the R-410A Pressure vs. Temperature Chart, find the temperature in the °F. Column.
  6. The difference between the thermometer reading and pressure to temperature conversion is the amount of subcooling.

Add charge to raise subcooling. Recover charge to lower subcooling.
Subcooling Formula = Sat. Liquid Temp. – Liquid Line Temp.
NOTE: To adjust subcooling, follow the sequence of S-108.
EXAMPLE:
a. Liquid Line Pressure = 417 PSIG
b. Corresponding Temp. = 120°F.
c. Thermometer on Liquid line = 109°F.
To obtain the amount of subcooling subtract 109°F from 120°F.
The difference is 11° subcooling. See the specification sheet or technical information manual for the design subcooling range for your unit.
There are other causes for high head pressure which may be found in the “Cooling / Heating Analysis Chart.”
If other causes check out normal, an overcharge or a system  containing non- condensables would be indicated.
If this system is observed:

  1. Start the system.
  2. Remove and capture small quantities of gas from the suction line dill valve until the head pressure is reduced to normal.
  3. Observe the system while running a cooling performance test. If a shortage of refrigerant is indicated, then the system contains non-condensables.

Charging Table

OD Ambient Temp (degF)| <65°F| 65°F to 105°F| >105°F
Subcooling (degF)| Weigh in Charge| 2T to 5T:8°F ±1°F| Weigh in Charge

SUPERHEAT AND SUBCOOLING ADJUSTMENT ON TXV APPLICATIONS
NOTE: Subcooling and superheat information is valid only while the unit is operating at 100% capacity or 100% compressor speed in CHARGE MODE.
Compressor speed is displayed under STATUS menu in the thermostat.

  1. Run system at least 10 minutes to allow pressure to stabilize. During the adjustment of subcooling, ambient temperature should be greater than 65°F and less than 105°F. If ambient temperature is out of range, don’t adjust subcooling.

  2. For best results, temporarily install a thermometer on the liquid line at the liquid line service valve and 4-6” from the compressor on the suction line. Ensure the thermometer makes adequate contact and is insulated for best possible readings. Use liquid line temperature to determine sub-cooling and vapor temperature to determine superheat.
    NOTE: An optional method is to locate the thermometer at the suction line service valve. Ensure the thermometer makes adequate contact and is insulated for best possible readings.

  3. The system subcooling should be 8°F ± 1°F. If not in that range, adjust subcooling and superheat according to the following procedure.
    a. If subcooling and superheat are low, adjust TXV to 7 to 9°F superheat, then check subcooling.
    NOTE: To adjust superheat, turn the valve stem clockwise to increase and counter clockwise to decrease.
    b. If subcooling is low and superheat is 7 to 9°F, add charge to rise subcooling to 8°F ± 1°F, then check superheat.
    c. If subcooling is low and superheat is high, add charge to rise subcooling to 8°F ± 1°F, then check superheat.
    d. If subcooling is 8°F ± 1°F and superheat is high, adjust the TXV valve to 7 to 9°F superheat, then check subcooling.
    e. If subcooling and superheat are high, adjust the TXV valve to 7 to 9°F superheat, then check subcooling.
    f. If subcooling is high and superheat is 7 to 9°F, remove charge to lower the subcooling to 8°F ± 1°F, then check superheat.
    g. If subcooling is high and superheat is low, adjust the TXV valve to 7 to 9°F superheat and remove charge to low the subcooling to 8°F ± 1°F.
    h. If subcooling is 8°F ± 1°F and superheat is low, adjust the TXV valve to 7 to 9°F superheat and remove charge to lower the subcooling 8°F ± 1°F, then check the superheat.
    NOTE: It is recommended to add charge in 4 oz. increments each time to achieve the target subcooling.

  4. Disconnect manifold set. Installation is complete.

SUBCOOLING ADJUSTMENT ON EEV APPLICATIONS
NOTE: Subcooling information is valid only while the unit is operating at 100% capacity or 100% compressor speed in CHARGE MODE.
Compressor speed is displayed under STATUS menu in the thermostat.

  1. Run system at least 20 minutes to allow pressure to stabilize. During the adjustment of subcooling, ambient temperature should be greater than 65°F and less than 105°F. If ambient temperature is out of range, don’t ad- just subcooling.

  2. For best results, temporarily install a thermometer on the liquid line at the liquid line service valve. Ensure the thermometer makes adequate contact and is insulated for best possible readings. Use liquid line temperature to determine sub-cooling.

  3. The system subcooling should fall in the range shown in following table. If not in that range, adjust subcooling according to the following procedure.
    a. If subcooling is low, add charge to adjust the subcooling to 8°F ± 1°F.
    b. If subcooling is high, remove charge to lower the subcooling to specified range.
    NOTE: It is recommended to add charge in 4 oz. increments each time to achieve the target subcooling.

  4. Disconnect manifold set. Installation is complete.

CHECKING THERMOSTATIC EXPANSION VALVE OPERATION

  1. Remove the remote bulb of the thermostatic expansion valve from the suction line.
  2. Start the system and cool the bulb in a container of ice water, closing the valve. As you cool the bulb, the suction pressure should fall and the suction temperature will rise.
  3. Next warm the bulb in your hand. As you warm the bulb, the suction pressure should rise and the suction temperature will fall.
  4. If a temperature or pressure change is noticed, the expansion valve is operating. If no change is noticed, the valve is restricted, the power element is faulty, or the equalizer tube is plugged.
  5. Capture the charge, replace the valve and drier, evacuate and recharge.

NON-CONDENSABLES
If non-condensables are suspected, shut down the system and allow the pressures to equalize. Wait at least 15 minutes. Compare the pressure to the temperature of the coldest coil since this is where most of the refrigerant will be. If the pressure indicates a higher temperature than that of the coil temperature, non-condensables are present.
Non-condensables are removed from the system by first removing the refrigerant charge, replacing and/or installing liquid line drier, evacuating and recharging.
COMPRESSOR BURNOUT
When a compressor burns out, high temperature develops causing the refrigerant, oil and motor insulation to decompose forming acids and sludge.
If a compressor is suspected of being burned-out, attach a refrigerant hose to the liquid line dill valve and properly remove and dispose of the refrigerant.
NOTICE: Violation of EPA regulations may result in fines or other penalties.
Now determine if a burn out has actually occurred. Confirm by analyzing an oil sample using a Sporlan Acid Test Kit, AK-3 or its equivalent.
Remove the compressor and obtain an oil sample from the suction stub. If the oil is not acidic, either a burnout has not occurred or the burnout is so mild that a complete clean-up is not necessary.
If acid level is unacceptable, the system must be cleaned by using the clean- up drier method.
CAUTION
Do not allow the sludge or oil to contact the skin. Severe burns may result.
NOTE: The Flushing Method using R-11 refrigerant is no longer approved by Daikin Brand Heating-Cooling.
REFRIGERANT PIPING
The piping of a refrigeration system is very important in relation to system capacity, proper oil return to compressor, pumping rate of compressor and cooling performance of the evaporator. A bi-flow filter drier must be brazed on by the installer onsite. Ensure the bi-flow filter drier pain finish is intact after brazing. If the paint of the steel filter drier has been burned or chipped, repaint or treat with a rust preventative. The recommended location of the filter drier is before the expansion device at the indoor unit. The liquid line must be insulated if more than 50 ft. of liquid line will pass through an area that may reach temperatures of 30°F of higher than ambient in cooling mode and/or if the temperature inside the conditioned space may reach a temperature lower than ambient in heating mode. FVC oils maintain a consistent viscosity over a large temperature range which aids in the oil return to the compressor; however, there will be some installations which require oil return traps. These installations should be avoided whenever possible, as adding oil traps to the refrigerant lines also increases the opportunity for debris and moisture to be introduced into the system. Avoid long running traps in horizontal suction line.

INSTALLATION OF REFRIGERATION PIPING FROM VERTICAL TO HORIZONTALGoodman
GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner - SERVICING
10FIGURE 1-2. INSTALLATION OF REFRIGERANT PIPING (VERTICAL)
NEW CONSTRUCTION SHOWN

NOTE If line set is installed on the exterior of an outside wall, similar installation practices are to be used.

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner - SERVICING
11

SECTION 3. OUTDOOR UNIT IS ABOVE THE INDOOR UNIT

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner - SERVICING
12

  1. Gas line must be sloped continuously towards the indoor unit.
  2. The maximum elevation (vertical) difference between the outdoor unit and indoor unit is 200 feet.
  3. The maximum line set equivalent length is 250 feet, which includes pressure losses of any elbow, bends, etc. The max- imum line set actual length is 200 feet.
  4. Inverted suction loop is not required at either unit.
  5. An accumulator is not required for outdoor unit (accumulators are factory installed).

SECTION 4. OUTDOOR UNIT IS BELOW THE INDOOR UNIT

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner - SERVICING
14

  1. The maximum elevation (vertical) difference between the outdoor unit and the indoor unit is 90 feet.
  2. Suction line must be installed in a manner to prevent liquid migration to the outdoor unit from the indoor unit.
    The Air Conditioner condenser unit is shipped with a predetermined factory charge level as shown in the following chart.
    For longer line sets greater than 15 feet, add 0.6 ounces of refrigerant per foot.

DUCT STATIC PRESSURES AND/OR STATIC PRESSURE DROP ACROSS COILS
This minimum and maximum allowable duct static pressure for the indoor sections are found in the specifications section.
Tables are also provided for each coil, listing quantity of air (CFM) versus static pressure drop across the coil. Too great an external static pressure will result in insufficient air that can cause icing of the coil. Too much air can cause poor humidity control and condensate to be pulled off the indoor coil causing condensate leakage. Too much air can also cause motor overloading and in many cases this constitutes a poorly designed system.
AIR HANDLER EXTERNAL STATIC
To determine proper air movement, proceed as follows:

  1. Using a draft gauge (inclined manometer), measure the static pressure of the return duct at the inlet of the unit, (Negative Pressure).

  2. Measure the static pressure of the supply duct, (Positive Pressure).

  3. Add the two (2) readings together for total absolute value of external static pressure (for example, -0.30” wc +0.20” wc = 0.50” wc total static pressure). CHECKING STATIC PRESSURE ON TWO PIECE AIR HANDLER
    ● Measure the static pressure of the supply duct at the outlet of the unit
    ● Measure the static pressure between the outlet of the evaporator coil and the inlet of the air handler
    ● Since the evaporator coil is not part of the blower unit or furnace, it must be not considered in calculating the static pressure of the blower unit or furnace
    ● NOTE: Both readings may be taken simultaneously if so desired
    NOTE: Both readings may be taken simultaneously and read directly on the manometer if so desired.

  4. Consult proper table for quantity of air.
    If external static pressure is being measured on a furnace to determine airflow, supply static must be taken between the “A” coil and the furnace.

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner - SERVICING
17

CHECKING STATIC PRESSURE SINGLE PIECE AIR HANDLER

  • Measure the static pressure of the supply duct at the outlet of the air handler
  • Measure the static pressure of the return duct at the inlet of the air handler
  • Single piece air handler evaporator coil is already con sidered in airflow calculation
  • NOTE: Both readings may be taken simultaneously and read if so desired

COIL STATIC PRESSURE DROP

  1. Using a draft gauge (inclined manometer), connect the positive probe underneath the coil and the negative probe above the coil.
  2. A direct reading can be taken of the static pressure drop across the coil.
  3. Consult proper table for quantity of air.

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner - SERVICING
18

CHECKING STATIC PRESSURE FURNACE

  • Measure static pressure of the return duct at the inlet of the furnace
  • Measure the static pressure of the supply duct at the outlet of the furnace
  • NOTE: Both readings may be taken simultaneously and read if so desired

If the total external static pressure and/or static pressure drop exceeds the maximum or minimum allowable statics, check for closed dampers, dirty filters, undersized or poorly laid out duct work.
AIRFLOW CONSIDERATION
Airflow demands are managed differently in a fully communicating system than in a non-communicating wired system.
The system operating mode (as determined by the thermostat) determines which unit calculates the system airflow demand. If the indoor unit is responsible for determining the airflow demand, it calculates the demand and sends it to the ECM motor. If the outdoor unit or thermostat is responsible for determining the demand, it calculates the demand and transmits the demand along with a fan request to the indoor unit. The indoor unit then sends the demand to the ECM motor. The table below lists the various communication systems, the operating mode, and airflow demand source.

System System Operating Mode Airflow Demand Source
Any Cooling Outdoor Unit
Heat Pump Heating Only Outdoor Unit
Continuous Fan Thermostat
Air Handler or Modular blower HP + Electric Heat Strips Either outdoor unit

or indoor unit, which has higher Airflow demand
Electric Heat Strips Only| Indoor Unit
Gas Furnace| Combustion Heat| Indoor Unit

For example, assume the system is an outdoor unit matched with an indoor unit. With a call for cooling, the outdoor unit will calculate the system’s cooling airflow demand. The outdoor unit will then send a fan request along with the cooling airflow demand to the indoor unit. Once received, the indoor unit will send the cooling airflow demand to the ECM motor. The ECM motor then delivers the cooling airflow.
In continuous fan mode, the communicating thermostat provides the airflow demand. The communicating provides 4 continuous fan speeds (25%, 50%, 75% and 100% of maximum airflow). During continuous fan operation, the thermostat sends a fan request along with the continuous fan demand to the indoor unit. The indoor unit, in turn, sends the demand to the ECM motor. The ECM motor delivers the requested continuous fan airflow.

INDOOR UNIT TROUBLESHOOTING FOR TXV APPLICABLE UNIT (MBVC**00AA-1)

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner - SERVICING
19

AUXILIARY ALARM SWITCH
The control is equipped with two Auxiliary Alarm terminals, labeled CAS, which are typically utilized in series with a condensate switch but could also be used with compatible CO2 sensors or fire alarms.

This feature can be activated or deactivated through the thermostat user menus. The auxiliary alarm switch must be normally closed and open when the alarm occurs. For example, a normally closed condensate switch will open when the base pan’s water level  reaches a particular level. The control will respond by turning off the blower motor and outdoor unit and displaying the proper fault codes. If the switch is later detected closed for 30 seconds, normal operation resumes and the error message is removed. The error will be maintained in the equipment’s fault history. See FIGURE 15 on the following page for the connection location.
CIRCULATOR BLOWER
This air handler is equipped with a variable speed circulator blower. This blower provides several automatically-adjusted blower speeds. The Specification Sheet applicable to your model provides an airflow table, showing the relationship between airflow (CFM) and external static pressure (E.S.P.). The electric heat dip switch default position is set to the OFF, OFF, OFF position and should be adjusted by the in- staller to match the installation requirements for the correct electric heating CFM.
Using the Electric Heat Airflow table below, set dip switches 9, 10, and 11 for the installed heater kit. Verify selected CFM by counting the green CFM LED blinks. The green CFM LED blinks once for each 100 CFM of airflow. If an electric heater kit has not been installed, set dip switches 9, 10, and 11 to any appropriate heater kit setting (see next page table for valid settings).
During the cooling operation, the outdoor unit will determine the indoor airflow.

INDOOR UNIT TROUBLESHOOTING FOR TXV APPLICABLE UNIT (MBVC**00AA-1)

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner - SERVICING
21

NOTE: Upon start up in communicating mode the circuit board may display an “Ec” error. This is an indication that the dip switches on the control board need to be configured in accordance with the Electric Heating Airflow Table. Configuring the dip switches and resetting power to the unit will clear the error code.
TROUBLESHOOTING
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS
NOTE: Discharge body’s static electricity before touching unit. An electrostatic can adversely affect electrical components. Use the following precautions during air handler installation and servicing to protect the integrated control module from damage. By putting the air handler, the control, and the person at the same electrostatic potential, these steps will help avoid exposing the integrated control module to electrostatic discharge. This procedure is applicable to both installed and uninstalled (ungrounded) blowers.

  1. Disconnect all power to the blower. Do not touch the integrated control module or any wire connected to the control prior to discharging your body’s electrostatic charge to ground.
  2. Firmly touch a clean, unpainted, metal surface of the air handler blower near the control. Any tools held in a person’s hand during grounding will be discharged.
  3. Service integrated control module or connecting wiring following the discharge process in step 2. Use caution not to recharge your body with static electricity; (i.e., do not move or shuffle your feet, do not touch ungrounded objects, etc.). If you come in contact with an ungrounded object, repeat step 2 before touching control or wires.
  4. Discharge your body to ground before removing a new control from its container. Follow steps 1 through 3 if installing the control on a blower. Return any old or new controls to their containers before touching any ungrounded object.

DIAGNOSTIC CHART
WARNING
HIGH VOLTAGE
Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death.
Refer to the Troubleshooting Chart at the end of this manual for assistance in determining the source of unit operational problems. The 7 segment LED display will provide any active fault codes. An arrow printed next to the display indicates proper orientation (arrow points to top of display). See following image.

FAULT RECALL
The integrated control module is equipped with a momentary push-button switch that can be used to display the last six faults on the 7 segment LED display. The control must be in Standby Mode (no thermostat inputs) to use the feature. Depress the push-button for approximately two seconds. The LED display will then display the six most recent faults beginning with the most recent fault and decrementing to the least recent fault. The faults may be cleared by depressing the button for greater than five seconds.
NOTE: Consecutively repeated faults are displayed a maximum of three times. Example: A clogged return air filter causes the air handler’s motor to repeatedly enter a limiting condition. The control will only store this fault the first three consecutive times the fault occurs.
INDOOR UNIT TROUBLESHOOTING FOR TXV APPLICABLE UNIT (MBVC**00AA-1)

7 SEGMENT LED (characters will alternate) DESCRIPTIONOFCONDITION
(nodisplay) INTERNAL CONTROL FAULT / NO POWER
On STANDBY, WAITING FOR INPUTS
Ec HEATER KIT TOO LARGE, TOO SMALL, OR NO MATCH
E5 FUSE OPEN
EF AUXILIARY SWITCH OPEN
d0 DATA NOT ON NETWORK
d1 INVALIDDATAONNETWORK
d4 INVALID Bluetooth® SHARED DATA LOADER BTSDL01  DATA
b0 BLOWER MOTOR NOT RUNNING
b1 BLOWER MOTOR COMMUNICATION ERROR
b2 BLOWER MOTOR HP MISMATCH
b3 BLOWER MOTOR OPERATING IN POWER, TEMP. ,OR SPEED LIMIT
b4 BLOWER MOTOR CURRENT TRIP OR LOST ROTOR
b5 BLOWER MOTOR ROTOR LOCKED
b6 OVER/UNDER VOLTAGE TRIP OR OVER TEMPERATURE TRIP
b7 INCOMPLETE PARAMETER SENT TO MOTOR
b9 LOW INDOOR AIRFLOW
C1 LOW STAGE COOL – LEGACY MODE ONLY
C2 HIGHSTAGECOOL-LEGACYMODEONLY
P1 LOW STAGE HEAT PUMP HEAT – LEGACY MODE ONLY
P2 HIGH STAGE HEAT PUMP HEAT – LEGACY MODE ONLY
h1 EMERGENCY HEAT LOW – COMMUNICATING MODE ONLY
h2 EMERGENCY HEAT HIGH – COMMUNICATING MODE ONLY
FC FAN COOL – COMMUNICATING MODE ONLY
FH FAN HEAT – COMMUNICATING MODEONLY
F FAN ONLY
H1 ELECTRIC HEAT LOW
H2 ELECTRIC HEAT HIGH
dF DEFROST – COMMUNICATING MODE ONLY

(Note: defrost is displayed as H1 in a legacy setup)
GREEN CFM LED-EACH FLASH REPRESENTS 10CFM
(USE FOR AIRFLOW APPROXIMATION ONLY) – EXAMPLE: 8 FLASHES = 800CFM

INDOOR UNIT TROUBLESHOOTING FOR TXV APPLICABLE UNIT (MBVC**00AA-1)

Symptoms of Abnormal Operation (Legacy & ComfortNet™Thermostat)| 7 – S egment LED Codes Characters Will Alternate| Fault Description| ComfortNet™ Thermostat Only| Possible Causes| Corrective Actions| Notes & Cautions
---|---|---|---|---|---|---
Message| Code
•  LED display is ON continuously| On| • Normal operation| None| None| • Normal operation| • None| • Normal o p eration
• Electric heaters fail to energize on a call for W1 or Auxiliary/ Emergency heat
• Integrated control module LED display provides  the indicated error code.
• ComfortNet™thermostat “Call for Service” icon illuminated
• ComfortNet™thermostat scrolls “Check Air Handler” message| EC| • Heater kit selected via
dipswitches is too large for
heater kit s specified in
shared data set| HTR TOO
LARGE| EC| • Heater kit selected via
dipswitches is too large for heater
kits in shared data set| • Verify electric heat dipswitch settings
• Verify the installed electric heater
is valid for the air handler blower.
Check nameplate or Specification
Sheet applicable to your model for
allowable heater kit(s).
• Verify shared data set is correct
for the specific model. Re-pop ulate
data using correct Bluetooth®
Shared Data Loader BTSDL01
if required.| • Turn power OFF prior to repair.
• Use Bluetooth® Shared Data Loader BTSDL01 for the specific model.
• Insert Bluetooth® Shared Data Loader BTSDL 01 BEFORE turning
power ON. Bluetooth® Shared Data Loader BTSDL01 may be removed
after data is loaded.
• Turn power off before removing Bluetooth® Shared Data Loader BTSDL01.
• Electric heat airflow is higher than
expected on a call for W1 or
Auxiliary/ Emergency heat
• Integrated control module LED display provides the indicated error code.| EC| • Heater kit selected via
dipswitches is too small for heater kits specified in
shared data set| HTR TOO
SMALL| EC| • Heater kit selected via
dipswitches is too small for heater kits in shared data set| • Verify electric heat dipswitch settings
• Verify the installed electric heater
is valid for the air handler blower.
Check nameplate or Specification
Sheet applicable to your model
for
allowable heater kit(s).
• Verify shared data set is correct
for the specific model. Re-pop ulate
data using correct Bluetooth®
Shared Data Loader BTSDL01
if required.| • Turn power OFF prior to repair.
• Use Bluetooth® Shared Data Loader BTSDL01 for the specific model.
• Insert Bluetooth® Shared Data Loader BTSDL 01 BEFORE turning
power ON. Bluetooth® Shared Data Loader BTSDL01 may be removed
after data is loaded.
• Turn power off before removing Bluetooth® Shared Data Loader BTSDL01.
•  Electric heat airflow is higher than
expected on a call for W1 or Auxiliary/
Emergency heat
• Integrated control module LED display provides the indicated error code.| EC| • Heater kit selected via
dipswitches does not
heater kits specified in
shared data set| NO HTR
MATCH| EC| • Heater kit selected via
dipswitches is doesn’t match
heater kits in shared data
set| • Verify electric heat dipswitch settings
• Verify the installed electric heater
is valid for the air handler blower.
Check nameplate or Specification
Sheet applicable to your model* for
allowable heater kit(s).
• Verify shared data set is correct
for the specific model. Re-pop ulate
data using correct Bluetooth®
Shared Data Loader BTSDL01 if required.| • Turn power OFF prior to repair.
• Use Bluetooth® Shared Data Loader BTSDL01 for the specific model.
• Insert Bluetooth® Shared Data Loader BTSDL01 BEFORE turning
power ON. Bluetooth® Shared Data Loader BTSDL01 may be removed
after data is loaded.
• Turn power off before removing Bluetooth® Shared Data Loader BTSDL01.
• Integrated control module LED display EF error code.
• ComfortNet™thermostat “Call for Service”.| EF| • Aux switch open| Aux Alarm
Fault| EF| • High water level in the
evaporation coil.| • Check overflow pan and service| • Turn power OFF prior to
service.
•  Air handler blower fails to operate
• Integrated control module LED display provides no signal.
• ComfortNet™ thermostat “Call for Service” icon illuminated
• ComfortNet™ thermostat scrolls “Check Air Handler” message| No Display| • No 208/230 volt power to air handler blower or no 24 volt power to integrated control module
• Blown fuse or circuit
breaker
• Integrated control module has an internal fault.| INTERNAL
FAULT| EE| • Manual disconnect switch OFF or 24 volt wire improperly connected or loose
• Blown fuse or circuit breaker
• Integrated control module has an internal fault| • Assure 208/230 volt and 24 volt
power to air handler blower and
integrated control module.
• Check integrated control module
fuse (3A).  Replace if necessary.
• Check for possible shorts in
208/230 volt and 24 volt circuits.
Repair as necessary.
• Replace bad integrated control
module.| • Turn power OFF prior to repair.
• Replace integrated control module fuse with 3A automotive fuse.
• Replace integrated control module with correct replacement part
• Read precautions in “Electrostatic Discharge” section of manual.
•  Air handler blower fails to operate.
• Integrated control module LED display provides indicated error code.
• ComfortNet™ thermostat “Call for Service” icon illuminated.
• ComfortNet™ thermostat scrolls “Check Air Handler” message.| d0| • Data not yet on network.| NO NET
DATA| d0| • Air handler blower does not
contain any shared data.| • Populate shared data set using
Bluetooth® Shared Data Loader
BTSDL01.| • Turn power OFF prior to repair
• Use Bluetooth® Shared Data Loader BTSDL01 for the specific model.
• Insert Bluetooth® Shared Data Loader BTSDL01 BEFORE turning power ON. Bluetooth® Shared Data
Loader BTSDL01 may be removed after data is loaded.
• Error code will be cleared once data is loaded.
• Turn power off before removing Bluetooth® Shared Data Loader BTSDL01
• Air handler blower fails to operate.
• Integrated control module LED display provides indicated error code.
• ComfortNet™ thermostat “Call for Service” icon illuminated.
• ComfortNet™ thermostat scrolls “Check Air Handler” message.| d1| • Invalid data on network.| INVALID
DATA| d1| • Air handler blower does not
contain an appropriate shared data set.| • Populate correct shared data set
using Bluetooth® Shared Data
Loader BTSDL01.| • Turn power OFF prior to repair
• Use Bluetooth® Shared Data Loader BTSDL01 for the specific model.
• Insert Bluetooth® Shared Data Loader BTSDL01 BEFORE turning power ON. Bluetooth® Shared Data
Loader BTSDL01 may be removed after data is loaded.
• Error code will be cleared once data is loaded.
• Operation different than expected or no operation.
• Integrated control module LED display provides indicated error code.
• ComfortNet™ thermostat “Call for Service” icon illuminated.
• ComfortNet™ thermostat scrolls “Check Air Handler” message.| d4| • Invalid Bluetooth® Shared Data Loader BTSDL01 data.| INVALID
MC DATA| d4| • Shared data set on Bluetooth®
Shared Data Loader BTSDL01 has been rejected by integrated control module| • Verify shared data set is correct
for the specific model. Re-populate
data using correct Bluetooth®
Shared Data Loader BTSDL01 if
required.| • Turn power OFF prior to repair
• Use Bluetooth® Shared Data Loader BTSDL01 for the specific model.
• Insert Bluetooth® Shared Data Loader BTSDL01 BEFORE turning power ON. Bluetooth® Shared Data
Loader BTSDL01 may be removed after data is loaded.
• Error code will be cleared once data is loaded.
• Turn power off before removing Bluetooth® Shared Data Loader BTSDL01
• Air handler blower fails to operate.
• Integrated control module LED display provides indicated error code.
• ComfortNet™ thermostat “Call for Service” icon illuminated.
• ComfortNet™ thermostat scrolls “Check Air Handler” message.| b0| • Circulator blower motor is not running when it should be running.| MOTOR NOT
RUN| b0| •  Loose wiring connection at circulator motor power leads or circulator motor power leads disconnected.
• Failed circulator blower motor.| • Tighten or correct wiring connection.
• Check circulator blower motor.
Replace if necessary.| • Turn power OFF prior to repair
• Replace circulator motor with correct  replacement part.
• Air handler blower fails to operate.
• Integrated control module LED display provides indicated error code.
• ComfortNet™ thermostat “Call for Service” icon illuminated.
• ComfortNet™ thermostat scrolls “Check Air Handler” message.| b1| • Integrated control module has lost communications with
circulator blower motor.| MOTOR
COMM| b1| • Loose wiring connection at circulator motor control leads.
• Failed circulator blower motor.
• Failed integrated control module.| • Tighten or correct wiring connection.
• Check circulator blower motor.
Replace if necessary.
• Check integrated control module.
Replace if necessary.| • Turn power OFF prior to repair
• Replace circulator motor with
correct  replacement part.
• Replace integrated control module with correct replacement part.
• Air handler blower fails to operate.
• Integrated control module LED display provides indicated error code.
• ComfortNet™ thermostat “Call for Service” icon illuminated.
• ComfortNet™ thermostat scrolls “Check Air Handler” message.| b2| • Circulator blower motor
horse power in shared data set does not match circulator blower motor horse power.| MOTOR
MISMATCH| b2| • Incorrect circulator blower motor in air handler blower.
• Incorrect shared data set in integrated control module.| • Verify circulator blower motor horse
power is the same specified for the
specific air handler blower model.
Replace is necessary.
• Verify shared data set is correct for
the specific model. Re-populate data
using correct Bluetooth® Shared Data
Loader BTSDL01 if required.| • Turn power OFF prior to repair
• Replace motor with correct
replacement part.
• Use Bluetooth® Shared Data
Loader BTSDL01 for the specific
model
• Insert Bluetooth® Shared Data
Loader BTSDL01 BEFORE turning power ON.  Bluetooth® Shared Data Loader BTSDL01 may be removed after data is loaded.
• Error code will be cleared once
shared data and motor horse
power match.
• Turn power off before removing
Bluetooth® Shared Data Loader
BTSDL01
• Air handler blower operates at reduced performance.
• Airflow delivered is less than expected.
• Integrated control module LED display provides b3 error code.| b3| • Circulator blower motor is operating in a power,
temperature, or speed limiting condition.| MOTOR
LIMITS| b3| • Blocked filters.
• Restrictive ductwork.
• Undersized ductwork.
• High ambient temperatures.| • Check filters for blockage. Clean
filters or remove obstruction.
• Check ductwork for blockage.
Remove obstruction.  Verify all registers are fully open.
• Verify ductwork is appropriately sized
for system.  Resize/replace ductwork if
necessary.
• See “Installation Instructions” for
installation requirements.| • Turn power OFF prior to repair.
• Air handler blower fails to operate.
• Integrated control module LED display provides indicated error code.
• ComfortNet™ thermostat “Call for Service” icon illuminated.
• ComfortNet™ thermostat scrolls “Check Air Handler” message.| b4| • Circulator blower motor
senses a loss rotor control.
• Circulator blower motor
senses high current.| MOTOR
TRIPS| b4| • Abnormal motor loading, sudden change in speed or torque, sudden blockage of air handler blower/coil air inlet or outlet.
• High loading conditions, blocked filters, very restrictive ductwork, blockage of air| • Check filters, filter grills/registers,
duct system, and air handler blower/coil air inlet/outlet for blockages.| • Turn power OFF prior to repair.
• Air handler blower fails to operate.
• Integrated control module LED display provides indicated error code.
• ComfortNet™ thermostat “Call for Service” icon illuminated.
• ComfortNet™ thermostat scrolls “Check Air Handler” message.| b5| • Circulator blower motor fails to start 10 consecutive times.| MTR LCKD
ROTOR| b5| • Obstruction in circulator blower
housing.
• Seized circulator blower motor
bearings.
• Failed circulator blower motor.| • Check circulator blower for obstructions. Remove and repair/ replace wheel/motor if necessary.
• Check circulator blower motor shaft
rotation and motor. Replace motor if
necessary.| • Turn power OFF prior to repair
• Replace motor with correct
replacement part.
• Replace wheel with correct
replacement part.
• Air handler blower fails to operate.
• Integrated control module LED display provides indicated error code.
• ComfortNet™ thermostat “Call for Service” icon illuminated.
• ComfortNet™ thermostat scrolls “Check Air| b6| • Circulator blower motor shuts down for over or under voltage condition.
• Circulator blower motor shuts down due to over temperature condition on power module.| MOTOR
VOLTS| b6| • High AC line voltage to air handler blower.
• Low AC line voltage to air hander blower.
• High ambient temperatures.| • Check power to air handler blower.
Verify line voltage to blower is within the range specified on the air handler
blower rating plate.
• See “Installation Instructions” for
installation requirements.| • Turn power OFF prior to repair.
• Air handler blower fails to operate.
• Integrated control module LED display provides indicated error code.
• ComfortNet™ thermostat “Call for Service” icon illuminated.
• ComfortNet™ thermostat scrolls “Check Air Handler” message.| b7| • Circulator blower motor does not have enough information to operate properly. Motor fails to
start 40 consecutive times.| MOTOR
PARAMS| b7| • Error with integrated control module.
• Motor has a locked rotor condition.| • Check integrated control module.
Verify control is populated with correct
shared data set.  See data errors above
for details.
• Check for locked rotor condition (see
error code above for details).| • Turn power OFF prior to repair.
• Replace with correct replacement part(s).
• Use Bluetooth® Shared Data Loader BTSDL01 for the specific
model.
• Insert Bluetooth® Shared Data
Loader BTSDL01 BEFORE
turning power ON.
• Bluetooth® Shared Data Loader
BTSDL01 may be removed after
data is loaded
• Turn power off before removing
Bluetooth® Shared Data Loader
BTSDL01.
• Air handler blower operates at reduced performance or operates on low stage when high stage is expected.
• Integrated control module LED display provides indicated error code.| b9| • Airflow is lower than
demanded.| LOW ID
AIRFLOW| b9| • Blocked filters.
• Restrictive ductwork.
• Undersized ductwork.| • Check filters for blockage. Clean
filters or remove obstruction.
• Check ductwork for blockage.
Remove obstruction.  Verify all registers are fully open.
• Verify ductwork is appropriately sized
for system.  Resize/replace ductwork if
necessary.| • Turn power OFF prior to repair.

TROUBLESHOOTING-INDOOR UNIT FOR EEV APPLICABLE UNIT
WARNING
HIGH VOLTAGE
Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death.

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner - SERVICING
23

INDOOR UNIT CONTROL BOARD

AUXILIARY ALARM SWITCH
The control is equipped with two Auxiliary Alarm terminals, labeled TB4 and TB5, which are typically utilized in series with a condensate switch but could also be used with compatible CO2 sensors or fire alarms.

The auxiliary alarm switch must be normally closed and open when the alarm occurs. For example, a normally closed condensate switch will open when the base pan’s water level reaches a particular level. The control will respond by turning off the blower motor and displaying the proper fault codes. If the switch is later detected closed for 30 seconds, normal operation resumes and the error message is removed. The switch is closed as part of the default factory setting. The error will be maintained in the equipment’s fault history.

CIRCULATOR BLOWER
This air handler is equipped with a variable speed circulator blower. This blower provides several automatically-adjusted blower speeds. The Specification Sheet applicable to your model provides an airflow table, showing the relationship between airflow (CFM) and external static pressure (E.S.P.).

TROUBLESHOOTING-INDOOR UNIT FOR EEV APPLICABLE UNIT
NOTE: Upon start up in communicating mode the circuit board may display an “Ed” error. This is an indication that the dip switches on the control board need to be configured in accordance with the Electric Heating Airflow Table. Configuring the dip switches and resetting power to the unit will clear the error code.

TROUBLESHOOTING
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS
NOTE: Discharge body’s static electricity before touching unit. Electrostatics can adversely affect electrical components.
Use the following precautions during air handler installation and servicing to protect the integrated control module from damage. By putting the air handler, the control, and the person at the same electrostatic potential, these steps will help avoid exposing the integrated control module to electrostatic discharge. This procedure is applicable to both installed and uninstalled (ungrounded) blowers.

  1. Disconnect all power to the blower. Do not touch the integrated control module or any wire connected to the control prior to discharging your body’s electrostatic charge to ground.
  2. Firmly touch a clean, unpainted, metal surface of the air handler blower near the control. Any tools held in a person’s hand during grounding will be discharged.
  3. Service integrated control module or connecting wiring following the discharge process in step 2. Use caution not to recharge your body with static electricity; (i.e., do not move or shuffle your feet, do not touch ungrounded objects, etc.). If you come in contact with an ungrounded object, repeat step 2 before touching control or wires.
  4. Discharge your body to ground before removing a new control from its container. Follow steps 1 through 3 if installing the control on a blower. Return any old or new controls to their containers before touching any ungrounded object.

DIAGNOSTIC CHART
WARNING

HIGH VOLTAGE
To avoid personal injury or death due to electrical shock, disconnect electrical power before performing any service or maintenance.
Refer to the Troubleshooting Chart at the end of this manual for assistance in determining the source of unit operational problems. The 7 segment LED display will provide any active fault codes. An arrow printed next to the display indicates proper orientation (arrow points to top of display).
See following image.

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner - SERVICING
25

FAULT RECALL
The integrated control module is equipped with a momentary push-button switch that can be used to display the last six faults on the 7 segment LED display.
To display the faults, follow the steps below.
NOTE: The integrated control module must be in Standby Mode (no thermostat inputs).

  1. Press FAULT RECALL button (for 2 to 5 seconds). The 7 segment LED display will blink “–”.
    NOTE: If FAULT RECALL button is not pressed long enough (for 2 to 5 seconds, the control goes back to Standby Mode. If the button is pressed for 5 to 10 seconds, control goes back to Standby Mode.

  2. Release the FAULT RECALL button. The 7 segment LED display will show the most recent fault.

  3. Subsequent pressing of the FAULT RECALL button will recall a previous fault. At the end of the faults, the 7 segment LED display will show “–” and go back to Standby Mode.
    NOTE: Consecutively repeated faults are displayed a maximum of three times. If the FAULT RECALL button is left untouched longer than 3 minutes, the control goes back to
    Standby Mode.

To clear the error code history:

  1. Press FAULT RECALL button until the 7 segment LED display blinks “–”.
  2. Release the FAULT RECALL button. The 7 segment LED display will show “88” and clear the faults.

NOTE: If FAULT RECALL button is help pressed for longer than 15 seconds, control goes back to Standby Mode.

DIAGNOSTIC CODES
TROUBLESHOOTING-INDOOR UNIT FOR EEV APPLICABLE UNIT

DIAGNOSTIC CODES

7 SEGMENT LED
DISPLAY| DESCRIPTION OF CONDITION
---|---
On| Normal Operation
Eb| NO HTR KIT INSTALLED – SYSTEM CALLING FOR AUXILIARY HEAT (Minor Error Code)
Ed| HEATER KIT DIP SWITCHES NOT SET PROPERLY
E5| FUSE OPEN
EF| AUXILIARY SWITCH OPEN
d0| DATA NOT ON NETWORK
d1| INVALID DATA ON NETWORK
d4| INVALID Bluetooth™ SHARED DATA LOADER DATA
b0| BLOWER MOTOR NOT RUNNING
b1| BLOWER MOTOR COMMUNICATION ERROR
b2| BLOWER MOTOR HP (Horse power) MISMATCH
b3| BLOWER MOTOR OPERATING IN POWER, TEMP., OR SPEED LIMIT
b4| BLOWER MOTOR CURRENT TRIP OR LOST ROTOR
b6| OVER/UNDER VOLTAGE TRIP OR OVER TEMPERATURE TRIP
b7| INCOMPLETE PARAMETER SENT TO MOTOR
b9| LOW INDOOR AIRFLOW (Minor Error Code) (without EH mode)
9b| LOW INDOOR AIRFLOW (Major Error Code) (EH mode only)
70| EEV DISCONNECTION DETECTED
73| LIQUID SIDE THERMISTOR ABNORMALITY
74| GAS SIDE THERMISTOR ABNORMALITY
75| PRESSURE SENSOR ABNORMALITY
77| INDOOR UNIT – THERMOSTAT COMMUNICATION ERROR
(STARTUP OPERATION & DURING OPERATION)
Hu| HUMIDIFICATION DEMAND (Running without heating)
FC| FAN COOL – COMMUNICATING MODE ONLY (Fan Demand-Cool)
FH| FAN HEAT – COMMUNICATING MODE ONLY (Fan Demand-Heat)
F| FAN ONLY (Fan Demand-Manual)
H1| ELECTRIC HEAT LOW (Heat Demand, Back-up Heat Demand)
H2| ELECTRIC HEAT HIGH (Heat Demand, Back-up Heat Demand)
dF| DEFROST – COMMUNICATING MODE ONLY (note: defrost is displayed as H1 in a legacy setup)

TROUBLESHOOTING-INDOOR UNIT FOR EEV APPLICABLE UNIT

7 Segment LED Display (State) Description of Condition
(No Display) INTERNAL CONTROL FAULT/NO POWER
On STANDBY, WAI TING FOR I NPUTS
FC FAN COOL-COMMUNI CATI NG MODE ONLY (Aux Heat Demand)
FH FAN HEAT-COMMUNI CATI NG MODE ONLY  (Aux Heat Demand)
_F FAN ONLY (Fan Demand-Manual)
H1 ELECTRI C HEAT LOW (Hea t Demand, Ba ck-up  Heat Demand)
H2 ELECTRIC HEAT HIGH (Heat Demand, Back-up Heat Demand)
dF DEFROST COMMUNI CATI NG MODE ONLY
Hu HUMI DI TY RUNNI NG WI THOUT HEATING (Humidificat on Demand)

2-digit 7 segment displays
WARNING
HIGH VOLTAGE!
TO AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRICAL SHOCK, DISCONNECT ELECTRICAL POWER BEFORE PERFORMING ANY SERVICE OR MAINTENANCE.
When the indoor unitis energized power supply, 2- digit 7 segment displays on indoor control board show current status of state, error code and airflow.

  1. State shows current operation status ofindoor unit described in righttable.
  2. Error code shows current error indoor units have. To see the previous error code, please follow the instruction of fault recall. For more information of error code, please see the table of indoor unit error code. Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner - SERVICING 27
  3. Airflowshows estimated CFM of indoorunit. For example, if the CFM is 1240CFM, 7 segmentdisplay shows “A…12…40…”. Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner - SERVICING 28

The contents indicated at 7 segment display vary from operation mode and status of indoor unit. In the event of showing some error code, please follow the instruction in the table of indoor unit error code to solve the error.

  1. Whentheunit is runningin normal mode, 2-digit 7 segmentdisplays show state and airflowstatus.
  2. Whentheunit is havingsome major error code in normalmode, 2-digit 7 segment displays keep showing error code.
  3. When the unit is having some minor error code in normal mode,2-digit 7 segmentdisplaysshow error code and airflow status.
  4. When the unit is having some minor error code during defrost operationin normal mode,2-digit 7 segmentdisplaysshow state “dF”, error code and airflow status.Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner - SERVICING 32
  5. When the unit is having some minor error code in emergencymode,2-digit 7 segmentdisplaysshow state (EE) and error code.

TROUBLESHOOTING-INDOOR UNIT FOR EEV APPLICABLE UNIT

MODE DISPLAY INTRODUCTION
A 2-digit display is provided on the Control Board as a backup tool to the thermostat for accessing error codes and erasing error code history of the indoor unit. Follow the information provided in this section to learn how to use the mode display.
DISPLAY
The display consists of 2 digits.

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner - SERVICING
34

DISPLAY BUTTON LAYOUT
The display buttons shown can be used to navigate and select items:

FAULT CODE HISTORY NAVIGATION
This mode will allow the user to see the six most recent system faults. Please follow the flow chart to navigate to error codes from screen zero.
For a list of the fault codes, please see the TROUBLESHOOTING tables in this document.
It is also possible to erase all the diagnostics codes from this menu.

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner - SERVICING
36

INDOOR UNIT (AMVE) ERROR CODES**

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner - Table
1Goodman
GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner - Table
2

AIR CONDITIONER ADVANCED FEATURE MENU

HEAT PUMP / FAULT CODE HISTORY

SUBMENU ITEM| INDICATION/USER MODIFIABLE OPTIONS| COMMENTS
ALL| (The Active and History Fault codes are displayed.)| Active fault code and up to 6 fault code histories.
ACTIVE| (The Active Fault codes are displayed.)| Active fault code only.
HISTORY| (The History Fault codes are displayed .)| Up to 6 fault code histories.
REFRESH| N/A| Selecting this menu will refresh the display.
HEAT PUMP / CONFIGRATION INFO

SUBMENU ITEM| INDICATION/USER MODIFIABLE OPTIONS| COMMENTS
HVAC DEVICE| HEAT PUMP| The type of HVAC Device.
FIRMWARE VERSION| | Specific number associated with the control software.
MODEL NUMBER| VZC20001*| This number match the model name found on the serial plate.
SERIAL NUMBER| ***
| This number match the serial number found on the serial plate.
HEAT PUMP / DEVICE STATUS

SUBMENU ITEM| INDICATION(Units)| COMMENTS
HEAT CAPACITY REQUEST| %| The request for heating.
0% means the system is off.
All other values mean the system is running.
COOL CAPACITY REQUEST| %| The request for cooling.
0% means the system is off.
All other values mean the system is running.
HEAT CAPACITY REQUEST DURING DEFROST| %| Indoor heat request during defrost operation.
It states that additional capacity is being requested or if it is not being requested.
The outdoor unit will request supplemental heating while a defrost cycle is running.
0% means defrost is not being requested and additional heating is not requested and additional heating is not required.
All other values mean defrost is being requested and additional heat is being requested.
DEHUMIDIFICATION REQUEST| %| Request for dehumidification.
0% means dehumidification is not being requested. All other values mean dehumidification is being requested.
OUTDOOR FAN SPEED| RPM| Current speed of the outdoor fan in rotations per minute.
REQUESTED AIRFLOW| CFM| This is the airflow the indoor unit will try to deliver while the unit is active.
REPORTED AIRFLOW| CFM| Indoor airflow (in cubic feet per minute) as reported by the indoor unit.
BOOST MODE| OFF or ON| If this feature is available and enabled, an inverter can ramp the compressor above default speeds to increase capacity.
This shows if the feature is active or inactive.
To check if this function is enabled, find the Boost _Mode Enable item in the setting for this unit.
HEAT PUMP / SENSOR DATA

SUBMENU ITEM| INDICATION(Units)| COMMENTS
OUTDOOR TEMP| F| Displays the outdoor air temperature.
COIL TEMP| F| Displays the outdoor coil temperature.
LIQUID LINE TEMP| F| Displays the outdoor liquid temperature.
DISCHARGE TEMP| F| Displays the outdoor discharge temperature.
DEFROST SENSOR| F| Displays the defrost temperature.
SUCTION PRESSURE| PSI| Displays the pressure of taken slightly upstream of the suction accumulator.

