STIEBEL ELTRON WPM COMMISSIONING Heat Pump Manager User Manual
- June 16, 2024
- STIEBEL ELTRON
Table of Contents
COMMISSIONING
Heat pump manager
» WPM
General information
These instructions are intended for qualified contractors.
Not all features described in these instructions are available on every heat
pump.
The latest version of these instructions can be found on our website.
1.1 Relevant documents
WPM operating instructions
Heat pump operating and installation instructions
Operating and installation instructions for system components
WPM system notification list
Installation instructions for heat pump cascade with WPM
Note
Please see device’s operating instructions for information on the “Guarantee”
and “Environment and recycling”.
1.2 Safety instructions
1.2.1 Structure of safety instructions
KEYWORD Type of risk
Here, possible consequences are listed that may result from failure to observe
the safety instructions.
Steps to prevent the risk are listed.
1.2.2 Symbols, type of risk
Symbol | Type of risk |
---|---|
Injury | |
Electrocution |
1.2.3 Keywords
KEYWORD | Meaning |
---|---|
DANGER | Failure to observe this information will result in serious injury or |
death.
WARNING| Failure to observe this information may result in serious injury or
death.
CAUTION| Failure to observe this information may result in non-serious or
minor injury.
1.3 Other symbols in this documentation
Note
General information is identified by the adjacent symbol.
Read these texts carefully.
Symbol | Meaning |
---|---|
Material losses (appliance damage, consequential losses and environmental |
pollution)
| Appliance disposal
This symbol indicates that you have to do something. The action you need to
take is described step by step.
…„ „ These symbols show you the software menu level (in this example level 3).
1.4 Units of measurement
Note
All measurements are given in mm unless stated otherwise.
Safety
Only a qualified contractor should carry out installation, commissioning,
maintenance and repair of the appliance.
2.1 Instructions, standards and regulations
Note
Observe all applicable national and regional regulations and instructions.
2.2 General safety instructions
We guarantee trouble-free function and operational reliability only if
original accessories and spare parts intended for the appliance are used.
2.3 Notes
– The appliance should only be operated once it is fully installed and all
safety equipment has been fitted.
2.4 Test symbols
See type plate on the appliance.
Appliance description
The WPM heat pump manager is the main controller of the extendible WPM system. The device assists the control of one direct heating circuit and two heating circuits with mixer. Two heat pumps can be operated in a cascade. The device provides a 230 V fault contact for external pick-up of system faults. High efficiency circulation pumps can be connected directly via relay outputs or PWM outputs. The PCB of the WPM is located in a wall mounting enclosure that can also accommodate other components such as the relay for the top-hat rail. The entire system is operated via the integral programming unit with Touch- Wheel. An internet interface and Smart Home interfaces are available as options.
Cascade control
Up to 6 heat pump stages can be controlled for heat generation.
The maximum permitted configuration for cascade control is subject to the type
of heat pump you are using.
- 6 single compressor heat pumps
- From the third connected heat pump upwards, a WPE heat pump extension must be used
Function overview
- The 4-wire data BUS enables rapid installation and system extension using the WPE heat pump extension
- Control of a second heat source for DHW and heating
- Demand-dependent control of different circulation pumps
- Input of the system and heat pump frost limits
- At least 10 h power reserve for the clock
- Automatic pump kick control
- Reset option
- Stored notification list with precise fault code indication on the display, including date, time and heat pump index
- Fast and precise fault diagnosis with a system analyser including temperature scanning of heat pumps and peripherals without additional equipment
- Default settings for time switch programs for all heating and DHW circuits
Product name | Part number |
---|---|
WPM | 234727 |
3.1 Accessories
The following accessories can be installed for additional control of the heat
pump.
3.1.1 FE 7 remote control
The rotary selectors on the FE 7 remote control can be used to make the following settings:
- Changing the set room temperature for heating circuit 1 by ± 5 °C
- Changing the operating mode
Note that the set room temperature can be changed only in adjustable operating modes.
Symbol | Operating mode |
---|---|
PROGRAMMED OPERATION | |
ECO MODE | |
COMFORT MODE |
Note
The remote control is only effective in the heat pump manager’s PROGRAMMED
OPERATION mode.
You can set the temperature for heating times in PROGRAMMED OPERATION mode on
the remote control.
3.1.2 FET remote control
The FET digital remote control enables one heating zone to be controlled. The remote control measures the relative humidity and room temperature.
3.1.3 Internet Service Gateway ISG
The Internet Service Gateway (ISG) is an Ethernet gateway in a wall mounting
enclosure and is connected into the LAN (local area network).
The device enables the operation, adjustment and checking of heat pump system
data via the browser of a computer, laptop or tablet in the local home
network.
If the customer so wishes, data from the device can be transferred to our
SERVICEWELT portal automatically over the internet.
3.1.4 WPE heat pump extension
The WPE heat pump extension supplements the WPM system withadditional functions. These additional functions can be adjusted on the programming unit of the WPM heat pump manager.
The WPE heat pump extension provides:
- Two additional heating circuits with mixer
- A swimming pool controller for primary and secondary integration of a swimming pool
- Two additional 0…10V interfaces
- Two differential controllers
- Switching outputs
The WPE heat pump extension:
- Allows cascades of up to six heat pumps
- Supplements the basic functions of the WPM heat pump manager with options for connecting a building management system
3.1.5 EASYTRON Connect
The EASYTRON Connect system is designed for individual room control of heating systems in buildings. The system can be connected to a heat pump via ISG web or operated independently. Connecting the system to a heat pump enables demand-dependent individual room control. Operation can be via the EASYTRON Connect app.
If the system has an integral heat pump, the following functions are possible:
- The system can optimise heat pump heating curves for the connected heating circuits.
- The system can open all heating circuits for heat pump defrost.
- The system enables the identification of rooms to be cooled by the heat pump.
The system can be used for heating systems with wall mounted radiators or
underfloor heating. If the heating system has an integral DHW cylinder, the
system can influence DHW heating.
The system can control 24 rooms. In each room, max. four actuators for
radiators or channels for underfloor heating can be controlled.
In conjunction with a control unit for underfloor heating, one room
temperature sensor is required per room.
Appliance compatibility
Note
Some heat pumps should not be connected directly to the heat pump manager.
- With these heat pumps, use an indoor unit in which the heat pump manager is factory-fitted.
- Observe the information in the heat pump documentation.
Connecting external components
WARNING Electrocution Carry out all electrical connection and
installation work in accordance with national and regional regulations.
WARNING Electrocution
Isolate the heat pump from the power supply when carrying out any work.
WARNING Electrocution
Only components that operate with safety extra low voltage (SELV) and that
ensure secure separation from the mains voltage supply may be connected to the
low voltage terminals of the appliance. Connecting other components can make
parts of the appliance
and connected components live.
Only use components which have been approved by us.
Note
In conjunction with the WPM heat pump manager, use the HSM mixer servomotor.
5.1 Sensor installation
Connect all of the required sensors before commissioning the appliance.
5.1.1 AF PT outside temperature sensor
The temperature sensors have a significant influence on the function of your
heating system. Therefore ensure sensors are correctly positioned and well
insulated.
Install the outside temperature sensor on a north or north-eastern wall.
Minimum clearances: 2.5 m above the ground, and 1 m to the side of windows and
doors. The outside temperature sensor should be freely exposed to the elements
but not placed in direct sunlight. Never mount the outside temperature sensor
above windows, doors or air ducts.
Installation:
- Pierce the cable grommet at the appropriate place using a pointed object.
- Insert the cable grommet into the recess on the sensor retainer.
- Pass a lead through the cable grommet.
- Connect the lead to the terminal.
- Tighten the screws on the terminal.
- Connect the connecting cable to sensor terminal X1.3.
- Press the sensor retainer into the sensor enclosure until it clicks audibly into place.
- Secure the sensor enclosure to the wall using a screw and rawl plug.
5.1.2 TAF PT immersion/contact sensor
Installation as contact sensor
- Clean the pipe.
Note
The recesses on the retaining clip are of different sizes.
- Press the smaller recess on the retaining clip into one of the notches on the sensor.
- Press the larger recess of the retaining clip onto the sensor.
- Apply heat conducting paste to the sensor.
- Secure the sensor with the retaining clip and the cable tie.
Installation as an immersion sensor
The immersion sensor is required for the sensor well in the buffer cylinder.
- Press the spring downwards. The spring is used for fixing the sensor in the sensor well.
- Apply heat conducting paste to the sensor.
- Push the sensor into the sensor well.
5.1.3 Sensor resistance values
Temperature in °C | PT 1000 sensor Resistance in Ω |
---|---|
-30 | 882 |
-20 | 922 |
-10 | 961 |
0 | 1000 |
10 | 1039 |
20 | 1078 |
25 | 1097 |
30 | 1117 |
40 | 1155 |
50 | 1194 |
60 | 1232 |
70 | 1271 |
80 | 1309 |
90 | 1347 |
100 | 1385 |
110 | 1423 |
120 | 1461 |
5.2 FE7 remote control
Note
If you are connecting an FE 7 remote control, you cannot use an FET remote
control.
FE7 connection array
With the FE7 remote control you can adjust the set room temperature for heating circuit 1 by ± 5 °C. This function is enabled only in PROGRAMMED OPERATION. You can also change the operating mode.
