AprilAire E100 Pro 100 Pint Whole House Dehumidifier Owner’s Manual
- June 16, 2024
- Aprilaire
Table of Contents
E100 Pro 100 Pint Whole House Dehumidifier
Product Information
Specifications
- Model: E080 & E100 Dehumidifier
Product Usage Instructions
Safety Instructions
Be sure to read and understand all safety precautions and
instructions before installing and operating the unit.
- ! WARNING
- ! CAUTION
- NOTICE
Whole Home Dehumidification
To use the dehumidifier for whole home dehumidification:
-
1. Use the ON/OFF Power Switch, located by the power cord, to
apply power to the dehumidifier.
Note: The ON/OFF Power Switch should stay ON unless the unit
will not be used for an extended period. Use the ON/OFF Button on
the control panel to turn the unit off for short durations. With
the ON/OFF Button in the ON position and the dehumidifier idle
(neither the fan nor the compressor running) the unit will use less
than 3W of power.
-
1. Use the ON/OFF Button on the control panel to turn the
dehumidifier ON.
The first press of a button will turn on the display light, so
if the display was dark, you might need to press it again. Once ON,
the display will show the current dehumidifier setting.
-
The dehumidifier blower will turn on, and the words “AIR
SAMPLING” will appear on the display. This indicates that the
dehumidifier is sampling the air to determine if dehumidification
is needed and shows the measured humidity level. -
If the Relative Humidity (RH) is above the setting, the
compressor turns on to dehumidify the space. The word
“DEHUMIDIFYING” appears when the compressor is turned on.
Energy Savings Tips
Here are some energy savings tips for using the
dehumidifier:
- TBD
Maintenance
To maintain the dehumidifier:
- TBD
Ventilation
To ensure proper ventilation:
- TBD
Zoning the Dehumidifier
To zone the dehumidifier:
- TBD
Required Components
The following components are required for installation:
- TBD
Installer Setup
To set up the dehumidifier:
- TBD
FAQ (Frequently Asked Questions)
- TBD
INSTALLED BY:
Product Info & Digital Manual
INSTALLATION AND OWNER’S MANUAL
Model E080 & E100 Dehumidifier
INSTALLER PHONE:
DATE INSTALLED:
PLEASE LEAVE THIS MANUAL WITH THE DEHUMIDIFIER OWNER
1 English
Table of Contents
Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . 3 Whole Home Dehumidification . . . . . . . . . . . . .
. . . . . . . . . . . . . 3 Operating the Dehumidifier . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . 3
Energy Savings Tips . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . 4 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . 4
Cleaning the Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . 4 Cleaning the Drain . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . 5 Specifications . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Preparing the
Unit for Installation . . . . . . . . . . . . . . . . . . . . . . . 6
Repositioning the Control for the Application . . . . . . .7
Moving the Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . .7 Installing the Duct Collars . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . .7 Installing the Dehumidifier . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . 8 Dehumidifier Location . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . 8 Leveling and Raising the
Dehumidifier . . . . . . . . . . . . . . . 8 Installing a Condensate Pan Under
the Dehumidifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . 8 Installing the Drain . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . 9 Installing Ductwork . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Ducting
the Dehumidifier Inlet and Outlet to the HVAC System . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Ducting the
Dehumidifier Outlet to the HVAC System with Dedicated Dehumidifier Inlet
Register . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .11
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . 11 Wiring to the HVAC System . . . . . . .
. . . . . . . . . . . . . . . . . . . . 12 Optional W & Y Wiring . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . 12 Wiring to External or Remote
Controls . . . . . . . . . . . . . . . 12 Wiring to a Float Switch . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . 12
Ventilation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . 13 Zoning the Dehumidifier . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . 14
Required Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . 14 Installer Setup . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . 15
Setting Up Remote Control Crawl Space/ Sealed Attic . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Setting
Up Ventilation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . 16 Setting Up Zoning . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . 16 Setting Up External Control . . . . . . . . . . . . .
. . . . . . . . . . . . . . . 16 Allowing DEH W/AC . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . 16 Applying an RH Offset . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Starting Up the
Unit and Sequence of Operation . . . . . .17 Using the Dehumidifier Control
Only . . . . . . . . . . . . . . . . . 17 Using a Model 76 as a Remote Control
. . . . . . . . . . . . . . 17 Using an External Control . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . 17 Two-Zone Operation . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . 17 Troubleshooting . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Diagnostic Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . 18 Service Parts . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . 22 Limited Warranty . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Warranty
Registration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
23
2 English
SAFETY INSTRUCTIONS
Be sure to read and understand all safety precautions and instructions before
installing and operating the unit .
! WARNING
The following precautions indicate a hazardous situation that, if not avoided,
could result in death or serious injury . · Always disconnect electrical power
before starting
installation or servicing to avoid electric shock . · Always wear
glasses/goggles and gloves when
installing the unit . Sharp edges may cause serious cuts . Use care when
cutting plenum openings and handling ductwork . · Be sure to use caution when
handling the unit . Dropping the unit may cause personal injury or equipment
damage .
! CAUTION
The following precautions indicate a hazardous situation that, if not avoided,
could result in minor or moderate injury . · Be sure the installation, service
and maintenance
are performed by a qualified service technician. Improper installation may
cause injury or property damage . · This unit is not intended for use by
persons (including children) with reduced physical, sensory or mental
capabilities, or lack of experience and knowledge, unless they have been given
supervision or instruction concerning use of the unit by a person responsible
for their safety . · Be sure to supervise children to ensure that they do not
play with the unit . · Be sure to replace a damaged supply cord . It must be
replaced by a special cord or assembly available from the manufacturer or its
service agent .
NOTICE
The following statements indicate a situation which can cause damage to the
equipment and personal property, or cause the equipment to operate improperly.
· Do not use in pool applications. Pool chemicals can
damage the dehumidifier. · Do not use solvents or cleaners on or near the
circuit board. Chemicals can damage circuit board components. · Wait 24 hours
before running the unit if it was not shipped or stored in the upright
position. · Do not use dehumidification to prevent window condensation in the
winter. To address window condensation, use ventilation to lower indoor
humidity in the winter.
WHOLE HOME DEHUMIDIFICATION
The AprilAire® Dehumidifier controls the humidity level in your entire home .