A representative menu is posted. Item ames and setting value are subject to change.

SERVICING
AIR CONDITIONER ADVANCED FEATURE MENU

HEAT PUMP / DEVICE SETTING (1)

SUBMENU ITEM| INDICATION(Units)| COMMENTS
BOOST MODE ENABLE| OFF or ON| BOOST MODE is ON by default. See BOOST MODE section of this manual for more details.
BOOST TEMP| Always Active or 70F to 105F in icrements| If enabled, when the ambient outdoor temperature is greater than this selected value, boost mode will be operational.
Below this tenperature the mode will not function. There is also an option to keep boost mode countinuously enabled.
INDOOR/OUTDOOR HEIGHT DIFFERENCE| Both Units at Same Level, Outdoor Unit is Lower, or Indoor Unit is Lower| If the outdoor & indoor units are within +/- 15 ft. vertical distance, select SAME LEVEL. If the outdoor unit is more than 15 ft. below the indoor unit, select OUTDOOR LOWER. If the outdoor unit is more than 15 ft. above the indoor unit, select INDOOR LOWER.
RESET FOR SYSTEM SET UP| NO or YES| Selecting yes will reset any system setting to their factory defaults.
SYSTEM VERIFICATION TEST| OFF or ON| System Verification Test must be run after installation. This is approximately a 5-15 minute test. If operation mode is set to COOL mode, the system will enter CHARGE mode upon completion, otherwise it will stop.
PUMP DOWN| OFF or ON| Enter PUMP DOWN Mode.
This procedure runs the equipment for approximately 15 minutes and allows accumulation of refrigerant at the outdoor unit for purposes of removing & replacing the indoor unit or outdoor unit.
ACTIVATE CHARGE MODE| OFF or ON| Enter Charging Mode. This allows for a steady system operation for a duration of approximately 1 hour to allow for refrigerant charging of the system

via the charge port.

COOLING TRIM FACTOR(HIGH) 1, 2| -15% to +15% in 5% increments| Select this airflow trim when inverter system is running high compressor speeds during a cooling cycle.
COOLING TRIM FACTOR(MID)| -15% to +15% in 5% increments,20 30, Full(Max)
3| Select this airflow trim when inverter system is running mid-range (intermediate) compressor speeds during a cooling cycle.
COOLING TRIM FACTOR(LOW)| -15% to +15% in 5% increments,20 30, Full(Max) *3| Select this airflow trim when inverter system is running low compressor speeds during a cooling cycle.
COOLING AIRFLOW PROFILE| A, B, C, or D| If it is desirable to quickly ramp up the indoor airflow select profile A.
If it is desirable to reach nominal airflow quickly, but a slower ramp up time is required, select profile B.
If dehumidification is required immediately when cooling mode begins select profile C.
If a slower airflow ramp up / ramp down time is required in addition to dehumidification select profile D.
BLOWER ON DELAY-COOLING| 5, 10, 20 or 30 Seconds| Delay between compressor turning on and indoor blower turning on during a cooling cycle.
BLOWER OFF DELAY-COOLING| 30, 60, 90 or 120 Seconds| Delay between compressor shutting off and the indoor blower shutting off after a cooling cycle.

A representative menu is posted. Item names and setting value are subject to change.
1 At Cool and Heat Hi speed trim, SXV906010 with VC960804C,
*VM970804C and MVC800804C combination trim more than 5% settings are invalid. Trimmed up CFM makes miss matching error.
2 Other than the above, depending on the connected indoor unit, there are restrictions on the positive side Trim setting.
If you want to change the Cool Airflow Trim to positive side, be sure to confirm the Airflow Trim restrictions in the latest indoor unit installation manual.
The latest manual can be obtained from the website “PartnerLink(InfoFinderPlus/Literature)”.
[PartnerLink URL] https://partnerlinkmarketing.goodmanmfg.com/goodman/info- finder-plus
3 The Inverter system uses lower compressor speed and lower indoor unit CFM to optimize system performance.
To obtain 100% CFM for home circulation, use full Trim setting instead of Int/Low speed.
This is recommended for applications with unusually cold return temperatures such as basements.
*4 Please refer to the page of “DEHUMIDIFICATION SELECT” for details of this function.

SERVICING
AIR CONDITIONER ADVANCED FEATURE MENU

AIR CONDITIONER / DEVICE SETTING (2)

SUBMENU ITEM| INDICATION(Units)| COMMENTS
DEHUMIDIFICATION ENABLE*4| Standard, OFF, A, B or C| Selecting “OFF” disables dehumidification selecting.
“Standard”, “A”, “B” or “C” enables dehumidification.
RESET COOLING SETTINGS| NO or YES| Selecting yes will reset any cooling setting to their factory defaults.
RPS RANGE FOR COOLING| .* to *. RPS,…(Total 5 Ranges)| When determining the appropriate compressor speed for cooling, select the range that contains the desired value.
The Selected RPS for Cooling menu is where you will select your desired value within this selected range.
SELECTED RPS FOR COOLING|
.* RPS| This value will be a number inside the RPS Range for Cooling.
If you’d like to select a RPS from a different range, you must change the RPS Range for Cooling setting first, then restart the device setting page.

A representative menu is posted. Item names and setting value are subject to change.
1 At Cool and Heat Hi speed trim, SXV906010 with VC960804C,
VM970804C and MVC800804C combination trim more than 5% settings are invalid. Trimmed up CFM makes miss matching error.
2 Other than the above, depending on the connected indoor unit, there are restrictions on the positive side Trim setting.
If you want to change the Cool Airflow Trim to positive side, be sure to confirm the Airflow Trim restrictions in the latest indoor unit installation manual.
The latest manual can be obtained from the website “PartnerLink(InfoFinderPlus/Literature)”.
[PartnerLink URL]
https://partnerlinkmarketing.goodmanmfg.com/goodman/info- finder-plus*
3 The Inverter system uses lower compressor speed and lower indoor unit CFM to optimize system performance.
To obtain 100% CFM for home circulation, use full Trim setting instead of Int/Low speed.
This is recommended for applications with unusually cold return temperatures such as basements.
*4 Please refer to the page of “DEHUMIDIFICATION SELECT” for details of this function.

SERVICING
EMERGENCY MODE FOR EEV APPLICABLE INDOOR UNIT
WARNING
HIGH VOLTAGE
Disconnect ALL power before servicing.
Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death.
Emergency mode is to only be used in a situation where communication between equipment (broken wires) or a failed thermostat cannot be immediately corrected or replaced. This mode will allow for cooling or heating to be activated without the need of  communication wires or a thermostat. Once corrections have been made to wiring or the thermostat, emergency mode must be turned off and the system returned to normal operation (this applies to both the indoor and outdoor units).
NOTE: Emergency mode  does not control to a specific room temperature set point. Exact room temperature achieved is related to the building load at the time emergency mode is activated. This is only a temporary solution.
At first inspection, if the outdoor unit is displaying one of the following error codes: E51 (outdoor communication error), Eb0 (no indoor airflow), Eb9 (low indoor airflow), Ed2 (Indoor unit is too small and cannot provide airflow of outdoor unit) or the indoor unit is displaying error code E77 (no thermostat communications) it is acceptable to use emergency mode if the equipment cannot be immediately fixed. Cycling power to the equipment may temporarily clear error codes, but doing so may not fix the underlying problem.
NOTE: If after initial power up communication issues occur due to faulty wires or a thermostat these error codes may not be displayed.
In emergency mode, the unit will function according to the mode selected on the appropriate dip switches. Operation in emergency mode must be limited to a minimum and should be viewed as a temporary solution before the issue with the unit is resolved and system operates in normal mode.
NOTE: In the emergency operation, the operating status will not be shown in the thermostat status menu or on the outdoor 7-segment displays. The 7-segment displays on indoor control board will display “EE”.

HEATING EMERGENCY MODE

Emergency Heating mode is to be used when communication between the indoor unit and thermostat is not functioning properly.
This mode will run the electric heat strips independently of any thermostat in one of two modes: High Heat Level or Low Heat Level. Dip Switch Bank DS-6 (specifically dip switches S-21 and S-22) on the indoor control is used to engage emergency heating mode. Default setting for these two dip switches are in the OFF position (S21 set to ON and S22 set to ON will enable Low Heat Level Emergency Mode. S21 set to OFF and S22 set to ON will enable High Heat Level Emergency Mode).
NOTE: once equipment has been fixed, these dip switches must be placed back in the OFF position. During operation, the indoor fan and electric heater kit will be turned on and off at following intervals based on the Heat Level selected. 2 stage electric  heater kits will be energized in stage 2.

| Heating On| Heating Off
---|---|---
High Heat Level| 8 minutes| 8 minutes
Low Heat Level| 7 minutes| 15 minutes

Emergency Heat Mode Airflow: DIP switches S-9, S-10, S-11 and S-12 must be set to the correct size electric heat kit that has been installed. These are located on dip switch bank DS-3 of the indoor control. See the Switch Bank DS-3 Indoor Control Board Settings table to properly select heater kit size.
To activate heating emergency mode, appropriately select switches S-21 and S-22 from dip switch bank DS-6 on the indoor control board depending on the heat level required in accordance with the Switch Bank DS-6 Indoor Control Board Settings table.
NOTE: During the heating emergency mode, outdoor unit must stop operation. Once the communication is established, heating emergency mode must be terminated so that the system resumes operation in normal mode. To eliminate the heating emergency mode, dip switches S-21 and S-22 from dip switch bank DS-6 on the indoor control board must be set back to default factory settings (normal operating mode).
SERVICING
Upon start up in emergency mode the circuit board may display an “Ed” error. This is an indication that the DIP switches on the control board need to be configured in accordance with the Electric Heating Airflow Table. Configuring the DIP switches to the unit will clear the error code.

Switch Bank DS-3
Indoor Control Board Settings

Heater Kit Selection| Heater kW| Dip Switch Setting
AMVE24BP14| AMVE36CP14| AMVE48DP14| AMVE60DP14| S-9| S-10| S-11| S-12
No Heater| –| –| –| –| OFF| OFF| OFF| OFF
First| 3| 5| 5| 5| ON| ON| ON| ON
Second| 5| 6| 6| 6| ON| ON| ON| OFF
Third| 6| 8| 8| 8| ON| ON| OFF| ON
Fourth| 8| 10| 10| 10| ON| ON| OFF| OFF
Fifth| 10| 15| 15| 15| ON| OFF| ON| ON
Sixth| X| 19| 20| 20| ON| OFF| ON| OFF
Seventh| X| X| X| 25| ON| OFF| OFF| ON
Switch Bank DS-6
Indoor Control Board Settings

Function| S-21| S-22
Normal operation| OFF| OFF
Emergency Mode| Cooling Emergency mode/Fan only Emergency mode| ON| OFF
Heating Emergency mode (High heat level)| OFF| ON
Heating Emergency mode (Low heat level)| ON| ON
Switch Bank DS-2
Outdoor Control Board Settings

Function| S-1| S-2
Normal operation| ON| ON
Emergency Mode| Cooling Emergency mode (Low cool Level)| ON| OFF
Cooling Emergency mode (Medium cool Level)| OFF| ON
Cooling Emergency mode (High cool level)| OFF| OFF

NOTE: Default factory settings are marked with *.

COOLING EMERGENCY MODE

Cooling emergency mode is to be used when communication between the indoor and outdoor units is not functioning properly and temporary cooling operation is required.
This mode enables the outdoor unit and indoor unit to run independently of each other.
There are two key steps to setup Cooling Emergency Mode.
a) Select the appropriate airflow on the indoor unit and enable emergency indoor airflow operation (using Dip switches S-13 and S-14 of Switch Bank DS-4 on the indoor unit to select desired 25%, 50%, 75% or 100% airflow. In addition, set switch bank DS-6 dip switches S-21 to ON and S-22 to OFF enabling emergency indoor fan).
b) Select the desired cooling level at the outdoor unit (there are 3 levels available: Low Cool Level, Medium Cool Level, High Cool Level selectable by dip switch bank DS-2 on the outdoor unit). See Dip Switch Position DS2-1 and DS2-2 Table for cooling level selection.

Switch Bank DS-4 Indoor Fan Settings

Function| Value| SW13| SW14| SW15| SW16
Fan Only Speed %| 25| OFF| OFF| –| –
50| ON| OFF| –| –
75| OFF| ON| ON*| –
100| ON| ON| OFF| –

During operation the indoor unit will provide constant airflow as selected (even if the compressor has stopped). The indoor unit will continue to operate the electronic expansion valve for refrigerant super heat control and the compressor will cycle at the interval selected by dip switch bank DS-2.

Dip Switch Position Function
DS2-1 DS2-2
ON ON
ON OFF

(Low Cool Level)
OFF| ON| Emergency Mode
(Medium Cool Level)
OFF| OFF| Emergency Mode
(High Cool Level)
| ON time| OFF time| Avg. Run Time
---|---|---|---
Low Cool Level| 7 minutes| 15 minutes| 30%
Medium Cool Level| 8 minutes| 10 minutes| 50%
High Cool Level| 15 minutes| 6 minutes| 70%

NOTE: This mode does not require a thermostat. Any thermostat requests will be ignored while in emergency operation.
NOTE: Set indoor DS-4 (Indoor fan setting) and DS-6 (Indoor emergency mode enable) before setting outdoor DS-2 dip switch settings. Otherwise, the compressor may be damaged in operation.
NOTE: When proper communication is established, these switches must be returned to default settings
The compressor speed will automatically adjust based on the outdoor ambient temperature. If ambient temperature is higher than 95°F, the outdoor unit can operate at 100% compressor speed. If ambient temperature is lower than 70°F, the unit will run at 50% compressor speed. Between 95°F and 70°F, the compressor speed will adjust linearly as shown.

SERVICING
TROUBLESHOOTING- OUTDOOR UNIT AND INDOOR UNIT FOR EEV APPLICABLE UNIT

Dipswitch Default Factory Settings

Switch #| Setting| Function
ID DS-1| 1| OFF| No Use
2| OFF| No Use
3| OFF| No Use
4| OFF| No Use
ID DS-2| 5| OFF| No Use
6| OFF| No Use
7| OFF| No Use
8| OFF| No Use
ID DS-3| 9| OFF| Heater Kit Selection in Emergency Mode
10| OFF| Heater Kit Selection in Emergency Mode
11| OFF| Heater Kit Selection in Emergency Mode
12| OFF| Heater Kit Selection in Emergency Mode
ID DS-4| 13| ON| Allow in Emergency Mode (Fan Emergency Mode)
14| OFF| Allow in Emergency Mode (Fan Emergency Mode)
15| ON| EEV Enable
16| OFF| No Use
ID DS-5| 17| ON| Emergency EEV Opening
18| OFF| Emergency EEV Opening
19| OFF| EEV Emergency Mode

20| OFF| No Use
ID DS-6| 21| OFF| Emergency mode (Cooling and Heating Emergency Mode)
22| OFF| Emergency mode (Cooling and Heating Emergency Mode)
23| OFF| No Use
24| OFF| No Use
OD DS-1| 1| ON| CT Communication Enable
2| ON| CT Communication Enable

OD DS-2| 1| OFF| Cooling Emergency mode
2| OFF| Cooling Emergency mode

  • Must be set at factory setting to operate the normal mode.
    ** Must be set at factory setting indoor unit with EEV. It’s prohibited to change setting.

