AprilAire E100 Pro 100 Pint Whole House Dehumidifier Owner’s Manual

June 16, 2024
Aprilaire

E100 Pro 100 Pint Whole House Dehumidifier

Product Information

Specifications

  • Model: E080 & E100 Dehumidifier

Product Usage Instructions

Safety Instructions

Be sure to read and understand all safety precautions and
instructions before installing and operating the unit.

  • ! WARNING
  • ! CAUTION
  • NOTICE

Whole Home Dehumidification

To use the dehumidifier for whole home dehumidification:

  1. 1. Use the ON/OFF Power Switch, located by the power cord, to  

    apply power to the dehumidifier.

Note: The ON/OFF Power Switch should stay ON unless the unit
will not be used for an extended period. Use the ON/OFF Button on
the control panel to turn the unit off for short durations. With
the ON/OFF Button in the ON position and the dehumidifier idle
(neither the fan nor the compressor running) the unit will use less
than 3W of power.

  1. 1. Use the ON/OFF Button on the control panel to turn the  

    dehumidifier ON.

The first press of a button will turn on the display light, so
if the display was dark, you might need to press it again. Once ON,
the display will show the current dehumidifier setting.

  1. The dehumidifier blower will turn on, and the words “AIR
    SAMPLING” will appear on the display. This indicates that the
    dehumidifier is sampling the air to determine if dehumidification
    is needed and shows the measured humidity level.

  2. If the Relative Humidity (RH) is above the setting, the
    compressor turns on to dehumidify the space. The word
    “DEHUMIDIFYING” appears when the compressor is turned on.

Energy Savings Tips

Here are some energy savings tips for using the
dehumidifier:

  • TBD

Maintenance

To maintain the dehumidifier:

  • TBD

Ventilation

To ensure proper ventilation:

  • TBD

Zoning the Dehumidifier

To zone the dehumidifier:

  • TBD

Required Components

The following components are required for installation:

  • TBD

Installer Setup

To set up the dehumidifier:

  • TBD

FAQ (Frequently Asked Questions)

  1. TBD

INSTALLED BY:
Product Info & Digital Manual

INSTALLATION AND OWNER’S MANUAL
Model E080 & E100 Dehumidifier

INSTALLER PHONE:

DATE INSTALLED:

PLEASE LEAVE THIS MANUAL WITH THE DEHUMIDIFIER OWNER
1 English

Table of Contents

Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Whole Home Dehumidification . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Operating the Dehumidifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Energy Savings Tips . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Cleaning the Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Cleaning the Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Preparing the Unit for Installation . . . . . . . . . . . . . . . . . . . . . . . 6 Repositioning the Control for the Application . . . . . . .7
Moving the Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7 Installing the Duct Collars . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7 Installing the Dehumidifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Dehumidifier Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Leveling and Raising the Dehumidifier . . . . . . . . . . . . . . . 8 Installing a Condensate Pan Under the Dehumidifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Installing the Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Installing Ductwork . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Ducting the Dehumidifier Inlet and Outlet to the HVAC System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Ducting the Dehumidifier Outlet to the HVAC System with Dedicated Dehumidifier Inlet Register . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11

Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Wiring to the HVAC System . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Optional W & Y Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Wiring to External or Remote Controls . . . . . . . . . . . . . . . 12 Wiring to a Float Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Ventilation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Zoning the Dehumidifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Required Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Installer Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Setting Up Remote Control ­ Crawl Space/ Sealed Attic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Setting Up Ventilation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Setting Up Zoning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Setting Up External Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Allowing DEH W/AC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Applying an RH Offset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Starting Up the Unit and Sequence of Operation . . . . . .17 Using the Dehumidifier Control Only . . . . . . . . . . . . . . . . . 17 Using a Model 76 as a Remote Control . . . . . . . . . . . . . . 17 Using an External Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Two-Zone Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Diagnostic Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Service Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Limited Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Warranty Registration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

2 English

SAFETY INSTRUCTIONS
Be sure to read and understand all safety precautions and instructions before installing and operating the unit .
! WARNING
The following precautions indicate a hazardous situation that, if not avoided, could result in death or serious injury . · Always disconnect electrical power before starting
installation or servicing to avoid electric shock . · Always wear glasses/goggles and gloves when
installing the unit . Sharp edges may cause serious cuts . Use care when cutting plenum openings and handling ductwork . · Be sure to use caution when handling the unit . Dropping the unit may cause personal injury or equipment damage .
! CAUTION
The following precautions indicate a hazardous situation that, if not avoided, could result in minor or moderate injury . · Be sure the installation, service and maintenance
are performed by a qualified service technician. Improper installation may cause injury or property damage . · This unit is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the unit by a person responsible for their safety . · Be sure to supervise children to ensure that they do not play with the unit . · Be sure to replace a damaged supply cord . It must be replaced by a special cord or assembly available from the manufacturer or its service agent .
NOTICE
The following statements indicate a situation which can cause damage to the equipment and personal property, or cause the equipment to operate improperly. · Do not use in pool applications. Pool chemicals can
damage the dehumidifier. · Do not use solvents or cleaners on or near the
circuit board. Chemicals can damage circuit board components. · Wait 24 hours before running the unit if it was not shipped or stored in the upright position. · Do not use dehumidification to prevent window condensation in the winter. To address window condensation, use ventilation to lower indoor humidity in the winter.