A powerful blower inside the dehumidifier draws air into the cabinet where it
is filtered before having moisture removed . A sealed refrigeration system
removes moisture by moving the air through a series of tubes and fins that are
kept colder than the dew point of the incoming air . The dew point is the
temperature at which moisture in the air will condense, much like what occurs
on the outside of a cold glass on a hot summer day . The condensed moisture
drips into the dehumidifier drain pan to a drain tube routed to the nearest
floor drain or condensate pump . After the moisture is removed, the air moves
through a second coil where it is reheated before being sent back into the
home . The air leaving the dehumidifier will be warmer and drier than the air
entering the dehumidifier . You can reduce the amount of humidity that enters
the home by closing windows, doors and fireplace flues when outdoor humidity
is high, and by drying clothes outside . Direct exhaust from kitchen vents and
bath fans is the best means of controlling humidity due to cooking and
showers/baths . The dehumidifier is not designed to prevent window
condensation in winter . Use ventilation to lower indoor humidity levels in
the winter .
OPERATING THE DEHUMIDIFIER
1 . Use the ON/OFF Power Switch, located by the power cord, to apply power to
the dehumidifier .
NOTE: The ON/OFF Power Switch should stay ON unless the unit will not be used
for an extended period. Use the ON/ OFF Button on the control panel to turn
the unit off for short durations. With the ON/OFF Button in the ON position
and the dehumidifier idle (neither the fan nor the compressor running) the
unit will use less than 3W of power.
1
2
3 4
Figure 1: Exterior Components of the Dehumidifier
1 – Control Panel 2 – ON/OFF Power Switch
3 – Filter Access Door Retaining Screw
4 – Filter Access Door
3 English
2 . Use the ON/OFF Button (see Figure 2) on the control panel to turn the
dehumidifier ON . The first press of a button will turn on the display light,
so if the display was dark, you might need to press it again . Once ON, the
display will show the current dehumidifier setting .
Figure 2: Turning Dehumidifier On 3 . The dehumidifier blower will turn on,
the word
SETTING disappears from the display, and the words AIR SAMPLING appear (see
Figure 3) . This wording indicates that the dehumidifier is sampling the air
to determine if dehumidification is needed and shows the measured humidity
level . If the control is already ON, lowering the setting will initiate air
sampling .
AIR SAMPLING
Figure 3: Air Sampling 4 . If the Relative Humidity (RH) is above the setting,
the
compressor turns on to dehumidify the space . The word DEHUMIDIFYING appears
when the compressor is turned on (see Figure 4) .
ENERGY SAVINGS TIPS
ENERGY SAVINGS TIP #1: Adjust the humidity setting to be as high as is
comfortable to reduce dehumidifier run time . If it feels clammy or “smells
musty,” lower the humidity setting . To save energy, turn the dehumidifier to
OFF when you open your windows, just as you would with air conditioning .
ENERGY SAVINGS TIP #2: If vacating your home for an extended period in the
summer, set the RH at 55% and set your thermostat as high as you are
comfortable setting it to in the cooling mode . This will keep the humidity at
a controlled level while minimizing the amount of cooling energy used .
MAINTENANCE
CLEANING THE FILTER
After initial installation the air filter and drain should be checked and
cleaned every 6 months . 1 . Press the ON/OFF Button on the control panel to
turn
the unit OFF . 2 . Loosen the retaining screw on the filter access door
(see Figure 1) from the drain side of the dehumidifier until it releases and
then remove the filter door . 3 . Slide the filter out of the dehumidifier . 4
. Rinse the filter with water to remove dust and collected particles from the
filter . 5 . Shake off excess water from the filter . 6 . Clean the drain as
described in Cleaning the Drain on page 5 . 7 . Reinstall the filter . An
arrow on the filter frame shows the direction of airflow and it should point
into the dehumidifier . 8 . If the filter does not slide back in, make sure
the drain insert has been properly installed . See Installing the Drain on
page 9. 9 . Replace the filter access door and tighten the retaining screw .
10 . Press the ON/OFF Button to turn the dehumidifier back ON . The CLEAN
FILTER service reminder (see Figure 5) will display on the control every 6
months . To clear the service message, press the p and q buttons
simultaneously for 3 seconds .
Figure 4: Dehumidifying
4 English
Figure 5: Clean Filter Service Reminder
CLEANING THE DRAIN
1 . With the filter door on the drain side of the dehumidifier removed, reach
in and pull out the drain insert using the finger loop (see Figure 6) .
1
Figure 6: Drain Cleaning
1 – Drain Insert
2 . Clean the drain pan and drain insert using a mild detergent .
3 . If the drain has a capped tee or elbow to allow cleaner to be poured
directly in the drain, remove the cap and pour approximately one cup of
vinegar into the tube (see Figure 7) . If there is no visible access to the
drain line from outside of the dehumidifier, pour approximately one cup of
vinegar into the drain pan of the dehumidifier where the drain insert was
located .
4 . Reinstall the drain insert by gently placing the tip into the drain
opening and rocking the insert downwards into place . When inserted properly,
the top of the drain insert will be at the same height as the filter guide
channel .
5 . If the dehumidifier has clear flexible drain tubing, look for excess
buildup in the drain line that might prevent water flow, and replace as needed
. Clear, smooth, flexible 3/4″ inner diameter (ID) drain tubing is available
in most hardware stores or Do-ItYourself (DIY) retail stores .
NOTICE
Running the dehumidifier without the drain insert can lead to condensate
leaks.
90-2607
NOTE: Drain insert must be installed before operationg. 1
2 90-2693
Figure 7: Capped Drain Access for Cleaning Process
1 – Cap
2 – Condensate Drain Line
5 English
SPECIFICATIONS
Unit Weight Capacity 80°F, 60% RH Conditions Power 115 VAC, Single Phase, 60
Hz Dehumidifier Inlet Air Conditions Filter
Airflow
Model E080 63 lbs .
80 pints per day @ 185 CFM
Model E100 64 lbs .
