Danfoss OPTD7 VACON NXP Air Cooled User Guide

June 16, 2024
Danfoss

Danfoss OPTD7 VACON NXP Air Cooled

Danfoss-OPTD7-VACON-NXP-Air-Cooled-PRODUCT

Product Information

Specifications

Technical item or function Technical data Description
Transformer primary/input voltage range Min 380 V AC -15% Max 690 V AC +15%
Transformer ratio primary:secondary 60:1
Transformer secondary/output voltage range 14 V rms Between the terminals

L1/L2/L3
Input impedence| L1/L2 = 50 k
L1/L3 = 25 k
L2/L3 = 25 k
L3 is internal virtual common|
Cable recommendation| Max 1.5 mm2, shielded| From transformer output to OPTD7 option board
Measurement resolution| 10 bit|
Voltage measurement accuracy| 0.2%| For D7 board measurement, transformer not included
Frequency measurement accuracy| Accuracy:|

Product Overview

Intended Use
The OPTD7 option board is designed for line voltage measurement purposes.

Transformer Compatibility
The OPTD7 option board comes with a transformer suitable for voltage range 380-690 V. However, it cannot be used with pulsewidth modulated (PWM) voltage input. If the input voltage to be measured is not within the voltage range, a custom-built transformer can be used. The transformation ratio parameter can be adjusted based on the transformer’s primary to secondary ratio. Please refer to the specification section for more information.

Measurement Signal Limit
The measurement signal connected to the OPTD7 option board should not exceed 14.26 Vrms.

Product Usage Instructions

Installation

  1. Ensure that the power supply is turned off before installation.
  2. Connect the transformer output to the OPTD7 option board using a shielded cable with a maximum cross-sectional area of 1.5 mm2.
  3. Make sure the transformer is compatible with the voltage range of 380-690 V (excluding PWM voltage input).
  4. If using a custom-built transformer, adjust the transformation ratio parameter as per the transformer’s primary to secondary ratio.

Line Voltage Measurement

  1. Power on the equipment.
  2. Ensure that the measurement signal connected to the OPTD7 option board does not exceed 14.26 Vrms.
  3. The OPTD7 option board will provide accurate voltage measurements with a resolution of 10 bits and an accuracy of 0.2%.

FAQ

Can I dispose of the equipment containing electrical components with domestic waste?
No, you should not dispose of equipment containing electrical components together with domestic waste. Please collect it separately in accordance with local and currently valid legislation.

Introduction

Purpose of the Operating Guide
This operating guide provides the information on the VACON® NX Line Voltage Measurement OPTD7 Option Board used in VACON® NXP drives. It is intended for qualified personnel. Read and follow the instructions to use the drive safely and professionally.

Additional Resources
Other resources are available to understand advanced AC drive functions and programming.

  • The VACON® NX manuals provide greater detail on working with parameters and show many application examples.
  • The VACON® NX I/O Boards User Manual gives more information on the I/O boards and their installation.
  • Instructions for operation with option boards and other optional equipment. Supplementary publications and manuals are available from Danfoss.

Disposal
Do not dispose of equipment containing electrical components together with domestic waste. Collect it separately in accordance with local and currently valid legislation.

Product Overview

Intended Use
OPTD7 is an AC sinusoidal voltage measurement option board used in VACON® NXP drives. VACON® NXP drive measures the line voltage, frequency and voltage angle information using this board. VACON® NXP can compare this information with its output volt-age angle when it is running. This feature can be used to develop applications for different purposes using NC61131-3 application programming tool.

Danfoss-OPTD7-VACON-NXP-Air-Cooled-FIG- \(1\)

Illustration 1: OPTD7 Option Board Layout

The OPTD7 option board is delivered with the transformer which is suitable for voltage range 380-690 V.

Illustration 2: Transformer

NOTE! The transformer can not be used with the pulse width modulated (PWM) voltage input.