WHOLE HOME DEHUMIDIFICATION
The AprilAire® Dehumidifier controls the humidity level in your entire home . A powerful blower inside the dehumidifier draws air into the cabinet where it is filtered before having moisture removed . A sealed refrigeration system removes moisture by moving the air through a series of tubes and fins that are kept colder than the dew point of the incoming air . The dew point is the temperature at which moisture in the air will condense, much like what occurs on the outside of a cold glass on a hot summer day . The condensed moisture drips into the dehumidifier drain pan to a drain tube routed to the nearest floor drain or condensate pump . After the moisture is removed, the air moves through a second coil where it is reheated before being sent back into the home . The air leaving the dehumidifier will be warmer and drier than the air entering the dehumidifier . You can reduce the amount of humidity that enters the home by closing windows, doors and fireplace flues when outdoor humidity is high, and by drying clothes outside . Direct exhaust from kitchen vents and bath fans is the best means of controlling humidity due to cooking and showers/baths . The dehumidifier is not designed to prevent window condensation in winter . Use ventilation to lower indoor humidity levels in the winter .
OPERATING THE DEHUMIDIFIER
1 . Use the ON/OFF Power Switch, located by the power cord, to apply power to the dehumidifier .
NOTE: The ON/OFF Power Switch should stay ON unless the unit will not be used for an extended period. Use the ON/ OFF Button on the control panel to turn the unit off for short durations. With the ON/OFF Button in the ON position and the dehumidifier idle (neither the fan nor the compressor running) the unit will use less than 3W of power.
1
2

3 4

Figure 1: Exterior Components of the Dehumidifier

1 – Control Panel 2 – ON/OFF Power Switch

3 – Filter Access Door Retaining Screw
4 – Filter Access Door

3 English

2 . Use the ON/OFF Button (see Figure 2) on the control panel to turn the dehumidifier ON . The first press of a button will turn on the display light, so if the display was dark, you might need to press it again . Once ON, the display will show the current dehumidifier setting .
Figure 2: Turning Dehumidifier On 3 . The dehumidifier blower will turn on, the word
SETTING disappears from the display, and the words AIR SAMPLING appear (see Figure 3) . This wording indicates that the dehumidifier is sampling the air to determine if dehumidification is needed and shows the measured humidity level . If the control is already ON, lowering the setting will initiate air sampling .
AIR SAMPLING
Figure 3: Air Sampling 4 . If the Relative Humidity (RH) is above the setting, the
compressor turns on to dehumidify the space . The word DEHUMIDIFYING appears when the compressor is turned on (see Figure 4) .

ENERGY SAVINGS TIPS
ENERGY SAVINGS TIP #1: Adjust the humidity setting to be as high as is comfortable to reduce dehumidifier run time . If it feels clammy or “smells musty,” lower the humidity setting . To save energy, turn the dehumidifier to OFF when you open your windows, just as you would with air conditioning . ENERGY SAVINGS TIP #2: If vacating your home for an extended period in the summer, set the RH at 55% and set your thermostat as high as you are comfortable setting it to in the cooling mode . This will keep the humidity at a controlled level while minimizing the amount of cooling energy used .
MAINTENANCE
CLEANING THE FILTER
After initial installation the air filter and drain should be checked and cleaned every 6 months . 1 . Press the ON/OFF Button on the control panel to turn
the unit OFF . 2 . Loosen the retaining screw on the filter access door
(see Figure 1) from the drain side of the dehumidifier until it releases and then remove the filter door . 3 . Slide the filter out of the dehumidifier . 4 . Rinse the filter with water to remove dust and collected particles from the filter . 5 . Shake off excess water from the filter . 6 . Clean the drain as described in Cleaning the Drain on page 5 . 7 . Reinstall the filter . An arrow on the filter frame shows the direction of airflow and it should point into the dehumidifier . 8 . If the filter does not slide back in, make sure the drain insert has been properly installed . See Installing the Drain on page 9. 9 . Replace the filter access door and tighten the retaining screw . 10 . Press the ON/OFF Button to turn the dehumidifier back ON . The CLEAN FILTER service reminder (see Figure 5) will display on the control every 6 months . To clear the service message, press the p and q buttons simultaneously for 3 seconds .

Figure 4: Dehumidifying

4 English

Figure 5: Clean Filter Service Reminder

CLEANING THE DRAIN
1 . With the filter door on the drain side of the dehumidifier removed, reach in and pull out the drain insert using the finger loop (see Figure 6) .
1

Figure 6: Drain Cleaning
1 – Drain Insert
2 . Clean the drain pan and drain insert using a mild detergent .
3 . If the drain has a capped tee or elbow to allow cleaner to be poured directly in the drain, remove the cap and pour approximately one cup of vinegar into the tube (see Figure 7) . If there is no visible access to the drain line from outside of the dehumidifier, pour approximately one cup of vinegar into the drain pan of the dehumidifier where the drain insert was located .
4 . Reinstall the drain insert by gently placing the tip into the drain opening and rocking the insert downwards into place . When inserted properly, the top of the drain insert will be at the same height as the filter guide channel .
5 . If the dehumidifier has clear flexible drain tubing, look for excess buildup in the drain line that might prevent water flow, and replace as needed . Clear, smooth, flexible 3/4″ inner diameter (ID) drain tubing is available in most hardware stores or Do-ItYourself (DIY) retail stores .
NOTICE
Running the dehumidifier without the drain insert can lead to condensate leaks.

90-2607
NOTE: Drain insert must be installed before operationg. 1

2 90-2693

Figure 7: Capped Drain Access for Cleaning Process

1 – Cap

2 – Condensate Drain Line

5 English

SPECIFICATIONS

Unit Weight Capacity 80°F, 60% RH Conditions Power 115 VAC, Single Phase, 60 Hz Dehumidifier Inlet Air Conditions Filter
Airflow

Model E080 63 lbs .
80 pints per day @ 185 CFM

Model E100 64 lbs .
100 pints per day @ 280 CFM

5 .1A operating current

6 .9A operating current

Dehumidification: 50°F­104°F, 40°F dew point minimum Ventilation: 40°F­140°F, 0% RH­99% RH (non-condensing)

MERV 8, washable

External Static Pressure (“WC)

Airflow (CFM)

External Static Pressure (“WC)

Airflow (CFM)

0 .0

185

0 .0

280

0 .2

135

0 .2

245

0 .4

85

0 .4

210

0 .6

175

NOTE: Rated capacity and current draw measured at 80°F/60% RH inlet conditions at 0.0 external static pressure.
PREPARING THE UNIT FOR INSTALLATION
IMPORTANT: Cut the strap securing the compressor shipping support bracket and remove the strap and shipping bracket . See Figure 8 . 1 . Clip off and remove the plastic straps securing the
compressor to the shipping bracket . 2 . Remove the two screws securing the shipping
bracket to the housing . Remove and discard the shipping bracket, and reinstall the two screws in the dehumidifier .

