OSRAM OTi DALI 25 Optotronic LED Power Supply Instruction Manual
- June 3, 2024
- OSRAM
Table of Contents
OPTOTRONIC® LED Power Supply
OTi DALI 25/220-240/700 NFC I
OTi DALI 35/220-240/1A0 NFC I
OTi DALI 60/220-240/1A4 NFC I
Instruction Manual
OTi DALI 25 Optotronic LED Power Supply
Picture only for reference, valid print on product 5)
OTi DALI 25 | OTi DALI 35 | OTi DALI 60 | |
---|---|---|---|
35 x* | 35 x* | 20 x* | |
20 x* | 20 x* | 12 x* | |
**** | ≤ 17 A | ≤ 17 A | ≤ 20 A |
T H
| ≤ 220 μs| ≤ 220 μs| ≤ 200 μs
V N AC
| 220 – 240 V
V N DC
| 176 – 276 V
- Note for mains through wiring:
The maximum through wiring current of 3A must be considered.9)
Safety information for recessed mounting and covering with thermally insulating material acc. to IEC 60598-1:2020 13)
OTi DALI 25 NFC I
Suitable for covering with thermally insulating material 14)| OTi DALI 35
NFC I
Suitable for covering with thermally insulating material 14)
---|---
|
Permitted use up to ta=25°C and tc=80°C without impairing safety or lifetime.
16)| Permitted use up to ta=25°C and tc=90°C without impairing safety or
lifetime. 16)
OTi DALI 60 NFC I
Suitable for covering with thermally insulatingmaterial 14)| OTi DALI 60
NFC I
Not suitable for covering with thermally insulating material 15)
|
Permitted use up to ta=25°C and tc=85°C without impairing safety or lifetime.
16)|
Irated ≤ 1050 mA
Prated ≤ 40 W| 1050 mA < Irated ≤ 1400 mA
40 W < Prated ≤ 58 W
Note: Declared tc value on product applies for normal use without covering with thermally insulating material. 17)
Position 18)| | Cable type (tested acc. to EN 60598-1) 19)|
Remark 20)
A| Output / SEC| • H03VV-F 2×0.5
• H03VV-F 2×0.75
• H03VVH2-F 2×0.75
• Style 21073| –
B1| Output / SEC| • H05VV-F 2×1.0
• H05VV-F 2×1.5| –
B2 or C 21)
|
Input / PRI + DALI one cable 22)
| • H05VV-F 2×1.0
• H05VV-F 2×1.5
• H05VV-F 3×1.5
• H05VV-F 5×1.5
• NYM-J 3×1.5
• NYM-J 5×1.5| –
B2 and C 23)| Input / PRI + DALI two cables 24)| • H05VV-F 2×1.0
• H05VV-F 2×1.5
• H05VV-F 3×1.5
• H05VV-F 5×1.5
• NYM-J 3×1.5
• NYM-J 5×1.5| Mains through wiring current ≤3A* 25)
E| 2-wire connector for earthing 26)| For solid conductors only 27)
- Safety information for mains through wiring: Cable temperature in the cable clamp compartment depends on cable type, ambient temperature and through wiring current. Therefore through wiring current is limited. 28)
Installing and operating information: Connect only LED load type. LED module
will be switched off when output voltage is outside the voltage range given on
the driver. Wiring information (see fig. A): Do not connect the outputs of two
or more units. The DALI interface provides basic insulation against mains.
Output current adjustment = via programming software using the DALI interface
or via Near Field Communication (NFC) in mains off mode only. Unit is
permanently damaged if mains is applied to the terminals 21/22. Lines 21/22
max. 2 m whole length excl. modules. Emergency Lighting: This LED power supply
complies with EN 61347-2-13 Annex J and is suitable for emergency lighting
fixtures according to EN 60598-2-22. Hereby OSRAM GmbH declares that the radio
equipment types OTi DALI 25 NFC I, OTi DALI 35 NFC I and OTi DALI 60 NFC I are
in compliance with Directive 2014/ 53/ EU and the relevant statutory
instruments. The full text of the EU declaration of conformity or the UK
declaration of conformity is available at the following internet address:
www.osram.com/ot-indoor-ce. Frequency
range: 13 553 – 13 567 kHz. Technical support:
www.osram.com,+49 (0)89-6213- 6000. 1) Constant
current LED Power Supply; 2) tc point; 3) Wire preparation; push in; 4)
Designed and engineered in Germany/Italy; Made in Bulgaria; 5) picture only
for reference, valid print on product; 6) Mains; 7) Input; 8) Output; 9) Note
for mains through wiring: The maximum through wiring current of 3A must be
considered. 10) Year; 11) Week; 12) Through-looping; 13) Safety information
for recessed mounting and covering with thermally insulating material acc. to
IEC 60598-1:2020; 14) Suitable for covering with thermally insulating
material; 15) Not suitable for covering with thermally insulating material;
16) Permitted use up to ta=25°C and tc=85°C without impairing safety or
lifetime. 17)
Note: Declared tc value on product applies for normal use without
covering with thermally insulating material. 18) Position; 19) Cable types
(tested acc. to EN 60598-1); 20) Remark; 21) B2 or C; 22) one cable; 23) B2
and C; 24) two cables; 25) Mains through wiring current ≤3A; 26) 2-wire
connector for earthing; 27) For solid conductors only; 28) Safety information
for mains through wiring: Cable temperature in the cable clamp compartment
depends on cable type, ambient temperature and through wiring current.
Therefore through wiring current is limited.
WARNING: DALI (FELV) control terminals are not safe to touch. Circuits connected to any DALI (FELV) control terminal shall be insulated for the LV supply voltage of the control gear, and any terminals connected to the DALI (FELV) circuit shall be protected against accidental contact.
OSRAM GmbH
Berliner Allee 65
86153 Augsburg
Germany
www.osram.com
References
- Digital Systems | OSRAM Digital Systems
- OSRAM Americas | OSRAM SYLVANIA Homepage
- OSRAM Americas | OSRAM SYLVANIA Homepage
- Digital Systems | OSRAM Digital Systems
- OSRAM – Ñто Ñвет | Light is OSRAM
Read User Manual Online (PDF format)