Connect the remote control to terminal X1.13.
5.3 FET remote control
Note
If you are connecting one or multiple FET remote controls, you cannot use an
FE 7 remote control.
FET connection array
The FET digital remote control enables convenient operation of one heating zone.
- Attach the remote control to one of the CAN B terminals.
- Observe the FET operating instructions.
5.4 Internet Service Gateway ISG
The Internet Service Gateway ISG enables you to operate the heat pump within
your local home network and via the internet when you are away.
- Attach the Internet Service Gateway to one of the CAN B terminals (not one marked “+”).
- Observe the ISG operating instructions.
The ISG is not supplied with power by the heat pump.
Commissioning
Only qualified contractors may carry out any adjustments to the heat pump manager (see list in the chapter “Settings / Setting parameters” in the heat pump manager commissioning instructions), commission the device and instruct the system user in its use. Commissioning must be carried out in accordance with these installation instructions and the operating and installation instructions of all components belonging to the heat pump system.
Note
Our customer support can assist with commissioning, which is a chargeable
service.
6.1 Bus initialisation
Connecting the bus cable not only establishes the electrical connection for
system communication. As part of commissioning, connecting the bus cable will
also assign the appliance-specific address required for switching the heat
pump.
6.1.1 General information
Note
The control panel for each heat pump provides space for the connection of two
3-core BUS cables, i.e. the BUS cable between the heat pumps is wired in
parallel.
Note
In a cascade, heat pumps designed to heat DHW must always be initialised
first. The remaining heat pumps can then be initialised in any order.
Note
All necessary sensors must be connected before the voltage is connected to the
WPM. Any sensors connected later will not be recognised by the WPM. Example:
No DHW parameters, programs or temperatures are displayed if the DHW cylinder
sensor was not connected at the time of commissioning. No values can be
programmed for these parameters.
Note
If incorrectly initialised, all IWS (internal heat pump controllers) must be
reset and reinitialised (see chapter “Reset options / Reinitialising the
IWS”).
Note
The entire heat pump system will be shut down if the BUS cable between the WPM
and the heat pump is interrupted.
Note
The connection between heat pump manager and heat pump is carried out via CAN
bus. The connection can have a line or star topology.
If you want to initialise a heat pump cascade, refer to the document
“Installation instructions for heat pump cascade with WPM”. You can find this
document in the download area of the WPM on our website.
6.1.2 Sequence when activating the heat pumps for bus initialisation
Requirement: The appliances (heat pump, heat pump manager (WPM) and, where applicable, heat pump extension (WPE)) are connected to each other via the bus.
For bus initialisation, it is essential that you comply with the following sequence:
Connect the WPM to the mains voltage.
- Connect the WPE (if installed) to the mains voltage.
- Connect the internal heat pump controller (IWS) to the mains voltage.
- Leave the mains voltage to the compressor and emergency/booster heater switched off, so that the heat pump does not start up uncontrolled during initialisation.
In the DIAGNOSIS/SYSTEM menu, all connected BUS subscribers and their
respective software versions are shown under BUS SUBSCRIBER.
After completing initialisation of the heat pump, use the DIAGNOSIS / SYSTEM
menu under HEAT PUMP TYPES to check that all connected heat pumps are being
displayed.
▶If not all bus subscribers or connected heat pumps are displayed, you will
need to reinitialise the IWS (see chapter “Reset options”).
6.2 System configuration through parameter settings
If the system is operating incorrectly, you should first check the parameter
settings (see chapter “Settings / Parameter summary”).
6.3 Reset options
6.3.1 Reinitialising the IWS
If commissioning or initialisation of the system failed (not all bus
subscribers or connected heat pumps were displayed), carry out this reset.
To do so, proceed as follows:
-
Switch OFF the mains voltage to the WPM.
-
Switch OFF the mains voltage to the WPE (if installed).
-
Switch OFF the mains voltage to the heat pump.
-
Disconnect the BUS connections.
-
Switch ON the mains voltage to the heat pump.
-
Hold the reset key until the two outer LEDs are constantly illuminated.
-
Release the reset key. The IWS has now been reset and is ready for renewed initialisation.
-
Switch off the mains power supply to the heat pump.
-
Disconnect the bus connections.
-
Switch the mains power supply (to the heat pump, WPM, WPE) back on.
-
Carry out BUS initialisation (see chapter “Commissioning /BUS initialisation”).
-
Reset the system-specific parameters for the WPM and WPE.
6.3.2 Heat pump reset
This reset should be performed if a heat pump-specific fault or hardware fault occurs five times in the space of two hours’ runtime.
▶Activate the HEAT PUMP RESET parameter in the COMMISSIONING menu.
The fault is cleared. The heat pump is ready to be returned to use.
Commissioning wizard
The device has a commissioning wizard that will take you throughthe most
important settings the first time it is started.
▶Follow the instructions on the display.
Menu
Note
Not all appliance parameters and values are displayed in the different menus;
it depends which heat pump type and accessories are connected.
Note
Certain menu items are protected by a code. The factory-set code is 1000.
Note
The menu items shown in grey are visible only if the WPE heat pump extension
is connected.
8.1 Menu structure
INFO
SYSTEM
HEAT PUMP
ENERGY FOOTPRINT
DIAGNOSIS
SYSTEM STATUS
HEAT PUMP STATUS
HEAT PUMP ANALYSIS
SYSTEM
INTERNAL CALCULATION
NOTIFICATIONLIST
RELAY TEST SYSTEM
RELAY TEST HEAT PUMP
PROGRAMS
HEATING PROGRAM
DHW PROGRAM
COOLING PROGRAM
PARTY PROGRAM
HOLIDAY PROGRAM
HEAT-UP PROGRAM
PASTEURISATION PROGRAM
DHW CIRCULATION PROGRAM
SWIMMING POOL PROGRAM
SILENT PROGRAM 1
SILENT PROGRAM 2
SETTINGS
VIEW
GENERAL
FAVOURITES
HEATING
DHW
HYBRID MODULE
COOLING
SWIMMING POOL
DIFFERENTIAL CONTROLLER 1
DIFFERENTIAL CONTROLLER 2
THERMOSTAT FUNCTION 1
THERMOSTAT FUNCTION 2
COMMISSIONING
SOURCE
HEATING
DHW
COMPRESSOR
SILENT MODE
I/O CONFIGURATION
EMERGENCY OPERATION
RESET
8.2 Menu description
INFO
In the INFO menu you can check set and actual values for temperatures, flow
rates and pressures in the heating system and heat pump.
In the INFO menu you can check set and actual values for temperatures, flow
rates and pressures in the heating system and heat pump.
Note
Please note that actual and set values can only be displayed if the
appropriate sensors are connected.
SYSTEM
… … ROOM TEMPERATURE|
---|---
FE7|
ACTUAL TEMPERATURE FE7
Actual room temperature for heating circuit 1 (HK1) (displayed only if FE 7
remote control is connected)| °C
SET TEMPERATURE FE7
Set room temperature for heating circuit 1 (HK1) (displayed only if FE 7
remote controlis connected)| °C
FET 1|
ACTUAL TEMPERATURE FET 1
Actual room temperature for the allocated heating circuit (displayed only if
FET remote controlis connected)| °C
SET TEMPERATURE FET 1
Set room temperature for the allocated heating circuit (displayed only if FET
remote control is connected)| °C
RELATIVE HUMIDITY FET 1| %
DEW POINT TEMPERATURE FET 1
Dew point temperature (displayed only if FET remote control is connected)| °C
FET 2|
ACTUAL TEMPERATURE FET 2
Actual room temperature for the allocated heating circuit (displayed only if
FET remote control is connected)| °C
SET TEMPERATURE FET 2
Set room temperature for the allocated heating circuit (displayed only if FET
remote control is connected)| °C
RELATIVE HUMIDITY FET 2| %
DEW POINT TEMPERATURE FET 2
Dew point temperature (displayed only if FET remote control is connected)| °C
FET 3|
ACTUAL TEMPERATURE FET 3
Actual room temperature for the allocated heating circuit (displayed only if
FET remote control is connected)| °C
SET TEMPERATURE FET 3
Set room temperature for the allocated heating circuit
(displayed only if FET remote control is connected)| °C
RELATIVE HUMIDITY FET 3| %
DEW POINT TEMPERATURE FET 3
Dew point temperature (displayed only if FET remote control is
connected)C1875:D1881C1897C1875:D1884C1875:D1884C1897CC1875:C1884| °C
---|---
FET 4| %
ACTUAL TEMPERATURE FET 4
Actual room temperature for the allocated heating circuit (displayed only if
FET remote control is connected)| °C
SET TEMPERATURE FET 4
Set room temperature for the allocated heating circuit (displayed only if FET
remote control is connected)| °C
RELATIVE HUMIDITY FET 4| %
DEW POINT TEMPERATURE FET 4
Dew point temperature (displayed only if FET remote control is connected)| °C
FET 5|
ACTUAL TEMPERATURE FET 5
Actual room temperature for the allocated heating circuit (displayed only if
FET remote control is connected)| °C
SET TEMPERATURE FET 5
Set room temperature for the allocated heating circuit (displayed only if FET
remote control is connected)| °C
RELATIVE HUMIDITY FET 5| %
DEW POINT TEMPERATURE FET 5
Dew point temperature (displayed only if FET remote control is connected)| °C
… … HEATING|
OUTSIDE TEMPERATURE| °C
ACTUAL TEMPERATURE HK 1
Actual heating circuit temperature, heating circuit 1| °C
SET TEMPERATURE HK 1
Set heating circuit temperature, heating circuit 1 (HK1).
With fixed value control, the fixed temperature is displayed.| °C
ACTUAL TEMPERATURE HK 2
Actual heating circuit temperature, heating circuit 2| °C
SET TEMPERATURE HK 2
Set heating circuit temperature, heating circuit 2 (HK2).
With fixed value control, the fixed temperature is displayed.| °C
ACTUAL TEMPERATURE HK 3
Actual heating circuit temperature, heating circuit 3| °C
SET TEMPERATURE HK 3
Set heating circuit temperature, heating circuit 3 (HK3).
With fixed value control, the fixed temperature is displayed.| °C
ACTUAL TEMPERATURE HK 4
Actual heating circuit temperature, heating circuit 4| °C
SET TEMPERATURE HK 4
Set heating circuit temperature, heating circuit 4 (HK4).
With fixed value control, the fixed temperature is displayed.| °C
ACTUAL TEMPERATURE HK 5
Actual heating circuit temperature, heating circuit 5| °C
SET TEMPERATURE HK 5
Set heating circuit temperature, heating circuit 5 (HK5).
With fixed value control, the fixed temperature is displayed.| °C
ACTUAL FLOW TEMPERATURE WP | °C |
---|---|
ACTUAL FLOW TEMPERATURE NHZ | °C |
ACTUAL RETURN TEMPERATURE WP | °C |
ACTUAL FLOW TEMPERATURE | °C |
ACTUAL RETURN TEMPERATURE | °C |
SET FIXED TEMPERATURE | °C |
ACTUAL BUFFER TEMPERATURE | °C |
SET BUFFER TEMPERATURE | °C |
HEATING PRESSURE | bar |
FLOW RATE | l/min |
SYSTEM FROST PROTECTION | °C |
… … DHW|
---|---
ACTUAL TEMPERATURE Actual DHW temperature| °C
SET TEMPERATURE Set DHW temperature| °C
FLOW RATE| l/min
… … HYBRID MODULE|
ACTUAL TEMPERATURE 2ND HEAT GENERATOR| °C
SET TEMPERATURE 2ND HEAT GENERATOR| °C
ACTUAL MIXER TEMPERATURE 2ND HEAT GENERATOR| °C
SET MIXER TEMPERATURE 2ND HEAT GENERATOR| °C
COOLING
EXTERNAL HEAT SOURCE
ELECTRIC REHEATING
SOURCE
DHW CIRCULATION
SWIMMING POOL
DIFFERENTIAL CONTROLLER 1
DIFFERENTIAL CONTROLLER 2
THERMOSTAT FUNCTION 1
THERMOSTAT FUNCTION 2
HEAT PUMP
Notice
The values displayed for heat amount, power consumption, electricity
consumption and efficiency are based on measured correlations that are
specific to each type. The displayed values are not suitable for billing
purposes, for example. Additional consumption may be caused by components
which are installed outside the appliance.
The displayed values are primarily used for comparing different periods of use
in order to demonstrate trends in a specific system. The displayed values are
greatly influenced by factors such as the building, the installation location,
the installation and the environmental conditions prevailing during the period
of analysis.
For technical reasons, some of the displayed values may be considerably
inaccurate.
PROCESS DATA
AMOUNT OF HEAT
POWER CONSUMPTION
RUNTIME
STARTS
ENERGY FOOTPRINT
**** Notice The values displayed for heat amount, power consumption,
electricity consumption and efficiency are based on measured correlations that
are specific to each type. The displayed values are not suitable for billing
purposes, for example.
Additional consumption may be caused by components which are installed outside
the appliance. The displayed values are primarily used for comparing different
periods of use in order to demonstrate trends in a specific system. The
displayed values are greatly influenced by factors such as the building, the
installation location, the installation and the environmental conditions
prevailing during the period of analysis.
For technical reasons, some of the displayed values may be considerably
inaccurate.
In this menu, you will find values for electricity consumption, the amount of
heat delivered and efficiency. The displayed values are calculated on a
rolling basis. The period covered is specified.
h Hour
M Month
ENTIRE SYSTEM
POWER CONSUMPTION
EFFICIENCY
DIAGNOSIS
For heating system and heat pump troubleshooting and analysis, you can call up
all important process data and BUS subscribers under DIAGNOSIS and carry out a
relay test.
SYSTEM STATUS
HEAT PUMP STATUS
HEAT PUMP ANALYSIS
SYSTEM
INTERNAL CALCULATION
NOTIFICATIONLIST
RELAY TEST SYSTEM
- The outputs are converted if an HMH or second heat generator are used.
RELAY TEST HEAT PUMP
PROGRAMS
Here you can set all the times for the different programs and start the heat-
up program.
Setting pairs of switching times
In most programs, you can set three pairs of switching times per day or block
of days. The switching time pairs are shown on the display, to the right of
the clock. Each switching time pair consists of a start time and an end time.
After a switching time pair has expired, the heat pump switches to the
operating mode applicable at the time.
Periods around midnight
Switching time pairs can be programmed only up to 24:00. If you want to choose
periods that extend beyond midnight, you will need to set an additional
switching time pair for the following day.
Deleting switching time pairs
By resetting the start time to “–:–“, the associated end time is automatically
reset.
HEATING PROGRAM
DHW PROGRAM
COOLING PROGRAM
PARTY PROGRAM
HOURS
HOLIDAY PROGRAM
HEAT-UP PROGRAM
PASTEURISATION PROGRAM
DHW CIRCULATION PROGRAM
SWIMMING POOL PROGRAM
SILENT PROGRAM 1
SILENT PROGRAM 2
Menu: PROgRAMS
HEATING PROGRAM
Select HEATING PROGRAM to determine the times during which rooms should be
heated to the set comfort value. In the periods in between, heating takes
place to the set ECO value. The times are determined individually for each
available heating circuit.
Note
You can set the set values for each heating circuit under SETTINGS / HEATING /
HEATING CIRCUIT / COMFORT TEMPERATURE and ECO TEMPERATURE.
DHW PROGRAM
Select DHW PROGRAM to determine the times during which DHW should be heated to
the set comfort value. In the periods in between, DHW is heated to the set ECO
value.
Note
You can adjust the set values under SETTINGS / DHW / DHW TEMPERATURES /
COMFORT TEMPERATURE or ECO TEMPERATURE.
COOLING PROGRAM
Use the COOLING PROGRAM menu item to select the times during which cooling to
the SET ROOM TEMPERATURE should take place.
In the periods in between, no cooling occurs. The times are determined
individually for the available cooling circuits.
Note
You can select the set values for the relevant cooling circuit under menu item
SETTINGS / COOLING / COOLING CIRCUIT / SET ROOM TEMPERATURE.
PARTY PROGRAM
Note
In the start display, party mode is not displayed.
Select PARTY PROGRAM, to extend by a few hours the period in which the heat pump provides room heating to comfort temperature. After the period has expired, the heat pump switches to the operating mode applicable at the time.
Note
You can adjust the set values under SETTINGS / HEATING / HEATING CIRCUIT /
COMFORT TEMPERATURE or ECO TEMPERATURE.
HOLIDAY PROGRAM
In the holiday program, the heat pump provides room heating up to the ECO
temperature for a freely adjustable period. The set room temperature is
reduced to the ECO temperature. Frost protection for DHW heating remains
active. After the period has expired, the heat pump switches to the operating
mode applicable at the time.
The start day of the holiday period begins at 00:00. The final day of the
holiday period ends at 24:00.
The program can be terminated before the end of the set time period by
changing the operating mode to COMFORT MODE or PROGRAMMED OPERATION.
„ … HEAT-UP PROGRAM
Use the heat-up program to dry your screed with a defined temperature profile. To prevent damage to the appliance and/or the installation, observe the following:
- Perform hydronic balancing of the underfloor heating system.
- Open all lines of the underfloor heating system.
The heating output required for the floor heating program may exceed the design output of the heat pump. As a result, it may not be possible to achieve the required flow temperature with the heat pump. For problem-free heating/screed drying, therefore, we recommend using an external mobile electric heating appliance.
If screed drying with the heat pump, you will need to activate the electric emergency/booster heater.
During the period that the heat-up program is enabled, the EMERGENCY
OPERATION mode is not available.
Heating occurs over a definable period to an adjustable temperature sequence.
After a heat-up program has finished, the heat pump switches to the last
operating mode selected.
Note
During the period that the heat-up program is enabled, the heat pump will reach maximum output more frequently. The energy demand and noise level will be higher than in normal operation.
Material losses
Incorrect settings can cause damage to the heat pump or screed. With ground
source heat pumps, the heat source can also be damaged.
- Please note the differences between air source heat pumps and ground source heat pumps described below.
Air source heat pumps
By operating at the output limit, the evaporator can defrost frequently due to
the high cooling capacity. If the heating system has not been hydronically
balanced or if not all heating lines are open, defrosting faults can occur at
heating circuit temperatures below 25 °C. This is due to protective functions
which are intended to prevent the condenser from freezing.
Ice can form on the fan and air ducts even at temperatures above the freezing point, which can lead to noise or, in extreme cases, to the fan becoming blocked.
- If the fan is blocked, adjust the LOWER APP LIMIT HZG to a value above the current outside temperature.
- For heat pumps with output-dependent control, limit the heating output of the heat pump in menu “SETTINGS / SILENT MODE / OUTPUT REDUCTION / OUTPUT” to 75 %.
- Once the ice has melted, set parameter LOWER APP LIMIT HZG back to its initial value.
- Set the heating output of the heat pump in menu “SETTINGS / SILENT MODE / OUTPUT REDUCTION / OUTPUT” back to its initial value.
Ground source heat pumps
If screed drying is carried out with a ground source heat pump, theheat source
can be overloaded, especially a geothermal probe. Theground around the
geothermal probe may freeze in the process.Heat transfer to the ground will be
irreparably damaged.
Screed drying with a geothermal probe:
Note
If screed drying with a geothermal probe, obtain an approval from the
manufacturer of the geothermal probe.
- Set the minimum source temperature to > 2 °C (see parameter MIN SOURCE TEMPERATURE in menu COMMISSIONING / SOURCE).
- Set the temperature spread on the heat source side to < 3 K via the flow rate (see parameter BRINE PUMP RATE in menu COMMISSIONING / SOURCE).
In some circumstances, screed drying may take longer than anticipated or may
not be completed.
Screed drying with a geothermal collector:
If screed drying with a geothermal collector before the heating season, screed
drying must be completed by the end of August at the latest. Otherwise the
geothermal collector may not regenerate in time for the heating season.
**HEATING CIRCUIT SELECTION**
Select HEATING CIRCUIT SELECTION to select the heating circuit required for
the heat-up program.
In the heat pump manager, heating circuit 1 and heating circuits 2 and 3 can
be selected. If the WPE heat pump extension is installed in the system,
heating circuit 1 or heating circuits 2 to 5 can be selected.
When heating circuits 2 to 3 or 2 to 5 are in operation, the mixer regulates
the flow temperature in the selected heating circuit to the set values.
If only the direct heating circuit 1 is operational, the set values are
reduced by 5 K to even out temperature differences in the buffer cylinder.
If the system is operated without a buffer cylinder, a distinction must be
drawn between inverter heat pumps and on/off heat pumps.
Inverter heat pumps without buffer cylinder
The internal sensor on the heat pump controls the heating circuit temperature
by balancing the flow and return temperature. A sensor must not be connected
to the heat pump manager for this purpose. Buffer charging pump 1 acts as
heating circuit pump 1.
The heat pump extension has no function here.
On/off heat pumps without buffer cylinder
Only heating circuit 1 can be selected for the heat-up program.
Heating circuit sensor 1 must be connected to the heat pump.
Buffer charging pump 1 acts as heating circuit pump 1.
The heat pump extension has no function here.
SETTINGS
Material losses
Incorrect settings can cause damage to the heat pump or screed. The temperatures and time periods must be specified by the screed contractor responsible.
- Ask the screed contractor responsible for the details required.
Y Temperature
X Time
1 Maximum temperature (MAXIMUM TEMPERATURE)
2 Low end temperature (LOW END TEMPERATURE)
3 Duration of low end temperature (DURATION BASE TEMP)
4 Rise K/day (RISE PER DAY)
5 Duration of maximum temperature (MAX TEMPERATURE DURATION)
6 Start
7 End
Note
On expiry of the period over which the screed is heated to maximum
temperature, the temperature is reduced in equal steps to the low end
temperature.
Six parameters are available to determine the temperatures and periods for the heat-up program. These parameters can be adjusted sequentially as soon as the heat-up program is activated.
- Set the program to ON using the Touch-Wheel. Confirm the selection with OK.
- Use the Touch-Wheel to select the parameter you want to set. Confirm the selection with OK.
- Use the Touch-Wheel to set the desired value. Confirm the selection with OK.
- Adjust the other parameters in the same way.
LOW END TEMPERATURE
Here you can set the temperature to which the screed is initially heated.
DURATION BASE TEMP
Here you can set how long the LOW END TEMPERATURE is maintained.
MAXIMUM TEMPERATURE
Here you can set the maximum temperature to which the screed is heated.
MAX TEMPERATURE DURATION
Here you can set how long the MAXIMUM TEMPERATURE is maintained.
RISE PER DAY
Here you can set by how many degrees Kelvin/day the temperature rises before
the MAXIMUM TEMPERATURE is reached.
**** PASTEURISATION PROGRAM
Note
For the PASTEURISATION PROGRAM, an emergency/ booster heater or external heat
source must be connected.
In menu item PASTEURISATION PROGRAM, you can specify the days and times at
which the DHW cylinder heats the content to the highest value.
START TIME
Here you can specify the start time at which the DHW cylinder heats the
content to the highest value.
DAYS
Here you can set the days on which the DHW cylinder heats the content to the
highest value.
** DHW CIRCULATION PROGRAM
Select DHW CIRCULATION PROGRAM to determine the times during which the DHW
circulation pump is controlled according to the time program.
SWIMMING POOL PROGRAM
Select SWIMMING POOL PROGRAM to determine the times during which swimming pool
water heating should take place. Outside those times, the swimming pool water
heating will be switched off.
Note
You can adjust the set value under SETTINGS / SWIMMINGPOOL / SET TEMPERATURE.
**SILENT PROGRAM 1
Select SILENT PROGRAM 1 to determine the times during which the heat pump is
offset to a reduced noise mode.
By reducing the fan speed, the noise level of the heat pump is reduced. On
certain heat pumps, the compressor power may also be reduced.
SILENT PROGRAM 2
Note
When SILENT PROGRAM 2 is enabled, operating costs will be higher.
Select SILENT PROGRAM 2 to determine the times during which the heat pump is
switched off. The internal emergency/booster heater or external heat source
takes over the heating and DHW heating operations.
„SETTINGS
Here, in addition to the general settings (e.g. time), you can set all of the
system-specific parameters for heating, cooling and DHW modes.
**** VIEW
In this menu item, you can determine what faults are displayed in the message
list. Depending on the code entered, the message list will display faults
relevant either to the qualified contractor or to the service department. If
no code is entered, only faults relevant to the device user are displayed in
the message list. Entering the code will also unlock the code-protected
parameters for a specified period.
GENERAL
TIME / DATE
Select TIME / DATE to set the current time, year, month and day.
SET SUMMER TIME
Select SET SUMMER TIME, to set the summer time dates.
Summertime is factory-set to begin on 25 March and to end on 25 October.
DAY BEGINNING
Set the beginning of summer time here.
DAY ENDING
Set the end of summer time here.
**LANGUAGE
Select LANGUAGE to change the system language.
CONTRAST
Select CONTRAST to adjust the display contrast.
****BRIGHTNESS
Select BRIGHTNESS to adjust the display brightness.
TOUCH SENSITIVITY
Select TOUCH SENSITIVITY to adjust the touch sensitivity of the Touch-Wheel
and the sensor keys.
TOUCH ACCELERATION
Select TOUCH ACCELERATION to adjust the speed of reaction of the Touch-Wheel
and the sensor keys.
FAVOURITES
Select FAVOURITES to select up to six temperatures that will be displayed in
the main display. These temperatures will be displayed sequentially in groups
of three.
****HEATING
**HEATING CIRCUIT 1 | HEATING CIRCUIT 2 | HEATING CIRCUIT 3 | HEATING
CIRCUIT 4 | HEATING CIRCUIT 5 With all heating circuit menu items, you can
specify the parameters independently of one another.
Note If the WPE heat pump extension is connected, you can specify
separate values for heating circuit 4 and heating circuit 5.
COMFORT TEMPERATURE
Select COMFORT TEMPERATURE to set the set room temperature for comfort mode.
When the heat pump is in comfort mode (see PROGRAMS / HEATING PROGRAM or
operating mode COMFORT MODE), the heat pump heats the heating water to the
value set here.
ECO TEMPERATURE
Select ECO TEMPERATURE to set the set room temperature for ECOmode. When the
heat pump is in ECO mode (see PROGRAMS / HEATING PROGRAM or operating mode ECO
MODE), the heat pumpheats the heating water to the value set here.
MINIMUM TEMPERATURE
The set MINIMUM TEMPERATURE is safeguarded by the controller of the relevant
heating circuit.
The minimum temperature ensures, with underfloor heating for example, that the
screed/substrate is never too cold.
MAXIMUM TEMPERATURE
The set MAXIMUM TEMPERATURE limits the permissible flow temperature in heating
circuit 2. The limit has priority over a higher set flow temperature
calculatedby the heat pump manager.
MIXER DYNAMICS
Using this value, the control characteristics or the effect of mixer runtime
on the controller can be adjusted.
Mixer runtime [s] | WPM setting |
---|---|
100 | 150 |
200 | 100 |
300 | 50 |
ROOM INFLUENCE
Only in conjunction with a remote control.
In this menu item you set the degree of influence that the outside temperature
or current room temperature has on the control unit.
With weather-compensated control, the room is heated in relation to the
outside temperature and the set heating curve.
With room temperature-dependent control, the room is heated consistently to
the temperature set on the remote control.
Setting | Weather-compensated control | Room temperature-dependent control |
---|---|---|
0 | 100 | 0 |
25 | 75 | 25 |
50 | 50 | 50 |
100 | 0 | 100 |
Heating circuit pump control with remote control
- Set the ROOM INFLUENCE to a value greater than 0.
If the actual room temperature is higher than the set room temperature plus 1 K, the heating circuit pump is switched off. If the actual room temperature is lower than the set room temperature, the heating circuit pump is switched on.
HEATING CURVE RISE
Menu item HEATING CURVE RISE enables you to set one heating curve each for
heating circuits 1, 2 and 3. If a heat pump extension is connected, this also
applies to heating circuits 4 and 5.
Recommendation:
Heating circuit| Heating curve rise Area heating| Radiator heatingsystem| Set
room temperature
---|---|---|---
1| 0.4| 1.1| 20 °C
2| 0.6| 0.9| 20 °C
3| 0.6| 0.9| 20 °C
4| 0.6| 0.9| 20 °C
5| 0.6| 0.9| 20 °C
If you select a temperature in the SETTINGS / HEATING / STANDARD SETTING under the parameter FIXED VALUE OPERATION menu, heating curve 1 is not displayed. The display will show SET FIXED TEMPERATURE with the relevant temperature.
X Outside temperature [°C] Y Heating circuit 1, heat pump return temperature
[°C] Heating circuit 2, heat pump flow temperature [°C] HEATING CURVE VIEW
The graphic that appears on the display shows the current heating curves for
the comfort and ECO modes.
X Outside temperature [°C] Y Return / flow temperature [°C] 1 Comfort mode
2 ECO mode
Adapting a heating curve
Example: During spring and autumn, at outside temperatures of between +5 °C
and +15 °C, the room temperature is too low even with the radiator valves
fully open. At an outside temperature of approx. 0 °C, the set room
temperature will be achieved. The heating curve is set to 1.0, relating to a
room temperature of 20 °C. With a parallel shift of the heating curve
accompanied by a reduction of the curve, the heating performance of the system
is corrected. The dotted line shows the heating curve reduced to 0.83 and the
set room temperature of 23.2 °C, increased by 3.2 °C.
X Outside temperature [°C] Y Return / flow temperature [°C]
STANDARD SETTING
BUFFER OPERATION
This parameter is used to determine the basic system configuration and thus
the overall behaviour of the system.
If a buffer cylinder is used:
-
Set the parameter to ON. Confirm the selection with OK. The buffer charging pump is also actuated with the compressor.
After a delay, the compressor is started.
If no buffer cylinder is used: -
Connect the heating circuit pump to the X2.6 connection.
-
Set the parameter to OFF. Confirm the selection with OK. The heating circuit pump runs continuously.
Note
An incorrect setting can lead to malfunctions.
SUMMER MODE
SUMMER MODE
With this parameter, automatic shutdown of heating mode can be activated in
summer.
With a building insulation value of 0 (see parameter BUILDING HEAT BUFFER): If
the current outside temperature exceeds the set outside temperature (see
parameter OUTSIDE TEMPERATURE), the system switches to summer mode. If the
current outside temperature falls below the set outside temperature, the
system switches to heating mode.
With a building insulation value of 1-3 (see parameter BUILDING HEAT BUFFER):
If the outside temperature averaged over a specified period exceeds the set
outside temperature (see parameter OUTSIDE TEMPERATURE), the system switches
to summer mode. If the outside temperature averaged over a specified period
falls below the set outside temperature, the system switches to heating mode.
When the parameter FIXED VALUE OPERATION is enabled, summer mode is
deactivated for heating circuit 1. Heating circuits 2-5 are not affected by
this.
OUTSIDE TEMPERATURE
- Using the Touch-Wheel, set the temperature at which the system should switch on or off.
BUILDING HEAT BUFFER
Select BUILDING HEAT BUFFER to specify the type of building with regard to insulation and heat loss. Changeover to and from summer mode is quicker or slower depending on the building type.
– Setting “0” = uninsulated
The outside temperature is compared directly with the set temperature trigger
point.
– Setting “1” = light insulation
Outside temperature is captured over a 24 hour period. An average is
calculated from the data.
Typically: Wood construction with rapid heat transfer and little or no thermal
insulation.
– Setting “2” = medium insulation
Outside temperature is captured over a 48 hour period. An average is
calculated from the data.
Typically: Brick construction with thermal insulation and average heat
transfer.
– Setting “3” = heavy insulation
The outside temperature is captured over a 72 hour period.
An average is calculated from the data.
Typically: Building with very slow heat transfer, e.g. very thick brick walls.
If the calculated outside temperature ≥ the set outside temperature, all heating circuits will switch to summer mode. Summer mode relates solely to the central heating function. With fixed value control, summer mode is disabled for heating circuit 1. Summer mode remains active for all other heating circuits. Changing the set temperature on remote controls will have no effect. The system will continue to run in summer mode.
FLOW PROP HEATING CIRC
Note
The control characteristics cannot be defined for heating circuits with mixer
and operation with buffer cylinders.
Select FLOW PROP HEATING CIRC to specify the temperature measurements on which
the control characteristics of the system are based.
Control characteristics can be based on the return temperature, the flow
temperature or on a specified combination of the two temperatures. The
relationship between flow and return temperature can be set in any
proportions.
Example:
Setting | Control | Flow [%] | Return [%] |
---|---|---|---|
0 | Return temperature control | 0 | 100 |
30 | 30 | 70 | |
50 | 50 | 50 | |
80 | 80 | 20 | |
100 | Flow temperature control | 100 | 0 |
MAXIMUM RETURN TEMP
Select MAXIMUM RETURN TEMP to specify the temperature at which the heat pump
switches off in heating mode. This defines when the heat pump is switched off
for safety reasons, based on the return temperature. In DHW mode the return
temperature is not scanned.
The idle time is specified in the parameter IDLE TIME (in the COMMISSIONING
/COMPRESSOR menu).
No fault message is shown on the display when this value is reached.
MAXIMUM FLOW TEMPERATURE
Select MAXIMUM FLOW TEMPERATURE to specify the temperature at which the heat
pump switches off in heating mode. This defines when the heat pump is switched
off for safety reasons, based on the flow temperature.
The idle time is specified in the parameter IDLE TIME (in the COMMISSIONING /
COMPRESSOR menu). No fault message is shown on the display when this value is
reached.
FIXED VALUE OPERATION
Note
If fixed value operation is active, cooling mode is not possible.
On/off heat pumps
In menu item FIXED VALUE OPERATION, you can specify the temperature to which
the set heating circuit temperature should be constantly regulated. The
outside temperature, set program times and summer mode do not affect this.
Fixed value operation relates solely to the control characteristics of heating
circuit 1.
It is used, for example, on systems in which a constant flow temperature is
required, such as air heating systems.
Inverter heat pumps
In menu item FIXED VALUE OPERATION, you can specify the temperature to which
the set heating circuit temperature should be regulated with selected flow
proportion. The outside temperature, set program times and summer mode do not
affect this.
Fixed value operation relates solely to the control characteristics of heating
circuit 1.
For inverter heat pumps, it is possible to set the output for fixed value
operation in the menu COMMISSIONING / COMPRESSOR / CONSTANT OUTPUT.
It is used, for example, on systems in which a constant flow temperature is
required, such as air heating systems.
HEATING CIRCUIT OPTIMAL
When an Uponor DEM-WP module is connected, the heating curve is dynamically
optimised for the heat demand of individual rooms. This involves modifying the
preset heating curve by up to 50 % of its original value.
The parameter HEATING CIRCUIT OPTIMAL is only displayed when the buffer
operation parameter is set to OFF and neither a mixer sensor nor an FE7 remote
control are connected.
The parameter HEATING CIRCUIT OPTIMAL can be set to ON or OFF.
The default value is OFF. This parameter may be set to ON only if an Uponor
DEM-WP module is connected.
This function is only active inCOMFORT MODE, ECO MODE and PROGRAMMED
OPERATION.
FROST PROTECTION
Select FROST PROTECTION to specify the outside temperature at which the frost
protection function is activated.
Frost protection function prevents freezing of pipework, open heating circuits
and radiators as well as the heat pump.
The heating circuit pumps are started when the temperature falls below the
frost protection temperature.
The circulation pumps are switched off when the temperature exceeds the frost
protection temperature.
Material losses
The frost protection function cannot protect fully sealed heating circuits and
radiators from ice formation, damage and consequential harm.
- Ensure that all heating circuits are slightly open and set the thermostatic valve to at least the frost protection setting.
REMOTE CONTROL FE7
This menu item is only displayed if the remote control is connected. With the
remote control, the set room temperature for heating circuit 1 can be adjusted
by ± 5 °C. The room sensor measures the actual room temperature. The
temperature is displayed in the heat pump manager. The actual room temperature
affects the control of heating circuit 1. The remote control is only active in
PROGRAMMED OPERATION.
ROOM INFLUENCE
In this menu item you set the degree of influence that the outside temperature
or current room temperature has on the control unit.
With weather-compensated control, the room is heated in relation to the
outside temperature and the set heating curve.
With room temperature-dependent control, the room is heated consistently to
the temperature set on the remote control.
Setting | Weather-compensated control | Room temperature-dependent control |
---|---|---|
0 | 100 | 0 |
25 | 75 | 25 |
50 | 50 | 50 |
100 | 0 | 100 |
Heating circuit pump control with remote control
f Set the ROOM INFLUENCE to a value greater than 0.
If the actual room temperature is higher than the set room temperature plus 1
K, the heating circuit pump is switched off.
If the actual room temperature is lower than the set room temperature, the
heating circuit pump is switched on.
ROOM CORRECTION
Select ROOM CORRECTION to correct the room temperature shown by +/-5 K.
PUMP CYCLES
This parameter affects the behaviour of the heat pump in heating circuit 1.
OFF
The heat pump operates continuously. It shuts down only when SUMMER MODE is
active.
ON
The heating circuit pump switches on and off according to the outside
temperature.
X Time in minutes
Y Outside temperature in °C
1 Pause
2 Pump runtime
**EXTERNAL HEAT SOURCE**
In this menu item, you can specify the parameters of an external heat source.
An electric threaded immersion heater in the buffer cylinder or a boiler connected to the heating flow in modulating mode (PWM or 0-10 V interface) can be used as an external heat source.
OFF
Set the parameter to OFF if you are not connecting an external heat source to the system.
THREADED IMMERSION HEATER
Set this parameter to ON if an electric threaded immersion heater is installed in the buffer cylinder.
Temperature sensor X1.10, incorporated in the threaded
immersion heater in the buffer cylinder, captures the temperature at the buffer cylinder output to the external heat source’s heating system.
The external heat source is actuated at temperatures below the set DUAL MODE TEMP HZG; its actuation is load-dependent, as the last stage of a heat pump cascade.
Conditions for activation:
- The temperature falls below the dual mode temperature.
- The heat pump is in operation.
- The actual temperature of the external heat source is lower than the set temperature. The set temperature of the threaded immersion heater is equal to the buffer cylinder set temperature.
Conditions for deactivation:
- The actual temperature of the external heat source is higher than the set temperature.
The set temperature of the threaded immersion heater is equal to the buffer cylinder set temperature plus the heating curve gap (parameter HEATING CURVE GAP).
The actual and set temperature of the external heat source can be checked in the INFO / SYSTEM / EXTERNAL HEAT SOURCE menu.
BOILER
- Set this parameter to ON if a gas/oil boiler is installed in the system.
- Temperature sensor X1.10 captures the temperature in the boiler flow.
- Connect sensor X1.6 to the heating flow of the boiler mixer circuit.
The external heat source is actuated at temperatures below the set DUAL MODE TEMP HZG; its actuation is load-dependent, as the last stage of a heat pump cascade.
The mixer is controlled according to the set temperature. The set temperature is calculated from the buffer cylinder set temperature plus the heating curve gap. The mixer is released if the actual temperature of the external heat source is higher than the set temperature.
Conditions for activation:
- The temperature falls below the dual mode temperature.
- The heat pump is in operation.
- The temperature must be at least 5 K lower than the set boiler temperature (parameter SET BOILER TEMPERATURE).
Conditions for deactivation:
- The maximum boiler set temperature has been reached.
The actual and set temperature of the external heat source can be checked in the INFO / SYSTEM / EXTERNAL HEAT SOURCE menu.
HZG PWM
Set this parameter to ON if an external heat generator is installed in the system with a PWM interface.
The external heat generator is connected to terminal X1.16.
Temperature sensor X1.10 captures the temperature in the external heat generator flow.
- Connect sensor X1.6 to the heating flow of the external heat generator.
The external heat source is actuated at temperatures below the set DUAL MODE TEMP HZG; its actuation is load-dependent, as the last stage of a heat pump cascade.
The external heat generator regulates the temperature to the calculated set value (set buffer temperature + heating curve gap (HEATING CURVE GAP)).
Conditions for activation:
- The temperature falls below the dual mode temperature.
- The heat pump is in operation.
- The set temperature (set buffer temperature + heating curve gap) has not been reached.
Conditions for deactivation:
- The set temperature (set buffer temperature + heating curve gap) has been reached.
HZG 0-10 V
-
Set this parameter to ON if an external heat source is installed in the system with a 0 -10 V interface.
The external heat generator is connected to terminal X1.16.
Temperature sensor X1.10 captures the temperature in the external heat generator flow. -
Connect sensor X1.6 to the heating flow of the external heat generator.
The external heat source is actuated at temperatures below the set DUAL MODE TEMP HZG; its actuation is load-dependent, as the last stage of a heat pump cascade.
The external heat generator regulates the temperature to the calculated set value (set buffer temperature + heating curve gap (HEATING CURVE GAP)).
Conditions for activation:
- The temperature falls below the dual mode temperature.
- The heat pump is in operation.
- The set temperature (set buffer temperature + heating curve gap) has not been reached.
Conditions for deactivation:
- The set temperature (set buffer temperature + heating curve gap) has been reached.
HEATING CURVE GAP
In conjunction with a threaded immersion heater
With this parameter you can set how large the temperature differential to the
set heating curve has to be in order to switch off again the threaded
immersion heater serving as an external heat source.
In conjunction with a boiler
With this parameter you can set how large the temperature differential to the
set heating curve has to be in order to feed the desired flow temperature into
the heating system. The desired flow temperature is calculated from the
heating circuit set temperature (buffer cylinder set temperature) and the
heating curve gap that is set here. The boiler mixer circuit is controlled
according to the flow temperature.
In conjunction with an external heat generator with a PWM or 0-10 V interface
With this parameter, you can set how large the temperature deviation from the
set heating curve has to be in order to switch the external heat generator off
again.
SET BOILER TEMPERATURE
Note
Set this parameter if you are using a cast iron boiler, in order to prevent the formation of condensate. Observe the boiler manufacturer’s instructions.
With this parameter you can set how high the temperature in the boiler should
be.
BLOCKING TIME EVU
During a tariff blocking time by the power supply utility, the heat pump
cannot meet a heat demand. With this parameter, you can specify the behaviour
of the external heat source during blocking time.
OFF
During blocking time, the external heat source assumes responsibility for
heating even above the dual mode temperature.
1-10 hours
If the external heat source is not to assume responsibility for heating during a blocking time, therequired blocking time can be specified in hours.
Set the number of hours of blocking time after which the external heat source
should assume responsibility for heating.
Confirm the selection with OK.
LOWER APP LIMIT HZG
With this parameter, you can specify the lower application limit of the heat
pump. Below the outside temperature that is set here, the heat pump is shut
down. Heating demand will be covered by the external heat source alone.
DUAL MODE TEMP HZG
With this parameter, you can specify the dual mode temperature of the heat
pump. Below this set outside temperature, the external heat source may back up
the heat pump if the heating output has not been reached. The external heat
source assumes responsibility for heating demand jointly with the heat pump.
HZG PWM
With this parameter you can set how quickly the external heat source/gas
burner corrects a deviation in temperature. The smaller the value, the quicker
control is restored.
Cooling and DHW heating with air/water heat pump cascades
With an air/water heat pump cascade, cooling and DHW heating can take place in
parallel.
In the SETTINGS / DHW / STANDARD SETTING / DHW MODE menu, set the parameter
PARTIAL PRIORITY to ON.
The heat pump specified for DHW and the corresponding DHWcharging pump are
switched on in response to DHW demand.
The remaining heat pumps in the cascade provide cooling.
COOLING
Here you can switch the cooling function of the heat pump on or off.
COOLING MODE
PASSIVE COOLING
Passive cooling is possible only with brine/water heat pumps.
Cooling takes place initially with the heating circuit pump. Controller output
X2.13 is switched on. Additional zone valves or diverter valves can be
actuated with controller output X2.13, for example.
If after 60 seconds the actual flow temperature is higher than the set flow
temperature, the source and buffer charging pumps are started.
On cascades, the additional source and buffer charging pumps are switched on
one after the other if the flow temperature cannot be further reduced. Whether
these additional pumps are activated depends on the set dynamics DYNAMICS
PASSIVE).
ACTIVE COOLING
Control characteristics with brine/water heat pumps
Cooling initially takes place passively (see PASSIVE COOLING). If theflow
temperature cannot be further reduced by passive cooling,
the compressor also starts.
On cascades, the additional source and buffer charging pumpsand compressor are
switched on one after the other if the flowtemperature cannot be further
reduced. Whether these additionalpumps are activated depends on the set
dynamics (DYNAMICSACTIVE or DYNAMICS PASSIVE).
Control characteristics with air/water heat pumps
Cooling takes place initially with the heating circuit pump. Controller output
X2.13 is switched on. Additional zone valves or diverter valves can be
actuated with controller output X2.13, for example. If after 60 seconds the
actual flow temperature is higher than the set flow temperature, the buffer
charging pump and compressor are started. On cascades, the additional buffer
charging pumps and compressor are switched on one after the other if the flow
temperature cannot be further reduced. Whether these additional pumps and
compressors are activated depends on the dynamics setting (DYNAMICS ACTIVE).
****HEAT INTERFACE UNIT When cooling without central dew point monitoring,
the system is controlled to an adjustable set temperature (SET FLOW
TEMPERATURE). Supercooling of the buffer cylinder (e.g. with photovoltaic
integration) is possible. Mixer control ensures that the selected flow
temperature is not undershot. Central dew point monitoring with an FET remote
control is not possible.
Ensure decentralised dew point monitoring in the respective residential units.