100 pints per day @ 280 CFM
5 .1A operating current
6 .9A operating current
Dehumidification: 50°F104°F, 40°F dew point minimum Ventilation: 40°F140°F, 0% RH99% RH (non-condensing)
MERV 8, washable
External Static Pressure (“WC)
Airflow (CFM)
External Static Pressure (“WC)
Airflow (CFM)
0 .0
185
0 .0
280
0 .2
135
0 .2
245
0 .4
85
0 .4
210
0 .6
175
NOTE: Rated capacity and current draw measured at 80°F/60% RH inlet conditions
at 0.0 external static pressure.
PREPARING THE UNIT FOR INSTALLATION
IMPORTANT: Cut the strap securing the compressor shipping support bracket and
remove the strap and shipping bracket . See Figure 8 . 1 . Clip off and remove
the plastic straps securing the
compressor to the shipping bracket . 2 . Remove the two screws securing the
shipping
bracket to the housing . Remove and discard the shipping bracket, and
reinstall the two screws in the dehumidifier .
2 1
90-1908
Figure 8: Preparing the Unit for Installation 1 – Clip Off Plastic Strap 2 –
Remove Shipping
Bracket
6 English
REPOSITIONING THE CONTROL FOR THE APPLICATION
Locate the onboard control panel on the top of the dehumidifier or at the
front of the dehumidifier if the control panel cannot be seen/accessed in the
top orientation . It may also be rotated 180 degrees in either orientation
(see Figure 10) .
2 1
1 2
INSTALLING THE DUCT COLLARS
· Use the screws in the parts bag to attach the duct collars to the inlet and
outlet of the dehumidifier . The outlet collar has a backflow damper .
· The outlet duct collar may be attached to the top or end of the unit . Move
the outlet cover to the location not being used . See Figure 11 .
· Make sure there are no bends in the ductwork coming off the outlet for a
minimum of 4″ . This precaution will ensure that the ductwork will not
interfere with the backflow damper function .
2
3
1
3
Figure 9: Control Panel Location
90-1884
1 – Control Panel Door 3 – Filter Access Door
2 – Control Panel
1
4 5
Figure 10: Control Panel Rotated 180 Degrees
90-2525
MOVING THE CONTROL
1 . Remove the front control panel door . 2 . Remove the filter access door
and filter . 3 . Detach the onboard control panel by removing the
four (4) screws around the control panel . NOTE: Use one hand to support the
bottom of the onboard control panel when removing. 4 . Keep the control panel
in the unit and relocate to
the front access hole . 5 . Secure the control panel with the same four screws
used to attach the control panel to the top of the unit . 6 . Secure the
control panel door to the top of the unit .
6
90-2592
Figure 11: Fully Ducted Installations
1 – Inlet Duct Collar 2 – Outlet Cover 3 – Outlet Duct Collar w/
Back Draft Damper
4 – End Discharge 5 – Move Outlet Cover
and Install Outlet Duct Collar to Top Discharge Location 6 – Top Discharge
7 English
INSTALLING THE DEHUMIDIFIER
DEHUMIDIFIER LOCATION
· Electrical service access and drain cleaning will require the removal of the
electrical service side panel (see Figure 12) . Allow sufficient space for
service on this side of the unit .
· The filter can be removed from either side of the dehumidifier . Allow
sufficient space for the filter to be removed and reinstalled .
· If locating the unit where it is not readily accessible (such as a crawl
space, an attic or even a basement for some individuals), consider controls
such as the Model 76 Dehumidifier Control, which can be mounted in the living
space and wired to the dehumidifier .
· For attic installations, suspending the dehumidifier is recommended .
· Always install the dehumidifier in or above a condensate pan when locating
in or above a finished space .
2
1
6″
LEVELING AND RAISING THE DEHUMIDIFIER
The feet can be adjusted to level the unit and accommodate drain fittings and
condensate pans as required . Use the top-mounted bubble level to adjust the
feet until the bubble is within the outer circle (see Figure 13) . Leveling is
required to ensure proper drainage from the dehumidifier . If installing a
condensate pump to the side of the unit more elevation than can be provided by
the adjustable feet may be needed . Risers or hanging kits are available to
lift the dehumidifier higher off the floor .
2
1
OK
OK
NO
4
6
5
4
15″ 3
Figure 12: Filter Access Clearance
90-1840
1 – Electrical Service and Drain Access this Side
2 – 6″ Minimum Clearance for Proper Airflow
3 – 15″ Minimum Clearance for Filter (Either Side)
4 – Filter 5 – Top View 6 – 6′ Power Cord
3 Figure 13: Leveling the Unit
90-2692
1 – Bubble Level 2 – Bubble Level Detail
3 – 3/4″ Drain 4 – 0 .38″ Minimum
2 .00″ Maximum
INSTALLING A CONDENSATE PAN UNDER THE DEHUMIDIFIER
Always install the dehumidifier in or above a condensate pan when locating it
above a finished space . Adhere to local codes regarding draining of the
condensate pan . If a condensate pump is needed, make sure it is in the
condensate pan as well . Install a float switch in the condensate pan and/or
use the overflow wires/terminals on the condensate pump to stop the
dehumidifier should overflow occur . See Wiring to a Float Switch on page 12.
8 English
INSTALLING THE DRAIN
Using Hard Pipe: · Install a 3/4″ PVC slip x 3/4″ MNPT PVC fitting to the
dehumidifier and use 3/4″ nominal PVC Schedule 40 pipe to run the condensate
line to the nearest floor drain or to an outside location that slopes away
from the building . · Always maintain a constant downward slope in drain
piping . Ensure that drain tubing does not interfere with removal of the side
panel or filter door . · Do not use metal fittings and only hand-tighten
threaded fittings . PTFE thread seal tape is recommended for threaded
connections . · Install a tee or three-way elbow at the dehumidifier outlet
with a small, capped vertical tube (do not cement cap in place) to allow for
cleaner to be poured into the drain line (see Figure 14) . · PVC primer and
cement is recommended for slip-fit connections (do not cement threaded
connections) .
1
INSTALLING DUCTWORK
· Use insulated duct when the dehumidifier is located in an unconditioned
space, such as an attic, garage or crawl space, or if connecting a fresh air
duct to the dehumidifier ductwork .
· Use zip ties, mastic, and tape as needed to seal the duct connections to the
dehumidifier and to seal the insulation sleeves to prevent condensation inside
the ductwork .
Connecting the dehumidifier to your HVAC system will pull air to be
dehumidified from the whole home and similarly will discharge air to the whole
home . Make sure the duct system pressure the dehumidifier will have to
operate against does not exceed 0 .4″ Water Column (WC) for Model E080 and 0
.6″ WC for Models E100/E100H . Measure the system pressure when the HVAC fan
is operating at the highest airflow (speed) setting . There are not always
readily available locations on the HVAC duct system for connecting 10″ ducts,
and some local codes do not allow ducting to the return side of the HVAC
system . If so, another option is to install just the discharge of the
dehumidifier to the HVAC system or to use dedicated registers for both the
inlet and discharge of the dehumidifier .
2
3
4
Figure 14: Capped Drain Access for Cleaning
90-2693
1 – Cap 2 – Small Section
of Drain Tube
3 – 3/4″ 3-Way elbow or Tee and Below
4 – Condensate Drain Line
Using Flexible Tubing:
· Install the provided 3/4″ NPT x 3/4″ hose barb fitting and use 3/4″ flexible drain tubing . Hand-tighten the fitting to the dehumidifier . PTFE thread seal tape is recommended for threaded connections .
· Always maintain a constant downward slope from the dehumidifier to the nearest floor drain or condensate pump, and do not allow soft tubing to curl up, which may result in air lock .
9 English
DUCTING THE DEHUMIDIFIER INLET AND OUTLET TO THE HVAC SYSTEM
Return-to-Return Basement Installation
Return-to-Supply Basement Installation
2
1
4
6′ Min
3
7 6 5
8 4
19
Return-to-Return Attic Installation
17
11
6′ Min
90-1886
18
9
Return-to-Supply Attic Installation 7
10
6
11
90-1887
12
13 15
14 90-1888
Figure 15: Four Installation Configurations
24″ Min
16
15
13 14
90-1889
1 – Air is Pulled from the Main Return Duct and Discharged to the Main Return
Duct
2 – 10″ Duct 3 – 6′ Minimum 4 – HVAC/Furnace 5 – Air is Pulled from the Main
Return Duct 6 – Model E080 0 .4″ WC Maximum 7 – Model E100H 0 .6″ WC Maximum 8
– Air is Discharged to the Supply Duct 9 – 10″ Duct
· Use when both sides of the duct system are accessible (see Figure 16) .
· When ducting from return to supply, the HVAC blower does not need to be
running when the dehumidifier is running .
· When ducting return to supply, allow adequate space before the first branch
duct to ensure the warm dehumidified air is thoroughly mixed with the HVAC
system air .
10 11 12 13 14 15 16 17 18 19 –
Plenum Box Air Handler Plenum Filter Condensate Pan 10″ Diameter Insulated Duct Both Sides 24″ Minimum 6′ Minimum Plenum Box or Y-Fitting Dehumidifier
· When ducting from return to return, wire the dehumidifier to the HVAC system
as shown in Figure 20 to ensure the HVAC blower runs when the dehumidifier is
operating .
· Wire the dehumidifier to the HVAC system (see Figure 20 for exact wiring)
and set up the dehumidifier to be disabled when the AC is running .
10 English
DUCTING THE DEHUMIDIFIER OUTLET TO THE HVAC SYSTEM WITH DEDICATED DEHUMIDIFIER INLET REGISTER
· To direct dehumidified air away from a potentially
4
wet AC coil:
– Duct to the supply side of the HVAC system
2 3
for air handler applications where air is pulled
through the AC coil (see Figure 16) .
1
Dedicated Return to Main Supply
1
2
3
Figure 16: Discharge to Supply Side
90-2691
1 – Supply 2 – Return
3 – HVAC Equipment
– Duct to the return side of the HVAC system for furnace applications where
air is pushed through the AC coil . Check local codes to verify that ducting
to the return side of the HVAC system is allowed (see Figure 17) .
Dedicated Return to Main Return
2
1
3
Figure 17: Discharge to Return Side
90-2691
1 – Supply 2 – Return
3 – HVAC Equipment
· Wire the dehumidifier to the HVAC system as shown in Figure 20 and set up
the dehumidifier to be disabled when the AC is running .
Use dedicated registers to duct the dehumidifier to the whole home when HVAC
system ductwork is unavailable or impractical (see Figure 18) .
6 Figure 18: Stand-Alone Duct
5 90-1893
1 – Air is Pulled from Ducted Space
2 – Dehumidified Space 3 – 10′ Minimum
4 – Dehumidified Air is Supplied to Ducted Space
5 – Dehumidifier 6 – Grill with 10″ Duct
Collar (2 Places)
WIRING
No additional wiring is needed unless: · the dehumidifier is ducted to the
HVAC system · a separate, external control such as a thermostat or
dehumidistat is to be used · a float switch, either integral to a condensate
pump
or mounted to the condensate pan, is used Use 18-22 AWG wire for any needed
wiring . Access the dehumidifier wiring terminals by pulling off the wiring
access cover near the dehumidifier control display (see Figure 19). Snap the
wiring access cover back into place after completing all wiring .
1
Figure 19: Wiring Access Cover Location 1 – Wiring Access Cover
90-1884
11 English
WIRING TO THE HVAC SYSTEM
When the dehumidifier is ducted to the HVAC system, it is recommended that it
also be wired to the HVAC system as shown in Figure 20 . If ducted to the HVAC
system in a return-to-return configuration, the dehumidifier must be wired to
the HVAC system to prevent short-circuiting dehumidified air directly back to
the dehumidifier inlet . In a return-to-supply ducting configuration, running
the HVAC fan with the dehumidifier ensures the warm dry air is mixed with room
air before being discharged to the home .
OPTIONAL W & Y WIRING Wire the W and/or Y terminal to the HVAC system when
using the ventilation feature of the dehumidifier . See Ventilation on page
13. Wire the dehumidifier Y terminal to the HVAC system to disable the
dehumidifier compressor from operating when the air conditioning is running .
See Allowing DEH W/AC on page 16 for additional setup steps required to access
this feature .
