Carrier TV-UCXPIO48 TruVu I O Expanders Instruction Manual

June 16, 2024
Carrier

TV-UCXPIO48 TruVu I O Expanders

TruVuTM I/O Expanders

Specifications

Driver Power: I/O Bus port

I/O Bus edge connector

TruVuTM Controllers require drv_fwex 107-06-2065 or later

Not used by the TV-UCXP I/O Expander

Inputs:

  • Input resolution
  • Input pulse frequency

Outputs:

  • Output resolution
  • Microprocessor Protection

Status indicators: Environmental operating range

Physical Terminal blocks and connectors:

  • 16 bit A/D

  • 40 pulses per second. Minimum pulse width (on or off time)
    required for each pulse is 12.5 msec.

  • 4 Outputs can be set as analog or binary outputs. Analog
    outputs can be used for 0-10 Vdc or 0-20 mA devices. Binary outputs
    have a built-in relay and can be used to switch external devices or
    relays up to 1A, 30 Vac/Vdc.

  • 12 bit D/A

  • 32-bit microprocessor with 256 kB Flash memory and 64 kB
    SRAM

  • The TV-UCXPIO48 has two fast acting , 5 mm x 20 mm glass
    fuses:

  • LEDs indicate status of communications, system state (running
    or errors), outputs, and power

  • Screw-type terminal blocks. 0.2 in (5.08 mm) pitch
    connectors

  • Overall dimensions:

    • A: 6.9 in. (17.53 cm)
    • B: 6.95 in. (17.65 cm)
    • Depth: 2.09 in. (5.31 cm)
    • Screw mounting dimensions:
    • C: 6.45 in (16.38 cm)
    • D: 4.1 in. (10.4 cm)
  • Weight: 1.1 lb. (0.49 kg)

  • Compliance:

    • United States of America: FCC compliant to Title CFR47, Chapter
      1, Subchapter A, Part 15, Subpart B, Class A; UL Listed to UL 916,
      PAZX, Energy Management Equipment

    • Canada: Industry Canada Compliant, ICES-003, Class A cUL Listed
      UL 916, PAZX7, Energy Management Equipment

    • Europe: Mark, UK: EN50491-5-2:2009; Part 5-2: EMC requirements
      for HBES/BACS used in residential, commercial and light industry
      environment RoHS Compliant: 2015/863/EU REACH Compliant

Product Usage Instructions

Installation

To install the TruVuTM I/O Expander (TV-UCXPIO48), follow these
steps:

  1. Ensure that you have the most current version of the
    Installation and Start-up Guide.

  2. Verify that you have all the necessary tools and equipment for
    installation.

  3. Choose a suitable location for the I/O Expander.

  4. Mount the I/O Expander using the provided screw mounting
    dimensions.

  5. Connect the I/O Bus port of the I/O Expander to the TruVu
    Universal Controller using an appropriate cable.

  6. Connect any additional inputs and outputs to the I/O Expander
    using the screw-type terminal blocks and connectors.

  7. Ensure that all connections are secure.

Start-up

To start-up the TruVuTM I/O Expander, follow these steps:

  1. Ensure that the TruVu Universal Controller is powered on and
    operational.

  2. Verify that the I/O Expander is properly connected to the TruVu
    Universal Controller.

  3. Power on the I/O Expander using the appropriate power
    source.

  4. Monitor the status indicators to ensure proper communication,
    system state, outputs, and power.

  5. Test the inputs and outputs to ensure they are functioning
    correctly.

FAQ

Q: What is the purpose of TruVuTM I/O Expanders?

A: TruVuTM I/O Expanders are used to provide additional inputs
and outputs to TruVu Universal Controllers.

Q: How many inputs and outputs does the TV-UCXPIO48 TruVuTM I/O

Expander provide?

A: The TV-UCXPIO48 TruVuTM I/O Expander provides 8 inputs and 4
outputs.

Q: What are the environmental operating range of TruVuTM I/O

Expanders?

A: The environmental operating range of TruVuTM I/O Expanders is
specified in the product documentation.

TruVuTM I/O Expanders
Installation and Start-up Guide
©2023 Carrier. All rights reserved. · Catalog No. 11-808-1009-01 · 10/23/2023

Verify that you have the most current version of this document from www.hvacpartners.com, the Carrier Partner Community website, or your local Carrier office. Important changes are listed in Document revision history at the end of this document.
©2023 Carrier. All rights reserved.

Contents
What are TruVuTM I/O Expanders? ………………………………………………………………………………………………..1 Specifications ……………………………………………………………………………………………………………………………… 2
TV-UCXPIO48 Expander power and communication configurations………………………………………………………4
Wiring the TV-UCXPIO48 to the controller’s I/O Bus ………………………………………………………………………….5 To mount the expander………………………………………………………………………………………………………………… 5 To wire an external power supply to the expander…………………………………………………………………………. 7 To wire the expander for communications…………………………………………………………………………………….. 8
To address the TV-UCXPIO48 ………………………………………………………………………………………………………9
Wiring inputs and outputs…………………………………………………………………………………………………………10 Inputs………………………………………………………………………………………………………………………………………… 10 Outputs ……………………………………………………………………………………………………………………………………… 11 Wiring specifications…………………………………………………………………………………………………………………..12 To wire inputs and outputs ………………………………………………………………………………………………………….12
To adjust input and output properties………………………………………………………………………………………….15 Input values ……………………………………………………………………………………………………………………………….15 Output values……………………………………………………………………………………………………………………………..17 Resolution values ……………………………………………………………………………………………………………………….18 Offset/Polarity values …………………………………………………………………………………………………………………19 To use an output’s Hand-Auto-Off switch ……………………………………………………………………………………..20
Troubleshooting ……………………………………………………………………………………………………………………..21 LED’s …………………………………………………………………………………………………………………………………………. 21 Troubleshooting inputs and outputs …………………………………………………………………………………………….22 To get the TV- UCXPIO48’s serial number ……………………………………………………………………………………..23 To monitor expander communication ………………………………………………………………………………………….24 To replace the TV-UCXPIO48’s fuses…………………………………………………………………………………………….24
Compliance …………………………………………………………………………………………………………………………..26 FCC Compliance …………………………………………………………………………………………………………………………26 CE and UKCA Compliance……………………………………………………………………………………………………………26 Industry Canada Compliance ………………………………………………………………………………………………………26
Document revision history ………………………………………………………………………………………………………..27

What are TruVuTM I/O Expanders?
TruVu I/O Expanders (part no. TV-UCXPIO48) connect to TruVu Universal Controllers to provide additional inputs and outputs. You can connect a single TV-UCXPIO48 to the TruVu Expandable Universal Equipment Controller 683 (part no.TV-UCXP683T and TV-UCXP683T-V )

This expander (part#)… TV-UCXPIO48

Provides this number of inputs… 8

And this number of outputs… 4

TV-UCXPIO48

TruVuTM I/O Expanders Installation and Start-up Guide

Carrier Proprietary and Confidential 1

©2023 Carrier. All rights reserved.

Specifications

Driver Power I/O Bus port I/O Bus edge connector

TruVuTM Controllers require drv_fwex 107-06-2065 or later
24 Vac ±10%, 50­60 Hz, 50 VA 26 Vdc ±10%, 12 W Provides communication to TV- UCXP683T and TV-UCXP683T-V host modules. The port’s End of Net? switch can be used to terminate the expander network.
Not used by the TV-UCXP I/O Expander

Inputs
Input resolution Input pulse frequency Outputs
Output resolution Microprocessor Protection
Status indicators Environmental operating range
Physical Terminal blocks and connectors

8 Inputs are configurable in the control program for 0­5 Vdc, 0­10 Vdc, 0­20 mA, RTD, thermistor, dry contact, or pulse counter.
16 bit A/D
40 pulses per second. Minimum pulse width (on or off time) required for each pulse is 12.5 msec.
4 Outputs can be set as analog or binary outputs. Analog outputs can be used for 0-10 Vdc or 0-20 mA devices. Binary outputs have a built-in relay and can be used to switch external devices or relays up to 1A, 30 Vac/Vdc.
12 bit D/A
32-bit microprocessor with 256 kB Flash memory and 64 kB SRAM
The TV-UCXPIO48 has two fast acting , 5 mm x 20 mm glass fuses:
· A 2A fuse for the TV-UCXPIO48’s power
· A 4A fuse which is not used by this expander The power and network ports comply with the EMC requirements EN50491-5-2.
LEDs indicate status of communications, system state (running or errors), outputs, and power
-40 to 158°F (-40 to 70°C), 10-95% relative humidity, non-condensing NOTES · The TV-UCXPIO48 is suitable for installation inside or outside the building
envelope. · Install in a UL Listed enclosure only.
· Do not change the position of the power or End of Net switch at temperatures
below -22°F (-30C) to ensure proper operation and electrical connectivity. Fire-retardant plastic ABS, UL94-5VA
Screw-type terminal blocks. 0.2 in (5.08 mm) pitch connectors

TruVuTM I/O Expanders Installation and Start-up Guide

Carrier Proprietary and Confidential 2

©2023 Carrier. All rights reserved.

Overall dimensions

A: B: Depth:

Screw mounting dimensions C: D:

6.9 in. (17.53 cm) 6.95 in. (17.65 cm) 2.09 in. (5.31 cm)
6.45 in (16.38 cm) 4.1 in. (10.4 cm)

Weight Compliance

1.1 lb. (0.49 kg)
United States of America: FCC compliant to Title CFR47, Chapter 1, Subchapter A, Part 15, Subpart B, Class A; UL Listed to UL 916, PAZX, Energy Management Equipment
Canada: Industry Canada Compliant, ICES-003, Class A cUL Listed UL 916, PAZX7, Energy Management Equipment
Europe: Mark, UK: EN50491-5-2:2009; Part 5-2: EMC requirements for HBES/BACS used in residential, commercial and light industry environment RoHS Compliant: 2015/863/EU REACH Compliant
Australia and New Zealand: C-Tick Mark, AS/NZS 61000-6-3

TruVuTM I/O Expanders Installation and Start-up Guide

Carrier Proprietary and Confidential 3

©2023 Carrier. All rights reserved.

TV-UCXPIO48 Expander power and communication configurations
Wire to the I/O Bus port for communication and then wire to an external transformer for power

See Wiring the TV-UCXPIO48 to the controller’s I/O bus (page 5).
WARNING Do not apply line voltage (mains voltage) to the controller’s ports and terminals.
CAUTIONS · The TV-UCXPIO48 is powered by a Class 2 power source. Take appropriate isolation measures when
mounting it in a control panel where non-Class 2 circuits are present.

TruVuTM I/O Expanders Installation and Start-up Guide

Carrier Proprietary and Confidential 4

©2023 Carrier. All rights reserved.

Wiring the TV-UCXPIO48 to the controller’s I/O Bus
When wiring the TV-UCXPIO48 to the controller, you must: 1 Mount the expander (page 5) 2 Wire an external power supply to the expander (page 7) 3 Wire the expander for communications (page 8)
To mount the expander
NOTE We recommend screw mounting when installing in a high temperature and high humidity environment.
DIN rail mount
1 Push down and pull out the center tabs shown below to clear the DIN rail trough on the back of the expander.

2 Place the expander on the DIN rail so that the rail is in the trough on the back of the expander.

3 Push the center tabs towards the expander until you hear them click. 4 Pull gently on the expander to verify that it is locked in place.

TruVuTM I/O Expanders Installation and Start-up Guide

Carrier Proprietary and Confidential 5

©2023 Carrier. All rights reserved.

Screw Mount
Leave about 2 in. (5 cm) on each side of the controller for wiring.
Insert #6 screws through the mounting tabs. Use no more than 8 in.lbs. torque to secure plastic tab to mounting surface.

A: B: C: D: Depth:

6.9 in. (17.53 cm) 6.95 in. (17.65 cm) 6.45 in. (16.38 cm) 4.1 in. (10.4 cm) 2.24 in (5.69 cm)

TruVuTM I/O Expanders Installation and Start-up Guide

Carrier Proprietary and Confidential 6

©2023 Carrier. All rights reserved.

To wire an external power supply to the expander
An external power supply is required to power the expander.
WARNING Do not apply line voltage (mains voltage) to the controller’s ports and terminals.
CAUTIONS · The TV-UCXPIO48 is powered by a Class 2 power source. Take appropriate isolation measures when mounting
it in a control panel where non-Class 2 circuits are present. · Carrier controllers can share a power supply as long as you:
· Maintain the same polarity. · Use the power supply only for Carrier controllers.

To wire the power supply to the expander
1 Make sure the TV-UCXPIO48’s power switch is in the OFF (down) position to prevent it from powering up before you can verify the correct voltage.

2 Remove power from the power supply. 3 Pull the red screw terminal connector from the expander’s power terminals labeled 24 V (+/-). 4 Connect the power supply’s wires to the red screw terminal connector. 5 Connect an 18 AWG or larger wire from the power supply’s negative (-) terminal to earth ground. This wire
must not exceed 12 in. (30.5 cm).

TruVuTM I/O Expanders Installation and Start-up Guide

Carrier Proprietary and Confidential 7

©2023 Carrier. All rights reserved.

6 Apply power to the power supply. 7 Measure the voltage at the red screw terminal connector to verify that the voltage is within the operating
range of 20 to 30 Vac or 23.4 to 30 Vdc. 8 Insert the red screw terminal connector into the expander’s power terminals. 9 To verify the polarity of the wiring, measure the voltage from the negative terminal of the red screw terminal
connector to a nearby ground. The reading should be 0V. 10 Turn on the TV- UCXPIO48’s power switch. 11 Verify that the PWR LED on top of the expander is on.
To wire the expander for communications
Wiring restrictions for connecting the expander to the controller Maximum length: 1000 feet (305 meters) 22 or 24 AWG, low-capacitance, twisted, stranded, shielded copper wire
WARNING Do not apply line voltage (mains voltage) to the expander’s ports and terminals.
1 Turn off the controller’s and expander’s power. 2 Wire the expander’s I/O Bus port to the same port on the controller.
NOTE Use the same polarity throughout the network segment. 3 Set the I/O Bus End of Net? switch to Yes to apply network termination and bias.
NOTE The controller has built-in I/O bus network termination. 4 Turn on the controller’s and expander’s power.

TruVuTM I/O Expanders Installation and Start-up Guide

Carrier Proprietary and Confidential 8

©2023 Carrier. All rights reserved.

To address the TV-UCXPIO48
1 Turn off the power switch on the controller that the TV-UCXPIO48 is attached to.
2 Set the TV-UCXPIO48’s address on the rotary switch to 1 as shown below.
3 Turn on the controller’s power switch. The controller reads the TV- UCXPIO48’s address each time you turn on the controller’s power.

TruVuTM I/O Expanders Installation and Start-up Guide

Carrier Proprietary and Confidential 9

©2023 Carrier. All rights reserved.

Wiring inputs and outputs

Inputs
The TV-UCXPIO48 has inputs that accept the following signal types.

Signal Type Thermistor 1
Dry contact 0­5 Vdc 0­10 Vdc 0­20 mA

Description
· Precon Type 2 (10kOhm at 77 °F) · Precon Type 3 (10kOhm at 77 °F) · Carrier YSI 5kOhm at 77 °F · TS-5700-850 10kOhm w/ 11kOhm shunt (5238 ohm@77°F) Input voltages should be from 0.09 Vdc to 4.36 Vdc for thermistors.
The maximum current when the contact is closed is 0.5 mA. The input voltage should be 4.5V when the contact is open. Maximum closed contact resistance is 1kOhms.
The input impedance of the TV-UCXPIO48 is approximately 221 kOhm when configured as a voltage input.
The input resistance on the positive (+) terminal is 200 Ohms when configured as a current input. Each 24 Vdc connector is capable of supplying 24 Vdc to multiple 4­20 mA transducers.

RTD 1

CAUTION Both connectors combined must not exceed: 66.7 mA for the TV-UCXP683T and TV-UCXP683T-V
· Platinum 1kOhm at 32°F (0°C) (0.00375 TCR) · Nickel-iron 1kOhm at 70°F (21°C) · Platinum TS-8000 1kOhm at 32°F (0°C) (0.00385 TCR) · Balco (nickel- iron) TS8000 1kOhm at 70°F (21°C)

Input voltages should be from 0.3­0.68V.

NOTE Carrier recommends use of an external current transducer between an RTD and the TV-UCXPIO48 to improve accuracy and resolution.

Pulse counter 2

Pulse counting up to 40 pulses per second. Minimum pulse width (on or off time) required for each pulse is 12.5 msec.

1 To use a thermistor or RTD not listed above, you can set up a custom translation table for your sensor in the controller’s driver.
2 The TV-UCXPIO48 can perform pulse counting for dry contact or voltage inputs if you assign the input to a Pulse to Analog Input microblock. See To adjust input and output properties (page 15).

WARNING Do not apply voltage to any input configured for 0-20 mA as this could damage the expander.

TruVuTM I/O Expanders Installation and Start-up Guide

Carrier Proprietary and Confidential 10

©2023 Carrier. All rights reserved.

Outputs
The TV-UCXPIO48’s universal outputs can be set as analog or binary on their two DIP switches. The expanders’ outputs return to their unconfigured state if they are removed from the program or the program is deleted from the controller. Also, outputs time out and return to their unconfigured or off state after two minutes of inactivity. The unconfigured state results in: · Not running control programs that are due to download · Losing power to the controller, but not the expander NOTE This does not apply to outputs that have been locked in the i-Vu® application.

Analog outputs
Outputs set up as analog can be used for: · 0-10 Vdc devices · 0-20 mA devices
WARNING Do not apply voltage to any output whose DIP switch is set to Analog.

If output controls a… 0­10 Vdc device 0­20 mA device

Resistance to ground must be… 500 Ohms minimum 500 Ohms maximum

NOTE The device must share the same ground as the expander.

Binary outputs
The outputs have a built-in relay and provide a dry contact so an external voltage source must be wired to one of the two terminals.
Outputs set up as binary can be used to switch external devices and relays up to 1A, 30 Vac/Vdc.

TruVuTM I/O Expanders Installation and Start-up Guide

Carrier Proprietary and Confidential 11

©2023 Carrier. All rights reserved.

Wiring specifications

Input wiring
Input
Thermistor Dry contact 0­5 Vdc 0­10 Vdc 0­20 mA
RTD

Maximum length
1000 feet (305 meters)
1000 feet (305 meters)
3000 feet (914 meters)
100 feet (30 meters)

Minimum gauge 22 AWG 26 AWG 26 AWG 22 AWG

Shielding Shielded
Shielded
Shielded or unshielded Shielded

NOTES
· Carrier recommends use of an external current transducer between an RTD and the TV-UCXPIO48 to improve accuracy and resolution.
· RTD inputs require either sensor calibration or an estimated offset correction for wiring resistance. See Offset and Polarity values (page 19).

Output wiring
To size output wiring, consider the following: · Total loop distance from the controller to the controlled device
NOTE Include the total distance of actual wire. For 2-conductor wires, this is twice the cable length. · Acceptable voltage drop in the wire from the controller to the controlled device · Resistance (Ohms) of the chosen wire gauge · Maximum current (Amps) the controlled device requires to operate

To wire inputs and outputs
WARNING Do not apply line voltage (mains voltage) to the controller’s ports and terminals.
1 Verify that the TV-UCXPIO48’s power and communications connections work properly. 2 Turn off the TV-UCXPIO48’s power. 3 Connect the input wiring to the UI screw terminals on the TV-UCXPIO48.

TruVuTM I/O Expanders Installation and Start-up Guide

Carrier Proprietary and Confidential 12

©2023 Carrier. All rights reserved.

WARNING Do not apply voltage to any input configured for 0-20 mA as this could damage the expander.
NOTE Connect the shield wire to the – terminal with the ground wire. Do not connect the shield wire at the other end of the cable as this will cause a ground loop error.

10 kOhm thermistor
Dry contact
1 kOhm RTD

+ Any input

+ Any input

+ Any input

2 wire

3 wire

External 24 Vdc half-wave power supply

4 wir e

V+

0-5 Vdc, 0-10 Vdc,

Out

or

4-20 mA

V+

0-5 Vdc, 0-10 Vdc,

Out

or 4-20 mA

Gnd

+ Any input
n/c –
+ Any input

V+ 0-5 Vdc, Out +

0-10 Vdc,

Gnd

or 4-20 mA

Out –

+ Any input

2 wire 3 wire

V+

0-5 Vdc, 0-10 Vdc,

Out

or

4-20 mA

V+

0-5 Vdc, Out 0-10 Vdc,

or Gnd

4-20 mA

+ Any input
n/c –
+ Any input

4 wir e

V+ 0-5 Vdc, Out +

0-10 Vdc,

Gnd

or 4-20 mA

Out –

+ Any input

24 Vdc connector

NOTE For a loop-powered 4-20 mA sensor, wire the sensor’s positive terminal to the + terminal on the TVUCXPIO48’s 24 Vdc connector. Wire the sensor’s negative terminal to an input’s + terminal.

TruVuTM I/O Expanders Installation and Start-up Guide

Carrier Proprietary and Confidential 13

©2023 Carrier. All rights reserved.

4 Connect binary and analog output wiring to the UO screw terminals on the TV- UCXPIO48 and to the controlled device. Connect the ground wire to the UO’s – terminal.

WARNING Do not apply voltage to any output whose DIP switch is set to Analog.

Analog outputs

Binary outputs


Any UO +

Any UO +

Any UO +

Any UO +

Any UO +

­ 0-1 0 V
+ 2-wire
Gnd

­

0-1 0 V

Hot

3-wire

­

Hot

0-1 0 V

Gnd

4-wire

­

0-20 mA

Hot

3-wire

­

Hot

0-20 mA

Gnd

4-wire

24 Vac/Vdc


Any UO +

Gnd Coil: 24 Vac/Vdc, 1 A max.
24 Vac/Vdc


Any UO

To external device 24 Vac/Vdc, 1A max.
24 Vac/Vdc

5 Set each output’s two DIP switches to the appropriate settings for the type of device wired to the output.

For… Analog 0-20 mA Analog 0-10 Vdc Binary

Set top DIP switch to… Up Up Down

Set bottom DIP switch to… Up Down N/A

CAUTION Outputs are set to Binary in the factory. To avoid damage to the expander, use a voltmeter to verify there is no voltage on the + and – terminals before setting the DIP switch to Analog.
6 Turn on the TV-UCXPIO48’s power.
See Troubleshooting inputs and outputs (page 22).

TruVuTM I/O Expanders Installation and Start-up Guide

Carrier Proprietary and Confidential 14

©2023 Carrier. All rights reserved.

To adjust input and output properties
An input or output must be assigned to its corresponding point in the control program. This is typically done when the control program is created, but you can adjust the settings at the time of installation in the i-Vu® interface. 1 In the i-Vu® User tab, select the equipment controlled by the TV-UCXPIO48. 2 On the Properties page, select the I/O Points tab. 3 For each point, type the expander’s rotary switch address in the Exp field and the number of the expander’s
corresponding input or output in the Num field. EXAMPLE If UO-01 on the TV- UCXPIO48 (which has a rotary switch address of 1) is used for the point Fan S/S, enter 1:1 in the Exp:Num column for Fan S/S. NOTE Do not assign the same output number to more than one point. 4 Enter the appropriate values for each input and output in the remaining columns. See Input values, Output values, Resolution values and Offset/Polarity values below.
CAUTION Do not assign two input microblocks to the same physical input using Dry Contact in one and Binary Input in the other. This results in faulty behavior. 5 If you have not performed the initial download to the attached controller, you must download now to verify inputs and outputs. 6 To verify each input’s operation, force each sensor to a known value, then compare it to the Value shown on the Properties page on the I/O Points tab. 7 To verify each output’s operation, lock each output to a known condition on the I/O Points tab, then verify that the equipment operates correctly.
See Troubleshooting inputs and outputs (page 22) .

Input values

Input Analog (BAI) 0-5 Vdc

I/O Type 0­5 Volt

0-10 Vdc

0­10 Volt

Sensor/Actuator Type
Linear Full Range No Translation Linear Full Range

Min/Max
Engineering values associated with 0 Vdc (Min) and 5 Vdc (Max) 1 N/A. The input microblock’s value will be the raw voltage of the input. Engineering values associated with 0 Vdc (Min) and 10 Vdc (Max) 1

TruVuTM I/O Expanders Installation and Start-up Guide

Carrier Proprietary and Confidential 15

©2023 Carrier. All rights reserved.

Input

I/O Type

Sensor/Actuator Type

Min/Max

2-10 Vdc 0-20 mA

0­10 Volt 0­20 mA

4-20 mA RTD

0­20 mA RTD Input

Thermistor

Thermistor

Pulse to Analog (BPTA) 3

No Translation
Linear w/Offset, 2­10 Volts Linear Full Range
No Translation
Linear w/Offset, 4­20 mA Select your RTD type or set up and select a Non- Linear, Custom Table 2, 4 Select your Thermistor type or set up and select a Non-Linear, Custom Table 2

N/A. The input microblock’s value will be the raw voltage of the input. Engineering values associated with 2 Vdc (Min) and 10 Vdc (Max) 1 Engineering values associated with 0 mA (Min) and 20 mA (Max) 1 N/A. The input microblock’s value will be the raw milliamps of the input. Engineering values associated with 4 mA (Min) and 20 mA (Max) 1 N/A
N/A

Pulse Counter Dry Contact or N/A

N/A

Binary Input

Binary (BBI)

Dry Contact

Dry Contact

N/A

N/A

CAUTION Do not assign two input microblocks to the same physical input using Dry Contact in one and Binary Input in the other. This results in faulty behavior. 5
1 The sensor reads a value and sends a corresponding signal (Volt or mA) to the TV-UCXPIO48’s physical input. The Analog Input microblock uses the Min and Max values to linearly translate the signal into the engineering value used in subsequent control logic. For example, set Min to 0 and Max to 10 for a 4­20 mA sensor that measures velocity from 0.0 to 10.0 inches/second so that when the input reads 4 mA, the microblock outputs a value of 0. Similarly, when the input reads 8 mA, the microblock outputs a value of 2.5.
2 You can set up a custom translation table on the driver’s Custom Translation Tables pages in the i-Vu® interface.
3 The control program must have one Pulse to Analog Input microblock for each pulse counting input.
4 To improve the accuracy for RTD sensors used with long cables, see Offset/Polarity values (page 19).
5 Binary Input and Dry Contact input types are not interchangeable. Setting an input to Dry Contact applies a wetting voltage to sense a dry contact. Setting an input to Binary Input will not apply a wetting voltage.

TruVuTM I/O Expanders Installation and Start-up Guide

Carrier Proprietary and Confidential 16

©2023 Carrier. All rights reserved.

Output values

Output

I/O Type

Sensor/Actuator Type

Min/Max

Analog (BAO)

0-10 Vdc

Electrical 0­10 Volt

2-10 Vdc 0-20 mA

Electrical 0­10 Volt
Electrical 0­20 mA

4-20 mA

Electrical 0­20 mA

Digital (Binary) (BBO)

Linear Full Range No Translation
Linear w/Offset, 2­10 Volts Linear Full Range No Translation
Linear w/Offset, 4­20 mA

Engineering values associated with 0 Vdc (Min) and 10 Vdc (Max) 1
N/A. The Analog Output microblock will output the same value that comes in to the microblock.
Engineering values associated with 2 Vdc (Min) and 10 Vdc (Max) 1
Engineering values associated with 0 mA (Min) and 20 mA (Max) 1
N/A. The Analog Output microblock will output the same value that comes in to the microblock.
Engineering values associated with 4 mA (Min) and 20 mA (Max) 1

Relay

Relay/Triac

N/A

N/A

Output

1 The Analog Output microblock uses the Min and Max values to linearly translate its incoming value into a physical output signal (Volt or mA) sent from the TV-UCXPIO48 to an actuator. For example, set Min to 0 and Max to 100 for an Analog Output microblock that receives a 0 to 100% open signal from a PID microblock and that controls a 0­10 Vdc actuator so that when the PID signal is 100%, the TV-UCXPIO48 output is 10 Vdc. Similarly, when the PID signal is 50%, the TV-UCXPIO48 output is 5 Vdc.

TruVuTM I/O Expanders Installation and Start-up Guide

Carrier Proprietary and Confidential 17

©2023 Carrier. All rights reserved.

Resolution values
Resolution is not particular to a type of input or output, but the driver handles analog and binary inputs and outputs differently. To set these values appropriately, you should understand how the driver uses them.

Resolution

Notes

Analog Input (BAI)
Analog Output (BAO)

The driver rounds the microblock’s present value according to the resolution.
EXAMPLE If the calculated present value is 13.789 and you set the Resolution to 0.1, the control program uses 13.8 for any calculations downstream from the microblock.
The driver rounds the wire input value to the microblock before performing any scaling calculations.
EXAMPLE If the wire input value is 13.789 and you set the Resolution to 0.1, the microblock uses 13.8 for any scaling calculations.

TruVuTM I/O Expanders Installation and Start-up Guide

Carrier Proprietary and Confidential 18

©2023 Carrier. All rights reserved.

Offset/Polarity values
Offset/Polarity is not particular to a type of input or output, but the driver handles analog and binary inputs and outputs differently. To set these values appropriately, you should understand how the driver uses them.

Offset/Polarity Analog Input (BAI)

Notes
Offset value (positive or negative) adds a fine adjustment to a sensor reading after all scaling for calibration.
EXAMPLE If a sensor reads 74.9°F when the actual measured value is 73.6°F, enter an Offset of ­1.3 to calibrate the sensor to the measured value.
RTD inputs require either sensor calibration or an estimated offset correction for wiring resistance. Cable length and size affects RTD sensor accuracy. Use the following information for a 100 ft. (30.48 m) cable as a guideline for entering an offset. For shorter cable, scale the offset linearly. For example, for a 50 ft. cable, use half the offset shown below.

RTD sensor

Offset for 100 ft. (30.48 m) cable

22 AWG

18 AWG

Platinum 1kOhm at 32°F (0°C) (0.00375 -1.5 TCR)

-0.59

Nickel-iron 1kOhm at 70°F (21°C)

-1.1

-0.43

Platinum TS-8000 1kOhm at

-1.5

32°F (0°C) (0.00385 TCR)

-0.59

Balco (nickel-iron) TS8000 1kOhm

-1.4

at 70°F (21°C)

-0.56

Cable resistance for signal and

3.1

ground wires (ohms)

1.24

Analog Output (BAO) You can use the Offset value (positive or negative) to calibrate an output, but you generally do not need to. If used, the driver adds the offset value to the wire input value before performing any scaling calculations to determine the TV-UCXPIO48’s output.

Binary Input (BBI)

Polarity determines the microblock’s present value when no signal is received from the equipment.
When no signal is received from the equipment, if Polarity is set to: normal–present value is off reversed–present value is on

Binary Output (BBO) Polarity determines the TV-UCXPIO48’s output based on the control program’s signal to the microblock.
When the control program’s signal to the microblock is on, if Polarity is set to: normal–output is on reversed–output is off
NOTE Regardless of Polarity, the output will be off if the TV-UCXPIO48 loses power.

TruVuTM I/O Expanders Installation and Start-up Guide

Carrier Proprietary and Confidential 19

©2023 Carrier. All rights reserved.

To use an output’s Hand-Auto-Off switch
You can control an output using the Hand-Auto-Off switch.

Set the switch to… Hand
Auto Off

To…
· Turn on a binary output.
· Allow an analog output to be controlled by the AO Hand Override
potentiometer. Let the control program control the output
Turn off the output

The AO Hand Override, located below the Hand-Auto-Off switch, allows you to manually control the output level of an analog output. Place the Hand-Auto-Off switch in the Hand position, then turn the potentiometer counterclockwise to reduce the output, or clockwise to increase the output.

The control program can monitor the status of a Hand-Auto-Off switch and display the status on the control program’s Properties page > I/O Points tab in the i-Vu® interface. The Value of the point monitoring the HandAuto-Off switch shows Off if the switch is set to Auto, and On if the switch is set to Hand or Off.
To monitor the position of the manual Hand-Auto-Off switch
1 Insert a BACnet Binary Input microblock in the control program. 2 On the microblock’s Properties page in the i-Vu® interface, set the I/O Type field to H-A-O Status Feedback. 3 In the Input Number field, type the number of the output you want to monitor.

TruVuTM I/O Expanders Installation and Start-up Guide

Carrier Proprietary and Confidential 20

©2023 Carrier. All rights reserved.

Troubleshooting

LED’s

The LED’s on the TV-UCXPIO48 show the status of certain functions.

If this LED is on… Pwr RX TX Sts
Status

Status is… The TV-UCXPIO48 has power. The TV-UCXPIO48 is receiving data from the I/O bus. The TV-UCXPIO48 is transmitting data over the I/O bus.

Green, slow blink:

Expander is functioning normally.

Red, fast blink:

The controller cannot update the expander’s firmware. In the i-Vu® application, go to the controller driver I/O Bus and Xnet Expanders page to see if the expander is communicating with the controller.

Green, fast blink: Red, continuously on:

Firmware download is in progress. Invalid configuration settings. Contact Technical Support.

Located just below each output’s AO Hand Override potentiometer, the LED flashes when the expander starts up. After startup, if the output is:
· Binary, the LED will be either on or off to indicate the output’s status. · Analog, the LED’s brightness indicates the strength of the output signal.

TruVuTM I/O Expanders Installation and Start-up Guide

Carrier Proprietary and Confidential 21

©2023 Carrier. All rights reserved.

Troubleshooting inputs and outputs
The i-Vu® interface shows if you have I/O errors resulting from: · A misconfigured microblock · A misconfiguration on the expander · A missing or disconnected expander
To check for errors: 1 In the i-Vu® User tab or Network tree, select the equipment controlled by the TruVuTM Controller. 2 On the Properties page, select the I/O Points tab. 3 Click the Name of any input or output whose name is red (indicates an error) to open its dialog box.

4 On the Details tab, scroll down to see the Reliability field under BACnet Configuration.

5 Anything other than No Fault Detected indicates an error. See the table below to determine the error and possible actions to take.

Reliability description
Communication Failure
Configuration Error

Possible error
· Expander is not connected to the controller.
· The expander has no power.
· The controller is offline.
· The microblock’s I/O Type and Sensor/Actuator Type are not compatible.
· The output’s DIP switch setting does not match the connected device.

Verify that…
· The expander is connected to the controller’s I/O bus port.
· The expander has power.
· The I/O Type and Sensor/Actuator Type combination is valid for the I/O number and microblock type.
· The DIP switch setting is appropriate for the output and microblock type.

TruVuTM I/O Expanders Installation and Start-up Guide

Carrier Proprietary and Confidential 22

©2023 Carrier. All rights reserved.

Reliability description
Over Range No Output No Sensor

Possible error

Verify that…

· Invalid expander address or I/O number.
· Input exceeds the Min/Max limits.
· Output’s Hand-Auto-Off switch is in Hand or Off position.
· No device is attached to the output.

· The expander is present and functional at the address shown in the i-Vu® interface and that I/O number is valid.
· The input is within the Min/Max limits.
· The expander’s Hand-Auto-Off switch is in the Auto position.
· The device is present and functioning.

Shorted Loop

· Internal voltage feedback does not correspond with commanded value.

· The load on the output is within the valid range.

· A voltage/current source has not been
connected to an output.

Open Loop

· Internal current feedback does not correspond with commanded value.

· The load on the output is within the valid range.

· A voltage/current source has not been

connected to an output.

Unreliable Other

· Feedback from the expander does not · Expander may be faulty. Contact

correspond with commanded value (for

Technical Support.

example, the output relay is not in

commanded state).

To get the TV-UCXPIO48’s serial number
If you need the TV-UCXPIO48’s serial number when troubleshooting, the number is laser-etched on the board inside the TV-UCXPIO48. To remove the cover, insert a small flathead screwdriver as shown below, and then gently pry up on the cover until it is released from the base.

TruVuTM I/O Expanders Installation and Start-up Guide

Carrier Proprietary and Confidential 23

©2023 Carrier. All rights reserved.

To monitor expander communication
You can add an analog input in a control program that will provide the communication status of the TV-UCXPIO48. If the input reads a value of 85, the expander is communicating. If the input reads 0, the expander is not communicating. To have the input provide the TV-UCXPIO48’s status, define the following properties for the input. Expander: The expander number you want to read Input Number: 1 Input Type: Special
To replace the TV-UCXPIO48’s fuses
The TV-UCXPIO48 has 2 fuses:

Symptoms of a blown fuse: Expander’s power fuse – The expander’s Pwr LED is not lit.

If you suspect a fuse is blown, remove the fuse as described below, and use a multimeter to check it. If the fuse is blown, try to determine why it blew before you replace it. Check the power wiring polarity of the TV-UCXPIO48 and any other devices that share the power supply. Use the same polarity for all of them.

The fuses are fast-acting, 5mm x 20mm glass fuses that you can purchase from one of the following vendors:

Manufacturer
Littelfuse Bussmann Belfuse Optifuse

Mfr. Part # for 2A fuse
0217002.HXP S500-2-R 5SF 2-R FSD-2A

TruVuTM I/O Expanders Installation and Start-up Guide

Carrier Proprietary and Confidential 24

©2023 Carrier. All rights reserved.

To replace a fuse: 1 Turn off the TV-UCXPIO48’s power switch. 2 On one end of the expander, insert a small flathead screwdriver as shown below, and then gently pry up on
the cover until it is released from the base.
3 Remove the cover from the base. 4 Use a fuse puller to remove the blown fuse. 5 Use the fuse puller to snap the new fuse into the fuse holder. 6 Replace the expander’s cover. 7 Depending on how you removed power in step 2, replace the expander’s power connector. 8 Turn on the TV-UCXPIO48’s power switch. 9 Verify the Pwr LEDs on.

TruVuTM I/O Expanders Installation and Start-up Guide

Carrier Proprietary and Confidential 25

©2023 Carrier. All rights reserved.

Compliance
FCC Compliance
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: 1 This device may not cause harmful interference. 2 This device must accept any interference received, including interference that may cause undesired
operation. NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy, and if it is not installed and used in accordance with this document, it may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at his own expense.
CAUTION Any modifications made to this device that are not approved by Carrier will void the authority granted to the user by the FCC to operate this equipment.
CE and UKCA Compliance
WARNING This is a Class B product. In a light industrial environment, this product may cause radio interference in which case the user may be required to take adequate measures.
Industry Canada Compliance
This Class A digital apparatus complies with Canadian ICES-003. Cet appareil numérique de la classe A est conforme à la norme NMB-003 du Canada.

TruVuTM I/O Expanders Installation and Start-up Guide

Carrier Proprietary and Confidential 26

©2023 Carrier. All rights reserved.

Document revision history

Important changes to this document are listed below. Minor changes such as typographical or formatting errors are not listed.

Date

Topic

  • For internal use only

Change description
No updates yet

Code*

TruVuTM I/O Expanders Installation and Start-up Guide

Carrier Proprietary and Confidential 27

©2023 Carrier. All rights reserved.

Carrier ©2023 · Catalog No. 11-808-1009-01 · 10/23/2023

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals