Panasonic Air Conditioner Instruction Manual
- June 16, 2024
- Panasonic
Table of Contents
Air Conditioner
Product Information
Specifications
-
Model No. Indoor Unit: CS-TZ20ZKEW, CS-TZ25ZKEW, CS-TZ35ZKEW,
CS-TZ42ZKEW, CS-TZ50ZKEW, CS-RZ25ZKEW, CS-RZ35ZKEW, CS-RZ50ZKEW,
CS-MTZ16ZKE -
Model No. Outdoor Unit Single Split: CU-TZ20ZKE, CU-TZ25ZKE,
CU-TZ35ZKE, CU-TZ42ZKE, CU-TZ50ZKE, CU-RZ25ZKE, CU-RZ35ZKE,
CU-RZ50ZKE -
Model No. Multi Split: CU-2Z35TBE, CU-2Z41TBE, CU-2Z50TBE,
CU-3Z52TBE, CU-3Z68TBE, CU-4Z68TBE, CU-4Z80TBE, CU-5Z90TBE,
CU-2TZ41TBE, CU-2TZ50TBE, CU-3TZ52TBE
Product Features
A new built-in Network Adaptor that allows you to control your
heatpump from anywhere.
Flexibility to connect Single Split System or Multi Split System
Air Conditioner to suit your needs.
Usage Instructions
Installation Instructions
Before operating the unit, please read these operating
instructions thoroughly and keep them for future reference. Before
installation, the installer should:
-
Read the Installation Instructions, then request the customer
keep them for future reference. -
Remove the remote control packed with the indoor unit.
Remote Control Setup
Follow these steps to set up the remote control:
- Pull out the back cover of the remote control.
- Insert AAA or R03 batteries.
- Close the cover.
Clock Setting
To set the clock:
- Press the CLOCK button.
- Use the arrow buttons to set the time.
- Press the confirm button to save the setting.
Basic Operation
To start/stop the operation and select the desired mode:
-
Press the POWER button to start/stop the operation.
-
Use the mode selection button to select the desired mode (AUTO,
DRY, HEAT, COOL). -
Use the temperature adjustment buttons to select the desired
temperature.
FAQ
Q: Can children use this appliance?
A: This appliance can be used by children aged from 8 years and
above and persons with reduced physical, sensory or mental
capabilities or lack of experience and knowledge if they have been
given supervision or instruction concerning use of the appliance in
a safe way and understand the hazards involved. Children shall not
play with the appliance. Cleaning and user maintenance shall not be
made by children without supervision.
Q: What should I do if I encounter any issues with the air
conditioner?
A: Please refer to the Troubleshooting section in the user
manual (pages 19-22) for assistance with any issues you may
encounter.
Operating Instructions
Air Conditioner
Model No. Indoor Unit
CS-TZ20ZKEW CS-TZ25ZKEW CS-TZ35ZKEW CS-TZ42ZKEW CS-TZ50ZKEW CS-RZ25ZKEW CS-
RZ35ZKEW CS-RZ50ZKEW CS-MTZ16ZKE
nanoeX
Outdoor Unit Single Split CU-TZ20ZKE CU-TZ25ZKE CU-TZ35ZKE CU-TZ42ZKE CU-
TZ50ZKE CU-RZ25ZKE CU-RZ35ZKE CU-RZ50ZKE
Multi Split CU-2Z35TBE CU-2Z41TBE CU-2Z50TBE CU-3Z52TBE CU-3Z68TBE CU-4Z68TBE
CU-4Z80TBE CU-5Z90TBE CU-2TZ41TBE CU-2TZ50TBE CU-3TZ52TBE
ENGLISH
Before operating the unit, please read these operating instructions thoroughly
and keep them for future reference. Before installation, the installer should:
Read the Installation Instructions, then request the customer keep them for
future reference. Remove the remote control packed with the indoor unit.
WEB-ACXF55-35141-EN
A new built-in Network Adaptor that allows you to control your heatpump from
anywhere.
Flexibility to connect Single Split System or Multi Split System Air
Conditioner to suit your needs.
For complete product features, please refer to catalogue.
Use the remote control within 8 m from the remote control receiver on the indoor unit.
B
2
Quick Guide
Inserting the batteries
2
A Clock setting
A
3
1 Press CLOCK , then
1
press to set the
1 Pull out the back cover of remote control.
2 Insert AAA or R03 batteries.
3 Close the cover.
time.
· Press CLOCK for approximately 5 seconds to show the time as 12-hour (am/pm) or 24-hour.
2 Press
to confirm.
Thank you for purchasing Panasonic Air Conditioner.
Table of Contents
Safety Precautions ……… 4-13 How to Use …………………14-15 To Learn More ………… 16-17
Cleaning the Air Conditioner ……………… 18 Troubleshooting………… 19-22 Information
…………………… 23
Accessories
· Remote control · AAA or R03 batteries × 2 · Remote control holder · Screws
for remote control
holder × 2
The illustrations in this manual are for explanation purposes only and may
differ from the actual unit. They are subject to change without notice.
B Basic operation
1 Press
to
start/stop the operation.
2 Press
to select
the desired mode.
AUTO DRY
HEAT COOL
POWER
· When the unit is ON, disappears
from the remote control display.
3 Press TEMP UP, TEMP DOWN to select the desired temperature.
Up
Down
Selection range: 16.0 °C ~ 30.0 °C / 60 °F ~ 86 °F. · Press for approximately
10 seconds to show the temperature as °C or °F.
3
Safety Precautions
To prevent personal injury, injury to others or property damage, please comply with the following: Incorrect operation due to failure to follow instructions below may cause harm or damage, the seriousness of which is classified as below: This appliances is not intended for accessibility by the general public.
This sign warns
WARNING of death or serious injury.
CAUTION
This sign warns of injury or damage to property.
The instructions to be followed are classified by the following symbols:
This symbol denotes an action that is PROHIBITED.
These symbols denote actions COMPULSORY.