SERVICING
COOLING EMERGENCY MODE WIRING FOR TXV APPLICABLE INDOOR UNIT
Cooling emergency mode is available when using a TXV applicable indoor unit.
To energize the blower at the appropriate speed, standard Legacy wiring is required. The image below shows how the thermostat input terminals are to be wired when selecting a cooling airflow.
NOTE: the blower will run continuously with this wiring which is required. The outdoor unit will cycle as described in the Cooling Emergency Mode section when appropriate dip switch modes are set. NOTE: Emergency heating mode is not available with TXV applicable indoor units. If communications still exist between the indoor unit and thermostat, the thermostat should be used to provide heating calls.

SERVICING

OUTDOOR UNIT – SETTING THE MODE DISPLAY
SERVICING

MODE DISPLAY INTRODUCTION
A 3-digit display is provided on the Control board as a backup tool to the thermostat for reading faults, fault history, monitoring and setting up the unit. Follow the information provided in this section to learn how to use the mode display.

DISPLAY

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner - SERVICING
39

DISPLAY BUTTON LAYOUT
The display buttons shown can be used to navigate and select items:

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner - SERVICING
40

Examples of button layout are shown above.
Identify correct display buttons on your unit Control board.

MODES
There are 5 modes which can be accessed using the setting display:
FAULT CODE, FAULT HISTORY, MONITORING, SETTING MODE 1 SETTING MODE 2.
To enter any of these modes, use the schemes shown in this section. Each mode has its own corresponding “Screen #” within the display itself which allows the user to navigate and use the features. (Example: The Fault Code is accessed and displayed from “Screen 0” of the 7-segment display. The Fault History is accessed and display using “Screen 1” of the display, etc.)

MODE FUNCTION DISPLAY SCREEN #
Fault Code Display Present fault (if any). 0 (Default)
Fault Code History 6 Recent faults stored. 1
Monitoring Mode *Monitors system values. 2
Setting Mode 1 *Can change system settings. 3
Setting Mode 2 *Can change system settings. 4

*See tables at the end of this section.

NAVIGATING THROUGH THE DISPLAY SCREENS

SCREEN 0| The home or default screen on the display.  This shows the most recent fault.
---|---
SCREEN 1| To access, hold the RECALL button for 5 seconds at screen 0.
SCREEN 2| To access, hold the RECALL button for 5 seconds at screen 1.
SCREEN 3| To access, hold the RECALL button .
SCREEN 4| To access, hold the RECALL and TEST buttons simultaneously

To return to SCREEN 0 of the display, press the LEARN button.

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner - SERVICING
41

FAULT CODE HISTORY NAVIGATION
< SCREEN 1>
This mode will allow the user to see the six most recent system faults.
For a list of the fault codes, please see the TROUBLESHOOTING tables in this document.

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner - SERVICING
42Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air
Conditioner - SERVICING 43Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air
Conditioner - SERVICING 44Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air
Conditioner - SERVICING 45

SCREEN 0 (Display FAULT CODE)

Setting No. Contents Notes
1 Fault code (present)

SCREEN 1 (Display FAULT CODES)

Setting No. Contents Notes
1 Fault code (latest) Latest
2 Fault code (2nd) 2nd
3 Fault code (3rd) 3rd
4 Fault code (4th) 4th
5 Fault code (5th) 5th
6 Fault code (6th) 6th

SCREEN 2 (MONITOR MODE)

Setting No. Contents Notes
1 Compressor operation time unit:hr (Multiply by 200,)
2 Operation code 0: Stop

1: Cooling Start-up
2: Heating Start-up
3: Oil Return Operation 4: Heating Operation
5: Defrost Operation
6: Cooling Operation
3| Compressor Reduction Mode| 0:OFF,1:ON
4| % demand| unit:% (Cut off the decimal first place.)
5| act % demand| unit:% (Cut off the decimal first place.)
6| Requested ID CFM| unit:CFM (Multiply by 10)
7| Reported ID CFM| unit:CFM (Multiply by 10)
8| Outdoor FAN RPM| unit:RPM (Multiply by 10)
9| Ta (Outdoor Air Temperature)| unit:F
10| Td (Discharge Temperature)| unit:F
11| Tm (Outdoor Coil Temperature)| unit:F
12| Tb (Defrost Sensor Temperature)| unit:F
13| Tl (Liquid Temperature)| unit:F
14| Pressure Sensor| unit:PSI

SCREEN 3 (SETTING MODE 1)

Setting No.| Contents| Setting| Installer / Serviceman Notes
---|---|---|---
1| Cool Airflow Trim High 1,2| 0: -15% 2: -5%    4: 5%     6: 15%
1: -10% 3: 0%     5: 10%|
2| Cool Airflow Trim Int| 0: -15% 3: 0%     6: 15%    9: Full (Max)3
1: -10% 4: 5%     7: 20%
2: -5%     5: 10% 8: 30%|
3| Cool Airflow Trim Low| 0: -15% 3: 0%     6: 15%    9: Full (Max)
3
1: -10% 4: 5%     7: 20%
2: -5%     5: 10% 8: 30%|
4| Cool Profile| 0: A        1: B       2: C         3:D|
5| Cool Fan ON Delay| 0: 5sec. 1: 10sec. 2: 20sec. 3: 30sec.|
6| Cool Fan OFF Delay| 0: 30sec. 1: 60sec. 2: 90sec. 3: 120sec.|
7| Dehumidification Select 4| 0: STD    2: A      4: C
1: OFF    3: B|
13| Airflow Trim Offset
1,*2| 0: 0%      1. +2.5%| Used for additional trim setting by adding 2.5% to basic airflow trim setting. This setting affects all trim settings except +15% High (cooling or heating).
14| Zoning Selection| 0: ON      1: OFF|
15| Circulation Selection| 0: ON      1: OFF|

NOTE: Parameters as per factory setting are highlighted in bold and underlined.
1 SXV906010 with VC960804C, VM970804C and MVC800804C combination trim more than 5% settings are invalid. Trimmed up CFM makes mismatching error.
2 Depending on the connected indoor unit, there are restrictions on the positive side Trim setting.
If you want to change the Cool Airflow Trim to positive side, be sure to confirm the Airflow Trim restrictions in the latest manual.
The latest manual can be obtained from the website “PartnerLink(InfoFinderPlus/Literature)”.
[PartnerLink URL]
https://partnerlinkmarketing.goodmanmfg.com/goodman/info- finder-plus*
3 The Inverter system uses lower compressor speed and lower indoor unit CFM to optimize system performance.
To obtain 100% CFM for home circulation, use full Trim setting instead of Int/Low speed.
This is recommended for applications with unusually cold return temperatures such as basements.
*4 Please refer to the page of “Dehumidification Select” for details of this function.

7-SEGMENT DISPLAY
SCREEN 4 (SETTING MODE 2)

Setting No.| Contents| Setting| Installer / Serviceman Notes
---|---|---|---
1| Maximum Defrost Interval| 0: 30min. _
_1: 60min.
2: 90min.
3: 120min.|
2| Set Maximum Current| N/A| Future Use
4| System Verification Test (System Test)| 0:ON    1: OFF|
7| Force Defrost Cycle| 0:ON    1: OFF|
8| Pump Down| 0:ON    1: OFF|
9| Charge Mode| 0:ON    1: OFF|
10| Maximum Compressor RPS for Cooling| |
11| Maximum Compressor RPS for Heating|
|
12| BOOST MODE Selection| 0:ON ** 1: OFF|
13| BOOST MODE Temperature|
0:105F,** 1:100F, 2:95F, 3:90F, 4:85F, 5:80F, 6:75F 7:70F 8: Always ON|

*Depends on tonnage. Can adjust compressor RPS in each 0.5 RPS
NOTES:

  • Parameters as per factory setting are highlighted in bold and underlined.
  • BOOST MODE is applicable only for *VXC20**1 or later revision.

TROUBLESHOOTING

OUTDOOR UNIT

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner -
TROUBLESHOOTING 1

Outdoor Normal Temperature Operating Range: 67-115°F / Indoor Normal Temperature Operating Range: 65 – 85°F
WARNING
AVOID CONTACT WITH THE CHARGED AREA.

  • NEVER TOUCH THE CHARGED AREA BEFORE CONFIRMING THAT THE RESIDUAL VOLTAGE IS 50 VOLTS OR LESS.
  1. SHUT DOWN THE POWER AND LEAVE THE CONTROL BOX FOR 10 MINUTES.
  2. MAKE SURE TO TOUCH THE EARTH GROUND TERMINAL TO RELEASE THE STATIC ELECTRICITY FROM YOUR BODY (TO PREVENT FAILURE OF THE PC BOARD).
  3. MEASURE THE RESIDUAL VOLTAGE IN THE SPECIFIED MEASUREMENT POSITION USING A VOM WHILE PAYING ATTENTION NOT TO TOUCH THE CHARGED AREA.
  4. IMMEDIATELY AFTER MEASURING THE RESIDUAL VOLTAGE, DISCONNECT THE CONNECTORS OF THE OUTDOOR UNIT’S FAN MOTOR . (IF THE FAN BLADE ROTATES BY STRONG WIND BLOW ING AGAINST IT, THE CAPACITOR WILL BE CHARGED, CAUSING THE DANGER OF ELECTRICAL SHOCK.)

OUTDOOR UNIT

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner -
TROUBLESHOOTING 2

Outdoor Normal Temperature Operating Range: 17-62°F / Indoor Normal Temperature Operating Range: 65 – 85°F
WARNING
AVOID CONTACT WITH THE CHARGED AREA.

  • NEVER TOUCH THE CHARGED AREA BEFORE CONFIRMING THAT THE RESIDUAL VOLTAGE IS 50 VOLTS OR LESS.
  1. SHUT DOWN THE POWER AND LEAVE THE CONTROL BOX FOR 10 MINUTES.
  2. MAKE SURE TO TOUCH THE EARTH GROUND TERMINAL TO RELEASE THE STATIC ELECTRICITY FROM YOUR BODY (TO PREVENT FAILURE OF THE PC BOARD).
  3. MEASURE THE RESIDUAL VOLTAGE IN THE SPECIFIED MEASUREMENT POSITION USING A VOM WHILE PAYING ATTENTION NOT TO TOUCH THE CHARGED AREA.
  4. IMMEDIATELY AFTER MEASURING THE RESIDUAL VOLTAGE, DISCONNECT THE CONNECTORS OF THE OUTDOOR UNIT’S FAN MOTOR . (IF THE FAN BLADE ROTATES BY STRONG WIND BLOW ING AGAINST IT, THE CAPACITOR WILL BE CHARGED, CAUSING THE DANGER OF ELECTRICAL SHOCK.)