It is possible to use custom built transformer when the input voltage to be measured is not within the voltage range 380-690 V. The transformation ratio parameter can be adjusted as per the transformer primary to secondary ratio. Please refer to specification sec-tion for more information.

NOTICE
The measurement signal connected into the OPTD7 option board can not exceed 14.26 Vrms. The OPTD7 option board can only be used in slot C of VACON® NXP drive.

Type ID : VB00379

Specification

Table 1 : OPTD7 Option Board (VB00379 based on revision X)

Technical item or function Technical data Description
Transformer primary/input voltage range Min 380 V AC -15%

Max 690 V AC +15%

|
Transformer ratio primary:secondary| 60:1|
Transformer secondary/output voltage range| 14 V rms| Between the terminals L1/L2/L3
Input impedence| L1/L2 = 50 kΩ L1/L3 = 25 kΩ L2/L3 = 25 kΩ| L3 is internal virtual common
Cable recommendation| Max 1.5 mm2, shielded| From transformer output to OPTD7 option board
Measurement resolution| 10 bit|
Voltage measurement accuracy| 0.2%| For D7 board measurement, transformer not included
Frequency measurement accuracy| Accuracy: <10 mHz

Resolution: 10 mHz

| In frequency range 45-65 Hz

OPTD7 Option Board Menu

Parameters

  • Transformer ratio: Transfer ratio of the measurement transformer.
  • Default value : 60.00(690 V/11.5 V)

In case using other measurement transformers than the one supplied with the board, the voltage measurement shows correct num-bers by setting the transformer ratio right.

Monitoring

  • Line voltage: Main voltage
  • Line frequency : Main frequency(including sign)

Application Examples

Line Synchronization

Features:

  • Frequency and phase angle synchronization between VACON® NXP drive and mains supply. Thus smooth Direct On Line (DOL) transfer of motor to the mains is possible with minimal peak current from the mains supply.
  • External synchronizer is not required.
  • Smooth transfer back to inverter with fast catch on fly feature.
  • Changeover activation possible through either I/O, fieldbus or keypad.
  • Compensation parameters for the changeover circuit delay and offset angle to the synchronization.
  • Indication for ‘Line Synch OK’ programmable to digital outputs.
  • Mains voltage and frequency monitoring on keypad and PC tool.
  • Applicable to any size of LV (low voltage) motor and MV (medium voltage) motor through step up transformer.
  • OPTD7 option board is used for mains supply voltage measurement as shown in Illustration 3.

Danfoss-OPTD7-VACON-NXP-Air-Cooled-FIG- \(4\)

Illustration 3: Block Diagram for Direct ON Line Transfer of Motor

  • Mains supply
  • Measurement transformer
  • VACON AC drive
  • Drive contactor
  • Bypass contactor

See Illustration 4 for the connection diagram example for OPTD7 option board and voltage transformer in Line Synchronization applications.

Operating Guide

Danfoss-OPTD7-VACON-NXP-Air-Cooled-FIG- \(5\)

Illustration 4: Connection in Line Synchronization Applications

Fundamental Front End (NXF)
OPTD7 option board is used to feedback the main supply voltage and frequency with VACON® NXF, fundamental front end. Funda-mental front end is IGBT based regenerative supply unit. It is used to supply one or multiple inverters in a common DC bus system. For more details, please refer to www.danfoss.com or contact Danfoss Sales Support.
See the connection of OPTD7 option board and voltage transformer in FFE applications in Illustration 5.

Danfoss-OPTD7-VACON-NXP-Air-Cooled-FIG- \(6\)

Illustration 5: Connection in FFE Applications

Vacon Ltd, Member of the Danfoss Group Runsorintie 7 FIN-65380 Vaasa www.danfoss.com

Danfoss can accept no responsibility for possible errors in catalogs, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

Danfoss A/S © 2023.03

AQ442338036238en-000201 / UD01056

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals