Danfoss FR9 VACON NXP Air Cooled Installation Guide
- June 16, 2024
- Danfoss
Table of Contents
Danfoss FR9 VACON NXP Air Cooled
Product Information
Specifications
- Product Name: ip00 modules
- Frames: fr9 to fr14
- Release Date: 28.02.2019
Delivered Modules / Installing AC Chokes and Power Module
Products Included in the Delivery
The following products are included in the delivery:
- Power module
- AC choke
- Control unit
Note : In FR9, the AC choke is inside the power module.
Lifting the Power Module
To lift the power module, follow these steps:
- Place the lifting hooks symmetrically in at least two holes.
- Ensure that the lifting devices can carry the weight of the module.
Installing the Power Module
To install the power module, consider the following measurements:
Frame| Device Width A/mm| Supporting Bar Range B/mm| Recommended Cabinet Width
C/mm
---|---|---|---
FR9| 480| A – 50 mm| 600
FR10| 500| A – 50 mm| 600
FR11| 709| A – 20 mm| 800
FI9| 239| A – 50 mm| 400
FI10| 239| A – 50 mm| 400
FI12| 478| A – 50 mm| 600
FI13| 708| A – 50 mm| 800
Note: For detailed drawings, refer to the manual.
Ventilation
Steering the Internal Air Flow
To steer the internal airflow, consider the following:
- Ensure that outgoing air is directed out of the cabinet to avoid mixing with incoming cooling air.
Arranging Ventilation of the Enclosure
To arrange ventilation of the enclosure, follow these guidelines:
- Ensure the closure is well-ventilated to keep the temperature below the maximum operating temperature.
- Repeated overheating will shorten the lifetime of the converter.
FAQ (Frequently Asked Questions)
- Q: Where can I find local contacts for support?
- A : You can find local contacts for support at https://www.danfoss.com/en/contact-us/contacts-list/
DELIVERED MODULES / INSTALLING
AC CHOKES AND POWER MODULE
Products included in the delivery
NOTE! FR12 = 2 x FR10; FI14 = 2 x FI13 power modules.
NOTE! In FR9, the AC choke is inside the power module.
Lifting the power module
c | Weight kg |
---|---|
FR9 | 146 |
FR10 | 123 |
FR11 | 210 |
FI9 | 65 |
FI10 | 100 |
FI12 | 200 |
FI13 | 302 |
NOTE! Place the lifting hooks symmetrically in at least two holes. The
lifting devices must be able to carry the weight of the module.
NOTE! The maximum allowed lifting angle is 45°.
Installing the power module
Frame| Device width A/mm| Supporting bar range B/mm|
Recommended cabinet width C/mm
---|---|---|---
FR9| 480| A – 50 mm| 600
FR10| 500| A – 50 mm| 600
FR11| 709| A – 20 mm| 800
FI9| 239| A – 50 mm| 400
FI10| 239| A – 50 mm| 400
FI12| 478| A – 50 mm| 600
FI13| 708| A – 50 mm| 800
NOTE! For detailed drawings, see the manual
VENTILATION
Steering the internal airflow
NOTE! Outgoing air must be directed out of the cabinet so that it does not mix with incoming cooling air.
Arranging ventilation of the enclosure
CAUTION! It is of utmost importance for the operation and lifetime of the frequency converter that the closure is well-ventilated to keep the temperature below the maximum operating temperature. Repeated overheating will shorten the lifetime of the converter
Table 1. Ventilation requirements table
__
__
Frame
| __
Cooling air required m 3/h
| Minimum air hole on switchgear/dm 2
---|---|---
1) Inlet| 2) Outlet
FR9| 1300| 9.1| 7
FR10| 2000| 9.5| 5
FR11| 3000| 14| 7.5
FI9| 1150| 5.5| 3
FI10| 1400| 6.5| 4
FI12| 2800| 13| 7
FI13| 4200| 19.5| 10.5
GROUNDING AND CABLING THE UNIT
Connecting the internal power cable
See the IP00 Module Installation Manual for details. NOTE! No external choke in FR9.
Installing the optical fibers
Installing the motor cable