OSRAM LS PD MULTI 3 FL Light And Motion Sensor Instructions
- June 16, 2024
- OSRAM
Table of Contents
**OSRAM LS PD MULTI 3 FL Light And Motion Sensor Instructions
**
Description
Function and application
The LS/PD MULTI 3 FL sensor detects the presence of people and measures the
intensity of ambient light.
The sensor is installed in lamps.
Construction
The sensor is made up of the following components:
- Light sensor (A)
- Motion sensor (B)
- LED (C)
- Connection cable (D)
- Housing (E)
Light and motion sensor Fitting instructions
Installation
Safety instructions
The sensor must only be installed and put into operation by a qualified
electrician. The applicable safety regulations and accident prevention
regulations must be observed.
WARNING!
Exposed, live cables or damaged housing.
Danger of electric shock!
- Only work on the sensor when it is de-energized.
CAUTION!
Destruction of the sensor and other devices through incorrect mounting!
- Only use OSRAM control units of the following types: DALI MULTI 3/ DIM MULTI 3, DALI MULTIeco/MULTIeco, DALI PROFESSIONAL Sensor Coupler.
- Do not connect control line with external voltage.
- Note the maximum total line length.
- Do not route the sensor line together with the power or lamp line.
Connecting the sensor
Connect the sensor using the supplied cable or a commercially available 4-pin
cable. If the cable is shortened or lengthened, ensure that the wiring is
correct.
Sensors can be connected in parallel via a Y-branch. For the maximum number of
sensors: see the separate control unit manual.
F Y-branch
G Sensor
Selecting the installation location
H Surveillance cone: entire workplace; not on window surfaces.
I Avoid exposure to direct light.
K Avoid drafts (e.g. from ventilators or fans).
L Installation distance = min. installation height
Appendix
Technical data
Combined control and supply connection| 4-pin modular connection (4p4c) 1:
Supply voltage 2: Light measurement value 3: Motion signal 4: Signal ground
Length 2.1 m
---|---
Maximum total length of signal line (incl. all connections to the control
units)| See control unit
Insulation| Basic insulation as per IEC 664
Dimensions (L x W x H)| 35 x 21 x 21 mm
Light sensor detection area| 20 – 600 lx (measured at sensor), opening angle
approx. 90°
Motion detection area| Conical, opening angle approx. 80°
Installation height| 2 – 4 m
****The CE requirements to EN 60928 are fulfilled.
The EMC requirements to EN 61547 are fulfilled.
Conformity with the relevant EU directives is confirmed by the CE symbol.
II 2009
LSPD_Multi3-FL_ma0902en_we1.01.indd
OSRAM GmbH
Kunden Service Center
Customer-Service-Center (CSC)
Steinerne Furt 62
86167 Augsburg
Germany
Tel : +49 (0) 1803 677 – 200
(kostenpflichtig / charges apply)
Fax.: +49 (0) 1803 677 – 202
www.osram.com
www.osram.de
Downloaded from Arrow.com
Documents / Resources
|
OSRAM LS PD MULTI 3 FL Light And Motion
Sensor
[pdf] Instructions
LS PD MULTI 3 FL Light And Motion Sensor, LS PD MULTI 3 FL, Light And Motion
Sensor, And Motion Sensor, Motion Sensor, Sensor
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>