Danfoss OPTCG VACON NXP Air Cooled Instruction Manual
- June 16, 2024
- Danfoss
Table of Contents
- Danfoss OPTCG VACON NXP Air Cooled
- Product Information
- Specifications
- Introduction
- Product Usage Instructions:
- FAQ
- INTRODUCTION
- ETHERNET BOARD TECHNICAL DATA
- INSTALLATION
- COMMISSIONING
- | Name| Default| Range| Description
- PROFINET IO
- APPENDIX
- License for LWIP
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Danfoss OPTCG VACON NXP Air Cooled
Product Information
Vacon NX AC Drives with OPTCP Profinet Option Board
Specifications
- Board Name: OPTCP
- Ethernet Connections: RJ-45 connector
- Interface: Shielded Twisted Pair (STP) CAT5e
- Transfer Cable Speed: 10 / 100 Mb
- Duplex: Half / Full
- Default IP Address: 192.168.0.10
- Protocol: Profinet I/O
- Humidity: 8%
Introduction
Vacon NX frequency converters can be connected to Ethernet using an Ethernet fieldbus board OPTCP. The OPTCP can be installed in board slots D or E.
Every appliance connected to an Ethernet network has two identifiers; a MAC address and an IP address. The MAC address (Address format: xx:xx:xx:xx:xx:xx) is unique to the appliance and cannot be changed. The Ethernet board’s MAC address can be found on the sticker attached to the board or by using the Vacon IP tool software NCIPConfig. You can find the software installation at www.vacon.com.
In a local network, IP addresses can be defined by the user as long as all units connected to the network are given the same network portion of the address. For more information about IP addresses, contact your Network Administrator. Overlapping IP addresses cause conflicts between appliances. For more information about setting IP addresses, see Section 3, Installation.
WARNING!
Internal components and circuit boards are at high potential when the
frequency converter is connected to the power source. This voltage is
extremely dangerous and may cause death or severe injury if you come into
contact with it.
Product Usage Instructions:
Installation:
To install the OPTCP Ethernet board, follow these steps:
- Ensure that the frequency converter is disconnected from the power source.
- Locate board slots D or E on the frequency converter.
- Insert the OPTCP board into the selected slot until it is securely in place.
- Connect the Ethernet cable to the RJ-45 connector on the OPTCP board.
- Connect the other end of the Ethernet cable to your Ethernet network.
- Ensure that all units connected to the network have unique IP addresses within the same network portion.
- Reconnect the frequency converter to the power source.
Using the MAC Address:
The MAC address of the Ethernet board can be found on the sticker attached
to the board or by using the Vacon IP tool software NCIPConfig. This address
is unique to the board and cannot be changed. Use this MAC address for network
identification or configuration purposes.
Setting IP Addresses:
In a local network, IP addresses can be defined by the user as long as all
units connected to the network are given the same network portion of the
address. To set IP addresses for the connected units, follow these steps:
- Contact your Network Administrator for information about IP address settings.
- Ensure that all units connected to the network have unique IP addresses within the same network portion.
- Avoid overlapping IP addresses to prevent conflicts between appliances.
FAQ
Q: Where can I find the MAC address of the Ethernet board?
A: The MAC address can be found on the sticker attached to the board or by
using the Vacon IP tool software NCIPConfig.
Q: Can I change the MAC address of the Ethernet board?
A: No, the MAC address is unique to the board and cannot be changed.
Q: What should I do if there are conflicts between appliances due to
overlapping IP addresses?
A: Contact your Network Administrator for assistance in resolving IP
address conflicts.
INTRODUCTION
Vacon NX frequency converters can be connected to Ethernet using an Ethernet
fieldbus board OPTCP.
The OPTCP can be installed in board slots D or E.