In combination with our heat interface units, connect the cooling output
signal to the controller of the heat interface unit via a corresponding
contactor/relay. For this, observe the operating and installation instructions
of the heat interface unit.
STANDARD SETTING
COOLING STAGES
Select the number of heat pumps enabled for cooling mode.
COOLING LIMIT
With this parameter, the lower application limit for cooling mode is
specified. If the outside temperature is below the set application limit,
cooling mode is deactivated.
COOLING CAPACITY
With this parameter, the maximum cooling capacity of the heat pump is
specified in kW.
FLOW TEMP HYSTERESIS
If the sum of the flow temperature and the set hysteresis is greater than the
set temperature, the compressor is switched on.
DYNAMICS ACTIVE
This parameter specifies how quickly the individual heat pumps in a cascade
start. The higher the set dynamics, the slower the downstream heat pumps start
up.
Dynamics for brine/water heat pump
– Dynamic 0
The compressor starts at the same time as the source pump.
– Dynamic 1
If the source pump has been running for 10 minutes and the current flow
temperature is higher than the set flow temperature with a hysteresis of 0.5
K, the compressor starts.
– Dynamics 10
If the source pump has been running for 30 minutes and the current flow
temperature is higher than the set flow temperature with a hysteresis of 2 K,
the compressor starts.
Note
With the other available values (2 to 9), the hysteresis is interpolated
correspondingly.
Dynamics with air/water heat pumps
– Dynamic 1
If the first compressor has been running for 10 minutes and the current flow
temperature is higher than the set flow temperature with a hysteresis of 0.5
K, the next downstream heat pump starts.
– Dynamics 10
If the first compressor has been running for 30 minutes and the current flow
temperature is higher than the set flow temperature with a hysteresis of 2 K,
the next downstream heat pump starts.
Note
With the other available values (2 to 9), the hysteresis is interpolated
correspondingly.
DYNAMICS PASSIVE
Dynamics with brine/water heat pumps
This parameter specifies how quickly the individual heat pumps in a cascade
start. The higher the set dynamics, the slower the downstream heat pumps start
up.
– Dynamic 1
After the controller output X2.13 has been switched, the source and buffer
charging pumps start in sequence, each after a delay of one minute.
– Dynamic 10
After the controller output X2.13 has been switched, the source and buffer
charging pumps start in sequence, each after a delay of five minutes.
Note
With the other available values (2 to 9), the hysteresis is interpolated
correspondingly.
ACTIVE COOLING / PASSIVE COOLING
Passive cooling is possible only with brine/water heat pumps.
AREA COOLING / FAN COOLING
Area cooling
In the case of area cooling, the cooling of the building takes place by means
of the available underfloor or wall heating. In order to monitor relative
humidity, an FET remote control for the heating circuit must be connected.
Fan cooling
In the case of fan cooling, the cooling of the building takes place by means
of fan convectors. In order to monitor room temperature, an FE 7 or FET remote
control for theheating circuit muste connected.
SET FLOW TEMPERATURE
Area cooling
The mixer regulates the flow temperature set here.
Fan cooling
When this temperature has been reached during cooling, the compressor is
switched off.
Under passive cooling, the source and buffer charging pumps are also switched
off.
FLOW TEMP HYSTERESIS
If the sum of the flow temperature and the set hysteresis is greater than the
set temperature, the compressor is switched on.
SET ROOM TEMPERATURE
The heat pump cools the room down to the room temperature set here minus a
fixed hysteresis of 2 K.
DYNAMICS ACTIVE
See description above.
DYNAMICS PASSIVE
See description above.
COOLING CIRCUIT 1 / 2 / 3 / 4 / 5
SET FLOW TEMPERATURE
In this menu item, you set the temperature required in the cooling circuit
heat exchanger in order to reach the set temperature in the respective room.
COOLING TYPE
Here you can specify whether the cooling circuit is used for fan or area
cooling.
SET ROOM TEMPERATURE
The heat pump cools the room down to the room temperature set here minus a
fixed hysteresis of 2 K.
INCREASE COOLING CURVE
With the INCREASE COOLING CURVE menu item, you can select a cooling curve for
each of the cooling circuits.
The set flow temperature is calculated from the cooling curve, outside
temperature and start temperature.
The minimum flow temperature depends on the type of cooling and whether a
buffer cylinder is installed.
Type of coolin | Minimum flow temperature [°C] |
---|---|
Fan cooling with buffer cylinder | 11 |
Fan cooling without buffer cylinder | 9 |
Area cooling | 15 |
START TEMPERATURE
The heat pump starts cooling at the room temperature that is set here.
COOLING CURVE VIEW
The graphic that appears on the display shows the current cooling curve.
**SWIMMING POOL
With the swimming pool function, the swimming pool water is heated to a set
temperature by means of a heat exchanger. The pump connected to terminal X4.12
pumps the heating water from a buffer cylinder through the heat exchanger. The
pump connected to terminal X4.13 pumps the water into the swimming pool. The
heat pump can also heat the swimming pool without a buffer cylinder. The pump
connected to terminal X4.12 pumps the heating water through the heat
exchanger. The pump connected to terminal X4.13 pumps the water into the
swimming pool.
SWIMMING POOL
Set whether the swimming pool function should be switched on or off.
DEMAND
The swimming pool function can be requested in various ways.
In order for swimming pool water heating to begin, the set conditions must be
met and the SWIMMING POOL PROGRAM (in the PROGRAMS menu) must be active.
Choose the conditions that activate the swimming pool function.
230 V INPUT
Heating of the swimming pool water can be requested via an external signal. As
soon as a 230 Vsignal is received at input X4.2, heating of the swimming pool
water commences.
SENSOR INPUT
If the temperature measured by swimming pool sensor X3.5 is lower than the
sum of the set temperature and hysteresis, heating of the swimming pool water
is started.
SET TEMPERATURE
** With this parameter you can set the set temperature for the swimming pool.
HYSTERESIS
The value set here specifies the temperature difference from the set
temperature at which heating of the swimming pool water commences.
BUFFER OPERATION
If a sensor is connected to terminal X3.4, swimming pool mode is possible without a buffer cylinder. The swimming pool sensor X3.4 is responsible for switching the heat pump on and off.
FIXED VALUE
In this menu item you set the temperature required in the heat exchanger in order to reach the set temperature in the swimming pool.
DIFFERENTIAL CONTROLLER 1 / 2
With the WPE heat pump extension, two differential controllers working independently of one another can be set up, each controlling one output (X4.10 and X4.11). Output X4.10 is controlled via differential sensors 1.1 (X3.9) and 1.2
(X3.10).
Output X 4.11 is controlled via differential sensors 2.1 (X 3.11) and 2.2 (X 3.12).
Example for output X4.10
The differential controller function can be used, for example, to connect a
water-bearing stove to a system with a buffer cylinder.
Here differential sensor 1.1 (X3.9) is positioned inside the water chamber of
the stove. Differential sensor 1.2 (X3.10) is located in the buffer cylinder.
If the differential between X3.9 and X3.10 exceeds the set start differential
and the maximum and minimum temperature limits are satisfied, output X4.10 is
switched on. A pump connected to output X4.10 supplies the water heated in the
stove to the buffer cylinder.
DIFFERENTIAL CONTROLLER 1 / 2
Set the parameter to ON or OFF.
START DIFFERENTIAL
Here you can set the temperature differential which must prevail between both sensors in order to switch on the associated output (X4.10 or X4.11). If the start differential set here is exceeded, the associated output is switched on.
HYSTERESIS
Example for output X4.10 With this parameter you can specify the extent to which the temperatures from differential sensors 1.1 and 1.2 can converge.
For the purposes of the calculation, the hysteresis set here is subtracted from the set start differential.
Only when the temperature differential has reached the start differential minus the set hysteresis does the output switch off.
MINIMUM TEMPERATURE
Example for output X4.10
Here you can set the minimum temperature that must be present at differential sensor 1.1 for the pump to start, once the start differential has been reached.
Menu: COMMISSIONING
Note
Differential sensor 1.1 must be installed at the heat source (e.g. the water
chamber of the stove).
MAXIMUM TEMPERATURE
Example for output X4.10
Here you can set the maximum temperature that must be present at differential
sensor 1.2.
If the temperature at differential sensor 1.2 is higher than the maximum
temperature, output X4.10 is switched off.
Note
Differential sensor 1.2 must be installed at the heat store (e.g. buffer
cylinder).
STOP DELAY
Example for output X4.10
This parameter specifies a run-on time for the pump (outpuX4.10).
THERMOSTAT FUNCTION 1 / 2
With the WPE heat pump extension, two thermostat functionsworking
independently of one another can be set up, each controlling one output (X4.10
and X4.11).
Output X4.10 is controlled via thermostatic sensor 1 (X3.9).
Output X 4.11 is controlled viathermostatic sensor 2 (X 3.11).
** THERMOSTAT FUNCTION 1 / 2
Set the parameter to ON or OFF.
SET TEMPERATURE
Example for output X4.10
You can set a temperature here. If this temperature is exceeded, the output
(X4.10) is switched on.
HYSTERESIS**
Example for output X4.10
You can set a temperature deviation here. If the actual temperature falls
below the set temperature by this value, the output (X4.10) is switched off.
COMMISSIONING
SOURCE
MIN SOURCE TEMPERATURE
Material losses
Never operate the heat pump with source temperatures below –9 °C.
When set to OFF, the temperature at the source sensor is not scanned.
If the actual temperature drops below the minimum source temperature, the
compressor is switched off and the idle time is set.
The compressor is enabled again after the idletime has expired and the fixed
hysteresis of 2 K has been exceeded.
The source pump will always be started 30 seconds earlier than the compressor,
which starts when there is a heat demand for central heating or DHW.
Note
The source pump runs on for 60 seconds after the heat pump has been shut down.
SOURCE MEDIUM
In this menu item you set the source medium used by the heat pump.
ETHYLENE GLYCOL
WATER
GROUNDWATER MODULE
MAX. SOURCE EXTRACTION RATE
In this menu item, you can set the maximum output to be extracted from the
heat source, to prevent the heat source from being overloaded.
CHARGING PUMP CONTROL
With these parameters, the operating characteristics and control of the
charging pumps can be specified.
STANDBY/HEATING/DHW/COOLING/DEFROST
Settings can be made for the charging pumps in these operating modes.
TYPE OF CONTROL
MINIMUM PUMP RATE
With this parameter, you set the minimum flow rate and therefore the pump
rate. The pump rate does not fall below the value set here.
AVERAGE PUMP RATE
With this parameter, you set the average flow rate and therefore the pump
rate. The pump rate will not exceed the value set here.
MAXIMUM PUMP RATE
With this parameter, you set the maximum flow rate and therefore the pump
rate. The pump rate will not exceed the value set here.
ADJUSTABLE PUMP RATE
With this parameter, you set the flow rate and therefore the pump rate. The
pump rate will not exceed the value set here.
SPREAD CONTROL
With this parameter, you can enable or disable spread control.
SET VALUES
PUMP RATE
In this menu item you can set the pump rate for the connected pump. The pump
rate is used to specify the flow rate. Please also note the information on
flow rate (see the operating instructions for the pump and the chapter
“Specification /Data table” in the operating and installation instructions for
the heat pump).
SPREAD
Here, you can set the temperature differential between the flow and return
sensors.
The heat pump keeps the temperature differential constant at the set value by
adjusting the circulation pump flow rate accordingly.
STANDARD SETTING
MINIMUM PUMP RATE
With this parameter, you set the minimum flow rate and therefore the pump
rate. The pump rate does not fall below the value set here.
Only applicable to spread control:
The time taken to achieve the set spread can vary on account of this setting.
MAXIMUM PUMP RATE
With this parameter, you set the maximum flow rate and therefore the pump
rate. The pump rate will not exceed the value set here.
Only applicable to spread control:
The time taken to achieve the set spread can vary on account of this setting.
HEATING
CONTROLLER DYNAMICS
The CONTROLLER DYNAMICS parameter influences the stabilisation speed of the
heat pump output controller.
The heat pump output controller functions primarily as an integral controller.
The control deviation (the differential between actual and set heating
circuit temperatures) is accumulated over time.
The result is the integral of the control deviation in Kelvin minutes.
Every time the switching value adjustable with this parameter is reached, the
output is switched one stage higher or lower.
Example: Where the control deviation is 5 K, it takes 10 minutes for the
switching value of 50 Kmin to be reached.
The compressor, or in a cascade the next compressor stage, then switches and
the integral of the control deviation is reset to zero.
Normally, the preselected CONTROLLER DYNAMICS should be sufficiently fast and
operate without oscillation. Heating systems that respond quickly require a
lower value, whilst very slow responding systems require a higher value to be
set.
HYSTERESIS
For on/off heat pumps with buffer cylinder, you can set here the start
hysteresis for the heat pump.
SPREAD CONTROL
The flow rate for the circulation pump is controlled automatically by the
heat pump.
SET SPREAD
Here, you can set the temperature differential between the flow and return
sensors.
The heat pump keeps the temperature differential constant at the set value by
adjusting the circulation pump flow rate accordingly.
MAXIMUM PUMP RATE
With this parameter, you set the maximum flow rate and therefore the pump
rate. The pump rate will not exceed the value set here.
The time taken to achieve the set spread can vary on account of this setting.
MINIMUM PUMP RATE
With this parameter, you set the minimum flow rate and therefore the pump
rate. The pump rate does not fall below the value set here.
The time taken to achieve the set spread can vary on account of this setting.
STANDBY PUMP RATE
Here, you can set the minimum pump rate for the internal circulation pump
while the heat pump is idle.
The pump will run at the output set here as long as the heat pump does not
receive a heat demand, as well as during power-OFF periods and idle times.
HEATING CIRC PUMP RATE
Set the flow rate via the heating circuit pump output. Please also note the
information on flow rate (see chapter “Specification /Data table” in the
operating and installation instructions for the heat pump).
DHW
DHW CIRCUIT PUMP RATING
Set the maximum flow rate via the DHW pump output. If noise occurs, reduce the
output.
COMPRESSOR
MINIMUM DEFROST TIME
Set here the defrost time for the heat pump defrost procedure.
The selected time applies to manual or demand-dependent defrosting.
START DEFROST
Manual defrost can be started only if the heat pump is in operation.
The defrost signal is displayed.
Maximum defrost time The maximum defrost time for all heat pumps is 20
minutes. Defrosting is terminated after the maximum defrost time has elapsed.
The heat pumps are then forced to operate in heating mode for 20 minutes.
Only then can a new defrost process be initiated.
IDLE TIME
To protect the compressor, an idle time is set following shutdown of a heat
pump. The default idle time of 10 or 20 minutes (according to heat pump type)
should normally not be reduced. Where a reduction is required because of
adjustments or repair work, reset the idle time back to 10 or 20 minutes
after completing the necessary work.
Note
During an intensive defrost, higher operating costs may be incurred.
****HEATING SYSTEM SIZING
The heat demand for the house is set here, taking into consideration the lowest regional temperatures (for example 10 kW heat demand at – 14 °C outside temperature).
During operation, the device will use this to calculate the optimum value for heat pump operation.
Refer to the building’s heat demand calculation to determine the values.
Please note that if a higher heat demand is set, the efficiency of the overall system will reduce. On the other hand, if the heat demand is set too low, a degree of comfort may be lost.
****DESIGN TEMPERATURE
Select the design temperature here. This will be the outside temperature (°C) for which heat demand was calculated, in the region where the heat pump is being used.
HEAT DEMAND
Select the heat demand calculated for the design temperature here.
CONSTANT OUTPUT
This parameter determines the heating output as a fixed value, for swimming pool operation and the heat-up program. The output is then controlled to the permanently set output, irrespective of the outside temperature.
CONDENSATE RIBBON HEATER
The condensate ribbon heater ensures that condensate can drain away even at low outside temperatures.
OUTSIDE TEMPERATURE
Set here the outside temperature above which the condensate ribbon heater is switched on.
QUICK START
During commissioning, you can test the heat pump function by triggering a heat pump quick start. When calling up parameters, OFF is shown on the display. If you set it to ON and press OK, a quick start is initiated. The value on the display visibly counts down from 60 to 0 s. On quick start the display then shows ON. After that, the heat pump and the associated buffer charging pump are switched on.
SILENT MODE
Reduced noise mode
SILENT MODE is an operating mode for air/water heat pumps in which the sound level of the heat pump is reduced.
Note
Silent mode has an effect on the heating output and efficiency of the heat
pump. When silent mode is active, operating costs will be higher. In silent
mode 2, heating and DHW heating are provided solely via the emergency/booster
heater.
In the “PROGRAMS / SILENT PROGRAM 1” menu, set the times when the heat pump
should switch to a quieter operating mode.
FAN REDUCTION
As soon as this parameter is set to ON, while SILENT PROGRAM 1 is enabled,
the fan speed of the heat pumps is reduced.
OUTPUT REDUCTION
As soon as this parameter is set to ON, while SILENT PROGRAM 1 is enabled,
the fan speed and the compressor output of the heat pump can be reduced
independently of each other by means of the following parameters.
OUTPUT
The reduction in the compressor output can be set here in %.
FAN
The reduction in the fan speed can be set here in %.
HEAT PUMP OFF
As soon as this parameter is set to ON, while SILENT PROGRAM 2 is enabled,
the heat pump is switched off and the internal or external second heat source
takes over the DHW / Central heating function.
POWER-OFF
During a tariff blocking time by the power supply utility, the heat pump
cannot meet a heat demand. With this parameter, you can specify the
characteristics of the heat pump and the internal reheating stages during a
tariff blocking time.
OFF
No heat generator is blocked during the tariff blocking time.
HEAT PUMP + ELECTRIC BOOSTER HEATER
During the tariff blocking time, the heat pump and the electric
emergency/booster heater are blocked.
HEAT PUMP
The heat pump is blocked during the tariff blocking time.
ELECTRIC BOOSTER HEATER
During the tariff blocking time, the electric emergency/booster heater is
blocked.
SYSTEM TYPE
If an HMH is installed in the heating system, this value must be set to 1.
I/O CONFIGURATION
INPUT X1.13
In this menu item, you can set which functions of input X 1.13 should be
adopted.
Never apply external voltages.
39
▶
References
- Home - domain expired
- Home - domain expired
- Home - domain expired
- STIEBEL ELTRON International
- STIEBEL ELTRON International
- Ersatzteil- und Zubehörshop
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>