WIRING TO EXTERNAL OR REMOTE CONTROLS
The dehumidifier can be wired to an external control that senses the humidity
in the living space, such as an AprilAire Thermostat or the Model 76
Dehumidifier Control . This is most often done when the dehumidifier is ducted
to the HVAC system and is located in a hard-to-reach location such as an attic
or basement . The Model 76, when used as a remote control, allows the user to
see the humidity sensed by the dehumidifier and adjust the dehumidifier
setting from a remote location . This is most often used when the dehumidifier
is not ducted to the HVAC system and serves a hard-to-reach location such as a
crawl space or basement . If using an external control, wire to the DH
terminals of the dehumidifier (see Figure 21) . Most external controls use a
normally open switch that closes with a dehumidification demand, in which case
leave the NC/NO switch in the NO position . For controls that use a normally
closed switch, put the NC/NO switch in the NC position . If using the
AprilAire Model 76 as a remote control, wire to the {+ – A B} terminals .
Refer to the installation instructions for the control being used for wiring
details .
+ – A B ODT VENT DEH Remote Sensor Dampers
FLOAT DH DH Switch
GhRf Cf Gs W Y HVAC EQUIP.
1 2
4 3
G
R
R
C
C
G
W
W
Y
Y
5
90-1859
Figure 20: Wiring to HVAC System
1 – Existing Wire 2 – New Wire 3 – Thermostat or Zone
Control Board
4 – HVAC Equipment 5 – Optional Wires
1
2
90-2694
Figure 21: Wiring to an External or Remote Control
1 – Use for External
2 – Use for Remote
Control Applications
Control Applications
WIRING TO A FLOAT SWITCH
Use only if the installation includes a float switch or a condensate pump .
The dehumidifier leaves the factory with a jumper wire installed in the float
switch terminals . Remove the jumper and wire the float switch terminals to
the float switch or condensate pump overflow switch as shown in Figure 22 .
12 English
FLOAT DH DH Switch
1
1
Figure 22: Float Switch Wiring 1 – Normal Closed
Float Switch
90-1857
VENTILATION
The dehumidifier can activate a normally closed damper to bring in outdoor air
through a fresh air intake duct . This feature cannot be used when a Model 76
has been installed in a remote control application and should not be used in
two-zone installations . 1 . Install the Fresh Air Inlet (FAI) duct and damper
as
shown in Figure 23 and Figure 24 .
2 4
M3IN
90-1898
Figure 24: External Control Ventilation Installation
1 – Air is Pulled from Outside
2 – HVAC/Furnace
3 – 6′ Minimum 4 – Normally Closed
Vent Damper
2 . Install the Outdoor Temperature Sensor (ODT) as shown in Figure 25 and Figure 26 only needed if ventilation will be limited during high or low outdoor temperature conditions .
1 2
1 2
5 3
4 90-1897
Figure 23: Onboard Control Ventilation Installation
1 – Air is Pulled from Outside
2 – 6′ Minimum 3 – HVAC/Furnace
4 – Balancing Dampers 5 – Normally Closed
Vent Damper
4
3
B2202617-D
Figure 25: ODT Mounted Outside
1 – North, East or West Side of Home
2 – Outdoor Temperature Sensor
3 – Above Expected Snow Line
4 – Outdoor Temperature Sensor Leads
13 English
1
2
3 B2202617-E
Figure 26: ODT Mounted in Intake Duct
1 – Center Line 2 – 36″ Maximum
3 – Outside Wall
3 . Wire the FAI damper, HVAC equipment and outdoor temperature sensor to the dehumidifier control as shown in Figure 27 .
+ – A B ODT VENT DEH Remote Sensor Dampers
FLOAT DHDH Switch
Gh Rf Cf Gs W Y HVAC EQUIP.
1 2 3
4
5
Y
Y
W
W
G
C
C
R
R
G
90-1861
Figure 27: Ventilation Wiring
1 – Optional Outdoor Temperature Sensor (Model 8052)
2 – 6″ Normally Closed Damper or 8190FF
3 – 24 VAC (10 VA MIN) Transformer (E100V: Use external 24V port)
4 – HVAC Equipment 5 – Thermostat or Zone
Control Board
4 . Use the setup menu to ENABLE ventilation: a . Enter the installer setup menu (see page 15) . b . Press the Mode button until the words VENT DISABLE appear . c . Press the s or t button to change to VENT ENABLE .
d . Press the Mode button and the words VENT TIMED will appear . Press the s
or t button to set temperature limits: · TIMED: no temperature limits · AUTO
B: Ventilation is not allowed if the ODT > 100°F or ODT < 0°F; ventilation is
allowed only when the heat is on if the ODT is between 0°F and 20°F · AUTO
C: Ventilation is not allowed if the ODT > 100°F or ODT < 0°F · AUTO D:
Ventilation is not allowed if the ODT > 90°F; ventilation is allowed only when
the heat is on if the ODT is between 0°F and 40°F
e . Press the Mode button and then use the s or t button to set the
ventilation time (minutes/hour) .
f . Press the Mode button repeatedly until the word DONE appears on the
display .
Whenever the heating, cooling or dehumidifier is turned on, the ventilation
damper will open and bring in outdoor air . If the equipment doesn’t run for
the set number of minutes, the dehumidifier will turn on the HVAC fan at the
end of the hour to ensure ventilation needs are met .
ZONING THE DEHUMIDIFIER
The dehumidifier can be configured to condition two independent spaces .
Zoning requires the installation of ductwork and dampers to direct air to and
from two locations . Scan the QR code for details on zoning the installation .
NOTE: Dehumidifier zoning is not recommended in HVAC zoning applications. In
this installation the dehumidifier controls the humidity in two separate
zones, a Primary and Secondary Zone . The dehumidifier will dehumidify the
Primary Zone as the first priority and will switch to the Secondary Zone after
the dehumidification needs of the Primary Zone have been satisfied .
IMPORTANT: Normally Closed dampers must be installed in the ducts serving the
Primary Zone and Normally Open dampers installed in the ducts serving the
Secondary Zone .
REQUIRED COMPONENTS
· 10″ ductwork and fittings · Grilles with 10″ duct collars · Drain line · 2
AprilAire Model 6510, 10″ Normally Closed damper · 2 AprilAire Model 6610,
10” Normally Open damper · 24 VAC transformer (40 VA min .) for dampers NOTE:
5442 Basement Kit includes 2 6510 Dampers, 2 6610 Dampers and a 24 VAC (40
VA) transformer.