Every appliance connected to an Ethernet network has two identifiers; a MAC
address and an IP address. The MAC address (Address format: xx:xx:xx:xx:xx:xx
) is unique to the appliance and cannot be changed. The Ethernet board’s MAC
address can be found on the sticker attached to the board or by using the
Vacon IP tool software NCIPConfig. You can find the software installation at
www.vacon.com
In a local network, IP addresses can be defined by the user as long as all
units connected to the network are given the same network portion of the
address. For more information about IP addresses, contact your Network
Administrator. Overlapping IP addresses cause conflicts between appliances.
For more information about setting IP addresses, see Section 3, Installation.
WARNING! Internal components and circuit boards are at high potential when the frequency converter is connected to the power source. This voltage is extremely dangerous and may cause death or severe injury if you come into contact with it.
ETHERNET BOARD TECHNICAL DATA
Overview
General | Board name | OPTCP |
---|
Ethernet connec-
tions
| Interface| RJ-45 connector
Communications| Transfer cable| Shielded Twisted Pair (STP) CAT5e
Speed| 10 / 100 Mb
Duplex| half / full
Default IP-address| 192.168.0.10
Protocol| Profinet I/O
Environment| Ambient operating temperature| –10°C…50°C
Storing tempera-
ture
| –40°C…70°C
Humidity| <95%, no condensation allowed
Altitude| Max. 1000 m
Vibration| 0.5 G at 9…200 Hz
Safety| | Fulfils EN50178 standard
Table 1. Ethernet board technical data
LED indications
Using the “Node Flashing Test” function you can determine to which device you are directly con-nected. For example in Siemens S7, by using the menu command “PLC > Diagnostics/Setting > Node Flashing Test…” you can identify the station connected directly to the PG/PC by the FORCE LED that flashes.
Ethernet
Common-use cases of Ethernet devices are ‘human to machine’ and ‘machine to machine’. Basic features of these two cases are presented in the pictures below.
- Human to machine (Graphical User interface, relatively slow communication) Note! NCDrive can be used in NXS and NXP drives via Ethernet. In NXL drives this is not possible.
- Machine to machine (Industrial environment, fast communication)
Connections and wiring
The Ethernet board supports 10/100Mb speeds in both Full- and Half-duplex
modes. However, using Profinet requires the Full-duplex mode and the
100-megabit speed. The boards must be connected to the Ethernet network with a
Shielded Twisted Pair (STP) CAT-5e cable. Use a so-called crossover cable if
you want to connect the Ethernet option board directly to the master device.
Use only industrial standard components in the network and avoid complex
structures to minimize the length of response time and the amount of incorrect
dispatches.
More information on Ethernet can be found at
www.odva.org.
INSTALLATION
Installing the Ethernet Option Board in a Vacon NX Unit
NOTE MAKE SURE THAT THE FREQUENCY CONVERTER IS SWITCHED OFF BEFORE AN OPTION OR FIELDBUS BOARD IS CHANGED OR ADDED!
NCDrive
NCDrive software can be used with the Ethernet board in NXS and NXP drives.
NOTE! Does not work with NXL
NCDrive software is recommended to be used in LAN (Local Area Network) only.
NOTE! If OPTCI Ethernet Option board is used for NC Tools connection, like
NCDrive, the OPTD3 board can not be used.
NOTE! NCLoad does not work via Ethernet. See NCDrive help for further
information
IP Tool NCIPConfig
To begin using the Vacon Ethernet board, you need to set an IP address. The
factory default IP ad dress is 192.168.0.10. Before connecting the board to
the network, its IP addresses must be set according to the network. For more
information about IP addresses, contact your network administrator.
You need a PC with an Ethernet connection and the NCIPConfig tool installed to
set the Ethernet board’s IP addresses. To install the NCIPConfig tool, start
the installation program from CD or download it from
www.vacon.com website. After starting the installation
program, follow the on-screen instructions.
Once the program is installed successfully, you can launch it by selecting it
in the Windows Start menu. Follow these instructions to set the IP addresses.
Select Help –> Manual if you want more information about the software
features.