2 1

90-1908
Figure 8: Preparing the Unit for Installation 1 – Clip Off Plastic Strap 2 – Remove Shipping
Bracket

6 English

REPOSITIONING THE CONTROL FOR THE APPLICATION
Locate the onboard control panel on the top of the dehumidifier or at the front of the dehumidifier if the control panel cannot be seen/accessed in the top orientation . It may also be rotated 180 degrees in either orientation (see Figure 10) .

2 1

1 2

INSTALLING THE DUCT COLLARS
· Use the screws in the parts bag to attach the duct collars to the inlet and outlet of the dehumidifier . The outlet collar has a backflow damper .
· The outlet duct collar may be attached to the top or end of the unit . Move the outlet cover to the location not being used . See Figure 11 .
· Make sure there are no bends in the ductwork coming off the outlet for a minimum of 4″ . This precaution will ensure that the ductwork will not interfere with the backflow damper function .

2

3

1

3
Figure 9: Control Panel Location

90-1884

1 – Control Panel Door 3 – Filter Access Door

2 – Control Panel

1

4 5

Figure 10: Control Panel Rotated 180 Degrees

90-2525

MOVING THE CONTROL
1 . Remove the front control panel door . 2 . Remove the filter access door and filter . 3 . Detach the onboard control panel by removing the
four (4) screws around the control panel . NOTE: Use one hand to support the bottom of the onboard control panel when removing. 4 . Keep the control panel in the unit and relocate to
the front access hole . 5 . Secure the control panel with the same four screws
used to attach the control panel to the top of the unit . 6 . Secure the control panel door to the top of the unit .

6

90-2592

Figure 11: Fully Ducted Installations

1 – Inlet Duct Collar 2 – Outlet Cover 3 – Outlet Duct Collar w/
Back Draft Damper

4 – End Discharge 5 – Move Outlet Cover
and Install Outlet Duct Collar to Top Discharge Location 6 – Top Discharge

7 English

INSTALLING THE DEHUMIDIFIER

DEHUMIDIFIER LOCATION

· Electrical service access and drain cleaning will require the removal of the electrical service side panel (see Figure 12) . Allow sufficient space for service on this side of the unit .
· The filter can be removed from either side of the dehumidifier . Allow sufficient space for the filter to be removed and reinstalled .
· If locating the unit where it is not readily accessible (such as a crawl space, an attic or even a basement for some individuals), consider controls such as the Model 76 Dehumidifier Control, which can be mounted in the living space and wired to the dehumidifier .
· For attic installations, suspending the dehumidifier is recommended .
· Always install the dehumidifier in or above a condensate pan when locating in or above a finished space .

2

1

6″

LEVELING AND RAISING THE DEHUMIDIFIER
The feet can be adjusted to level the unit and accommodate drain fittings and condensate pans as required . Use the top-mounted bubble level to adjust the feet until the bubble is within the outer circle (see Figure 13) . Leveling is required to ensure proper drainage from the dehumidifier . If installing a condensate pump to the side of the unit more elevation than can be provided by the adjustable feet may be needed . Risers or hanging kits are available to lift the dehumidifier higher off the floor .
2

1

OK

OK

NO

4

6

5

4

15″ 3

Figure 12: Filter Access Clearance

90-1840

1 – Electrical Service and Drain Access this Side
2 – 6″ Minimum Clearance for Proper Airflow

3 – 15″ Minimum Clearance for Filter (Either Side)
4 – Filter 5 – Top View 6 – 6′ Power Cord

3 Figure 13: Leveling the Unit

90-2692

1 – Bubble Level 2 – Bubble Level Detail

3 – 3/4″ Drain 4 – 0 .38″ Minimum
2 .00″ Maximum

INSTALLING A CONDENSATE PAN UNDER THE DEHUMIDIFIER
Always install the dehumidifier in or above a condensate pan when locating it above a finished space . Adhere to local codes regarding draining of the condensate pan . If a condensate pump is needed, make sure it is in the condensate pan as well . Install a float switch in the condensate pan and/or use the overflow wires/terminals on the condensate pump to stop the dehumidifier should overflow occur . See Wiring to a Float Switch on page 12.

8 English

INSTALLING THE DRAIN
Using Hard Pipe: · Install a 3/4″ PVC slip x 3/4″ MNPT PVC fitting to the
dehumidifier and use 3/4″ nominal PVC Schedule 40 pipe to run the condensate line to the nearest floor drain or to an outside location that slopes away from the building . · Always maintain a constant downward slope in drain piping . Ensure that drain tubing does not interfere with removal of the side panel or filter door . · Do not use metal fittings and only hand-tighten threaded fittings . PTFE thread seal tape is recommended for threaded connections . · Install a tee or three-way elbow at the dehumidifier outlet with a small, capped vertical tube (do not cement cap in place) to allow for cleaner to be poured into the drain line (see Figure 14) . · PVC primer and cement is recommended for slip-fit connections (do not cement threaded connections) .
1

INSTALLING DUCTWORK
· Use insulated duct when the dehumidifier is located in an unconditioned space, such as an attic, garage or crawl space, or if connecting a fresh air duct to the dehumidifier ductwork .
· Use zip ties, mastic, and tape as needed to seal the duct connections to the dehumidifier and to seal the insulation sleeves to prevent condensation inside the ductwork .
Connecting the dehumidifier to your HVAC system will pull air to be dehumidified from the whole home and similarly will discharge air to the whole home . Make sure the duct system pressure the dehumidifier will have to operate against does not exceed 0 .4″ Water Column (WC) for Model E080 and 0 .6″ WC for Models E100/E100H . Measure the system pressure when the HVAC fan is operating at the highest airflow (speed) setting . There are not always readily available locations on the HVAC duct system for connecting 10″ ducts, and some local codes do not allow ducting to the return side of the HVAC system . If so, another option is to install just the discharge of the dehumidifier to the HVAC system or to use dedicated registers for both the inlet and discharge of the dehumidifier .