14 English
5 4 3
2
6
6′
Min 9
1
7 8
90-1875
Figure 28: Whole-Home Primary Zone Installation
1 – Return from Secondary Zone
2 – Normally Closed Dampers
3 – Return Duct 4 – To/From Primary
Zone 5 – Supply Duct
6 – Supply to Secondary Zone
7 – Normally Open Damper
8 – Normally Open Damper
9 – 6′ Minimum
2
34
+ – A B ODT VENT DEH
5
1 . Plug unit in and turn power switch ON . 2 . The onboard control screen
should display OFF . If
not OFF, press the ON/OFF button to turn the unit OFF .
NOTE: If the display backlight is not on, the first button press (any button)
will only turn on the backlight. Press the button a second time to achieve
function. 3 . Hold the MODE button on the onboard control for 3
seconds to enter the installer setup menu . 4 . Navigate through the following
screens to set up
the dehumidifier for the installed application . 5 . Use the s or t button to
select items and use the
MODE button to switch to the next setup option . To exit the installer setup,
scroll through all options using the MODE button . 6 . After the installer
setup options have been completed, the word DONE will blink for 3 seconds and
the control will return to the OFF screen .
FLOAT DH DH Switch
Gh Rf Cf Gs W Y
1
90-1896
6
7
8
Figure 29: Two-Zone Wiring On-Board Control
1 – FLOAT Switch 2 – Remote 3 – Sensor 4 – Dampers 5 – HVAC Equipment
6 – 24 VAC (40 VA Min .) 7 – Normally CLosed
(Primary Zone) 8 – Normally Open
(Secondary Zone)
NOTE: Dehumidifier zoning is not recommended in HVAC zoning applications.
INSTALLER SETUP
Enter the setup menu if: · the dehumidifier is ducted to the HVAC system · an external or remote control will be used · ventilation or zoning will be used
15 English
SETTING UP REMOTE CONTROL CRAWL SPACE/SEALED ATTIC
If wiring to a Model 76 for remote control (see page 17 for details) press the
s or t button to ENABLE .
SETTING UP EXTERNAL CONTROL
If wiring to an external control (see page 12 for details) press the s or t
button to ENABLE .
SETTING UP VENTILATION
See page 13 for details if using the dehumidifier for ventilation .
ALLOWING DEH W/AC
To allow dehumidification during active air conditioning, select ENABLED and
press the MODE button .
SETTING UP ZONING
See page 14 if zoning the dehumidifier .
To disable dehumidification when the air conditioning is on, on select DISABLED and press the MODE button .
16 English
APPLYING AN RH OFFSET
An offset can be applied to the onboard humidity reading to avoid
discrepancies with other humiditymeasuring devices in the home . Use the s or
t button to select an offset from -5% to 5% . Press the MODE button to exit
the installer setup screens .
STARTING UP THE UNIT AND SEQUENCE OF OPERATION
Use the ON/OFF Power Switch near the power cord to apply power to the
dehumidifier.
USING THE DEHUMIDIFIER CONTROL ONLY
1 . Press the ON/OFF Button to turn the dehumidifier control ON . The display
will show the current humidity setting, and the dehumidifier blower and HVAC
blower (if wired to the HVAC system) will turn on to start sampling . The
setting will be replaced by the measured humidity and the words AIR SAMPLING
appear on the display .
2 . Use the s or t button to adjust the humidity setting as desired . The
recommended initial setting is between 55% and 59% .
3 . After three (3) minutes of sampling, the measured humidity will be
compared to the setting: a . If the humidity is above the setting, the
dehumidifier compressor turns on and the words AIR SAMPLING will be replaced
by the word DEHUMIDIFYING . The compressor remains on until the measured
humidity falls 3% RH below the setting . b . If the measured humidity is below
the setting, the blowers turn off and the display returns to showing the RH
setting .
4 . The dehumidifier will sample again every 60 minutes, or at any time if the
humidity setting is lowered .
USING A MODEL 76 AS A REMOTE CONTROL
1 . Press the ON/OFF Button to turn the dehumidifier control ON . The display
will show the word REMOTE to indicate that a remote control is to be used to
control the dehumidifier .
2 . At the Model 76, press the ON button; the Model 76 will display the RH
measured at the dehumidifier, and the dehumidifier blower will turn on to
start sampling the air .
3 . Use the s or t button on the Model 76 to adjust the dryness level as
desired . The dryness levels range from 1 to 7, with 1 being least dry and 7
being most dry; the recommended initial setting is 3 .
4 . After three (3) minutes of sampling, the measured humidity will be
compared to the setting: a . If the humidity is above the setting, the
dehumidifier compressor turns on and the word ON flashes on the Model 76
display . b . If the measured humidity is below the setting, the dehumidifier
blower turns off .
5 . The dehumidifier will sample again every 60 minutes, or at any time if the
dryness level is increased .
USING AN EXTERNAL CONTROL
1 . Press the ON/OFF Button to turn the dehumidifier control ON . The display
will show the word EXTERNAL to indicate that an external control is to be used
to control the dehumidifier .
2 . At the external control, initiate a dehumidification demand . Refer to the
literature provided with the external control . The dehumidifier fan and
compressor, and the HVAC fan (if wired to do so) will turn on and the word
DEHUMIDIFYING will appear on the display of the dehumidifier .
NOTE: When using an external control, there is a threeminute delay after
power-up (i.e., ON/OFF Power Switch is turned ON with unit plugged in) before
the dehumidifier will respond to an external control. This prevents
unanticipated, early start-up after power is applied. 3 . Discontinue the
demand at the external control; the
dehumidifier and HVAC fan will turn off .
TWO-ZONE OPERATION
The Primary Zone operates as listed for using the dehumidifier control or an
external control . “PRIMARY ZONE” shows on the display when operating . The
Secondary Zone uses the humidity setting on the dehumidifier control . During
Secondary Zone operation, the installed dampers are de-energized and the HVAC
blower (if on) stops . “SECONDARY ZONE” shows on the display when operating .
The Secondary Zone is sampled immediately after the Primary Zone has finished
sampling, or if there is a call for dehumidification from the Primary Zone,
17 English
immediately after the call has been satisfied . When an external control is
installed, the Secondary Zone will be sampled once per hour if there has not
been a call for dehumidification from the Primary Zone .
TROUBLESHOOTING
Technical support is available Monday through Friday 7:00 a .m . to 5:00 p .m
. CST at 800-334-6011 . Use the guides
on the following pages to identify and correct system faults . Contact
Technical Support before replacing the unit or any components and for
additional troubleshooting .
DIAGNOSTIC CODES
When an error occurs, the Diagnostic Code along with SERVICE REQUIRED will be
displayed on the control screen .
Table 1: Diagnostic Codes
Diagnostic Code
Failure Mode
Action
Reset
E1
Internal Humidity 1 . Cycle power to clear error code .
Cycle Power
or Temperature Sensor Open or
2 . If error code reoccurs, replace User Interface, Part No . 5445 .
Shorted
E2
High
1 . Verify that the fan works, the backflow damper swings freely,
Cycle Power
Refrigeration
and there is no blocked or restricted ductwork .
Pressure
2 . If the fault persists, call Technical Support .
E3
Model 76
1 . Check connections between Model 76 and dehumidifier control
Self-
Remote Control
board . Terminals should be fully inserted and secured in the
Correcting
Communication
control board and Model 76 control terminals .
Loss
2 . If connections are correct and secure, turn off the dehumidifier
and remove the Model 76 . Use a short section of 4-wire cable
to reconnect the Model 76 to the control board . Turn the
dehumidifier back on and increase the dryness level setting on
the Model 76 . If the dehumidifier turns on, a problem exists with
the wiring between the dehumidifier and control .
3 . If the dehumidifier does not turn on, call Technical Support .
E4
Insufficient
Capacity
1 . Check the frost sensor connection at the power board . The terminal should
be fully seated on the power board pins .
2 . Remove the side access panel and verify that the sensor is secured to the
suction line .
3 . If the sensor is connected and secured to the refrigeration line, proceed
to the next step .
4 . Reset the fault by cycling power to the dehumidifier . 5 . Turn the
humidity setting down (below room/home humidity
level) to make a dehumidification call .
Cycle Power
18 English
Table 1: Diagnostic Codes
Diagnostic Code
Failure Mode
Action
Reset
E4
Insufficient
Capacity
6 . Allow the fan and compressor to run for approximately 10-15 minutes and then enter diagnostic test mode by simultaneously pressing the s button and MODE button for 3 seconds . The LCD will display: · the temperature measured by the internal sensor while also displaying the words AIR SAMPLING and ON · the humidity measured by the internal sensor while also displaying %RH and the word ON · the frost sensor temperature while also displaying the word ON
Cycle Power
Scroll through these values and by using the s or t button . 7 . Record values and call Technical Support .
E5
High
Check the high temperature sensor connection at the power board . Cycle Power
Temperature
The terminal should be fully seated on the power board pins .
Thermistor Failure
Remove the side access panel and verify the sensor is not damaged and connected to the refrigeration line coming from the compressor .
If the sensor is connected and secured to the refrigeration line, it may need to be replaced with Part No . 5456 contact Technical Support to confirm .
E6
Low Temperature Check the low temperature sensor connection at the power board . Cycle Power
Thermistor Failure
Remove the side access panel and verify the sensor is not damaged and connected to the suction line .
If the sensor is connected and secured to the refrigeration line, it may need to be replaced with Part No . 5455 contact Technical Support to confirm .
E7
Float Switch
Open
Empty the condensate pan . Check the float switch connection at the control board . If not using a float switch, verify jumper is between float switch terminals on dehumidifier control board . If the problem persists, replace the float switch .
SelfCorrecting
E8
Inlet Air
1 . Verify all ductwork is properly sealed .
Self-
Temperature Out of 50°F104°F Range, or Dew
2 . Check for air leakage that might affect the temperature or RH of the incoming air .
Correcting
Point Below 40°F 3 . If the air temperture is in range and the dew point is above 40°F,
contact Technical Support .
E9
Outdoor Temperature Sensor Open or Shorted
1 . Check the sensor connection at the power board .
2 . Remove the wires from the terminals and measure the resistance . A short
circuit
Outdoor Temperature
0°F
Resistance 84,500 Ohms
SelfCorrecting
will have a resistance very close to 0 Ohms and an open circuit will have a very
20°F
46,000 Ohms
high resistance . Use the Ohms chart on page 21 to approximate the resistance
40°F
26,000 Ohms
based on outdoor temperature .
60°F
15,500 Ohms
3 . If the sensor is not reading
correctly, replace the sensor,
80°F
9,500 Ohms
Part No . 8052 .
100°F
6,000 Ohms
19 English
Table 2: Troubleshooting Guide
Symptom
Possible Reason
Troubleshooting Procedure
Dehumidifier does not turn on/run .
No power to unit .
· Check that the dehumidifier is plugged in . · Check that the power switch is turned ON . · Check that the control is turned ON . · Check that the circuit breaker has not tripped .
Dehumidifier blower is running but with little or no airflow .
Pressure drop across dehumidifier is higher than 0 .4″ WC for Model E080 or 0 .6″ WC for Model E100/ E100H .
· Check dehumidifier air filter and wash or replace . · Check for blocked
ductwork and clear . · Verify that the outlet collar with backflow damper is
installed on the
outlet side of the dehumidifier . · Check if backflow damper is blocked or
stuck and remove obstruction .
Dehumidifier
Float Switch
· If float switch is installed, check connections at control board and
blower is running open (E7 appears
empty the condensate pan .
but compressor is not .
on display) .
· If no float switch is installed, check that the jumper is installed at the float switch terminals on the control board .
Unit is defrosting .
· Frosting occurs when the incoming air is cool and dry, normally during Spring or Fall, or the airflow is restricted . Frosting due to cold/dry conditions is a normal part of operation and “DEFROSTING” will show on the display . If it is not cool and dry, look for blocked ductwork or a dirty filter .
Inlet air temperature is outside of the 50°F104°F range or the dew point is below 40°F and there is a demand for dehumidification .
· Verify all ductwork is properly sealed . Dehumidification will restart by itself when the incoming air temperature is within range and the dew point is above 40°F . E8 appears on the display when inlet air conditions prevent operation .
When zoned, the dehumidifier damper does not open in INSTALLER TEST mode .
Incorrect damper wiring or bad connection .
· Verify wiring between dampers and 24 VAC transformer . · If wired for Two
Zone operation, verify that 24 VAC transformer is 40 VA
minimum . · Check all wiring connections between dampers and control board . ·
Verify the normally closed dampers are in the Primary Zone ductwork
and the normally open dampers are in the Secondary Zone ductwork .
20 English
Table 2: Troubleshooting Guide (Continued)
Symptom
Possible Reason
Troubleshooting Procedure
The ventilation damper does not open when the HVAC fan is active .
Cycle time has been met . ODT error or outdoor air outside of ODT range .
· The damper will not open if the ventilation time has already been met .
· Check that the ODT is wired correctly to the dehumidifier control board and
connections are secure .
· Check that the ODT is installed in the outdoor air intake according to the
setup specified in VENTILATION ON PAGE 13 .
· Remove the ODT leads from the dehumidifier control board and check the
resistance . Compare the reading with the chart on the right .
Outdoor Temperature
0°F 20°F 40°F 60°F
Resistance 84,500 Ohms 46,000 Ohms 26,000 Ohms 15,500 Ohms
80°F
9,500 Ohms
100°F
6,000 Ohms
Dehumidifier is not draining properly .
The HVAC fan turns on unexpectedly . Dehumidifier is producing hot air .
Drain line blocked or unit not level .
Dehumidifier is sampling or ventilation in progress . Normal function .
· Verify that the unit is level . · Check the drain line blockages and check
for a continuous downward
slope . · Verify presence and condition of drain cover insert . See
Maintenance
on page 4 for cleaning procedure, or replace with Part No . 5885 if missing or
damaged . · The dehumidifier will turn on the HVAC fan during air sampling or
as needed to meet the ventilation time .
· Air is reheated across the condenser coil, resulting in a temperature rise
between inlet and outlet .
21 English
SERVICE PARTS
5 9
4 3 10
1 14
13
18 2
16A 17A 16B 17B
12A 15
6
11A
19
12B
11B
20
7 8
90-2595
No .
Part Description
Part No .
1 EZK Filter, 13 .5″ x 11 .875″ x 0 .875″
5881
2 Internal Control Board, Deh
5444
3 User Interface Assembly, Deh
5445
4 Wiring Access Door, AA Deh
5446
5 Hole Cover, UI Ctrl, Deh
5447
6 Door, Filter Access, AA Deh
5882
7 Outlet Duct Panel, Deh
5449
8 Backflow Damper, 10″, Deh
5450
9 Inlet Duct Panel, AA Deh
5451
10 Cover, Outlet, AA Deh
5452
Fan, 80pt Deh, with 6MFD Capacitor 11
Fan, 100pt Deh, with 12MFD Capacitor
5883 5886
Wire Harness, Power, Deh 12
Wire Harness, Power, Deh w/ Vent*
5884 5888
No .
Part Description
Part No .
13 Sensor, Low Temperature, Deh
5455
14 Sensor, High Temperature, Deh
5456
15 Leveling Foot, Deh
5457
16 Capacitor, Run, 50µF
5594
Capacitor, 6MFD, 250VAC, 80pt Deh 17
Capacitor, 12MFD, 450VAC, 100pt Deh
5582 5468
18 Drain Insert
5885
19 Drain Tube + Fitting
5692
20 8190FF/E100V Internal Wiring Harnesses 5914
Not Shown
8190FF/E100V External Wiring Harnesses 5887
22 English
LIMITED WARRANTY
Your AprilAire® Dehumidifier is expressly warranted for five (5) years from
date of installation to be free from defects in materials or workmanship . The
exclusive obligation of AprilAire under this warranty shall be to supply,
without charge, a replacement for any component which is found to be defective
within such five (5) year period and which is returned not later than thirty
(30) days after said five (5) year period by you to either your original
supplier or to AprilAire, Madison, Wisconsin 53701, together with the model
number and installation date of the dehumidifier . THIS WARRANTY SHALL NOT
OBLIGATE APRILAIRE FOR ANY LABOR COSTS AND SHALL NOT APPLY TO DEFECTS IN
WORKMANSHIP OR MATERIALS FURNISHED BY YOUR INSTALLER AS CONTRASTED TO DEFECTS
IN THE DEHUMIDIFIER ITSELF . IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS
FOR A PARTICULAR PURPOSE SHALL BE LIMITED IN DURATION TO THE AFORESAID FIVE
YEAR PERIOD . THE APRILAIRE LIABILITY FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES,
OTHER THAN DAMAGES FOR PERSONAL INJURIES, RESULTING FROM ANY BREACH OF THE
AFORESAID IMPLIED WARRANTIES OR THE ABOVE LIMITED WARRANTY IS EXPRESSLY
EXCLUDED . THIS LIMITED WARRANTY IS VOID IF DEFECT(S) RESULT FROM FAILURE TO
HAVE THIS UNIT INSTALLED BY A QUALIFIED HEATING AND AIR CONDITIONING
CONTRACTOR . IF THE LIMITED WARRANTY IS VOID DUE TO FAILURE TO USE A QUALIFIED
CONTRACTOR, ALL DISCLAIMERS OF IMPLIED WARRANTIES SHALL BE EFFECTIVE UPON
INSTALLATION . Some states do not allow limitations on how long an implied
warranty lasts or the exclusion or limitation of incidental or consequential
damages so the above exclusion or limitations may not apply to you . This
warranty gives you specific legal rights and you may also have other rights
which vary from state to state .
WARRANTY REGISTRATION
Visit us online at aprilaire .com to register your AprilAire product . If you
do not have online access, please mail a postcard with your name, address,
phone number, email address, product purchased, model number, date of
purchase, and dealer name and address to: AprilAire, P .O . Box 1467, Madison,
WI 53701 . Your warranty registration information will not be sold or shared
outside of this company.
23 English
Internal Use Only
10016378 · B2210022A · 4.22 © 2022 AprilAire | aprilairepartners.com |
800.334.6011
AprilAire reserves the right to change specifications without notice.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>