OUTDOOR UNIT ERROR CODES

Fault Code| Control Board LED Display| Transmitted Climate Talk Message| Thermostat Fault| Probable Causes| Corrective Actions
---|---|---|---|---|---
12| E12| OD CTRL FAIL1| Indicates a general memory error.| ● High electrical noise
● Faulty control board| ● Replace control board if necessary
13| E13| HI PRESSURE C (C = CRITICAL)| This error indicates the equipment is experiencing frequent high pressure faults.| ● Blocked/restricted condenser coil and/or lines
● Stop valve not completely open
● Overcharge
● Outdoor fan not running
● High pressure switch (HPS) inoperable
● Faulty TXV
● Faulty control board| ● Check and clean condenser coil and/or lines
● Check the opening of stop valve, should be full open; Repair/replace if needed
● Check refrigerant charge level; Adjust if needed
● Check outdoor fan motor & wiring; Repair/replace if needed
● Check TXV; Replace if needed
● Replace control board if necessary
14| | HI PRESSURE M (M = MINOR)| This error indicates the equipment is experiencing frequent high pressure faults. Control has determined continued operation is acceptable. This indicates they may be a problem with the equipment.| ● Blocked/restricted condenser coil and/or lines
● Stop valve not completely open
● Overcharge
● Outdoor fan not running
● High pressure switch (HPS) inoperable
● Faulty TXV
● Faulty control board| ●  Check and clean condenser coil and/or lines
● Check the opening of stop valve, should be full open; Repair/replace if needed
● Check refrigerant charge level; Adjust if needed
● Check outdoor fan motor & wiring; Repair/replace if needed
● Check TXV; Replace if needed
● Replace control board if necessary
● Check high pressure switch; Replace if necessary
15| E15| LOW PRESSURE C| This error indicates the equipment is experiencing frequent low pressure faults.| ● Stop valve not completely open
● Restriction in refrigerant lines
● Low refrigerant charge
● Refrigerant leak
● Low pressure sensor inoperable or not properly connected
● Indoor fan motor not functioning correctly
● Faulty TXV
● Faulty control board| ● Check the opening of stop valve, should be full open; Repair/replace if needed
● Check for restrictions in refrigerant line; Repair/replace if needed
● Check refrigerant charge level; Adjust if needed
● Test for system leaks using leak test procedure
● Check the connection to low pressure sensor; Repair/replace if needed
● Check TXV; Replace if needed
● Check indoor blower motor & wiring; Repair/replace if needed
● Replace control board if necessary
16| | LOW PRESSURE M| This error indicates the equipment is experiencing frequent low pressure faults. Control has determined continued operation is acceptable. This indicates they may be a problem with the equipment.| ● Stop valve not completely open
● Restriction in refrigerant lines
● Low refrigerant charge
● Refrigerant leak
● Low pressure sensor inoperable or not properly connected
● Indoor fan motor not functioning correctly
● Faulty TXV
● Faulty control board| ● Check the opening of stop valve, should be full open; Repair/replace if needed
● Check for restrictions in refrigerant line; Repair/replace if needed
● Check refrigerant charge level; Adjust if needed
● Test for system leaks using leak test procedure
● Check the connection to low pressure sensor; Repair/replace if needed
● Check TXV; Replace if needed
● Check indoor blower motor & wiring; Repair/replace if needed
● Replace control board if necessary
17| E17| COMPRESSOR FAIL| This error indicates the equipment is experiencing frequent compressor faults.| ● Stop valve not completely open
● The compressor wire is lost phase
● Compressor motor failure| ● Check the opening of stop valve, should be full open; Repair/replace if needed
● Check the wire between control board and compressor
● Inspect compressor motor for proper function; Replace if necessary
18| E18| OD CTRL FAIL2| Indicates the control board may need to be replaced.| ● Outdoor fan motor not connected properly
● Faulty control board
● Noise| ● Check wiring from Outdoor fan motor to control board; Repair if needed.
● Replace control board if necessary
19| E19| PCB OR FAN FAIL| This error indicates the equipment is experiencing frequent outdoor control board and/or motor faults.| ● Obstruction in fan rotation
● Outdoor fan motor not connected properly
● Outdoor fan not running
● Faulty control borad
● Noise| ● Check and clean grille or any debris
● Check wiring from Outdoor fan motor to control board; Repair if needed
● Check outdoor fan motor & wiring. Repair/replace if needed
● Replace control board if necessary
20| E20| EEV OPEN CKT| EEV coil is not connected.| ● Outdoor EEV coil is not connected.
● Faulty outdoor EEV coil.| ● Check outdoor EEV coil connection. Repair/replace as needed.
21| E21| EEV CTRL FAIL| This error indicates the equipment is experiencing frequent low discharge superheat faults.| ● Thermistors inoperable or improperly connected
● Faulty TXV
● Faulty outdoor EEV coil
● Faulty outdoor EEV
● Over charge
● Faulty pressure sensor
● Faulty control board| ● Check the connection to thermistors; Repair/replace if needed
● Check TXV; Replace/repair if needed
● Check outdoor EEV coil; Repair/replace if needed
● Check outdoor EEV; Replace/repair if needed
● Check refrigerant charge level; Adjust if needed
● Check pressure sensor; Repair/replace if needed
● Replace control board if necessary
22| E22| HI DISCH TEMP| This error indicates the equipment is experiencing frequent high discharge temperature faults.
Discharge thermistor is not put on correct position.| ** ● Discharge thermistor inoperable or improperly connected
● Discharge thermistor is put on incorrect position or off
● Low refrigerant charge
● Overcharge
● Faulty compressor| ● Check discharge thermistor resistance and connections; Repair/replace as needed
● Check discharge thermistor position
● Check refrigerant charge level; Adjust if needed
● Check the compressor; Repair/replace if needed
---|---|---|---|---|---
23| E23| DISCH TEMP FAIL| The control has detected that the Discharge Temperature Sensor is out of range.| ● Discharge thermistor inoperable or improperly connected| ● Check discharge thermistor resistance and connections; Repair/replace as needed
24| E24| HPS OPEN| The high pressure switch is open.| ● High pressure switch (HPS) inoperable| ● Check resistance on HPS to verify operation; Replace if needed
25| E25| AIR SENSOR FLT| The outdoor air temperature sensor is open or shorted.| ● Faulty outdoor thermistor sensor or disconnect| ● Inspect and test sensor; Replace sensor if needed
26| E26| PRESSURE SENSOR| The control determines that the pressure sensor is not reacting properly.| ● Low pressure sensor inoperable or not properly connected| ● Check the connection to low pressure sensor; Repair/replace if needed
27| E27| COIL TEMP FAIL1| The control detects that the Outdoor Defrost Sensor is out of range.| ● Outdoor defrost thermistor inoperable or not properly connected| ● Check the connection to OD defrost thermistor; Repair as needed
28| E28| COIL TEMP FAIL2| The control has detected that the Outdoor Coil Temperature Sensor is out of range.| ● Outdoor coil thermistor inoperable or not properly connected| ● Check the connection to OD coil thermistor; Repair/replace if needed
29| E29| LIQ TEMP FAIL| The control has detected that the Liquid Temperature Sensor is out of range.| ● Liquid thermistor inoperable or not properly connected| ● Check the connection to liquid thermistor; Repair/replace if needed
30| E30| OD CTRL FAIL3| Indicates the control board may need to be replaced.| ● Wiring to control board disconnected
● Faulty control board
● Noise| ● Check wiring to control board; Repair as needed
● Replace control board if necessary
31| E31| HI LEAK CURRENT| The control has detected high leakage current (high voltege).| ● Improper ground
● Faulty compressor| ●Check ground screws/lugs and wiring; Repair/replace if needed
● Check the compressor; Repair/replace if needed
32 2| E32| HI TEMP CTRL1| This error indicates the equipment is experiencing high temperature faults on the outdoor control board.| ● Ambient air conditions too high
● Cooling bracket screw(s) missing or not properly fastened (2-4 ton only)
● No or poor thermal grease coating between cooling plumbing and cooling bracket on control board (2-4 ton only)
● Outdoor fan low speed (5 ton only)
● No flow or limited flow through control board cooling circuit (potential restriction in line or low refrigerant) (2-4 ton only)
● Stop valve not completely open (2-4 ton only)| ● Cycle power; re-try during usable ambient temperature range
● Verify cooling bracket screws in place and secure; Secure fasteners as needed (2-4 ton only)
● Check thermal grease inside cooling bracket on control board; Apply additional grease as needed
● Check outdoor fan motor & wiring; Repair/replace if needed (5 ton only)
● Check for restriction in line
● Check refrigerant charge level; Adjust if needed (2-4 ton only)
● Check the opening of stop valve, should be full open;
Repair/replace if needed (2-4 ton only)
33
2| | HI TEMP CTRL2| This error indicates the equipment is experiencing high temperature faults on the outdoor control board. Control has determined continued operation is acceptable. This indicates they may be a problem with the equipment.| ● Ambient air conditions too high
● Cooling bracket screw(s) missing or not properly fastened (2-4 ton only)
● No or poor thermal grease coating between cooling plumbing and cooling bracket on control board (2-4 ton only)
● Outdoor fan low speed (5 ton only)
● No flow or limited flow through control board cooling circuit (potential restriction in line or low refrigerant) (2-4 ton only)
● Stop valve not completely open (2-4 ton only)| ● Cycle power; re-try during usable ambient temperature range
● Verify cooling bracket screws are in place and secure; Secure fasteners as needed (2-4 ton only)
● Check thermal grease inside cooling bracket on control board; Apply additional grease as needed
● Check outdoor fan motor & wiring; Repair/replace if needed (5 ton only)
● Check for restriction in line
● Check refrigerant charge level; Adjust if needed (2-4 ton only)
● Check the opening of stop valve – it should be fully open; Repair/replace if needed (2-4 ton only)
34| E34| CURRENT SPIKE| Board detected a high current condition. This indicates the potential for a short circuit.| ● Current spike in supply
● Stop valve not completely open
● The compressor wire is lost phase
● Faulty control board
● Faulty compressor| ● Check power supply for in-rush current during start-up or steady state operation
● Check the opening of stop valve, should be full open; Repair/replace if needed
● Check the wire between control board and compressor
● Replace control board if necessary
● Check the compressor; Repair/replace if needed
35| E35| HIGH CURRENT| Board detected a high current condition.| ● Short circuit condition
● Stop valve not completely open
● Overcharge
● Faulty control board
● Faulty compressor| ● Check installation clearances.
● Check the opening of stop valve, should be full open; Repair/replace if needed
● Check refrigerant charge level; Adjust if needed
● Replace control board if necessary
● Check the compressor; Repair/replace if needed.
---|---|---|---|---|---
36| E36| STARTUP ERROR| The control encountered an abnormal condition during the startup procedure.| ● Blocked/restricted condenser coil and/or lines
● The compressor wire is lost phase
● Inconsistent compressor load
● Faulty control board| ● Check and clean condenser coil and/or lines
● Check the wire between control board and compressor
● Replace control board if necessary
37| E37| OD CTRL FAIL4| Indicates the control board may need to be replaced.| ● Outdoor fan motor not connected properly
● Faulty control board| ● Check wiring from outdoor fan motor to control board; Repair if needed
● Replace control board if necessary
38| E38| COMP VOLTAGE| The control has detected a voltage related issue with the compressor.| ● High or low voltage from supply
● The compressor wire is lost phase
● Faulty control board| ● Correct low/high line voltage condition; Contact local utility if needed
● Check the wire between control board and compressor
● Replace control board if necessary
39| E39| OD CTRL FAIL5| Indicates the control board may need to be replaced.| ● Thermistors inoperable or improperly connected
● Faulty control board| ● Check the connection to thermistors; Repair/replace if needed
● Replace control board if necessary
40| E40| COMP MISMATCH| Control determines that its compressor requirement is different than the compressor capability.| ● Bluetooth® Shared Data Loader BTSDL01 not correct
● Control board mismatch| ● Check Bluetooth® Shared Data Loader BTSDL01 data vs. air conditioner model
● Verify control board size vs. air conditioner model; Replace control board if necessary
41| E41| LOW REFRIGERANT| The control has detected a low refrigerant condition.| ● Refrigerant leak
● Low refrigerant charge
● Thermisters inoperable or not properly connected| ● Test for system leaks using leak test procedure
● Check refrigerant charge level; Adjust if needed
● Checkthe connection to thermistor; Repair/replace if needed
42| E42| LOW LINE VOLT| Control detects a low power supply voltage condition.| ● Low line voltage supply| ● Check circuit breakers and fuses; Replace if needed
● Verify unit is connected to power supply as specified on rating plate
● Correct low line voltage condition; Contact local utility if needed
43| E43| HIGH LINE VOLT| Control detects a high power supply voltage condition.| ● High line voltage supply| ● Verify unit is connected to power supply as specified on rating plate
● Correct high line voltage condition; Contact local utility if needed
44| E44| OP TEMP RANGE| The control detects the outdoor temperature outside recommended operational range. Unit may continue to operate normally.| ● Ambient air conditions too high or low| ● Cycle power; re-try during usable ambient temperature range
45| E45| NO COOLING TEST| The control is unable to start the Cooling mode test because indoor heat has been turned on by thermostat. Please set thermostat to off position.| ● Heat provided by secondary heating source| ● Turn off heater using thermostat before running AHRI mode
46| E46| NO HEATING TEST| The control is unable to sart the Heating mode test becaue indoor heat has been turned on by thermostat. Please set thermostat to off position.| ● Heat provided by secondary heating source| ● Turn off heater using thermostat before running AHRI mode
47| E47| NO SYS VER TEST| The control is unable to start the System Verification test because indoor heat has been turned on by thermostat. Please set thermostat to off position.| ● Heat provided by secondary heating source| ● Turn off heater using thermostat before operation
48| E48| NO PUMP DOWN| The control is unable to enter the Pump Down Mode because indoor heat has been turned on by thermostat. Please set thermostat to off position.| ● Heat provided by secondary heating source| ● Turn off heater using thermostat before operation
49| E49| NO CHARGE MODE| The control is unable to enter Charging Mode because indoor heat has been turned on by thermostat. Please set thermostat to off position.| ● Heat provided by secondary heating source| ● Turn off heater using thermostat before operation
50| E50| LINE VOLT CTRL| This indicates there is a voltage issue on the control board. See service manual for troubleshooting information.| ● High or low voltage from supply
● Faulty control board| ● Correct low/high line voltage condition; Contact local utility if needed
● Replace control board if necessary
51* 2| E51| OD COMM ERROR| This indicates potential communication issues have been detected by the outdoor control board.| ● Communication wiring disconnected| ● Check communication wiring; Repair as needed
52| | COMP FAIL MINOR| This error indicates the equipment is experiencing frequent compressor faults. Control has determined continued operation is acceptable. This indicates they may be a problem with the equipment.| ● Stop valve not completely open
● The compressor wire is lost phase
● Compressor motor failure| ● Check the opening of stop valve, should be full open; Repair/replace if needed
● Check the wire between control board and compressor
● Inspect compressor motor for proper function; Replace if necessary
53| | PCB PR FAN MIN| This error indicates the equipment is experiencing frequent outdoor control board and/or motor faults. Control has determined continued operation is acceptable. This indicates there may be a problem with the equipment.| ● Obstruction in fan rotation
● Ooutdoor fan motor not connected properly
● Outdoot fan not running
● Faulty control board
● Noise| ● Check and clean grille of any debris
● Check wiring from outdoor fan motor to control board; Repair if needed
● Check outdoor fan motor & wiring; Repair/replace if needed
● Replace control board if necessary
---|---|---|---|---|---
54| | EEV MINOR| This error indicates the equipment is experiencing frequent low discharge superheat faults.
Control has determined continued operation is acceptable. This indicates they may be a problem with the equipment.| ● Thermistors inoperable or improperly connected
● Faulty TXV
● Faulty control board| ● Check the connection to thermistors; Repair/replace if needed
● Check TXV; Replace if needed
● Replace control board if necessary
55| | HI DIS TEMP MIN| This error indicates the equipment is experiencing frequent high discharge temperature faults.
Control has determined continued operation is acceptable. This indicates they may be a problem with the equipment.| ● Discharge thermistor inoperable or improperly connected
● Discharge thermistor is put on incorrect position or off
● Low refrigerant charge
● Overcharge
● Faulty compressor| ● Check discharge thermistor resistance and connections; Repair/replace as needed
● Check discharge thermistor position
● Check refrigerant charge level; Adjust if needed
● Check refrigerant charge level; Adjust if needed
● Check the compressor; Repair/replace if needed
57| | CL LOOP SWEAT| This indicates the control is sensing sweating on the cooling loop.| ● Refrigerant Leak
● Low refrigerant charge
● Faulty TXV
● Thermistors inoperable or improperly connection| ● Test for system leaks using leak test procedure
● Check refrigerant charge level; Adjust if needed
● Check TXV; Replace if needed
● Check the connection to thermistors; Repair/replace if needed
B0| Eb0| NO ID AIRFLOW| The estimated airflow from indoor subsystem is near to 0 CFM.| ● Failed indoor blower motor
● Indoor fan motor not properly connected
● Too much static pressure| ● Check ID fan motor wiring and connectors; Repair/replace if needed
● Check ID fan motor; Replace if needed
B9| Eb9| LOW ID AIRFLOW**| Estimated airflow from motor is lower than the airflow requirement.| ● Failed indoor blower motor
● Indoor fan motor not properly connected
● Too much static pressure| ● Check ID fan motor wiring and connectors; Repair/replace if needed

● Check ID fan motor; Replace if needed

D0| Ed0| NO NET DATA| Control board does not have the necessary data for it to properly perform its functions.| ● Air conditioner is wired as part of a communicating system and integrated control module does not contain any shared data.| ● Replace control board if necessary
● Re-write shared data using Bluetooth® Shared Data Loader BTSDL01
D1| Ed1| INVALID DATA| Control board does not the appropriate data needed to properly perform its functions.| ● Air conditioner is wired as part of a communicating system and integrated control module contains invalid shared data or network data is invalid for the integrated control module.| ● Replace control board if necessary
● Re-write shared data using Bluetooth® Shared Data Loader BTSDL01
D2| Ed2| INVALID SYSTEM| The airflow requirement is greater than the airflow capability of the indoor subsystem.| ● Air conditioner/heat pump is wired as part of a communicating system and outdoor unit requires airflow greater than indoor unit’s airflow capability
● Shared data is incompatible the system or missing parameters
● Communication wiring has loose connection.| ● Verify shared data is correct for your specific model; Repopulate data if required

● Check communication wiring. Repair as needed.