2

3

4

Figure 14: Capped Drain Access for Cleaning

90-2693

1 – Cap 2 – Small Section
of Drain Tube

3 – 3/4″ 3-Way elbow or Tee and Below
4 – Condensate Drain Line

Using Flexible Tubing:

· Install the provided 3/4″ NPT x 3/4″ hose barb fitting and use 3/4″ flexible drain tubing . Hand-tighten the fitting to the dehumidifier . PTFE thread seal tape is recommended for threaded connections .

· Always maintain a constant downward slope from the dehumidifier to the nearest floor drain or condensate pump, and do not allow soft tubing to curl up, which may result in air lock .

9 English

DUCTING THE DEHUMIDIFIER INLET AND OUTLET TO THE HVAC SYSTEM

Return-to-Return Basement Installation

Return-to-Supply Basement Installation

2

1

4

6′ Min

3

7 6 5

8 4

19

Return-to-Return Attic Installation

17

11

6′ Min

90-1886
18

9

Return-to-Supply Attic Installation 7

10

6

11

90-1887
12

13 15

14 90-1888

Figure 15: Four Installation Configurations

24″ Min
16
15

13 14
90-1889

1 – Air is Pulled from the Main Return Duct and Discharged to the Main Return Duct
2 – 10″ Duct 3 – 6′ Minimum 4 – HVAC/Furnace 5 – Air is Pulled from the Main Return Duct 6 – Model E080 0 .4″ WC Maximum 7 – Model E100H 0 .6″ WC Maximum 8 – Air is Discharged to the Supply Duct 9 – 10″ Duct
· Use when both sides of the duct system are accessible (see Figure 16) .
· When ducting from return to supply, the HVAC blower does not need to be running when the dehumidifier is running .
· When ducting return to supply, allow adequate space before the first branch duct to ensure the warm dehumidified air is thoroughly mixed with the HVAC system air .

10 11 12 13 14 15 16 17 18 19 –

Plenum Box Air Handler Plenum Filter Condensate Pan 10″ Diameter Insulated Duct Both Sides 24″ Minimum 6′ Minimum Plenum Box or Y-Fitting Dehumidifier

· When ducting from return to return, wire the dehumidifier to the HVAC system as shown in Figure 20 to ensure the HVAC blower runs when the dehumidifier is operating .
· Wire the dehumidifier to the HVAC system (see Figure 20 for exact wiring) and set up the dehumidifier to be disabled when the AC is running .

10 English

DUCTING THE DEHUMIDIFIER OUTLET TO THE HVAC SYSTEM WITH DEDICATED DEHUMIDIFIER INLET REGISTER

· To direct dehumidified air away from a potentially

4

wet AC coil:

– Duct to the supply side of the HVAC system

2 3

for air handler applications where air is pulled

through the AC coil (see Figure 16) .

1

Dedicated Return to Main Supply

1

2

3

Figure 16: Discharge to Supply Side

90-2691

1 – Supply 2 – Return

3 – HVAC Equipment

– Duct to the return side of the HVAC system for furnace applications where air is pushed through the AC coil . Check local codes to verify that ducting to the return side of the HVAC system is allowed (see Figure 17) .
Dedicated Return to Main Return

2

1

3

Figure 17: Discharge to Return Side

90-2691

1 – Supply 2 – Return

3 – HVAC Equipment

· Wire the dehumidifier to the HVAC system as shown in Figure 20 and set up the dehumidifier to be disabled when the AC is running .
Use dedicated registers to duct the dehumidifier to the whole home when HVAC system ductwork is unavailable or impractical (see Figure 18) .

6 Figure 18: Stand-Alone Duct

5 90-1893

1 – Air is Pulled from Ducted Space
2 – Dehumidified Space 3 – 10′ Minimum

4 – Dehumidified Air is Supplied to Ducted Space
5 – Dehumidifier 6 – Grill with 10″ Duct
Collar (2 Places)

WIRING
No additional wiring is needed unless: · the dehumidifier is ducted to the HVAC system · a separate, external control such as a thermostat or
dehumidistat is to be used · a float switch, either integral to a condensate pump
or mounted to the condensate pan, is used Use 18-22 AWG wire for any needed wiring . Access the dehumidifier wiring terminals by pulling off the wiring access cover near the dehumidifier control display (see Figure 19). Snap the wiring access cover back into place after completing all wiring .
1

Figure 19: Wiring Access Cover Location 1 – Wiring Access Cover

90-1884
11 English

WIRING TO THE HVAC SYSTEM
When the dehumidifier is ducted to the HVAC system, it is recommended that it also be wired to the HVAC system as shown in Figure 20 . If ducted to the HVAC system in a return-to-return configuration, the dehumidifier must be wired to the HVAC system to prevent short-circuiting dehumidified air directly back to the dehumidifier inlet . In a return-to-supply ducting configuration, running the HVAC fan with the dehumidifier ensures the warm dry air is mixed with room air before being discharged to the home .
OPTIONAL W & Y WIRING Wire the W and/or Y terminal to the HVAC system when using the ventilation feature of the dehumidifier . See Ventilation on page 13. Wire the dehumidifier Y terminal to the HVAC system to disable the dehumidifier compressor from operating when the air conditioning is running . See Allowing DEH W/AC on page 16 for additional setup steps required to access this feature .

WIRING TO EXTERNAL OR REMOTE CONTROLS
The dehumidifier can be wired to an external control that senses the humidity in the living space, such as an AprilAire Thermostat or the Model 76 Dehumidifier Control . This is most often done when the dehumidifier is ducted to the HVAC system and is located in a hard-to-reach location such as an attic or basement . The Model 76, when used as a remote control, allows the user to see the humidity sensed by the dehumidifier and adjust the dehumidifier setting from a remote location . This is most often used when the dehumidifier is not ducted to the HVAC system and serves a hard-to-reach location such as a crawl space or basement . If using an external control, wire to the DH terminals of the dehumidifier (see Figure 21) . Most external controls use a normally open switch that closes with a dehumidification demand, in which case leave the NC/NO switch in the NO position . For controls that use a normally closed switch, put the NC/NO switch in the NC position . If using the AprilAire Model 76 as a remote control, wire to the {+ – A B} terminals . Refer to the installation instructions for the control being used for wiring details .