Indoor unit
Power supply Air inlet
Air outlet
Remote control
Air inlet
Outdoor unit
Air outlet
4
WARNING
Indoor unit and outdoor unit
This appliance can be used by children aged from 8 years and above and persons
with reduced physical, sensory or mental capabilities or lack of experience
and knowledge if they have been given supervision or instruction concerning
use of the appliance in a safe way and understand the hazards involved.
Children shall not play with the appliance. Cleaning and user maintenance
shall not be made by children without supervision.
Please consult authorised dealer or specialist to clean the internal parts,
repair, install, remove, disassemble and reinstall the unit. Improper
installation and handling will cause leakage, electric shock or fire.
Confirm with authorised dealer or specialist on usage of any specified
refrigerant type. Using refrigerant type other than the specified may cause
product damage, burst and injury etc.
Do not use means to accelerate the defrosting process or to clean, other than
those recommended by manufacturer. Any unfit method or using incompatible
material may cause product damage, burst and serious injury.
Do not install the unit in a potentially explosive or flammable atmosphere.
Failure to do so could result in fire.
Do not insert your fingers or other objects into the air conditioner indoor or
outdoor unit, rotating parts may cause injury.
Do not touch the outdoor unit during lightning, it may cause electric shock.
Do not expose yourself directly to cold air for a long period to avoid excess
cooling.
Do not sit or step on the unit, you may fall down accidentally.
Remote control
Do not allow infants and small children to play with the remote control to
prevent them from accidentally swallowing the batteries.
Power supply
Do not use a modified cord, joint cord, extension cord or unspecified cord to
prevent overheating and fire.
To prevent overheating, fire or electric shock: · Do not share the same power
outlet with
other equipment. · Do not operate with wet hands. · Do not over bend the power
supply cord. · Do not operate or stop the unit by inserting or
pulling out the power plug.
If the supply cord is damaged, it must be replaced by the manufacturer,
service agent or similarly qualified persons in order to avoid a hazard.
It is strongly recommended to be installed with Earth Leakage Circuit Breaker
(ELCB) or Residual Current Device (RCD) to prevent electric shock or fire.
To prevent overheating, fire or electric shock: · Insert the power plug
properly. · Dust on the power plug should be periodically
wiped with a dry cloth.
Stop using the product if any abnormality/failure occurs and disconnect the
power plug or turn off the power switch and breaker. (Risk of
smoke/fire/electric shock) Examples of abnormality/failure · The ELCB trips
frequently. · Burning smell is observed. · Abnormal noise or vibration of the
unit is
observed. · Water leaks from the indoor unit. · Power cord or plug becomes
abnormally hot. · Fan speed cannot be controlled. · The unit stops running
immediately even if it is
switched on for operation. · The fan does not stop even if the operation is
stopped. Contact your local dealer immediately for maintenance/repair.
This equipment must be earthed to prevent electrical shock or fire.
Prevent electric shock by switching off the power supply and unplug: – Before
cleaning or servicing, – When extended non-use, or – During abnormally strong
lightning activity.
CAUTION
Indoor unit and outdoor unit
Do not wash the indoor unit with water, benzine, thinner or scouring powder to
avoid damage or corrosion at the unit. Do not use for preservation of precise
equipment, food, animals, plants, artwork or other objects. This may cause
quality deterioration, etc. Do not use any combustible equipment in front of
the airflow outlet to avoid fire propagation. Do not expose plants or pet
directly to airflow to avoid injury, etc.
Do not touch the sharp aluminium fin, sharp parts may cause injury.
Do not switch ON the indoor unit when waxing the floor. After waxing, aerate
the room properly before operating the unit. Do not install the unit in oily
and smoky areas to prevent damage to the unit. Do not dismantle the unit for
cleaning purpose to avoid injury. Do not step onto an unstable bench when
cleaning the unit to avoid injury. Do not place a vase or water container on
the unit. Water may enter the unit and degrade the insulation. This may cause
an electric shock. Do not open window or door for long time during operation,
it may lead to inefficient power usage and uncomfortable temperature changes.
Prevent water leakage by ensuring drainage pipe is: – Connected properly, –
Kept clear of gutters and containers, or – Not immersed in water After a long
period of use or use with any combustible equipment, aerate the room
regularly. After a long period of use, make sure the installation rack does
not deteriorate to prevent the unit from falling down.
5
Safety Precautions
Remote control
Do not use rechargeable (Ni-Cd) batteries. It may damage the remote control.
To prevent malfunction or damage of the remote control: · Remove the batteries
if the unit is not going
to be used for a long period of time. · New batteries of the same type must be
inserted following the polarity stated.
Power supply
Do not disconnect the plug by pulling the cord to prevent electric shock.
WARNING
This appliance is filled with R32 (mild flammable refrigerant). If the
refrigerant is leaked and exposed to an external ignition source, there is a
risk of fire.
Indoor unit and outdoor unit
The appliance shall be installed, and/or operated in a room with floor area
larger than Amin (m²) and keep away from ignition sources, such as
heat/sparks/open flame or hazardous areas such as gas appliances, gas cooking,
reticulated gas supply systems or electric cooking appliances, etc. (Refer to
Table A of Installation instructions table for Amin (m²)) Be aware that
refrigerant may not contain an odour, highly recommended to ensure suitable
flammable refrigerant gas detectors are present, operating and able to warn of
a leak. Keep any required ventilation openings clear of obstruction.
Do not pierce or burn as the appliance is pressurized. Do not expose the
appliance to heat, flame, sparks, or other sources of ignition. Else it may
explode and cause injury or death.
Precaution for using R32 refrigerant
The basic installation work procedures are the same as conventional
refrigerant (R410A, R22) models.
Since the working pressure is higher than that of refrigerant R22 models, some
of the piping and installation and service tools are special. Especially, when
replacing a refrigerant R22 model with a new refrigerant R32 model, always
replace the conventional piping and flare nuts with the R32 and R410A piping
and flare nuts on the outdoor unit side. For R32 and R410A, the same flare nut
on the outdoor unit side and pipe can be used.
The mixing of different refrigerants within a system is prohibited. Models
that use refrigerant R32 and R410A have a different charging port thread
diameter to prevent erroneous charging with refrigerant R22 and for safety.