D3| Ed3| INVALID CONFIG| There is a mismatch between the shared data and the control physical hardware.| ● Shared data sent to integrated control module does not match hardware configuration.| ● Verify shared data is correct for your specific model; Repopulate data if required.
D4| Ed4| INVALID MC DATA| The Bluetooth® Shared Data Loader BTSDL01 data has been rejected.| ● Shared data on Bluetooth® Shared Data Loader BTSDL01 has been rejected.| ● Verify shared data is correct for your specific model; Repopulate data if required.
Items below are messages only displayed on the thermostat screen.
11| E11| RUN SYS TEST| This test is required at startup. Installer should navigate to the ComforrtNet User Menu, choose Air Conditioner, then EQUIP TEST and SYSYTEM TEST. Selecting ON will run the required test.
Display will clear once testing is complete.| ● Incomplete SYSTEM TEST
● SYSTEM TEST is running| MESSAGE ONLY

TROUBLESHOOTING
RE-WRITING SHARED DATA TO OUTDOOR UNIT USING BLUETOOTH® SHARED DATA LOADER BTSDL01
Check Troubleshooting codes to determine the need to flash shared data to outdoor unit. Follow the below procedure to flash shared data.
Procedure to flash shared data to Outdoor unit using Bluetooth® Shared Data Loader BTSDL01

  1. Turn the power OFF to the outdoor unit.
  2. Disconnect the Climate Talk (CT) connector from the outdoor unit.
  3. Insert the Bluetooth® Shared Data Loader BTSDL01 on the outdoor unit.
  4. Turn the power ON to the outdoor unit.
  5. Verify that H1P (red LED) flashes twice. This step confirms that the data has been transferred from the Bluetooth® Shared Data Loader BTSDL01 to the outdoor unit.
  6. Turn the power OFF to the outdoor unit.
  7. Remove the Bluetooth® Shared Data Loader BTSDL01 from the unit.
  8. Connect the Climate Talk (CT) connector to the outdoor unit.
  9. Turn the power ON to the outdoor unit.
  10. Continue the operation of the unit as desired.

NOTE:

  1. If there is an error E11 on the 7-segment display of the Outdoor unit after step 11, run the System Verification Test on the Outdoor unit using the thermostat menu.
    • AC – Menu → Air Conditioner → Equip Test → Sys- tem Verification Test → ON
    • HP – Menu → Air Conditioner → Equip Test → Sys- tem Verification Test → ON

  2. The control boards for different 19.2 SEER2 OD units (2T, 3T, 4T, 5T) are different. Below are the names of the connectors for quick identification.
    • Bluetooth® Shared Data Loader BTSDL01 connector – X52A (white – 12 pin connector)
    • Climate Talk connector – X851A (green – 9 pin connector)
    • Red LED – H1P

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner -
TROUBLESHOOTING 3

TROUBLESHOOTING

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner -
TROUBLESHOOTING 4

NETWORK TROUBLESHOOTING
If a network communication error code has occurred, use the following steps to help troubleshoot the system. (For network communication error codes, refer to the table below and the tables of error codes for outdoor unit and indoor unit.)
After any wiring changes have been made or DS1 dip switches on the outdoor unit control board have been changed, apply power to the system and see if the error codes have cleared.

  1. Confirm low voltage wiring is correct per installation instructions. Check for miswiring. (i.e. Terminal 1 and 2 is reversed.)
    NOTE: A removable plug connector is provided with the control to make thermostat wire connections. This plug may be removed, wire connections made to the plug, and replaced. It is strongly recommended that you do not connect more than two wires into a single terminal in the field because there is a risk of the wires becoming loose, which may result in intermittent operation.

  2. Check wires for damage. (i.e. Broken wire at terminal, broken inside wire nuts or damaged cable between units.)

  3. Perform continuity check on wires to make sure cable is OK. Replace the cable if necessary.

  4. Change both dip switches of DS1 on the outdoor unit control board to the opposite position. See image above.

The integrated control module has some onboard tools that can be used to troubleshoot the network. These tools are:
red communications LED, green receive (Rx) LED, and the learn button.

  • Red communications LED – Indicates the status of the network. The table below indicates the LED status and the corresponding potential problem.
  • Green receive LED – Indicates network traffic. The table below indicates the LED status and the corresponding potential problem.
  • LEARN button – Used to reset the network. Press the button for approximately 5 seconds to reset the network.

LED COLOR| LED Status| Indication| Probable Causes| Corrective Actions
---|---|---|---|---
Red Communications LED Outdoor unit control board: (H1P) Indoor unit control board :(H2P)| Off| Normal condition| • None| • None
1 Flash| Communications failure| • Unknown packet is received
• Communications failure| • Depress learn button
• Verify wiring connection
2 Flash| Out-of-box reset| • Control power up
• Learn button depressed| • None
Green Receive LED Outdoor unit control board:(H2P)
Indoor unit control board:(H3P)| Off| No power Communications error| • No power to unit
• Open fuse
• Communication error| • Check circuit breakers and fuses; Reset/Replace if needed
• Reset network by depressing learn button
• Check communication wires (terminal 1/terminal 2 wires); Replace if needed
• Check for shorts in low voltage wiring.
1 Steady Flash| No network found| • Broken/disconnected communication wire(s)
• Unit is installed as a legacy/traditional system| • Check communication wires (terminal 1/terminal 2 wires); Replace if needed
• Check installation type (legacy/traditional or communicating)
Rapid Flashing| Normal network traffic| • Control is “talking” on network as expected| • None
On Solid| Terminal 1/Terminal 2 miss-wire| • Terminal 1 and Terminal 2 wires reversed at indoor unit, thermostat, or outdoor unit
• Short between terminal 1 and terminal 2 wires
• Short between terminal 1 or terminal 2 two wires and terminal C (24VAC) or terminal R (24VAC, COM)| • Check communication wires (terminal 1/terminal 2 wires); Replace if needed

THERMISTOR RESISTANCE VALUE

| | Tm : Coil TI : Liquid Tb : Defrost
Tgi: Indoor Gas Tli: Indoor Liquid| Tl : Liquid| Td : Discharge| Ta : Ambient
---|---|---|---|---|---
TEMP| TEMP| Thermistor Resistance| Volts| Thermistor Resistance| Volts| Thermistor Resistance| Volts| Thermistor Resistance| Volts
(℃)| (F)| R(kΩ)| DC(V)| R(kΩ)| DC(V)| R(kΩ)| DC(V)| R(kΩ)| DC(V)
-30| -22| 364.43| 4.58| 364.43| 4.58| 4759.15| 4.96| 362.48| 4.58
-25| -13| 267.00| 4.45| 267.00| 4.45| 3454.24| 4.94| 265.99| 4.45
-20| -4| 197.81| 4.29| 197.81| 4.29| 2533.62| 4.92| 197.31| 4.28
-15| 5| 148.10| 4.09| 148.10| 4.09| 1877.01| 4.90| 147.86| 4.09
-10| 14| 111.99| 3.86| 111.99| 3.86| 1403.82| 4.86| 111.88| 3.86
-5| 23| 85.49| 3.61| 85.49| 3.61| 1059.45| 4.82| 85.43| 3.61
0| 32| 65.84| 3.33| 65.84| 3.33| 806.47| 4.77| 65.80| 3.33
5| 41| 51.09| 3.04| 51.09| 3.04| 618.95| 4.70| 51.10| 3.04
10| 50| 39.96| 2.74| 39.96| 2.74| 478.76| 4.62| 39.99| 2.74
15| 59| 31.50| 2.44| 31.50| 2.44| 373.11| 4.53| 31.54| 2.44
20| 68| 25.01| 2.16| 25.01| 2.16| 292.86| 4.41| 25.06| 2.16
25| 77| 20.00| 1.89| 20.00| 1.89| 231.44| 4.28| 20.04| 1.89
30| 86| 16.10| 1.64| 16.10| 1.64| 184.11| 4.13| 16.13| 1.64
35| 95| 13.04| 1.42| 13.04| 1.42| 147.37| 3.95| 13.07| 1.42
40| 104| 10.63| 1.22| 10.63| 1.22| 118.68| 3.76| 10.65| 1.22
45| 113| 8.71| 1.04| 8.71| 1.04| 96.13| 3.56| 8.73| 1.05
50| 122| 7.18| 0.89| 7.18| 0.89| 78.29| 3.34| 7.18| 0.89
55| 131| 5.95| 0.76| 5.95| 0.76| 64.10| 3.11| –| –
60| 140| 4.96| 0.65| 4.96| 0.65| 52.76| 2.87| –| –
65| 149| 4.16| 0.56| 4.16| 0.56| 43.63| 2.64| –| –
70| 158| 3.50| 0.48| 3.50| 0.48| 36.26| 2.41| –| –
75| 167| 2.96| 0.41| 2.96| 0.41| 30.27| 2.18| –| –
80| 176| 2.51| 0.35| 2.51| 0.35| 25.38| 1.97| –| –
85| 185| 2.14| 0.30| 2.14| 0.30| 21.37| 1.77| –| –
90| 194| 1.83| 0.26| 1.83| 0.26| 18.06| 1.58| –| –
95| 203| 1.58| 0.23| 1.58| 0.23| 15.33| 1.41| –| –
100| 212| 1.36| 0.20| 1.36| 0.20| 13.06| 1.25| –| –
105| 221| 1.18| 0.17| 1.18| 0.17| 11.17| 1.11| –| –
110| 230| 1.02| 0.15| 1.02| 0.15| 9.59| 0.99| –| –
115| 239| 0.89| 0.13| 0.89| 0.13| 8.25| 0.87| –| –
120| 248| 0.78| 0.12| 0.78| 0.12| 7.13| 0.77| –| –
125| 257| 0.68| 0.10| 0.68| 0.10| 6.18| 0.68| –| –
130| 266| 0.60| 0.09| 0.60| 0.09| 5.37| 0.61| –| –
135| 275| 0.53| 0.08| 0.53| 0.08| 4.69| 0.54| –| –
140| 284| 0.47| 0.07| 0.47| 0.07| 4.10| 0.48| –| –
145| 293| 0.42| 0.06| 0.42| 0.06| 3.59| 0.42| –| –
150| 302| 0.37| 0.06| 0.37| 0.06| 3.16| 0.37| –| –

PRESSURE TEMPERATURE

R-410A Pressure vs. Temperature Chart

PSIG| °F| | PSIG| °F| | PSIG| °F| | PSIG| °F| | PSIG| °F| | PSIG| °F
12| -37.7| 114| 37.8| 216| 74.3| 318| 100.2| 420.0| 120.7| 522| 137.6
14| -34.7| 116| 38.7| 218| 74.9| 320| 100.7| 422.0| 121.0| 524| 137.9
16| -32.0| 118| 39.5| 220| 75.5| 322| 101.1| 424.0| 121.4| 526| 138.3
18| -29.4| 120| 40.5| 222| 76.1| 324| 101.6| 426.0| 121.7| 528| 138.6
20| -36.9| 122| 41.3| 224| 76.7| 326| 102.0| 428.0| 122.1| 530| 138.9
22| -24.5| 124| 42.2| 226| 77.2| 328| 102.4| 430.0| 122.5| 532| 139.2
24| -22.2| 126| 43.0| 228| 77.8| 330| 102.9| 432.0| 122.8| 534| 139.5
26| -20.0| 128| 43.8| 230| 78.4| 332| 103.3| 434.0| 123.2| 536| 139.8
28| -17.9| 130| 44.7| 232| 78.9| 334| 103.7| 436.0| 123.5| 538| 140.1
30| -15.8| 132| 45.5| 234| 79.5| 336| 104.2| 438.0| 123.9| 540| 140.4
32| -13.8| 134| 46.3| 236| 80.0| 338| 104.6| 440.0| 124.2| 544| 141.0
34| -11.9| 136| 47.1| 238| 80.6| 340| 105.1| 442.0| 124.6| 548| 141.6
36| -10.1| 138| 47.9| 240| 81.1| 342| 105.4| 444.0| 124.9| 552| 142.1
38| -8.3| 140| 48.7| 242| 81.6| 344| 105.8| 446.0| 125.3| 556| 142.7
40| -6.5| 142| 49.5| 244| 82.2| 346| 106.3| 448.0| 125.6| 560| 143.3
42| -4.5| 144| 50.3| 246| 82.7| 348| 106.6| 450.0| 126.0| 564| 143.9
44| -3.2| 146| 51.1| 248| 83.3| 350| 107.1| 452.0| 126.3| 568| 144.5
46| -1.6| 148| 51.8| 250| 83.8| 352| 107.5| 454.0| 126.6| 572| 145.0
48| 0.0| 150| 52.5| 252| 84.3| 354| 107.9| 456.0| 127.0| 576| 145.6
50| 1.5| 152| 53.3| 254| 84.8| 356| 108.3| 458.0| 127.3| 580| 146.2
52| 3.0| 154| 54.0| 256| 85.4| 358| 108.8| 460.0| 127.7| 584| 146.7
54| 4.5| 156| 54.8| 258| 85.9| 360| 109.2| 462.0| 128.0| 588| 147.3
56| 5.9| 158| 55.5| 260| 86.4| 362| 109.6| 464.0| 128.3| 592| 147.9
58| 7.3| 160| 56.2| 262| 86.9| 364| 110.0| 466.0| 128.7| 596| 148.4
60| 8.6| 162| 57.0| 264| 87.4| 366| 110.4| 468.0| 129.0| 600| 149.0
62| 10.0| 164| 57.7| 266| 87.9| 368| 110.8| 470.0| 129.3| 604| 149.5
64| 11.3| 166| 58.4| 268| 88.4| 370| 111.2| 472.0| 129.7| 608| 150.1
66| 12.6| 168| 59.0| 270| 88.9| 372| 111.6| 474.0| 130.0| 612| 150.6
68| 13.8| 170| 59.8| 272| 89.4| 374| 112.0| 476.0| 130.3| 616| 151.2
70| 15.1| 172| 60.5| 274| 89.9| 376| 112.4| 478.0| 130.7| 620| 151.7
72| 16.3| 174| 61.1| 276| 90.4| 378| 112.6| 480.0| 131.0| 624| 152.3
74| 17.5| 176| 61.8| 278| 90.9| 380| 113.1| 482.0| 131.3| 628| 152.8
76| 18.7| 178| 62.5| 280| 91.4| 382| 113.5| 484.0| 131.6| 632| 153.4
78| 19.8| 180| 63.1| 282| 91.9| 384| 113.9| 486.0| 132.0| 636| 153.9
80| 21.0| 182| 63.8| 284| 92.4| 386| 114.3| 488.0| 132.3| 640| 154.5
82| 22.1| 184| 64.5| 286| 92.8| 388| 114.7| 490.0| 132.6| 644| 155.0
84| 23.2| 186| 65.1| 288| 93.3| 390| 115.0| 492.0| 132.9| 648| 155.5
86| 24.3| 188| 65.8| 290| 93.8| 392| 115.5| 494.0| 133.3| 652| 156.1
88| 25.4| 190| 66.4| 292| 94.3| 394| 115.8| 496.0| 133.6| 656| 156.6
90| 26.4| 192| 67.0| 294| 94.8| 396| 116.2| 498.0| 133.9| 660| 157.1
92| 27.4| 194| 67.7| 296| 95.2| 398| 116.6| 500.0| 134.0| 664| 157.7
94| 28.5| 196| 68.3| 298| 95.7| 400| 117.0| 502.0| 134.5| 668| 158.2
96| 29.5| 198| 68.9| 300| 96.2| 402| 117.3| 504.0| 134.8| 672| 158.7
98| 30.5| 200| 69.5| 302| 96.6| 404| 117.7| 506.0| 135.2| 676| 159.2
100| 31.2| 202| 70.1| 304| 97.1| 406| 118.1| 508.0| 135.5| 680| 159.8
102| 32.2| 204| 70.7| 306| 97.5| 408| 118.5| 510.0| 135.8| 684| 160.3
104| 33.2| 206| 71.4| 308| 98.0| 410| 118.8| 512.0| 136.1| 688| 160.8
106| 34.1| 208| 72.0| 310| 98.4| 412| 119.2| 514.0| 136.4| 692| 161.3
108| 35.1| 210| 72.6| 312| 98.9| 414| 119.6| 516.0| 136.7| 696| 161.8
110| 35.5| 212| 73.2| 314| 99.3| 416| 119.9| 518.0| 137.0|
112| 36.9| 214| 73.8| 316| 99.7| 418| 120.3| 520.0| 137.3
Required Liquid Line Temperature