+ – A B ODT VENT DEH Remote Sensor Dampers

FLOAT DH DH Switch

GhRf Cf Gs W Y HVAC EQUIP.

1 2

4 3

G

R

R

C

C

G

W

W

Y

Y

5
90-1859

Figure 20: Wiring to HVAC System

1 – Existing Wire 2 – New Wire 3 – Thermostat or Zone
Control Board

4 – HVAC Equipment 5 – Optional Wires

1

2

90-2694

Figure 21: Wiring to an External or Remote Control

1 – Use for External

2 – Use for Remote

Control Applications

Control Applications

WIRING TO A FLOAT SWITCH
Use only if the installation includes a float switch or a condensate pump . The dehumidifier leaves the factory with a jumper wire installed in the float switch terminals . Remove the jumper and wire the float switch terminals to the float switch or condensate pump overflow switch as shown in Figure 22 .

12 English

FLOAT DH DH Switch

1

1
Figure 22: Float Switch Wiring 1 – Normal Closed
Float Switch

90-1857

VENTILATION
The dehumidifier can activate a normally closed damper to bring in outdoor air through a fresh air intake duct . This feature cannot be used when a Model 76 has been installed in a remote control application and should not be used in two-zone installations . 1 . Install the Fresh Air Inlet (FAI) duct and damper as
shown in Figure 23 and Figure 24 .

2 4
M3IN

90-1898
Figure 24: External Control Ventilation Installation

1 – Air is Pulled from Outside
2 – HVAC/Furnace

3 – 6′ Minimum 4 – Normally Closed
Vent Damper

2 . Install the Outdoor Temperature Sensor (ODT) as shown in Figure 25 and Figure 26 ­ only needed if ventilation will be limited during high or low outdoor temperature conditions .

1 2

1 2

5 3
4 90-1897

Figure 23: Onboard Control Ventilation Installation

1 – Air is Pulled from Outside
2 – 6′ Minimum 3 – HVAC/Furnace

4 – Balancing Dampers 5 – Normally Closed
Vent Damper

4

3

B2202617-D

Figure 25: ODT Mounted Outside

1 – North, East or West Side of Home
2 – Outdoor Temperature Sensor

3 – Above Expected Snow Line
4 – Outdoor Temperature Sensor Leads

13 English

1

2

3 B2202617-E

Figure 26: ODT Mounted in Intake Duct

1 – Center Line 2 – 36″ Maximum

3 – Outside Wall

3 . Wire the FAI damper, HVAC equipment and outdoor temperature sensor to the dehumidifier control as shown in Figure 27 .

+ – A B ODT VENT DEH Remote Sensor Dampers

FLOAT DHDH Switch

Gh Rf Cf Gs W Y HVAC EQUIP.

1 2 3

4

5

Y

Y

W

W

G

C

C

R

R

G

90-1861

Figure 27: Ventilation Wiring

1 – Optional Outdoor Temperature Sensor (Model 8052)
2 – 6″ Normally Closed Damper or 8190FF

3 – 24 VAC (10 VA MIN) Transformer (E100V: Use external 24V port)
4 – HVAC Equipment 5 – Thermostat or Zone
Control Board

4 . Use the setup menu to ENABLE ventilation: a . Enter the installer setup menu (see page 15) . b . Press the Mode button until the words VENT DISABLE appear . c . Press the s or t button to change to VENT ENABLE .

d . Press the Mode button and the words VENT TIMED will appear . Press the s or t button to set temperature limits: · TIMED: no temperature limits · AUTO ­ B: Ventilation is not allowed if the ODT > 100°F or ODT < 0°F; ventilation is allowed only when the heat is on if the ODT is between 0°F and 20°F · AUTO ­ C: Ventilation is not allowed if the ODT > 100°F or ODT < 0°F · AUTO ­ D: Ventilation is not allowed if the ODT > 90°F; ventilation is allowed only when the heat is on if the ODT is between 0°F and 40°F
e . Press the Mode button and then use the s or t button to set the ventilation time (minutes/hour) .
f . Press the Mode button repeatedly until the word DONE appears on the display .
Whenever the heating, cooling or dehumidifier is turned on, the ventilation damper will open and bring in outdoor air . If the equipment doesn’t run for the set number of minutes, the dehumidifier will turn on the HVAC fan at the end of the hour to ensure ventilation needs are met .
ZONING THE DEHUMIDIFIER
The dehumidifier can be configured to condition two independent spaces . Zoning requires the installation of ductwork and dampers to direct air to and from two locations . Scan the QR code for details on zoning the installation . NOTE: Dehumidifier zoning is not recommended in HVAC zoning applications. In this installation the dehumidifier controls the humidity in two separate zones, a Primary and Secondary Zone . The dehumidifier will dehumidify the Primary Zone as the first priority and will switch to the Secondary Zone after the dehumidification needs of the Primary Zone have been satisfied . IMPORTANT: Normally Closed dampers must be installed in the ducts serving the Primary Zone and Normally Open dampers installed in the ducts serving the Secondary Zone .
REQUIRED COMPONENTS
· 10″ ductwork and fittings · Grilles with 10″ duct collars · Drain line · 2 ­ AprilAire Model 6510, 10″ Normally Closed damper · 2 ­ AprilAire Model 6610, 10” Normally Open damper · 24 VAC transformer (40 VA min .) for dampers NOTE: 5442 Basement Kit includes 2 ­ 6510 Dampers, 2 ­ 6610 Dampers and a 24 VAC (40 VA) transformer.