-
Step 1. Connect your PC to the Ethernet network with an Ethernet cable. You can also connect the PC directly to the device using a crossover cable. This option may be needed if your PC does not support Automatic crossover function.
-
Step 2. Scan network nodes. Select Configuration –> Scan and wait until the devices connected to the bus in the tree structure are displayed to the left of the screen.
NOTE! Some switches block broadcast messages. In this case, each network node must be scanned separately. -
Step 3. Set names. Select the cell in column ‘Node’ and enter the name of the node.
-
Step 4. Set IP addresses. Change the node’s IP settings according to the network IP settings. The program will report conflicts with a red color in a table cell.
-
Step 5. Send configuration to boards. In the table view, check the boxes for boards whose configuration you want to send and select Configuration, then Configure. Your changes are sent to the network and will be valid immediately.
NOTE! Only A-Z, a-z and 0-9 symbols can be used in the drive name, no special characters, or Scandinavian letters (ä, ö, etc.)! The drive name can be freely formed using the allowed characters.
Update OPTCP Option Board program with the NCIPConfig Tool
In some cases it may be necessary to update the option board’s firmware.
Differing from other Vacon option boards, the Ethernet option board’s firmware
is updated with the NCIPConfig tool.
To start the firmware update, scan the nodes in the network according to the
instructions in section 3.2. Once you can see all nodes in the view, you can
update the new firmware by clicking the VCN packet field in NCIPCONFIG ‘s
table view on the right.
NOTE! The PC’s IP address must be chosen in the same IP address space as the
Ethernet board’s.
After clicking the VCN packet field, a file open window where you can choose a new firmware packet is displayed.
Select the desired packet and click Open.
NOTE!
Do not do a power up cycle after downloading the option board software or
installing a new option board to the drive within 1 minute. This may cause the
option board to go to “Safe Mode”. This situa-tion can only be solved by re-
downloading the software. The Safe Mode triggers a fault code (F54). The Board
slot error F54 may also appear due to a faulty board, a temporary malfunction
of the board or disturbance in the environment.
Configure Option board parameters
These features are available from NCIPConfig tool version 1.6.
In the tree-view, expand the folders until you reach the board parameters.
Slowly double-click the parameter (Comm. Time-out in figure below) and enter
new value. New parameter values are auto-matically sent to the option board
after the modification is complete.
NOTE! If the fieldbus cable is broken at the Ethernet board end or removed, a fieldbus error is im-mediately generated.
Example with Siemens PLC
- Create project
- Insert station
- Double-click hardware to open HW config window.
- Insert rail
- Insert power supply
- Insert CPU
- Change IP address and select subnet by clicking New.
- Click OK
- Click OK
- Now configuration should look like this
- Drag and drop OPTCP to Profinet IO system
- Select communication profile
- Change Optioncard properties
- Verify Device Name.
- Close window.
- Change IO cycle to 16 ms (minimum) or greater.
COMMISSIONING
The Vacon Ethernet board is commissioned with the control keypad by giving values to appropriate parameters in menu M7 (or with NCIPConfig tool, read chapter IP Tool NCIPConfig). Keypad com-missioning is only possible with NXS and NXP series AC drives. AC drives of the NXL series can only be commissioned with the NCIPConfig tool.
Expander board menu (M7)
The Expander board menu makes it possible for the user to see which expander
boards are con-nected to the control board and to reach and edit the
parameters associated with the expander board.
Enter the following menu level (G#) with the Menu button right. At this level,
you can browse trough slots A to E with the Browser buttons to see what
expander boards are connected. On the lowermost line of the display you see
the number of parameter groups associated with the board. If you still press
the Menu button right once you will reach the parameter group level where
there are one group in the Ethernet board case: Parameters. A further press on
the Menu button right takes you to Parameter group.