LIQUID PRESSURE AT SERVICE VALVE (PSIG)| REQUIRED SUBCOOLING TEMPERATURE (°F)
8| 10| 12| 14| 16| 18
189| 58| 56| 54| 52| 50| 48
195| 60| 58| 56| 54| 52| 50
202| 62| 60| 58| 56| 54| 52
208| 64| 62| 60| 58| 56| 54
215| 66| 64| 62| 60| 58| 56
222| 68| 66| 64| 62| 60| 58
229| 70| 68| 66| 64| 62| 60
236| 72| 70| 68| 66| 64| 62
243| 74| 72| 70| 68| 66| 64
251| 76| 74| 72| 70| 68| 66
259| 78| 76| 74| 72| 70| 68
266| 80| 78| 76| 74| 72| 70
274| 82| 80| 78| 76| 74| 72
283| 84| 82| 80| 78| 76| 74
291| 86| 84| 82| 80| 78| 76
299| 88| 86| 84| 82| 80| 78
308| 90| 88| 86| 84| 82| 80
317| 92| 90| 88| 86| 84| 82
326| 94| 92| 90| 88| 86| 84
335| 96| 94| 92| 90| 88| 86
345| 98| 96| 94| 92| 90| 88
354| 100| 98| 96| 94| 92| 90
364| 102| 100| 98| 96| 94| 92
374| 104| 102| 100| 98| 96| 94
384| 106| 104| 102| 100| 98| 96
395| 108| 106| 104| 102| 100| 98
406| 110| 108| 106| 104| 102| 100
416| 112| 110| 108| 106| 104| 102
427| 114| 112| 110| 108| 106| 104
439| 116| 114| 112| 110| 108| 106
450| 118| 116| 114| 112| 110| 108
462| 120| 118| 116| 114| 112| 110
474| 122| 120| 118| 116| 114| 112
486| 124| 122| 120| 118| 116| 114
499| 126| 124| 122| 120| 118| 116
511| 128| 126| 124| 122| 120| 118

WARNING
HIGH VOLTAGE
Disconnect ALL power before servicing.
Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death.
CAUTION
When replacing the electrical board, do NOT touch the hatched areas. Before installing the new electrical board, be sure to wipe the grease off the refrigerant tubing.
Exercise caution to not damage the electrical connections.
Disconnect as needed.

UNINSTALL THE ELECTRICAL BOARD
When uninstalling the main electrical board, remove the screws holding the cover in place. If board replacement is attempted without following proper uninstallation procedure, the refrigerant piping might be damaged. Always replace the grease with new grease on heat sink used for cooling. Not replacing grease may result in insufficient cooling and may damage the electrical board.

  1. Remove the fixing screw A.
  2. Lift the cover and open it in the direction shown in the figure.
  3. Remove fixing screws B affixing the sheet metal plate.
  4. Carefully slide the sheet metal plate with the electrical board behind the refrigerant tubing as shown.

INSTALL THE ELECTRICAL BOARD
When working on a service port, ensure that no refrigerant and/or compressor oil is sprayed onto the electrical board. This could damage the board’s functionality.

  1. Wipe the stale grease completely from the installed piping. If you reinstall the control board, make sure to wipe clean the heat sink on the board. Coat the surface with the standard quantity of the specified new grease.
  2. Carefully slide the sheet metal plate back in and fix the screws B.
  3. Do not apply force to the parts on the control board. Hold the control board plate NOT the control board.
  4. Ensure that the liquid tube does not come in contact with any part of the PCB assembly.
  5. Gently fit the tube in the heat sink troughs. Ensure good contact.
  6. Close the cover, slide it downwards, fix it with the nails (two nails) and tighten fixing screws A so that the piping is tightly connected.

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner -
TROUBLESHOOTING 6| Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner -
TROUBLESHOOTING 7
---|---

WARNING
AVOID CONTACT WITH THE CHARGED AREA.

  • EVER TOUCH THE CHARGED AREA BEFORE CONFIRMING THAT THE RESIDUAL VOLTAGE IS 50 VOLTS OR LESS.
  1. SHUT DOWN THE POWER AND LEAVE THE CONTROL BOX FOR 10 MINUTES.
  2. MAKE SURE TO TOUCH THE EARTH GROUND TERMINAL TO RELEASE THE STATIC ELECTRICITY FROM YOUR BODY (TO PREVENT FAILURE OF THE PC BOARD).
  3. MEASURE THE RESIDUAL VOLTAGE IN THE SPECIFIED MEASUREMENT POSITION USING A VOM WHILE PAYING ATTENTION NOT TO TOUCH THE CHARGED AREA.
  4. IMMEDIATELY AFTER MEASURING THE RESIDUAL VOLTAGE, DISCONNECT THE CONNECTORS OF THE OUTDOOR UNIT’S FAN MOTOR. (IF THE FAN BLADE ROTATES BY STRONG WIND BLOW ING AGAINST IT, THE CAPACITOR WILL BE CHARGED, CAUSING THE DANGER OF ELECTRICAL SHOCK.)

*SXV902410*
SXV903610**

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner -
TROUBLESHOOTING 8

WARNING
AVOID CONTACT WITH THE CHARGED AREA.

  • NEVER TOUCH THE CHARGED AREA BEFORE CONFIRMING THAT THE RESIDUAL VOLTAGE IS 50 VOLTS OR LESS.
  1. SHUT DOWN THE POWER AND LEAVE THE CONTROL BOX FOR 10 MINUTES.
  2. MAKE SURE TO TOUCH THE EARTH GROUND TERMINAL TO RELEASE THE STATIC ELECTRICITY FROM YOUR BODY (TO PREVENT FAILURE OF THE PC BOARD).
  3. MEASURE THE RESIDUAL VOLTAGE IN THE SPECIFIED MEASUREMENT POSITION USING A VOM WHILE PAYING ATTENTION NOT TO TOUCH THE CHARGED AREA.
  4. IMMEDIATELY AFTER MEASURING THE RESIDUAL VOLTAGE, DISCONNECT THE CONNECTORS OF THE OUTDOOR UNIT’S FAN MOTOR. (IF THE FAN BLADE ROTATES BY STRONG WIND BLOW ING AGAINST IT, THE CAPACITOR WILL BE CHARGED, CAUSING THE DANGER OF ELECTRICAL SHOCK.)

*SXV904810**

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner -
TROUBLESHOOTING 9

WARNING
AVOID CONTACT WITH THE CHARGED AREA.

  • EVER TOUCH THE CHARGED AREA BEFORE CONFIRMING THAT THE RESIDUAL VOLTAGE IS 50 VOLTS OR LESS.
  1. SHUT DOWN THE POWER AND LEAVE THE CONTROL BOX FOR 10 MINUTES.
  2. MAKE SURE TO TOUCH THE EARTH GROUND TERMINAL TO RELEASE THE STATIC ELECTRICITY FROM YOUR BODY (TO PREVENT FAILURE OF THE PC BOARD).
  3. MEASURE THE RESIDUAL VOLTAGE IN THE SPECIFIED MEASUREMENT POSITION USING A VOM WHILE PAYING ATTENTION NOT TO TOUCH THE CHARGED AREA.
  4. IMMEDIATELY AFTER MEASURING THE RESIDUAL VOLTAGE, DISCONNECT THE CONNECTORS OF THE OUTDOOR UNIT’S FAN MOTOR. (IF THE FAN BLADE ROTATES BY STRONG WIND BLOW ING AGAINST IT, THE CAPACITOR WILL BE CHARGED, CAUSING THE DANGER OF ELECTRICAL SHOCK.)

*SXV906010**

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner -
TROUBLESHOOTING 10

Troubleshooting Inverter – Cooling

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner -
TROUBLESHOOTING 11
Troubleshooting| Inverter – Cooling
---|---
Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner -
TROUBLESHOOTING 12

Troubleshooting
Error Code – 13

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner -
TROUBLESHOOTING 13

Troubleshooting
Error Code – 14

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner -
TROUBLESHOOTING 14

Troubleshooting
Error Code – 15 & 16

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner -
TROUBLESHOOTING 15

Troubleshooting
Error Code – 18 & 19

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner -
TROUBLESHOOTING 16

Troubleshooting
Error Code – 20

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner -
TROUBLESHOOTING 17

Troubleshooting
Error Code – 21

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner -
TROUBLESHOOTING 18

Troubleshooting
Error Code – 22

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner -
TROUBLESHOOTING 19

Troubleshooting
Error Code 23, 25, 27, 28, 29 

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner -
TROUBLESHOOTING 20

Troubleshooting
Error Code – 24

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner -
TROUBLESHOOTING 21

Troubleshooting
Error Code – 26

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner -
TROUBLESHOOTING 22

Troubleshooting
Error Code – 30

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner -
TROUBLESHOOTING 23

Troubleshooting
Error Code – 31

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner -
TROUBLESHOOTING 24

Troubleshooting
Error Code – 32 with cooling loop

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner -
TROUBLESHOOTING 25

Troubleshooting
Error Code – 32 with heat sink

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner -
TROUBLESHOOTING 26

Troubleshooting
Error Code – 57

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner -
TROUBLESHOOTING 27

Troubleshooting
Error Code – 70

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner -
TROUBLESHOOTING 28

Troubleshooting
Error Code – 73

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner -
TROUBLESHOOTING 29

Troubleshooting
Error Code – 74

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner -
TROUBLESHOOTING 30

Troubleshooting
Error Code – 75

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner -
TROUBLESHOOTING 31

Troubleshooting
Error Code – 77

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner -
TROUBLESHOOTING 32

Troubleshooting
Error Code B0 & B1

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner -
TROUBLESHOOTING 33

Troubleshooting
Error Code – B2-B6, B9

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner -
TROUBLESHOOTING 34Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air
Conditioner - TROUBLESHOOTING 35

Troubleshooting
Error Code – B7

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner -
TROUBLESHOOTING 36

Troubleshooting
Error Code – B9

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner -
TROUBLESHOOTING 37

Troubleshooting
Error Code – D0, D1, D4

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner -
TROUBLESHOOTING 38

Troubleshooting
Error Code – d2

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner -
TROUBLESHOOTING 39

Troubleshooting
Error Code – EC

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner -
TROUBLESHOOTING 40

*SXV90[24-36]10
**

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner -
TROUBLESHOOTING 41 NOTE: The compressor can operate normally in any of the following wiring connections shown on the right.
(Wiring connection between control board and compressor terminal)

*SXV904810**

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner -
TROUBLESHOOTING 43

WIRING DIAGRAM

*SXV906010
**

WARNING
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT.
MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner - WIRING
DIAGRAM 1

Wiring is subject to change. Always refer to wiring diagram on the unit for the most up to date wiring.

WARNING
HIGH VOLTAGE!

DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT.
MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
INDOOR UNIT FOR TXV APPLICABLE UNIT (MBVC**00AA-A)

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner - WIRING
DIAGRAM 3![Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner

NOTES:

  1. PLACE RED WIRES ON TRANSFORMER TERMINAL 2 FOR 208 VAC OPERATION.
  2. MANUFACTURER’S SPECIFIED REPLACEMENT PARTS MUST BE USED WHEN SERVICING.
  3. IF ANY OF THE ORIGINAL WIRES AS SUPPLIED WITH THIS UNIT MUST BE REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL HAVING A TEMPERATURE RATING OF AT LEAST 105°C. USE COPPER CONDUCTORS ONLY.
  4. UNIT MUST BE PERMANENTLY GROUNDED AND CONFORM TO N.E.C AND LOCAL CODES.
  5. TO RECALL THE LAST 6 FAULTS, MOST RECENT TO LEAST RECENT, DEPRESS SWITCH FOR MORE THAN 2 SECONDS WHILE IN STANDBY (NO THERMOSTAT INPUTS)
  6. RED STATUS LED PROVIDES NETWORK STATUS. GREEN RX LED INDICATES NETWORK TRAFFIC. USE LEARN BUTTON TO RESET NETWORK.
  7. DISCARD CONNECTOR PL1 WHEN INSTALLING OPTIONAL HEAT KIT.
  8. THE CONDENSATE ALARM SWITCH (CAS) TERMINALS CAN ONLY BE UTILIZED WITH COMMUNICATING MODE SETUPS AND MUST BE ENABLED WITH A COMMUNICATING THERMOSTAT. THIS FEATURE IS NOT OPERATIONAL WITH LEGACY SYSTEMS.
  9. USE N.E.C CLASS 2 WIRE.

Wiring is subject to change. Always refer to wiring diagram on the unit for the most up to date wiring.

INDOOR UNIT FOR EEV APPLICABLE UNIT (AMVE)**

WARNING
HIGH VOLTAGE!

DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT.
MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner - WIRING
DIAGRAM 5

NOTE: The position of the black square indicates the setting position of the selector switches (DS1-DS6).
Wiring is subject to change. Always refer to wiring diagram on the unit for the most up to date wiring.

ACCESSORIES

*EXPANSION VALVES
SXV9010**

Model Name TXV-Kit
*SXV902410** TXV-V24
*SXV903610** TXV-V36
*SXV904810** TXV-V48
*SXV906010** TXV-V60

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner - WIRING
DIAGRAM 6![Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner

AMVE
HEATER KIT

Goodman GSXV9 4 Ton 22 3 SEER2 Variable Speed Air Conditioner -
Table

*Revision level that may or may not be designated.
NOTE: Airflow selection should meet the minimum requirements as mentioned in the air handler Installation instructions.
For heater kit installation, it is important to set the capacity of the electric heater at Set-up menu on the thermostat and DIP switch on indoor unit control board. For more information, please see indoor unit I/O manual.

ELECTRIC HEAT AIRFLOW TABLE

Htr kW| 9| 10| 11| AMVE24BP14**| AMVE36CP14**| AMVE48DP14**| AMVE60DP14**
3| ON| ON| ON| 730| 850*| NR| NR
5| ON| ON| OFF| 780| 1250| 1250| 1250
6| ON| OFF| ON| 850| 1300| 1300| 1300
8| ON| OFF| OFF| 950| 1500| 1500| 1500
10| OFF| ON| ON| 1025| 1550| 1550| 1550
15| OFF| ON| OFF| NR| 1720| 1720| 1780
19
| OFF| OFF| ON| NR| NR| NR| NR
20| NR| 1800| 1815| 1850
21 or 25*| OFF| OFF| OFF| NR| NR| 1850| 1850

NOTE: Airflow data shown applies to the electric heat only in either legacy mode or communicating mode operation.
NR- Not rated
+For match up with a 2 ton outdoor unit: Heater kit application shall not exceed 10 kW.
Airflow for 5 kW up to 10 kW heater kits shall be set to 850 cfm speed tap of ON-ON-ON.
++For match up with a 3 ton outdoor unit: Heater kit application shall not exceed 15 kW.
Airflow for 5 kW up to 15 kW heater kits shall be set to 1300 cfm speed tap of ON-OFF-ON.
Airflow for 5 kW up to 20 kW heater kits shall be set to 1500 cfm speed tap of ON-OFF-OFF
** 3 kW heater kit is not applicable for this indoor application.