Therefore, check beforehand. [The charging port thread diameter for R32 and
R410A is 1/2 inch.] Must always ensure that foreign matter (oil, water, etc.)
does not enter the piping. Also, when storing the piping, securely seal the
opening by pinching, taping, etc. (Handling of R32 is similar to R410A.) ·
Operation, maintenance, repairing and
refrigerant recovery should be carried out by trained and certified personnel
in the use of flammable refrigerants and as recommended by the manufacturer.
Any personnel conducting an operation, servicing or maintenance on a system or
associated parts of the equipment should be trained and certified. · Any part
of refrigerating circuit (evaporators, air coolers, AHU, condensers or liquid
receivers) or piping should not be located in the proximity of heat sources,
open flames, operating gas appliance or an operating electric heater. · The
user/owner or their authorised representative shall regularly check the
alarms, mechanical ventilation and detectors, at least once a year, where as
required by national regulations, to ensure their correct functioning.
6
· A logbook shall be maintained. The results of these checks shall be recorded
in the logbook.
· In case of ventilations in occupied spaces shall be checked to confirm no
obstruction.
· Before a new refrigerating system is put into service, the person
responsible for placing the system in operation should ensure that trained and
certified operating personnel are instructed on the basis of the instruction
manual about the construction, supervision, operation and maintenance of the
refrigerating system, as well as the safety measures to be observed, and the
properties and handling of the refrigerant used.
· The general requirement of trained and certified personnel are indicated as
below:
a) Knowledge of legislation, regulations
and standards relating to flammable
refrigerants; and,
b) Detailed knowledge of and skills in
handling flammable refrigerants, personal
protective equipment, refrigerant leakage
prevention, handling of cylinders,
charging, leak detection, recovery and
disposal; and,
c) Able to understand and to apply in
practice the requirements in the national
legislation, regulations and Standards;
and,
d) Continuously undergo regular and further
training to maintain this expertise.
e) Air-conditioner piping in the occupied
space shall be installed in such a way
to protect against accidental damage in
operation and service.
f) Precautions shall be taken to avoid
excessive vibration or pulsation to
refrigerating piping.
g) Ensure protection devices, refrigerating
piping and fittings are well protected
against adverse environmental effects
(such as the danger of water collecting
and freezing in relief pipes or the
accumulation of dirt and debris).
h) Expansion and contraction of long runs
piping in refrigerating systems shall be
designed and installed securely (mounted
and guarded) to minimize the likelihood
hydraulic shock damaging the system.
i) Protect the refrigerating system from accidental rupture due to moving
furniture or reconstruction activities.
j) To ensure no leaking, field-made refrigerant joints indoors shall be
tightness tested. The test method shall have a sensitivity of 5 grams per year
of refrigerant or better under a pressure of at least 0.25 times the maximum
allowable pressure (>1.04 MPa, max 4.15 MPa). No leak shall be detected.
1. Installation (Space) · Product with flammable refrigerants, shall
be installed according to the minimum room area, Amin (m²) mentioned in Table
A of the Installation Instructions. · In case of field charge, the effect on
refrigerant charge caused by the different pipe length has to be quantified,
measured and labelled. · Must ensure the installation of pipe-work shall be
kept to a minimum. Avoid use dented pipe and do not allow acute bending. ·
Must ensure that pipe-work shall be protected from physical damage. · Must
comply with national gas regulations, state municipal rules and legislation.
Notify relevant authorities in accordance with all applicable regulations. ·
Must ensure mechanical connections be accessible for maintenance purposes. ·
In cases that require mechanical ventilation, ventilation openings shall be
kept clear of obstruction. · When disposal of the product, do follow to the
precautions in #12 and comply with national regulations. Always contact to
local municipal offices for proper handling.
7
Safety Precautions
2. Servicing 2-1. Service personnel · The system is inspected, regularly
supervised
and maintained by a trained and certified service personnel who is employed by
the person user or party responsible. · Ensure the actual refrigerant charge
is in accordance with the room size within which the refrigerant containing
parts are installed. · Ensure refrigerant charge not to leak. · Any qualified
person who is involved with working on or breaking into a refrigerant circuit
should hold a current valid certificate from an industry-accredited assessment
authority, which authorizes their competence to handle refrigerants safely in
accordance with an industry recognised assessment specification. · Servicing
shall only be performed as recommended by the equipment manufacturer.
Maintenance and repair requiring the assistance of other skilled personnel
shall be carried out under the supervision of the person competent in the use
of flammable refrigerants. · Servicing shall be performed only as recommended
by the manufacturer.
2-2. Work · Prior to beginning work on systems
containing flammable refrigerants, safety checks are necessary to ensure that
the risk of ignition is minimised. For repair to the refrigerating system, the
precautions in #2-2 to #2-8 must be followed before conducting work on the
system. · Work shall be undertaken under a controlled procedure so as to
minimize the risk of a flammable gas or vapour being present while the work is
being performed. · All maintenance staff and others working in the local area
shall be instructed and supervised on the nature of work being carried out. ·
Avoid working in confined spaces. Always ensure away from source, at least 2
meter of safety distance, or zoning of free space area of at least 2 meter in
radius. · Wear appropriate protective equipment, including respiratory
protection, as conditions warrant. · Keep all sources of ignition and hot
metal surfaces away.
8
2-3. Checking for presence of refrigerant
· The area shall be checked with an appropriate refrigerant detector prior to
and during work, to ensure the technician is aware of potentially flammable
atmospheres.
· Ensure that the leak detection equipment being used is suitable for use with
flammable refrigerants, i.e. non sparking, adequately sealed or intrinsically
safe.
· In case of leakage/spillage happened, immediately ventilate area and stay
upwind and away from spill/release.
· In case of leakage/spillage happened, do notify persons down wind of the
leaking/ spill, isolate immediate hazard area and keep unauthorised personnel
out.
2-4. Presence of fire extinguisher · If any hot work is to be conducted on the
refrigerating equipment or any associated parts, appropriate fire
extinguishing equipment shall be available at hand. · Have a dry powder or CO2
fire extinguisher adjacent to the charging area.
2-5. No ignition sources
· No person carrying out work in relation to a refrigerating system which
involves exposing any pipe work that contains or has contained flammable
refrigerant shall use any sources of ignition in such a manner that it may
lead to the risk of fire or explosion. They must not be smoking when carrying
out such work.
· All possible ignition sources, including
cigarette smoking, should be kept sufficiently
far away from the site of installation,
repairing, removing and disposal, during
which flammable refrigerant can possibly be
released to the surrounding space. · Prior to work taking place, the area
around
the equipment is to be surveyed to make sure that there are no flammable
hazards or ignition risks. · “No Smoking” signs shall be displayed.
2-6. Ventilated area
· Ensure that the area is in the open or that it is adequately ventilated
before breaking into the system or conducting any hot work.
· A degree of ventilation shall continue during the period that the work is
carried out.
· The ventilation should safely disperse any released refrigerant and
preferably expel it externally into the atmosphere.
2-7. Checks to the refrigerating equipment · Where electrical components are
being
changed, they shall be fit for the purpose and to the correct specification. ·
At all times the manufacturer’s maintenance and service guidelines shall be
followed. · If in doubt consult the manufacturer’s technical department for
assistance. · The following checks shall be applied to installations using
flammable refrigerants. – The actual refrigerant charge is in
accordance with the room size within which the refrigerant containing parts
are installed. – The ventilation machinery and outlets are operating
adequately and are not obstructed. – If an indirect refrigerating circuit is
being used, the secondary circuit shall be checked for the presence of
refrigerant. – Marking to the equipment continues to be visible and legible.
Markings and signs that are illegible shall be corrected. – Refrigerating pipe
or components are installed in a position where they are unlikely to be
exposed to any substance which may corrode refrigerant containing components,
unless the components are constructed of materials which are inherently
resistant to being corroded or are properly protected against being so
corroded.
2-8. Checks to electrical devices
· Repair and maintenance to electrical components shall include initial safety
checks and component inspection procedures.
· Initial safety checks shall include but not limit to:-
– That capacitors are discharged: this
shall be done in a safe manner to avoid
possibility of sparking.
– That there no live electrical components
and wiring are exposed while charging,
recovering or purging the system.
– That there is continuity of earth bonding. · At all times the manufacturer’s
maintenance
and service guidelines shall be followed. · If in doubt consult the
manufacturer’s
technical department for assistance. · If a fault exists that could compromise
safety,
then no electrical supply shall be connected to the circuit until it is
satisfactorily dealt with. · If the fault cannot be corrected immediately but
it is necessary to continue operation, an adequate temporary solution shall be
used. · The owner of the equipment must be informed or reported so all parties
are advised thereinafter.
9
Safety Precautions
3. Repairs to sealed components
· During repairs to sealed components, all electrical supplies shall be
disconnected from the equipment being worked upon prior to any removal of
sealed covers, etc.
· If it is absolutely necessary to have an electrical supply to equipment
during servicing, then a permanently operating form of leak detection shall be
located at the most critical point to warn of a potentially hazardous
situation.
· Particular attention shall be paid to the following to ensure that by
working on electrical components, the casing is not altered in such a way that
the level of protection is affected.This shall include damage to cables,
excessive number of connections, terminals not made to original specification,
damage to seals, incorrect fitting of glands, etc.
· Ensure that apparatus is mounted securely. · Ensure that seals or sealing
materials have
not degraded such that they no longer serve the purpose of preventing the
ingress of flammable atmospheres. · Replacement parts shall be in accordance
with the manufacturer’s specifications. NOTE: The use of silicon sealant may
inhibit the effectiveness of some types of leak detection equipment.
Intrinsically safe components do not have to be isolated prior to working on
them.
4. Repair to intrinsically safe components
· Do not apply any permanent inductive or capacitance loads to the circuit
without ensuring that this will not exceed the permissible voltage and current
permitted for the equipment in use.
· Intrinsically safe components are the only types that can be worked on while
live in the presence of a flammable atmosphere.
· The test apparatus shall be at the correct rating.
· Replace components only with parts specified by the manufacturer.
Unspecified parts by manufacturer may result ignition of refrigerant in the
atmosphere from a leak.
5. Cabling
· Check that cabling will not be subject to wear, corrosion, excessive
pressure, vibration, sharp edges or any other adverse environmental effects.
· The check shall also take into account the effects of aging or continual
vibration from sources such as compressors or fans.
6. Detection of flammable refrigerants
· Under no circumstances shall potential sources of ignition be used in the
searching or detection of refrigerant leaks.
· A halide torch (or any other detector using a naked flame) shall not be
used.
7. The following leak detection methods
are deemed acceptable for all refrigerant
systems
· No leaks shall be detected using detection equipment with sensitivity to
detect leakage of 5g/year of refrigerant or better under a pressure of at
least 0.25 times the maximum allowable pressure (>1.04 MPa, max 4.15 MPa), for
example, a universal sniffer.
· Electronic leak detectors may be used to detect flammable refrigerants, but
the sensitivity may not be adequate, or may need re-calibration. (Detection
equipment shall be calibrated in a refrigerant-free area.)
· Ensure that the detector is not a potential source of ignition and is
suitable for the refrigerant used.
· Leak detection equipment shall be set at a percentage of the LFL of the
refrigerant and shall be calibrated to the refrigerant employed and the
appropriate percentage of gas (25 % maximum) is confirmed.
· Leak detection fluids are also suitable for use with most refrigerants, for
example, bubble method and fluorescent method agents. The use of detergents
containing chlorine shall be avoided as the chlorine may react with the
refrigerant and corrode the copper pipe-work.
· If a leak is suspected, all naked flames shall be removed/extinguished.
· If a leakage of refrigerant is found which requires brazing, all of the
refrigerant shall be recovered from the system, or isolated (by means of shut
off valves) in a part of the system remote from the leak. The precautions in
8 must be followed to remove the refrigerant.
10
8. Removal and evacuation
· When breaking into the refrigerant circuit to make repairs or for any
other purpose conventional procedures shall be used. However, it is
important that best practice is followed since flammability is a
consideration. The following procedure shall be adhered to: remove refrigerant
-> purge the circuit with inert gas -> evacuate -> purge with inert gas ->
open the circuit by cutting or brazing.
· The refrigerant charge shall be recovered into the correct recovery
cylinders.
· The system shall be purged with OFN to render the appliance safe.
· This process may need to be repeated several times.
· Compressed air or oxygen shall not be used for this task.
· Purging shall be achieved by breaking the vacuum in the system with OFN and
continuing to fill until the working pressure is achieved, then venting to
atmosphere, and finally pulling down to a vacuum.
· This process shall be repeated until no refrigerant is within the system.
· When the final OFN charge is used, the system shall be vented down to
atmospheric pressure to enable work to take place.
· This operation is absolutely vital if brazing operations on the pipe work
are to take place.
· Ensure that the outlet for the vacuum pump is not close to any potential
ignition sources and there is ventilation available.
OFN = oxygen free nitrogen, type of
inert gas.
9. Charging procedures
· In addition to conventional charging procedures, the following requirements
shall be followed. – Ensure that contamination of different refrigerants does
not occur when using charging equipment. – Hoses or lines shall be as short as
possible to minimize the amount of refrigerant contained in them. – Cylinders
shall be kept in an appropriate position according to the instructions. –
Ensure that the refrigerating system is earthed prior to charging the system
with refrigerant. – Label the system when charging is complete (if not
already). – Extreme care shall be taken not to over fill the refrigerating
system.
· Prior to recharging the system it shall be pressure tested with OFN (refer
to #7).
· The system shall be leak tested on completion of charging but prior to
commissioning.
· A follow up leak test shall be carried out prior to leaving the site.
· Electrostatic charge may accumulate and create a hazardous condition when
charging and discharging the refrigerant. To avoid fire or explosion,
dissipate static electricity during transfer by grounding and bonding
containers and equipment before charging/discharging.
11
Safety Precautions
10. Decommissioning · Before carrying out this procedure, it is
essential that the technician is completely familiar with the equipment and
all its details. · It is recommended good practice that all refrigerants are
recovered safely. · Prior to the task being carried out, an oil and
refrigerant sample shall be taken in case analysis is required prior to re-use
of recovered refrigerant. · It is essential that electrical power is available
before the task is commenced. a) Become familiar with the equipment and
its operation. b) Isolate system electrically. c) Before attempting the
procedure ensure
that: · mechanical handling equipment is
available, if required, for handling refrigerant cylinders; · all personal
protective equipment is available and being used correctly; · the recovery
process is supervised at all times by a competent person; · recovery equipment
and cylinders conform to the appropriate standards. d) Pump down refrigerant
system, if possible. e) If a vacuum is not possible, make a manifold so that
refrigerant can be removed from various parts of the system. f) Make sure that
cylinder is situated on the scales before recovery takes place. g) Start the
recovery machine and operate in accordance with instructions. h) Do not over
fill cylinders. (No more than 80 % volume liquid charge). i) Do not exceed the
maximum working pressure of the cylinder, even temporarily. j) When the
cylinders have been filled correctly and the process completed, make sure that
the cylinders and the equipment are removed from site promptly and all
isolation valves on the equipment are closed off. k) Recovered refrigerant
shall not be charged into another refrigerating system unless it has been
cleaned and checked.
12
· Electrostatic charge may accumulate and create a hazardous condition when
charging or discharging the refrigerant. To avoid fire or explosion, dissipate
static electricity during transfer by grounding and bonding containers and
equipment before charging/discharging.
11. Labelling
· Equipment shall be labelled stating that it has been de-commissioned and
emptied of refrigerant.
· The label shall be dated and signed. · Ensure that there are labels on the
equipment
stating the equipment contains flammable refrigerant.
12. Recovery
· When removing refrigerant from a system, either for servicing or
decommissioning, it is recommended good practice that all refrigerants are
removed safely.
· When transferring refrigerant into cylinders, ensure that only appropriate
refrigerant recovery cylinders are employed.
· Ensure that the correct number of cylinders for holding the total system
charge are available.
· All cylinders to be used are designated for the recovered refrigerant and
labelled for that refrigerant (i.e. special cylinders for the recovery of
refrigerant).
· Cylinders shall be complete with pressure relief valve and associated shut-
off valves in good working order.
· Recovery cylinders are evacuated and, if possible, cooled before recovery
occurs.
· The recovery equipment shall be in good working order with a set of
instructions concerning the equipment that is at hand and shall be suitable
for the recovery of flammable refrigerants.
· In addition, a set of calibrated weighing scales shall be available and in
good working order.
· Hoses shall be complete with leak-free disconnect couplings and in good
condition.
· Before using the recovery machine, check that it is in satisfactory working
order, has been properly maintained and that any associated electrical
components are sealed to prevent ignition in the event of a refrigerant
release. Consult manufacturer if in doubt.
· The recovered refrigerant shall be returned to the refrigerant supplier in
the correct recovery cylinder, and the relevant Waste Transfer Note arranged.
· Do not mix refrigerants in recovery units and especially not in cylinders.
· If compressors or compressor oils are to be removed, ensure that they have
been evacuated to an acceptable level to make certain that flammable
refrigerant does not remain within the lubricant.
· The evacuation process shall be carried out prior to returning the
compressor to the suppliers.
· Only electric heating to the compressor body shall be employed to accelerate
this process.
· When oil is drained from a system, it shall be carried out safely.
13
How to Use
To adjust airflow direction
(swing)
nanoeX
Indicators
POWER TIMER nanoeX
Upper direction (swing)
· Do not adjust the flap by hand.
- For details operation, refer “To Learn More….”
Lateral direction: · For lateral direction, it is manually adjustable as shown.
Lateral direction
To adjust FAN SPEED and QUIET condition
FAN SPEED: · When FAN AUTO is selected, the fan speed is adjusted
automatically according to the operation mode. · Select the lowest fan speed
to have a low noise operation. QUIET: · This operation reduces airflow noise.
To enjoy fresher and cleaner environment
Not used in normal operation.
Press to turn the Wireless LAN feature ON or OFF.
Press to restore the remote control to default setting.
14
· This operation provides cleaner air, moisturises your skin and hair, and deodorises odours in the room. · Press nanoeTMX to activate this operation, either when the unit is ON or OFF. During nanoeTMX individual operation, the fan speed will follow the remote control setting. · If nanoeTMX is activated before the unit is turned off, the nanoeTMX operation will resume when the unit is turned on. This includes when TIMER ON is set.
· Press the button again to cancel.
Multi
· When the unit is turn off, nanoeTMX individual operation cannot be performed or will be stopped
if other indoor unit is activating HEAT mode.
To reach the desired temperature quickly
POWERFUL
(exit setting)
· This operation is automatically stop after 20 minutes. · Press the button
again to cancel.
To improve humidity and moisture level (Not applicable for Multi split system)
(exit setting)
· This operation reduces air dryness during COOL mode only. · Press the button again to cancel.
To maximise comfort while sleeping
See “To Learn More…” for details.
· This operation provides you with a comfortable environment while sleeping.
It will automatically adjust the sleep pattern temperature during the
activation period.
· The indoor unit indicator will dim when this operation is activated. This is
not applicable if the indicator brightness has been manually dimmed.
· This operation is incorporated with the activation timer (0.5, 1, 2, 3, 4,
5, 6, 7, 8 or 9 hours).
· This operation can be set together with timer. Sleep operation has the
priority over OFF timer.
· This operation can be cancelled by pressing the respective button until the
sleep timer reaches 0.0h.
To set the timer
You can set the timer to turn on and off the unit at 2 different preset time.
1
2
3
1 Select TIMER ON or TIMER OFF. · Each time pressed:
(exit setting)
Example: OFF at 22:00
2 Set the time. 3 Confirm the setting.
· To cancel the timer, press or to select the respective setting or , then
press .
· If the timer has been cancelled manually or due to power failure, you can
restore the timer again. Press or to select the respective setting or , then
press
.
· The nearest timer setting is displayed and will activate in sequence.
· The timer operation follows the clock setting on the remote control and will
repeat daily when timer has been set. For clock setting, refer to Quick Guide.
To connect to a network
· For Wireless LAN Module operation setup, please refer the User’s Manual from
Comfort Cloud App. 1. Sign-in “Panasonic Comfort Cloud” app. 2. Under Menu,
select “User’s Manual”. · If the Wireless LAN LED blinks continuously and you
do not want to use the app, press the Wireless LAN button to turn it off.
Note
,
,
· Can be selected at the same time.
· Can be activated in all modes.
, · Cannot be selected at the same time.
15
To Learn More…
Single Single split system Multi Multi split system
Operation mode
· It is possible to operate the indoor units individually or simultaneously.
The priority of operation is placed on the first unit that turned on. · During
operation, HEAT and COOL modes cannot activate at the same time for different
indoor units. · The power indicator blinks to indicate the indoor unit is
standing by for different operation mode.
AUTO : The POWER indicator blinks at the initial stage.
Single Multi
· The unit will select an operation mode every 10 minutes depending on the
setting and room temperature.
· The unit will select an operation mode every 3 hours depending on the
setting, room and outdoor temperature.
HEAT : The POWER indicator blinks at the initial stage. The unit will take
some time to warm up. · If the HEAT mode system has been locked, and other
operation mode is selected, the indoor unit stops and the POWER indicator
blinks.
COOL : Provides efficient comfort cooling to suit your needs.
DRY : Operates at low fan speed for a gentle cooling operation.
Energy saving temperature setting
You may save energy when operating the unit within the recommended temperature
range.
HEAT : 20.0 °C ~ 24.0 °C / 68 °F ~ 75 °F. COOL: 26.0 °C ~ 28.0 °C / 79 °F ~ 82
°F.
Air flow direction
In COOL/DRY mode: The horizontal flap swings up/down automatically. Once the
temperature is achieved, the horizontal flap is fixed at upper position.
In HEAT mode: The horizontal flap fixed at the predetermined position.
In COOL/DRY mode: The horizontal flap swings up/down automatically.
In HEAT mode: The horizontal flap is fixed to upper position when discharge
air temperature is cold. The horizontal flap swings up-down automatically when
discharge air temperature is warm.
In MILD DRY (Not applicable for Multi split system): When vertical airflow
direction is set to AUTO, it stops at lower position to avoid cold air
contact. However, you can adjust the flap direction manually.
Auto restart control
When power is resumed after a power failure, the operation will restart automatically with the last operation mode and airflow direction. · This control is not applicable when TIMER is set.
16
Operating conditions
Use this air conditioner in the temperature range indicated in the table.
Temperature °C (°F)
Indoor
DBT
WBT
Single split outdoor unit 1 Multi split outdoor unit 2
DBT
WBT
DBT
WBT
COOL
Max. Min.
32 (89.6) 16 (60.8)
23 (73.4) 11 (51.8)
43 (109.4) -10 (14.0)
26 (78.8) –
46 (114.8) -10 (14.0)
26 (78.8) –
Max. 30 (86.0)
–
24 (75.2) 18 (64.4) 24 (75.2) 18 (64.4)
HEAT
Min.
16 (60.8)
–
-15 (5.0) -16 (3.2) -15 (5.0) -16 (3.2)
DBT: Dry bulb temperature, WBT: Wet bulb temperature
1 CU-TZ20ZKE, CU-TZ25ZKE, CU-TZ35ZKE, CU-TZ42ZKE, CU-TZ50ZKE, CU-RZ25ZKE, CU-RZ35ZKE, CU-RZ50ZKE 2 CU-2Z35TBE, CU-2Z41TBE, CU-2Z50TBE, CU-3Z52TBE, CU-3Z68TBE, CU-4Z68TBE, CU-4Z80TBE, CU-5Z90TBE,
CU-2TZ41TBE, CU-2TZ50TBE, CU-3TZ52TBE
17
Cleaning the Air Conditioner
Cleaning has to be carried out at regular intervals to ensure the unit is at
optimal performance. A dirty unit may cause malfunction and you may retrieve
“H 99” error code. Consult an authorised dealer.