Profinet parameters
| Name| Default| Range| Description
---|---|---|---|---
1| Comm. Timeout| 10| 0…255 s|
2| IP Part 1| 192| 1…223| IP Address Part 1
3| IP Part 2| 168| 0…255| IP Address Part 2
4| IP Part 3| 0| 0…255| IP Address Part 3
5| IP Part 4| 10| 0…255| IP Address Part 4
6| SubNet Part 1| 255| 0…255| Subnet Mask Part 1
7| SubNet Part 2| 255| 0…255| Subnet Mask Part 2
8| SubNet Part 3| 0| 0…255| Subnet Mask Part 3
9| SubNet Part 4| 0| 0…255| Subnet Mask Part 4
10| DefGW Part 1| 192| 0…255| Default Gateway Part 1
11| DefGW Part 2| 168| 0…255| Default Gateway Part 2
12| DefGW Part 3| 0| 0…255| Default Gateway Part 3
13| DefGW Part 4| 1| 0…255| Default Gateway Part 4
14| InputAssembly| –| –| NOT USED in Profinet
15| OutputAssembly| –| –| NOT USED in Profinet
Table 2. Ethernet parameters
IP Address
IP is divided into 4 parts. (Part = Octet) Default IP Address is 192.168.0.10.
Communication timeout
Defines how much time can pass from the last received message from the Master
Device before fieldbus fault is generated. Communication timeout is disabled
when given the value 0. The commu-nication timeout value can be changed from
the keypad or with NCIPConfig tool (see chapter IP Tool NCIPConfig).
NOTE!
If the fieldbus cable is broken at the Ethernet board end or removed a
fieldbus error is immediately generated.
All Ethernet parameters are saved to the Ethernet board (not to the control
board). If the Ethernet board is replaced by a new one you must re-configure
the new Ethernet board. Option board para-meters can also be saved to the
keypad using the NCIPConfig tool or the NCDrive.
Start-up test
In the AC drive application:
Choose Fieldbus (Bus/Comm) as the active control place (see Vacon NX User’s
Manual, Chapter 7.3.3).
In the Master software:
- Set Control Word value to 0hex.
- Set Control Word value to 47Ehex.
- Set Control Word value to 47Fhex.
- Frequency converter status is RUN.
- Set Reference value to 5000 (=50.00%).
- The Actual value is 5000 and the frequency converter output frequency is 25.00 Hz.
- Set Control Word value to 477hex.
- Frequency converter status is STOP.
PROFINET IO
PROFINET is the Ethernet-based automation standard of PROFIBUS International for the implementation of an integrated and consistent automation solution based on Industrial Ethernet. PROFINET supports the integration of simple distributed field devices and time-critical applications in (switch-ed) Ethernet communication, as well as the integration of component-based distributed automation systems for vertical and horizontal integration of networks.
**Vendor profile
**
In vendor mode there are three PPO types; PPO3,PPO4,PPO6. These PPO types should have same functionality than Vacon NX Profibus. In PPO mode control word and status word goes though state machine.
Control word (Vendor profile)
The Control command for the state machine (see Figure 2) The state machine
describes the device status and the possible control sequence of the frequency
converter.
The control word is composed of 16 bits that have the following meanings:
Table 3.
Bit | Description |
---|---|
Value = 0 | |
0 | STOP 1 (by ramp) |
1 | STOP 2 (by coast) |
2 | STOP 3 (by ramp) |
3 | RUN DISABLE |
4 | No action |
5 | No action |
6 | No action |
7 | No action |
8 | No action |
9 | No action |
10 | Disable fieldbus control |
11 | Fieldbus DIN1=OFF |
12 | Fieldbus DIN2=OFF |
13 | Fieldbus DIN3=OFF |
14 | Fieldbus DIN4=OFF |
15 | Fieldbus DIN5=OFF |
Status word (Vendor profile)
Information about the status of the device and messages is indicated in the
Status word. The Status word is composed of 16 bits that have the following
meanings:
Bit | Description |
---|---|
Value = 0 | |
0 | Not Ready (initial) |
1 | Not Ready |
2 | DISABLE |
3 | NO FAULT |
4 | STOP 2 |
5 | STOP 3 |
6 | START ENABLE |
7 | No Warning |
8 | Reference ≠ Actual value |
9 | Fieldbus control OFF |
10 | Not used |
11 | Not used |
12 | FC stopped |
13 | FC not ready |
14 | Not used |
15 | Not used |
Table 4.