14 English

5 4 3

2

6

6′
Min 9

1

7 8
90-1875
Figure 28: Whole-Home Primary Zone Installation

1 – Return from Secondary Zone
2 – Normally Closed Dampers
3 – Return Duct 4 – To/From Primary
Zone 5 – Supply Duct

6 – Supply to Secondary Zone
7 – Normally Open Damper
8 – Normally Open Damper
9 – 6′ Minimum

2

34

+ – A B ODT VENT DEH

5

1 . Plug unit in and turn power switch ON . 2 . The onboard control screen should display OFF . If
not OFF, press the ON/OFF button to turn the unit OFF .
NOTE: If the display backlight is not on, the first button press (any button) will only turn on the backlight. Press the button a second time to achieve function. 3 . Hold the MODE button on the onboard control for 3
seconds to enter the installer setup menu . 4 . Navigate through the following screens to set up
the dehumidifier for the installed application . 5 . Use the s or t button to select items and use the
MODE button to switch to the next setup option . To exit the installer setup, scroll through all options using the MODE button . 6 . After the installer setup options have been completed, the word DONE will blink for 3 seconds and the control will return to the OFF screen .

FLOAT DH DH Switch

Gh Rf Cf Gs W Y

1

90-1896

6

7

8

Figure 29: Two-Zone Wiring On-Board Control

1 – FLOAT Switch 2 – Remote 3 – Sensor 4 – Dampers 5 – HVAC Equipment

6 – 24 VAC (40 VA Min .) 7 – Normally CLosed
(Primary Zone) 8 – Normally Open
(Secondary Zone)

NOTE: Dehumidifier zoning is not recommended in HVAC zoning applications.

INSTALLER SETUP

Enter the setup menu if: · the dehumidifier is ducted to the HVAC system · an external or remote control will be used · ventilation or zoning will be used

15 English

SETTING UP REMOTE CONTROL ­ CRAWL SPACE/SEALED ATTIC
If wiring to a Model 76 for remote control (see page 17 for details) press the s or t button to ENABLE .

SETTING UP EXTERNAL CONTROL
If wiring to an external control (see page 12 for details) press the s or t button to ENABLE .

SETTING UP VENTILATION
See page 13 for details if using the dehumidifier for ventilation .

ALLOWING DEH W/AC
To allow dehumidification during active air conditioning, select ENABLED and press the MODE button .

SETTING UP ZONING
See page 14 if zoning the dehumidifier .

To disable dehumidification when the air conditioning is on, on select DISABLED and press the MODE button .

16 English

APPLYING AN RH OFFSET
An offset can be applied to the onboard humidity reading to avoid discrepancies with other humiditymeasuring devices in the home . Use the s or t button to select an offset from -5% to 5% . Press the MODE button to exit the installer setup screens .
STARTING UP THE UNIT AND SEQUENCE OF OPERATION
Use the ON/OFF Power Switch near the power cord to apply power to the dehumidifier.
USING THE DEHUMIDIFIER CONTROL ONLY
1 . Press the ON/OFF Button to turn the dehumidifier control ON . The display will show the current humidity setting, and the dehumidifier blower and HVAC blower (if wired to the HVAC system) will turn on to start sampling . The setting will be replaced by the measured humidity and the words AIR SAMPLING appear on the display .
2 . Use the s or t button to adjust the humidity setting as desired . The recommended initial setting is between 55% and 59% .
3 . After three (3) minutes of sampling, the measured humidity will be compared to the setting: a . If the humidity is above the setting, the dehumidifier compressor turns on and the words AIR SAMPLING will be replaced by the word DEHUMIDIFYING . The compressor remains on until the measured humidity falls 3% RH below the setting . b . If the measured humidity is below the setting, the blowers turn off and the display returns to showing the RH setting .
4 . The dehumidifier will sample again every 60 minutes, or at any time if the humidity setting is lowered .

USING A MODEL 76 AS A REMOTE CONTROL
1 . Press the ON/OFF Button to turn the dehumidifier control ON . The display will show the word REMOTE to indicate that a remote control is to be used to control the dehumidifier .
2 . At the Model 76, press the ON button; the Model 76 will display the RH measured at the dehumidifier, and the dehumidifier blower will turn on to start sampling the air .
3 . Use the s or t button on the Model 76 to adjust the dryness level as desired . The dryness levels range from 1 to 7, with 1 being least dry and 7 being most dry; the recommended initial setting is 3 .
4 . After three (3) minutes of sampling, the measured humidity will be compared to the setting: a . If the humidity is above the setting, the dehumidifier compressor turns on and the word ON flashes on the Model 76 display . b . If the measured humidity is below the setting, the dehumidifier blower turns off .
5 . The dehumidifier will sample again every 60 minutes, or at any time if the dryness level is increased .
USING AN EXTERNAL CONTROL
1 . Press the ON/OFF Button to turn the dehumidifier control ON . The display will show the word EXTERNAL to indicate that an external control is to be used to control the dehumidifier .
2 . At the external control, initiate a dehumidification demand . Refer to the literature provided with the external control . The dehumidifier fan and compressor, and the HVAC fan (if wired to do so) will turn on and the word DEHUMIDIFYING will appear on the display of the dehumidifier .
NOTE: When using an external control, there is a threeminute delay after power-up (i.e., ON/OFF Power Switch is turned ON with unit plugged in) before the dehumidifier will respond to an external control. This prevents unanticipated, early start-up after power is applied. 3 . Discontinue the demand at the external control; the
dehumidifier and HVAC fan will turn off .
TWO-ZONE OPERATION
The Primary Zone operates as listed for using the dehumidifier control or an external control . “PRIMARY ZONE” shows on the display when operating . The Secondary Zone uses the humidity setting on the dehumidifier control . During Secondary Zone operation, the installed dampers are de-energized and the HVAC blower (if on) stops . “SECONDARY ZONE” shows on the display when operating . The Secondary Zone is sampled immediately after the Primary Zone has finished sampling, or if there is a call for dehumidification from the Primary Zone,
17 English

immediately after the call has been satisfied . When an external control is installed, the Secondary Zone will be sampled once per hour if there has not been a call for dehumidification from the Primary Zone .
TROUBLESHOOTING
Technical support is available Monday through Friday 7:00 a .m . to 5:00 p .m . CST at 800-334-6011 . Use the guides on the following pages to identify and correct system faults . Contact Technical Support before replacing the unit or any components and for additional troubleshooting .

DIAGNOSTIC CODES
When an error occurs, the Diagnostic Code along with SERVICE REQUIRED will be displayed on the control screen .

Table 1: Diagnostic Codes

Diagnostic Code

Failure Mode

Action

Reset

E1

Internal Humidity 1 . Cycle power to clear error code .

Cycle Power

or Temperature Sensor Open or

2 . If error code reoccurs, replace User Interface, Part No . 5445 .

Shorted

E2

High

1 . Verify that the fan works, the backflow damper swings freely,

Cycle Power

Refrigeration

and there is no blocked or restricted ductwork .

Pressure

2 . If the fault persists, call Technical Support .

E3

Model 76

1 . Check connections between Model 76 and dehumidifier control

Self-

Remote Control

board . Terminals should be fully inserted and secured in the

Correcting

Communication

control board and Model 76 control terminals .

Loss

2 . If connections are correct and secure, turn off the dehumidifier

and remove the Model 76 . Use a short section of 4-wire cable

to reconnect the Model 76 to the control board . Turn the

dehumidifier back on and increase the dryness level setting on

the Model 76 . If the dehumidifier turns on, a problem exists with

the wiring between the dehumidifier and control .

3 . If the dehumidifier does not turn on, call Technical Support .

E4

Insufficient

Capacity

1 . Check the frost sensor connection at the power board . The terminal should be fully seated on the power board pins .
2 . Remove the side access panel and verify that the sensor is secured to the suction line .
3 . If the sensor is connected and secured to the refrigeration line, proceed to the next step .
4 . Reset the fault by cycling power to the dehumidifier . 5 . Turn the humidity setting down (below room/home humidity
level) to make a dehumidification call .

Cycle Power

18 English

Table 1: Diagnostic Codes

Diagnostic Code

Failure Mode

Action

Reset

E4

Insufficient

Capacity

6 . Allow the fan and compressor to run for approximately 10-15 minutes and then enter diagnostic test mode by simultaneously pressing the s button and MODE button for 3 seconds . The LCD will display: · the temperature measured by the internal sensor while also displaying the words AIR SAMPLING and ON · the humidity measured by the internal sensor while also displaying %RH and the word ON · the frost sensor temperature while also displaying the word ON

Cycle Power

Scroll through these values and by using the s or t button . 7 . Record values and call Technical Support .

E5

High

Check the high temperature sensor connection at the power board . Cycle Power

Temperature

The terminal should be fully seated on the power board pins .

Thermistor Failure

Remove the side access panel and verify the sensor is not damaged and connected to the refrigeration line coming from the compressor .

If the sensor is connected and secured to the refrigeration line, it may need to be replaced with Part No . 5456 ­ contact Technical Support to confirm .

E6

Low Temperature Check the low temperature sensor connection at the power board . Cycle Power

Thermistor Failure

Remove the side access panel and verify the sensor is not damaged and connected to the suction line .

If the sensor is connected and secured to the refrigeration line, it may need to be replaced with Part No . 5455 ­ contact Technical Support to confirm .

E7

Float Switch

Open

Empty the condensate pan . Check the float switch connection at the control board . If not using a float switch, verify jumper is between float switch terminals on dehumidifier control board . If the problem persists, replace the float switch .

SelfCorrecting

E8

Inlet Air

1 . Verify all ductwork is properly sealed .

Self-

Temperature Out of 50°F­104°F Range, or Dew

2 . Check for air leakage that might affect the temperature or RH of the incoming air .

Correcting

Point Below 40°F 3 . If the air temperture is in range and the dew point is above 40°F,

contact Technical Support .

E9

Outdoor Temperature Sensor Open or Shorted

1 . Check the sensor connection at the power board .
2 . Remove the wires from the terminals and measure the resistance . A short circuit

Outdoor Temperature
0°F

Resistance 84,500 Ohms

SelfCorrecting

will have a resistance very close to 0 Ohms and an open circuit will have a very

20°F

46,000 Ohms

high resistance . Use the Ohms chart on page 21 to approximate the resistance

40°F

26,000 Ohms

based on outdoor temperature .

60°F

15,500 Ohms

3 . If the sensor is not reading

correctly, replace the sensor,

80°F

9,500 Ohms

Part No . 8052 .

100°F

6,000 Ohms

19 English

Table 2: Troubleshooting Guide

Symptom

Possible Reason

Troubleshooting Procedure

Dehumidifier does not turn on/run .

No power to unit .

· Check that the dehumidifier is plugged in . · Check that the power switch is turned ON . · Check that the control is turned ON . · Check that the circuit breaker has not tripped .

Dehumidifier blower is running but with little or no airflow .

Pressure drop across dehumidifier is higher than 0 .4″ WC for Model E080 or 0 .6″ WC for Model E100/ E100H .

· Check dehumidifier air filter and wash or replace . · Check for blocked ductwork and clear . · Verify that the outlet collar with backflow damper is installed on the
outlet side of the dehumidifier . · Check if backflow damper is blocked or stuck and remove obstruction .

Dehumidifier

Float Switch

· If float switch is installed, check connections at control board and

blower is running open (E7 appears

empty the condensate pan .

but compressor is not .

on display) .

· If no float switch is installed, check that the jumper is installed at the float switch terminals on the control board .

Unit is defrosting .

· Frosting occurs when the incoming air is cool and dry, normally during Spring or Fall, or the airflow is restricted . Frosting due to cold/dry conditions is a normal part of operation and “DEFROSTING” will show on the display . If it is not cool and dry, look for blocked ductwork or a dirty filter .

Inlet air temperature is outside of the 50°F­104°F range or the dew point is below 40°F and there is a demand for dehumidification .

· Verify all ductwork is properly sealed . Dehumidification will restart by itself when the incoming air temperature is within range and the dew point is above 40°F . E8 appears on the display when inlet air conditions prevent operation .

When zoned, the dehumidifier damper does not open in INSTALLER TEST mode .

Incorrect damper wiring or bad connection .

· Verify wiring between dampers and 24 VAC transformer . · If wired for Two Zone operation, verify that 24 VAC transformer is 40 VA
minimum . · Check all wiring connections between dampers and control board . · Verify the normally closed dampers are in the Primary Zone ductwork
and the normally open dampers are in the Secondary Zone ductwork .

20 English

Table 2: Troubleshooting Guide (Continued)

Symptom

Possible Reason

Troubleshooting Procedure

The ventilation damper does not open when the HVAC fan is active .

Cycle time has been met . ODT error or outdoor air outside of ODT range .

· The damper will not open if the ventilation time has already been met .

· Check that the ODT is wired correctly to the dehumidifier control board and connections are secure .
· Check that the ODT is installed in the outdoor air intake according to the setup specified in VENTILATION ON PAGE 13 .
· Remove the ODT leads from the dehumidifier control board and check the resistance . Compare the reading with the chart on the right .

Outdoor Temperature
0°F 20°F 40°F 60°F

Resistance 84,500 Ohms 46,000 Ohms 26,000 Ohms 15,500 Ohms

80°F

9,500 Ohms

100°F

6,000 Ohms

Dehumidifier is not draining properly .
The HVAC fan turns on unexpectedly . Dehumidifier is producing hot air .

Drain line blocked or unit not level .
Dehumidifier is sampling or ventilation in progress . Normal function .

· Verify that the unit is level . · Check the drain line blockages and check for a continuous downward
slope . · Verify presence and condition of drain cover insert . See Maintenance
on page 4 for cleaning procedure, or replace with Part No . 5885 if missing or damaged . · The dehumidifier will turn on the HVAC fan during air sampling or as needed to meet the ventilation time .
· Air is reheated across the condenser coil, resulting in a temperature rise between inlet and outlet .

21 English

SERVICE PARTS
5 9

4 3 10

1 14
13

18 2

16A 17A 16B 17B

12A 15

6

11A

19

12B

11B

20

7 8
90-2595

No .

Part Description

Part No .

1 EZK Filter, 13 .5″ x 11 .875″ x 0 .875″

5881

2 Internal Control Board, Deh

5444

3 User Interface Assembly, Deh

5445

4 Wiring Access Door, AA Deh

5446

5 Hole Cover, UI Ctrl, Deh

5447

6 Door, Filter Access, AA Deh

5882

7 Outlet Duct Panel, Deh

5449

8 Backflow Damper, 10″, Deh

5450

9 Inlet Duct Panel, AA Deh

5451

10 Cover, Outlet, AA Deh

5452

Fan, 80pt Deh, with 6MFD Capacitor 11
Fan, 100pt Deh, with 12MFD Capacitor

5883 5886

Wire Harness, Power, Deh 12
Wire Harness, Power, Deh w/ Vent*

5884 5888

No .

Part Description

Part No .

13 Sensor, Low Temperature, Deh

5455

14 Sensor, High Temperature, Deh

5456

15 Leveling Foot, Deh

5457

16 Capacitor, Run, 50µF

5594

Capacitor, 6MFD, 250VAC, 80pt Deh 17
Capacitor, 12MFD, 450VAC, 100pt Deh

5582 5468

18 Drain Insert

5885

19 Drain Tube + Fitting

5692

20 8190FF/E100V Internal Wiring Harnesses 5914

Not Shown

8190FF/E100V External Wiring Harnesses 5887

22 English

LIMITED WARRANTY
Your AprilAire® Dehumidifier is expressly warranted for five (5) years from date of installation to be free from defects in materials or workmanship . The exclusive obligation of AprilAire under this warranty shall be to supply, without charge, a replacement for any component which is found to be defective within such five (5) year period and which is returned not later than thirty (30) days after said five (5) year period by you to either your original supplier or to AprilAire, Madison, Wisconsin 53701, together with the model number and installation date of the dehumidifier . THIS WARRANTY SHALL NOT OBLIGATE APRILAIRE FOR ANY LABOR COSTS AND SHALL NOT APPLY TO DEFECTS IN WORKMANSHIP OR MATERIALS FURNISHED BY YOUR INSTALLER AS CONTRASTED TO DEFECTS IN THE DEHUMIDIFIER ITSELF . IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE SHALL BE LIMITED IN DURATION TO THE AFORESAID FIVE YEAR PERIOD . THE APRILAIRE LIABILITY FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES, OTHER THAN DAMAGES FOR PERSONAL INJURIES, RESULTING FROM ANY BREACH OF THE AFORESAID IMPLIED WARRANTIES OR THE ABOVE LIMITED WARRANTY IS EXPRESSLY EXCLUDED . THIS LIMITED WARRANTY IS VOID IF DEFECT(S) RESULT FROM FAILURE TO HAVE THIS UNIT INSTALLED BY A QUALIFIED HEATING AND AIR CONDITIONING CONTRACTOR . IF THE LIMITED WARRANTY IS VOID DUE TO FAILURE TO USE A QUALIFIED CONTRACTOR, ALL DISCLAIMERS OF IMPLIED WARRANTIES SHALL BE EFFECTIVE UPON INSTALLATION . Some states do not allow limitations on how long an implied warranty lasts or the exclusion or limitation of incidental or consequential damages so the above exclusion or limitations may not apply to you . This warranty gives you specific legal rights and you may also have other rights which vary from state to state .

WARRANTY REGISTRATION
Visit us online at aprilaire .com to register your AprilAire product . If you do not have online access, please mail a postcard with your name, address, phone number, email address, product purchased, model number, date of purchase, and dealer name and address to: AprilAire, P .O . Box 1467, Madison, WI 53701 . Your warranty registration information will not be sold or shared outside of this company.

23 English

Internal Use Only
10016378 · B2210022A · 4.22 © 2022 AprilAire | aprilairepartners.com | 800.334.6011
AprilAire reserves the right to change specifications without notice.

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Aprilaire User Manuals

Related Manuals