· Before cleaning, switch off the power supply and unplug the unit. · Do not
touch the aluminium fin as the sharp parts may cause injury. · Do not use
benzine, thinner or scouring powder. · Use soap ( pH 7) or neutral household
detergent only. · Do not use water hotter than 40 °C / 104 °F.
Indoor unit
Do handle the unit surface with care to avoid scratches by sharp or rough
items (e.g. fingernails, tools, rings, etc). Wipe the unit gently with a soft
damp cloth. The coils and fans should be cleaned periodically by an authorised
dealer.
Front panel
Wash gently and dry. How to remove front panel
2 Pull upward.
Horizontal
1 Raise over horizontal level.
Indoor unit
Front panel
Aluminium fin
AUTO OFF/ON
nanoeX
Air filters
Outdoor unit Clean the debris that surround the unit. Clear any blockage from
the drain pipe.
Air filters Once every 2 weeks · Wash/rinse the filters gently with water to
avoid damaging the surface. · Dry the filters thoroughly under a shade, away
from fire or direct sunlight. · Replace any damaged filters. Remove air filter
Attach air filter
Close it securely 2 Match and push in.
Remove from the unit
Insert into the unit
AUTO OFF/ON
1 Hold
nanoeX
horizontally.
3 Close down. 4 Press both ends of the front panel.
18
Troubleshooting
The following symptoms do not indicate malfunction.
Symptom
Cause
POWER indicator blinks before the unit is switched on.
· This is the preliminary step to prepare for the TIMER operation after it has been set. When Timer is set ON, the unit may start earlier (up to 35 minutes) before the actual set time to achieve the desired temperature on time.
POWER indicator blinks during HEAT mode · The unit is in defrost mode (and AIR SWING has been with no warm air supply (and flap is closed). set to AUTO).
POWER indicator blinks, then stops blinking · The system has been locked to operate in HEAT mode
during COOL/DRY mode.
only.
TIMER indicator is always ON.
· When Timer has been set, the Timer setting repeats daily.
Operation is delayed a few minutes after restarting.
· The delay is a protection to the unit’s compressor.
Cooling/heating capacity is reduced during lowest fan speed setting.
· The lowest fan speed is to have a low noise operation, so cooling/heating capacity may be reduced depending on the condition. Increase the fan speed to increase the capacity.
In COOL mode, when the room temperature reaches near the set temperature, the compressor stops, then the indoor unit fan speed reduced.
· To prevent the room humidty rising. The indoor fan will resume running according to the set fan speed when room temperature increase.
Indoor fan stops occasionally during heating · To avoid unintended cooling effect. operation.
Indoor fan stops occasionally during automatic · This is to help remove the surrounding odour. fan speed setting.
Airflow continues even after operation has stopped.
· To extract the remaining heat from the indoor unit (maximum 30 seconds).
The room has a peculiar odour.
· This may be due to damp smell emitted by the wall, carpet, furniture or clothing.
Cracking sound during operation.
· Changes in temperature caused the unit to expand and contract.
Water flowing sound during operation.
· Refrigerant flow inside the unit.
Mist emerges from indoor unit.
· During cooling operation, the discharged cold air may condense to water vapour.
Outdoor unit emits water or steam.
· During cooling operation, condensation occurs on cold pipes and the condensed water may drip from the outdoor unit.
· During heating operation, frost formed on the outdoor unit during deice cycle melts and is discharged as water or steam.
Discoloration of some plastic parts.
· Discoloration is subjected to the types of materials used in plastic parts. It is accelerated when exposed to heat, sun light, UV light or environmental factors.
Soft buzzing sound from indoor unit during nanoeTMX operation.
· It is normal when the nanoeTMX generator is working. If you are concerned about the sound, cancel the nanoeTMX operation.
Wireless LAN indicator is ON when the unit is OFF.
· The unit’s wireless LAN connection with the router has been activated.
19
Troubleshooting
Check the following before calling for servicing.
Symptom
Check
Operation in HEAT/COOL mode is not working · Set the temperature correctly.
efficiently.
· Close all doors and windows.
· Clean or replace the filters.
· Clear any obstruction at the air inlet and air outlet
vents.
Noisy during operation.
· Check if the unit has been installed at an incline.
· Close the front panel properly.
Remote control does not work.
· Insert the batteries correctly.
(Display is dim or transmission signal is weak.)
· Replace weak batteries.
The unit does not work.
· Check if the circuit breaker is tripped.
· Check if timers have been set.
The unit does not receive the signal from the · Make sure the receiver is not obstructed.
remote control.
· Certain fluorescent lights may interfere with the signal
transmitter. Consult an authorised dealer.
The nanoeTMX indicator at the indoor unit is · Use the remote control to retrieve the error code and
not ON when nanoeTMX is activated.
consult an authorised dealer.
20
When…
The remote control is missing or a malfunction has occurred
1. Raise the front panel.
2. Press AUTO OFF/ON once to use in AUTO mode.
3. To operate forced COOL mode, press AUTO OFF/ON hold until you
AUTO OFF/ON
hear 1 beep, then release. (This operation shall be performed by service
personnel)
4. To operate forced HEAT mode, repeat step 3. Press AUTO OFF/ON until
you hear 2 beep, then release. (This operation shall be performed by
service personnel)
5. Press AUTO OFF/ON again to turn off the unit.
The indicators are too bright
· To dim or restore the indicators’ brightness on the unit, press seconds.
on the remote for 5
Conducting a seasonal inspection after extended period of non-use · Check the
batteries.
· Check that there is no obstruction around the air inlets and outlet vents.
· Use AUTO OFF/ON on the unit to select COOL or HEAT mode. For details, refer
“The remote control is missing or a malfunction has occurred” above. After 15
minutes of operation, it is normal to have the following temperature
difference between the air inlet and outlet vents:
COOL: 8 °C / 14.4 °F HEAT: 14 °C / 25.2 °F
The units will be not used for an extended period · Activate HEAT mode for 2~3
hours to remove any moisture left in the internal parts thoroughly. This is to
prevent mould growth.
· Turn off the power supply and unplug the unit.
· Remove the batteries from the remote control.
NON SERVICEABLE CRITERIAS
TURN OFF THE POWER SUPPLY AND UNPLUG THE UNIT. Then consult an authorised
dealer in the following conditions: · Abnormal noise during operation. ·
Water/foreign particles have entered the remote control. · Water is leaking
from the indoor unit. · The circuit breaker switches off frequently. · The
power cord becomes unnaturally warm. · The switches or buttons are not
functioning properly.
21
Troubleshooting
How to retrieve error codes
If the unit stops and the TIMER indicator blinks, use the remote control to retrieve the error code.
1 Press for 5 seconds
3 Press for 5 seconds to quit checking
2 Press until you hear beep sound, then write down the error code
4 Turn the unit off and inform the error code to an authorised dealer.
· For certain errors, you may restart the unit for limited operation if there are 4 beeps when operation starts.
Diagnostic display
Abnormality/Protection control
Diagnostic display
Abnormality/Protection control
H 00
No memory of failure
H 41
Abnormal wiring or piping connection
H 11 H 12 H 14
H 15
H 16
H 17 H 19 H 21 H 23
H 24 H 25 H 26 H 27 H 28
H 30 H 31 H 32 H 33 H 34
H 35
H 36
H 37 H 38 H 39
Indoor/outdoor abnormal communication
Indoor unit capacity unmatched
Indoor intake air temperature sensor abnormality
Outdoor compressor temperature sensor abnormality
Outdoor current transformer (CT) abnormality
Outdoor suction temperature sensor abnormality
Indoor fan motor mechanism lock
Indoor float switch operation abnormality
Indoor heat exchanger temperature sensor 1 abnormality
Indoor heat exchanger temperature sensor 2 abnormality
Indoor ion device abnormality
Minus ION abnormality
Outdoor air temperature sensor abnormality
Outdoor heat exchanger temperature sensor 1 abnormality
Outdoor discharge pipe temperature sensor abnormality
Abnormal swimming pool sensor
Outdoor heat exchanger temperature sensor 2 abnormality
Indoor/outdoor misconnection abnormality
Outdoor heat sink temperature sensor abnormality
Indoor/outdoor water adverse current abnormality
Outdoor gas pipe temperature sensor abnormality
Outdoor liquid pipe temperature sensor abnormality
Indoor/outdoor mismatch (brand code)
Abnormal indoor operating unit or standby units
H 50 H 51 H 52 H 58 H 59 H 64 H 67 H 70
H 71
H 72 H 79
H 85
H 97 H 98 H 99 F 11 F 16 F 17 F 18 F 87
F 90
F 91 F 93
F 94
F 95
F 96
F 97 F 98 F 99
Ventilation fan motor locked Ventilation fan motor locked Left-right limit switch fixing abnormality Indoor gas sensor abnormality Eco sensor abnormality Outdoor high pressure sensor abnormality nanoe abnormality Light sensor abnormality DC cooling fan inside control board abnormality Abnormality tank temperature sensor Wireless LAN module write error Abnormal communication between indoor & wireless LAN module Outdoor fan motor mechanism lock Indoor high pressure protection Indoor operating unit freeze protection 4-way valve switching abnormality Total running current protection Indoor standby units freezing abnormality Dry circuit blocked abnormality Control box overheat protection Power factor correction (PFC) circuit protection Refrigeration cycle abnormality Outdoor compressor abnormal revolution Compressor discharge pressure overshoot protection Outdoor cooling high pressure protection Power transistor module overheating protection Compressor overheating protection Total running current protection Outdoor direct current (DC) peak detection
- Some error code may not be applicable to your model. Consult an authorised dealer for clarification.
22
Information
Information for Users on Collection and Disposal of Old Equipment and Used
Batteries
These symbols on the products, packaging, and/or accompanying documents mean
that used electrical and electronic products and batteries must not be mixed
with general household waste. For proper treatment, recovery and recycling of
old products and used batteries, please take them to applicable collection
points in accordance with your national legislation. By disposing of them
correctly, you will help to save valuable resources and prevent any potential
negative effects on human health and the environment. For more information
about collection and recycling, please contact your local authority. Penalties
may be applicable for incorrect disposal of this waste, in accordance with
national legislation.
For Business users in the European Union and some other European countries
If you wish to discard electrical and electronic equipment, please contact
your dealer or supplier for further information.
[Information on Disposal in other Countries outside the European Union] These
symbols are only valid in the European Union. If you wish to discard these
items, please contact your local authority or dealer and ask for the correct
Pb method of disposal. Note for the battery symbol (bottom two symbol
examples):
This symbol might be used in combination with a chemical symbol. In this case
it complies with the requirement set by the Directive for the chemical
involved.
WARNING
This symbol shows that this equipment uses a flammable refrigerant. If the
refrigerant is leaked, together with an external ignition source, there is a
possibility of ignition.
This symbol shows that a service personnel should be handling this equipment
with reference to the Installation Instructions.
This symbol shows that the Operation Instructions should be read carefully.
This symbol shows that there is information included in the Operation
Instructions and/or Installation Instructions.
This air conditioner incorporates a device that generates a biocidal product.
Free radicals generated by a device incorporated in the air conditioner have
the capacity to inhibit pollutants, such as certain types of bacteria,
viruses, mould. Active substances : Free radicals generated in situ from
ambient air or water.
Usage : This device function can be operated ON / OFF by “nanoe X” icon
button. Do refer to “How to Use” for more detail.
23
Website: http://www.panasonic.com © Panasonic Corporation 2023
Manufactured by: Panasonic Corporation 1006, Oaza Kadoma, Kadoma City, Osaka
571-8501, Japan
Importer: Panasonic Marketing Europe GmbH Authorized Representative in EU:
Panasonic Testing Centre Winsbergring 15, 22525 Hamburg, Germany
Contact in the UK: Panasonic UK, a branch of Panasonic Marketing Europe GmbH
Maxis 2, Western Road, Bracknell, Berkshire, RG12 1RT
WEB-ACXF55-35141-EN FC0223-1
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>