Comes straight from the frequency converter **Bits of the State Machine
State Machine
The state machine describes the device status and the possible control
sequence of the frequency converter. The state transitions can be generated by
using the “Control word”. The “Status word” indicates the current status of
the state machine. The modes INIT, STOP, RUN and FAULT correspond to the
actual mode of the Frequency converter.
NOTE! Always set CW bit0 to 0 after fault reset before proceeding!
Reference
This is the reference 1 to the frequency converter. Used normally as Speed
reference.
The allowed scaling is –10000…10000. In the application, the value is scaled
in percentage of the fre-quency area between set minimum and maximum
frequency.
- -10000 = 100,00 % (Direction reverse)
- 0 = 0,00 % (Direction forward)
- 10000 = 100,00 % (Direction forward)
Actual value
This is the actual value from the frequency converter. Value between -10000…10000. In the applica-tion, the value is scaled in percentage of frequency area between set minimum and maximum fre-quency.
- -10000 = 100,00 % (Direction reverse)
- 0 = 0,00 % (Direction forward)
- 10000 = 100,00 % (Direction forward)
Process data in
ProcessData Master -> Slave
The Master can write max. 8 additional setting values to the device with the
help of the Process Data. How these setting values are used is totally
dependent on the application in use.
Process data out
ProcessData Slave -> Master
The master can read the frequency converter’s actual values using the process
data variables. Depending on the used application, the contents are either
standard or can be selected with a para-
meter.
Bypass profile
In BYPASS mode there are three types.
Control Word (Bypass profile)
The meanings of the Control Word bits is application-dependent.
Status Word (Bypass profile)
The meanings of the Status Word bits are application-dependent.
Profidrive profile
The PROFIDRIVE profile has been jointly defined by drive manufacturers. The profile specifies aspects of drive parameterization and how the setpoints and actual values should be transmitted. This makes drives in a fieldbus vendor- independent and possible to be replaced by a drive from a different vendor. The profile contains specifications needed for speed control and positioning and it specifies the basic drive functions while leaving sufficient freedom for application-specific expansions and further developments.
Application class 1
The Profinet board supports Application Class 1 of the Profidrive profile
(version 4.1 ). Application Class 1 defines Standard Telegram 1. The standard
telegrams have the following structure:
I/O data num- ber | 1 | 2 |
---|---|---|
Setpoint | STW1 | NSOLL_A |
Actual value | ZSW1 | NIST_A |
Table 5.
STW1
STW1 is the Profidrive profile’s control word. The control word is for
controlling the drive from a fieldbus. It is sent by the fieldbus master to
the drive. The drive switches between its states accord-ing to the bit-coded
instructions on the control word. Because the STW1 and the drive’s own control
words are different the STW1 has to be written to Drive Interface through
state machine. Some of the STW1 bits go straight to Drive Interface.
The STW1 is composed of 16 bits that have the following meanings:
Bits | Description |
---|---|
Value = 0 | |
0 | OFF |
1 | Coast stop (No OFF2 / OFF2) |
2 | Quick stop (No OFF3 / OFF3) |
3 | Disable operation |
4 | Reset ramp generatorb |
5 | Freeze ramp generatorb |
6 | Disable setpoint |
7 | |
8 | Jog 1 OFFa |
9 | Jog 2 OFFa |
10 | No control by PLC |
11 | Device-specific |
12-15 | Device-specific |
a Optional; depends on application
b Depends on application
ZSW1
ZSW1 is the Profidrive profile’s status word. Status word indicates
information about the status of the device. Also messages are indicated in the
Status word. The ZSW1 Status word is composed of 16 bits that have the
following meanings:
Bits | Description |
---|---|
Value = 0 | |
0 | Not ready to switch on |
1 | Not ready to operate |
2 | Operation disabled |
3 | No fault |
4 | Coast stop activated (No OFF2 / OFF2) |
5 | Quick stop activated (No OFF3 / OFF3) |
6 | Switching on not inhibited |
7 | No warning |
8 | Speed error out of tolerance range |
9 | No control requested |
10 | f or n not reached |
11 | Device-specific |
12 | Device-specific |
13 | Device-specific |
14-15 | Device-specific |
NSOLL_A
NSOLL_A is the reference to the drive. It is used normally as Speed reference.
Reference is a 16-bit word containing a sign bit and a 15-bit integer. A
negative reference (indicating reversed direction of rotation) is formed by
calculating the two’s complement from the corresponding positive reference.
The allowed scaling is –10000…10000. In the drive application, the value is
scaled in percentage of the frequency area between set minimum and maximum
frequency.
- -10000 = 100,00 % (Direction reverse)
- 0 = 0, 00 % (Direction forward)
- 10000 = 100,00 % (Direction forward)
NIST_A
NIST_A is the actual value from the frequency converter. It contains values
between -10000…10000. In the application, the value is scaled in percentage of
frequency area between set minimum and maximum frequency.
- -10000 = 100,00 % (Direction reverse)
- 0 = 0, 00 % (Direction forward)
- 10000 = 100,00 % (Direction forward)
State Machine
The state machine describes the device status and the possible control
sequence of the frequency converter. The state transitions can be generated by
using the “Control word”. The “Status word” indicates the current status of
the state machine. The modes INIT, STOP, RUN and FAULT corres-pond to the
actual mode of the Frequency converter
Additional Process data in
ProcessData Master -> Slave
The Master can write max. 8 additional setting values to the device with the
help of the Process Data. How these setting values are used is totally
dependent on the application in use.
Additional Process data out
ProcessData Slave -> Master
The master can read the frequency converter’s actual values using the process
data variables. Depending on the used application, the contents are either
standard or can be selected with a parameter.
Parameter channel
The Parameter channel can be used to access the Drive’s parameters and the PROFIDRIVE’s parameters.
Figure 4. Data flow for Base Mode Parameter Access
Parameters are read/written with function blocks in Siemens PLC. Function
block SFB 52 “RDREC” is for reading and SFB53 “WRREC” for writing. See more
detailed information in document Commu-nication Function Blocks for PROFIBUS
and PROFINET on www.profibus.com.
Parameter Access Service | Index |
---|---|
Base Mode Parameter – Global | 0xB02F |
Global Parameters
Global parameters are related to the complete device.
Supported parameter accesses:
- Request parameter value, single
- Change parameter value, single
- Request parameter value, multi-parameter
- Change parameter value, multi-parameter
- Request parameter value, several array elements
- Change parameter value, several array elements
- Change parameter value, several array elements, Format Byte
It is possible to read and write parameters from and to the drive. In order to process them through the Base Mode Parameter Access mechanism, you should:
- set requested PNU to 10001 (0x2711)
- set requested subindex with the drive parameter ID
NOTE: Parameters which are read from the drive have always the format set to “Word” – 0x42.
Error
Value
| Meaning
---|---
0x00| Impermissible PNU
0x01| Cannot change value
0x02| Low or high limit exceeded
0x03| Faulty subindex
0x04| No array
0x05| Incorrect data type
0x06| Setting not permitted
0x07| Cannot change description
0x09| No description
0x0B| No operation priority
0x0F| No text array available
0x11| Cannot execute the request. Rea- son not specified
0x14| Value impermissible
0x15| Response too long
0x16| Parameter address impermissi-
ble
0x17| Illegal format
0x18| Number of values inconsistent
0x19| Axis/DO nonexistent
0x20| Cannot change text
|
0x65| Invalid Request Reference
0x66| Invalid Request ID
0x67| Invalid Axis number / DO-ID
0x68| Invalid number of parameters
0x69| Invalid attribute
0x6B| Request too short
Table 6 PROFIDRIVE parameter request error codes
PROFIDRIVE’s profile-specific parameters
PNU | Signification | Datatype |
---|---|---|
922 | Telegram Selection | |
930 | Operating Mode | |
944 | Fault Message Counter | |
947 | Fault Number | |
950 | Scaling of the Fault Buffer | |
964 | Drive Unit Identification | |
965 | Profile Identification Number | |
975 | DO Identification |
980
to 989
| __
Number List of Defined Parameter
|
Request Header, Meaning of the fields
Field | Meaning | Range |
---|---|---|
Request Reference | Master sets unique identification for every query. | 1…255 |
Request ID | Defines the type of the message. | 0x01 = Request Parame- ter |
0x02 = Change Parameter
DO-ID| Set to “1”.| 0…255
Number of Parameters| Specifies the number of parame- ters in request.| 1…38
Attribute| Type of object being accessed.| 0x10 = Value
Number of Elements| Number of array elements or length of string accessed.|
1…234
Parameter Number| Addresses of the accessed PROFI- drive parameter.| 1…65535
(0x2711) Access to drive parameters
Subindex| Addresses of the first array ele- ment of the accessed parameter.|
0…65535
Format| Format of the request.| 0x00 = Reserved
0x01 – 0x36 = Data types 0x37 – 0x3F = Reserved 0x40 = Zero
0x41 = Byte 0x42 = Word
0x43 = Double word 0x44 = Error
0x45 – 0xFF = Reserved
Number of Values| Number of following values or number of following data type
ele- ments.| 0…234
Error Number| See Table 6 on page 36.|
Response Header, Meaning of the fields
Field | Meaning | Range |
---|---|---|
Request Reference | Mirrored from request. | 1…255 |
Response ID | Slave’s response. | 0x01 = Request OK 0x02 = Change OK 0x81 = |
Request Failed 0x82 = Change Failed
DO-ID| Mirrored from request.| –
Number of Parame- ters| Number of parameters in response.| 1…38
Format| Data type of response value.| 0x00 = Reserved
0x01 – 0x36 = Data types 0x37 – 0x3F = Reserved 0x40 = Zero
0x41 = Byte 0x42 = Word
0x43 = Double word 0x44 = Error
0x45 – 0xFF = Reserved
Number of Values| Number of values in response.| 1…234
Value| Value of request.| –
Parameter data transfer examples
Reading parameter:
Request parameter value, single:
- 05 = Request Reference
- 01 = Request ID
- 01 = DO-ID
- 01 = No. of parameters
- 10 = Attribute
- 01 = No. of elements
- 2711 = Parameter number (0x2711 Request Drive Parameters) 0065 = Subindex (0x65 = ID 101 Min Frequency)
Response:
- 05 = Request Reference. Mirrored 01 = Request ID
- 01 = DO-ID. Mirrored
- 01 = No. of parameters. Mirrored 42 = Format (42 = word)
- 01 = No. of values
- 0000 = Value
Request parameter value, single:
- 06 = Request Reference
- 01 = Request ID
- 01 = DO-ID
- 01 = No. of parameters
- 20 = Attribute
- 01 = No. of elements
- 2711 = Parameter number (0x2711 Request Drive Parameters)
- 0065 = Subindex (0x65 = ID 101 Min Frequency)
Error Response:
-
06 = Request Reference. Mirrored
-
81 = Request ID (Bit7 = 1, Error Response)
-
01 = DO-ID. Mirrored
-
01 = No. of parameters. Mirrored
-
44 = Format (44 = word)
-
01 = No. of values
-
0009 = Error Value (9 = No Description data available)
APPENDIX
Process Data OUT (Slave- > Master)
The fieldbus master can read the frequency converter’s actual values using
process data variables. Basic, Standard, Local/Remote, Multi-Step, PID control
and Pump and fan control applications use process data as follows:
Data | Value | Unit | Scale |
---|---|---|---|
Process data OUT 1 | Output Frequency | Hz | 0,01 Hz |
Process data OUT 2 | Motor Speed | rpm | 1 rpm |
Process data OUT 3 | Motor Current | A | 0,1 A |
Process data OUT 4 | Motor Torque | % | 0,1 % |
Process data OUT 5 | Motor Power | % | 0,1 % |
Process data OUT 6 | Motor Voltage | V | 0,1 V |
Process data OUT 7 | DC link voltage | V | 1 V |
Process data OUT 8 | Active Fault Code | – | – |
The Multipurpose application has a selector parameter for every Process Data. The monitoring val-ues and drive parameters can be selected using the ID number (see NX All in One Application Ma-nual, Tables for monitoring values and parameters). Default selections are as in the table above.
Process Data IN (Master - > Slave)
ControlWord, Reference and Process Data are used with All-in One applications
as follows:
Basic, Standard, Local/Remote, Multi-Step applications
Data | Value | Unit | Scale |
---|---|---|---|
Reference | Speed Reference | % | 0.01% |
ControlWord | Start/Stop Com- mand |
Fault reset Com-
mand
| –| –
PD1 – PD8| Not used| –| –
Multipurpose control application
Data | Value | Unit | Scale |
---|---|---|---|
Reference | Speed Reference | % | 0.01% |
ControlWord | Start/Stop Command Fault reset Command | – | – |
Process Data IN1 | Torque Reference | % | 0.1% |
Process Data IN2 | Free Analogue INPUT | % | 0.01% |
Process Data IN3 | Adjust Input | % | 0.01% |
PD3 – PD8 | Not Used | – | – |
PID control and Pump and fan control applications
Data | Value | Unit | Scale |
---|---|---|---|
Reference | Speed Reference | % | 0.01% |
ControlWord | Start/Stop Command Fault reset Command | – | – |
Process Data IN1 | Reference for PID control- ler | % | 0.01% |
Process Data IN2 | Actual Value 1 to PID con- troller | % | 0.01% |
Process Data IN3 | Actual Value 2 to PID con- troller | % | 0.01% |
PD4–PD8 | Not Used | – | – |
License for LWIP
Copyright (c) 2001, 2002 Swedish Institute of Computer Science.
All rights reserved.
Redistribution and use in source and binary forms, with or without
modification, are permitted provided that the following conditions are met:
- Redistributions of source code must retain the above copyright notice, this list of conditions and the following disclaimer.
- Redistributions in binary form must reproduce the above copyright notice, this list of conditions and the following disclaimer in the documentation and/or other materials provided with the distribu-tion.
- The name of the author may not be used to endorse or promote products derived from this software without specific prior written permission.
THIS SOFTWARE IS PROVIDED BY THE AUTHOR “AS IS” AND ANY EXPRESS OR IMPLIED WARRANTIES, INCLUDING, BUT NOT LIMITED TO, THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE DISCLAIMED. IN NO EVENT SHALL THE AUTHOR BE LIABLE FOR ANY DIRECT, INDIRECT, INCIDENTAL, SPECIAL, EXEMPLARY, OR CONSEQUENTIAL DAMAGES (INCLUDING, BUT NOT LIMITED TO, PROCUREMENT OF SUBSTITUTE GOODS OR SERVICES; LOSS OF USE, DATA, OR PROFITS; OR BUSINESS INTERRUPTION) HOWEVER CAUSED AND ON ANY THEORY OF LIABILITY, WHETHER IN CONTRACT, STRICT LIABILITY, OR TORT (INCLUDING NEGLIGENCE OR OTHERWISE) ARISING IN ANY WAY OUT OF THE USE OF THIS SOFTWARE, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE.
Find your nearest Vacon office on the Internet at: www.vacon.com
Manual authoring:
documentation@vacon.com
Vacon Plc. Runsorintie 7
65380 Vaasa Finland
Subject to change without prior notice
© 2012 Vacon Plc.
References