TCL 9789879 Air Conditioner Multi Split

June 16, 2024
TCL

TCL-logo

TCL 9789879 Air Conditioner Multi Split

TCL-9789879-Air-Conditioner-Multi-Split-image

Product Information

Specifications

  • Fuse Rating: 4A / 250V
  • Disconnection Means: Must provide full disconnection under overvoltage category III conditions
  • Installation: Must be in accordance with applicable national\ regulations and wiring rules
  • Intended Use: Air conditioning domestic environments

Product Usage Instructions

Safety Rules and Recommendations for the Installer

  • Before accessing the terminals, disconnect all power circuits from the power supply.
  • Install the appliance in accordance with national wiring regulations.

Safety Rules and Recommendations for the User

  • Cleaning and maintenance must be carried out by specialized technical personnel. Disconnect the appliance from the mains electricity supply before cleaning or maintenance.
  • Do not use the appliance for any purpose other than air conditioning domestic environments.
  • Recycle or dispose of the batteries in the remote controller properly.
  • If the appliance emits smoke or there is a smell of burning, immediately cut off the power supply and contact the Service Centre.
  • Have repairs carried out only by an authorized Service Centre of the manufacturer.
  • If not using the device for a long time, unhook the automatic switch.
  • Properly adjust the airflow direction.

Safety Rules and Prohibitions

  • Do not obstruct the air inlet or outlet of the indoor or outdoor unit, as it can reduce efficiency and cause failures or damages.
  • This appliance is not intended for use by persons (including children) with reduced physical, sensory, or mental capabilities, unless supervised or instructed by someone responsible for their safety.
  • Children should be supervised to ensure they do not play with the appliance.
  • If the supply cord is damaged, it must be replaced by the manufacturer, its service agent, or similarly qualified persons to avoid hazards.

Names of Parts

  1. Indoor unit 1
  2. Indoor unit 2
  3. Indoor unit 3
  4. Indoor unit 4
  5. Air Intake
  6. Front Panel
  7. Electrostatic Filter (optional)
  8. Air Filter
  9. Display Panel
  10. Air Outlet
  11. Emergency Panel
  12. Vertical Adjustment Louver
  13. Charcoal Filter (optional)
  14. Horizontal Adjustment Louver
  15. Air Intake
  16. Drain Hose (Note: Condensate water drains at COOLING or DRY operation)
  17. Pipes and Power Connection Cord
  18. Air Outlet
  19. Remote Controller

FAQs

Q: Can I clean and maintain the appliance myself?

A: No, cleaning and maintenance must be carried out by specialized technical personnel.

Q: Can I use the appliance for purposes other than air conditioning domestic environments?

A: No, the appliance is specifically made for air conditioning domestic environments and should not be used for any other purpose.

Q: What should I do if there is smoke or a smell of burning coming from the appliance?

A: Immediately cut off the power supply and contact the Service Centre.

Q: Can I repair the appliance myself?

A: No, repairs should only be carried out by an authorized Service Centre of the manufacturer. Incorrect repair could expose the user to the risk of electric shock, etc.

Q: What should I do if the supply cord is damaged?

A: It must be replaced by the manufacturer, its service agent, or similarly qualified persons in order to avoid hazards.

(For Multi split)

SAFETY RULES AND RECOMMENDATIONS FOR THE INSTALLER

The ratings of the fuse installed in the built
in control unit are 4A / 250V .
The appliance must be fitted with means for
disconnection from the supply mains having a contact separation in all poles that provide full disconnection under overvoltage category III conditions, and these means must be incorporated in the fixed wiring in accordance with the wiring rules.

Only use the air conditioner as instructed in
this booklet.
The appliance must be installed in accordance
with applicable national regulations.
Before accessing the terminals , all the power
circuits must be disconnected from the power supply.
The appliance shall be installed in accordance
with national wiring regulations.

1

SAFETY RULES AND RECOMMENDATIONS FOR THE USER

Cleaning and maintenance must be carried out
by specialized technical personnel. In any case disconnect the appliance from the mains electricity supply before carrying out any cleaning or maintenance.
This appliance has been made for air
conditioning domestic environments and must not be used for any other purpose.
The batteries in remote controller must be
recycled or disposed of properly.

If the appliance gives off smoke or there is a
smell of burning, immediately cut off the pow er supply and contact the Service Centre.
Have repairs carried out only by an authorised
Service Centre of the manufacturer . Incorrect repair could expose the user to the risk of electric shock, etc.
Unhook the automatic switch if you foresee
not to use the device for a long time. The airflow direction must be properly adjusted

2

SAFETY RULES AND PROHIBITIONS

Do not obstruct the air inlet or outlet of the
indoor or the outdoor unit. The obstruction of these openings causes a reduction in the operative efficiency of the conditioner with possible consequent failures or damages.
This appliance is not intended for use by
persons (including children ) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.

Children should be supervised to ensure
that they do not play with the appliance. If the supply cord is damaged, it must be replaced by the manufacturer,its service agent or similarly qualified persons in order to avoid a hazard.

3

NAMES OF PARTS

Indoor unit 4

Indoor unit 3 Indoor unit 2

Indoor unit 1
1 2
3

4 5
6

1. Air Intake 2. Front Panel

MODE

FAN

ECO

SWING MUTE HEALTH TURBO

SLEEP

TIMER

DISPLAY SWING IFEEL CLEAN I SET

15

3. Electrostatic Filter (optional)

7 8 9 10
11

4. Air Filter

5. Display Panel

12

6. Air Outlet

7. Emergency Panel

13

8. Vertical Adjustment Louver

14

9. Charcoal Filter (optional)

10. Horizontal Adjustment Louver

11. Air Intake

12 .Drain Hose Note: Condensate water drains at COOLING or DRY operation.

Outdoor unit

13 .Pipes and Power Connection Cord

14. Air Outlet

15. Remote Controller

Note: the above figures are only intended to be a simple diagram of the appliance and may not correspond to the appearance of the units that have been purchased.

5

INDOOR UNIT DISPLAY

2

3

1

No. Led
1 SLEEP

2

Temperature display (if present) /Error code

3 TIMER

Function

SLEEP mode
(1) Lights up during Timer operation when the air conditioner is operational (2)Displays the malfunction code when fault occurs.
Lights up during Timer operation.

The shape and position of switches and indicators may be different according to the model, but their function is the same.

5

EMERGENCY FUNCTION & AUTO-RESTART FUNCTION

If the remote controller fails to work or maintenance necessary, proceed as following: Open and lift the front panel up to an angle to reach the emergency button. For heating model, press the emergency button first and the unit will operate in COOL mode. Press for a second time within 3 seconds, and unit will operate in HEAT mode. Press for third after 5 seconds, the unit will turn off. For cooling only models, press the emergency button once, and the unit will operate in COOL mode. Press again, the unit will turn off.
The appliance is preset with an auto-restart function. In case of a sudden power failure, the module will memorizes the setting conditions before the power failure. When the power restores, the unit will restart automatically with the previous settings preserved by the memory function.

front panel
Emergency button The emergency button is located on E-box cover of the unit under the front panel.

The shape and position of the emergency button may be different according to the model, but their function is the same.

6

REMOTE CONTROLLER

For ON/OFF models 7

For inverter models

REMOTE CONTROLLER

Remote controller buttons

No.

Buttons

Function

1

To turn on/off the air conditioner

2

GENTLE WIND

To activate the function of Gentle wind.

3

MODE

To select the operation mode: AUTO, COOL, DRY, FAN, HEAT.

4

(TEMP UP)

To increase the setting temperature, lengthen the time in TIMER setting.

5

(TEMP DN)

To decrease the setting temperature, reduce the time in TIMER setting.

6

To adjust the air flow direction vertically(optional).

7

To adjust the air flow direction horizontally.

8

FAN

To adjust the fan speed: auto, mute, low, mid-low, mid, mid-hign, high. Turbo

9

I FEEL

To activate the function of I FEEL

10

I SET

To activate the function of I SET

11

TURBO

To switch on/off the TURBO mode

12

To switch on/off the GENERATOR mode

13

TIMER/SLEEP

To switch on/off the TIMER function and SLEEP mode

14

ECO/DISPLAY

To switch on/off the ECO mode and LED display light

15

HEALTH/CLEAN

To switch on/off the HEALTH function and Auto Clean function..

16 TIMER/SLEEP + ECO/DISPLAY To switch on/off the CHILL WIND and HOT WIND fucntion.

17 ECO/DISPLAY + HEALTH/CLEAN To switch on/off the CHILL WIND and HOT WIND fucntion.

18

( + )

To activate the function of Child Lock, press and buttons together for more than 3 seconds.

The display and some functions of the remote control may vary according to the model. The shape and position of buttons and indicators may vary according to the model, but their function is the same. The unit confirms the correct reception of each button with a beep. Certain functions may not be available for your air conditioner. The batteries in remote controller must be recycled or disposed of properly.

8

REMOTE CONTROLLER

Remote controller DISPLAY, meaning of symbols on the liquid crystal display

No.

Symbols

Meaning

1

AUTO MODE indicator

2 3 4 5 6

7

8

or

9

10

11 (FLASH)
12

13 14

15

16

17

18

19

COOLING MODE indicator DRY MODE indicator FAN MODE indicator HEATING MODE indicator BATTERY indicator TEMPERATURE/ CLOCK indicator FLAP SWING (Air flow) indicator MUTE indicator FAN SPEED indicator AUTO FAN indicator TURBO indicator CHILD LOCK indicator I FEEL indicator GENTLE WIND indicator CHILL WIND indicator ECO indicator HEALTHY indicator GENERATOR MODE indicator

20

TIMER indicator

21

SLEEP MODE indicator

22

HOT WIND indicator

23

DISPLAY LIGHT indicator

24

CLEAN function indicator

25

8 C heating function indicator

9

Replacement of Batteries
Remove the battery cover plate from the rear of the remote controller, by sliding it in the direction of the arrow. Install the batteries according the direction (+and -)shown on the Remote Controller. Reinstall the battery cover by sliding it into place.
Use 2 LRO 3 AAA (1.5V) batteries . Do not use rechargeable batteries . Replace the old batteries with new ones of the same type when the display is no longer legible. Do not dispose batteries as unsorted municipal waste. Collection of such waste separately for special treatment is necessary. Recommendations for locating and using the remote controller holder (if present). The remote controller be kept in a wall-mounted holder.
10

OPERATING INSTRUCTIONS

The air sucked by the fan enters from the grill and passes through the filter, then it is cooled/dehumidified or heated through the heat exchanger.
The direction of the air outlet is motorized up and down by flaps, and manually moved right and left by the vertical deflectors, for some models, the vertical deflectors could be controlled by motor as well.

Filter
Heat Exchanger

Fan

Turn ON / Turn OFF the air conditioner

Press the button

to turn on or turn off the air conditioner.

COOLING MODE
The cooling function allows the air conditioner to cool the room and at the same time reduces Air humidity. To activate the cooling function ( COOL ) , press the MODE button until the symbol appears on the display. With the button or set a temperature lower than that of the room.
11

OPERATING INSTRUCTIONS
HEATING MODE
The heating function allows the air conditioner to heat the room. To activate the heating function ( HEAT ) , press the MODE button until the symbol appears on the display. With the button or set a temperature higher than that of the room.
In HEATING operation, the appliance can automatically activate a defrost cycle, which is essential to clean the frost on the condenser so as to recover its heat exchange function. This procedure usually lasts for 2-10 minutes. During defrosting, indoor unit fan stop operation. After defrosting, it resumes to HEATING mode automatically.
DRY MODE
This function reduces the humidity of the air to make the room more comfortable.
To set the DRY mode , Press MODE until appears in the display. An automatic
function of pre-setting is activated.
FAN MODE(Not FAN button)
Fan mode, air ventilation only.
To set the FAN mode, press MODE until appears on the display.
AUTO MODE
Automatic mode.
To set the AUTO mode, press MODE until appears on the display.
In AUTO mode the run mode will be set automatically according to the room temperature.
12

OPERATING INSTRUCTIONS
Change the fan speed
Press FAN button to set the running fan speed, it can be set to AUTO/ MUTE/ LOW/ MID-LOW/ MID/ MID-HI/ HIGH/TURBO speed. Flashing

AIR FLOW CONTROL

1. Normal 4 way air flow (vertical and horizontal):

(1) Press

to activate the horizontal flaps to

swing from up to down. Press again to stop the swing

movement at the current angle.

(2) Press

to active the vertical deflectors to

swing from left to right. Press again to stop the swing

movement at the current angle.

2. Vector precise air flow (1)Press and hold for 1s, it will go into the horizontal
vector air flow, you can select a small swing angle you want:

Stop selection for 5s, press

again, exit the horizontal vector precise air flow.

(2) Press and hold for 1s, it will go into the vertical vector air flow:

Stop selection for 5s, press

again, exit the vertical vector precise air flow.

3. If the vertical deflectors are positioned manually whichplaced under the flaps, they are allowed to move the air flow direct to rightward or leftward.

This adjustment must be done while the appliance is switched off.
Flaps manually, the delicate mech-anism might seriously damaged!

Never poke fingers, sticks or other objects in the air inlet or outlet vents. Such accidental contact with liveparts might cause unforeseeable damage or injury.

flap movement Vertical Deflectors
Horizontal Flaps

13

OPERATING INSTRUCTIONS
GENTLE WIND (Optinal)
In this mode the appliance will close its vertical louvers, the air flow through the holes of louvers, the room is cool but no winds. Press the GENTLE WIND button shortly, the appears on the display, and the appliance will run in GENTLE WIND mode. Press again to cancel it.. NOTE: The gentle wind function is available in COOLING mode only.
I FEEL function
I FEEL
Press I FEEL button to active the function, the will appear on the remote display. Do it again to deactivate this function. This function enables the remote control to measure the temperature at its current location, and send this signal to the air conditioner to optimize the temperature around you and ensure the comfort. It will automatically deactivate 2 hours later.
Turbo function
To activate turbo function, press the TURBO button, and will appear on the display. Press again to cancel this function. In COOL/HEAT mode, when you select TURBO feature, the appliance will operate the fast cooling/ fast heating with the highest fan speed.
14

OPERATING INSTRUCTIONS
GENERATOR MODE (Optional)
The air conditioner works in generator mode, it is helpful for the unstable net power area. Through GEN mode,you can choose the current level of the unit.There are three levels (L1,L2,L3) in this mode, and the current increases in turn. To activate GEN function,pressing the button GEN and the unit current level will cycle as below OFF L3 L2 L1 Running current (% of rated current): L1: 30%, L2: 50%, L3:70% To cancel this function,press the GEN until code OF appers on the display.
SLEEP MODE
Pre-setting automatic operating program.
Press SLEEP button and hold for 2s to activate the sleep mode, and appears on the display. Press and hold for 2s again to cancel this mode.
In sleep mode, the air conditioner will automatically adjust the temperature and fan speed to make the room more comfortable during the night. After 10 hours running in sleep mode, the air conditioner will change to the previous setting mode.
ECO MODE
In this mode the appliance automatically sets the operation to save energy.
Press the ECO button, the appears on the display, and the appliance will run in ECO mode. Press again to cancel it..
NOTE: The ECO function is available in both COOLING and HEATING modes.
15

OPERATING INSTRUCTIONS
LED display light ON/OFF
Press DISPLAY button and hold for 2s to turn on/off the indoor LED display light.

HEALTH function (Optional)
Press HEALTH button to active / exit the health functions such as ion generator/ plasma etc
Note: Health function is not available when the air conditioner is off.

SELF-CLEAN function (Optional)

1. This function help carry away the accumulated dirt, bacteria, etc from the evaporator.
2. Turn off the air conditioner, press “CLEAN” button to enter this function and it will show “CL” on the display of indoor unit.
3. This function will run about 30 minutes, and it will exit automatically. You will hear 2 beeps when it’s finished or cancelled.
4. It’s normal if there are some noise during this function process, as plastic materials expand with heat and contract with cold.
5.We suggest operate this function as the following ambient condition to avoid certain safety protection features.

Indoor unit Outdoor unit

Temp<30 5 <Temp<30

6. We suggest operate this function once every 3 months.

16

OPERATING INSTRUCTIONS

TIMER MODE—-SET TIMER OFF

TIMER

To set the air conditioner switching-off automatically.

With the AC on, press the Timer button and then use the and buttons to set the length of time before the AC
will turn off. Press the timer button again to start the countdown.

Note:To cancel the set function, press the TIMER button again.
Note:In case of power off,it is necessary to set TIMER OFF again

TIMER MODE—-SET TIMER ON
TIMER To set the air conditioner switching-on automatically.
With the AC off, press the Timer button and use the and buttons to set the desired amount of time before the
AC turns on. Press the timer button again to start the countdown. When the timer setting was done, you can set the operation mode, fan speed, desired temperature, air flow when air conditioner star to run.
Note: To cancel the timer function ,press the TIMER button again.
Note: In case of power off, it is necessary to set TIMER ON again
17

OPERATING INSTRUCTIONS
CHILL wind/ HOT wind function (Optional)
1. In cooling mode, press both TIMER/SLEEP and ECO/DISPLAY buttons and hold for 2s to active the chill wind function.
2. In heating mode, press both TIMER/SLEEP and ECO/DISPLAY buttons and hold for 2s to active the hot wind function.
3. Press both TIMER/SLEEP and ECO/DISPLAY buttons and hold for 2s to exit the chill wind or hot wind function.
8 heating function (Optional)
1.Press both ECO/DISPLAY and HEALTH/CLEAN buttons and hold for 2s to active the 8 heating.
2.If the air conditioner is standby, this function enable the air conditioner automatically start heating when the indoor temperature isequal or lowerthan 8 , it willreturn standby if thetemperature is equalor higher than18 .
3.When the AC was turn off, press both ECO/DISPLAY and HEALTH/CLEAN buttons and hold for 2s to exit the 8 heating.
I SET function(Optional)
In each mode of COOLING/HEATING/FAN/DRY, adjust the temperature(COOLING/HEATING), fan speed (COOLING/ HEATING/FAN)and swing as your favourite, then keep pressing “I SET” button over 3 seconds until “AU” appears on the display and the background of display change to lighting, the remote controller will run and remember these settings. You can reset it by repeat the above operation. In each mode of COOLING/HEATING/FAN/DRY, press “I SET” button to active this function, the AC will run as your favourite setting and you will see AU flashing on the remote controller. Press it again or other buttons to cancel this function.
18

OPERATING INSTRUCTIONS

Operating Temperature
The air conditioner is programmed for comfortable and suitable living conditions as below if used outside the conditions, certain safety protection features might come into effect.,

Fix air conditioner:

MODE Temperature

Cooling operating

Heating operating Drying operating

Room temperature

17 ~32

0 ~27

17 ~32

Outdoor temperature

15 ~43 For T1 Climate
15 ~52 For T3 Climate

-7 ~24

15 ~43 For T1 Climate
15 ~52 For T3 Climate

Inverter air conditioner:

MODE Temperature

Cooling operating

Room temperature

17 ~32

Outdoor temperature

15 ~53
-15 ~53 For models with low temperature cooling system

Heating operating Drying operating

0 ~30 -20 ~30

17 ~32
15 ~53
-15 ~53 For models with low temperature cooling system

The unit does not operate immediately if it is turned on after being turned off or after changing the mode during operation.This is a normal self- protection action, you need to wait for about 3 minutes.
The capacity and efficiency are according to the test conducted at full-load operation(The highest speed of indoor fan motor and the maximum open angle of the flaps and deflectors are requested.)

19

INSTALLATION

MANUAL—Important considerations for R32/R290

Special Tools

Tool Name Mini Vacuum Pump

Requirement(s) for Use
It should be an explosion-proof vacuum pump; can ensure certain precision and its vacuum degree should be lower than 10Pa.

Filling Device

It should be a special explosion-proof filling device; have certain precision and its filling deviation should be less than 5g.

Leak Detector

It should be calibrated regularly; and its annual leak rate should not exceed 10g.

A) The maintenance site should be equipped with a fixed-type combustible refrigerant concentration detector and connected to a safeguard alarm system; its error must be not more than 5%.
B) The installation site should be equipped with a portable combustible refrigerant Concentration Detector concentration detector which can realize two-level audible and visual alarm;
its error must be not more than 10%. C) The concentration detectors should be calibrated regularly. D) It is necessary to check and confirm the functions before using the concentration
detectors.

Pressure Gauge

A) The pressure gauges should be calibrated regularly. B) The pressure gauge used for Refrigerant 22 can be used for Refrigerants R290
and R161; the pressure gauge used for R410A can be used for Refrigerant 32.

Fire Extinguisher

It is necessary to carry fire extinguisher(s) when installing and maintaining an air conditioner. On the maintenance site, there should be two or more kinds of dry powder, carbon dioxide and foam fire extinguishers and that such fire extinguishers should be placed at stipulated positions, with eye-catching labels and in handy places.

23

INSTALLATION MANUAL—Important considerations for R32/R290
Installation Safety Principles
1. Site Safety

Open Flames Prohibited 2. Operation Safety
Open Flames Prohibited

Ventilation Necessary

Mind Static Electricity Must wear protective clothing and anti-static gloves Don`t use mobile phone

3. Installation Safety
Refrigerant Leak Detector Appropriate Installation Location

The left picture is the schematic diagram of a refrigerant leak detector.

Please note that:
1. The installation site should be in a well-ventilated condition.
2. The sites for installing and maintaining an air conditioner using Refrigerant R290 should be free from open fire or welding, smoking, drying oven or any other heat source higher than 370 which easily produces open fire; the sites for installing and maintaining an air conditioner using Refrigerant R32 should be free from open fire or welding, smoking, drying oven or any other heat source higher than 548 which easily produces open fire.
3. When installingan air conditioner,it is necessary to take appropriate anti-static measures such as wear anti-static clothing and/or gloves.
4. It is necessary to choose the site convenient for installation or maintenance wherein the air inlets and outlets of the indoor and outdoor units should be not surrounded by obstacles or close to any heat source or combustible and/or explosive environment.
5. If the indoor unit suffers refrigerant leak during the installation, it is necessary to immediately turn off the valve of the outdoor unit and all the personnel should go out till the refrigerant leaks completely for 15 minutes. If the product is damaged, it is a must to carry such damaged product back to the maintenance station and it is prohibited to weld the refrigerant pipe or conduct other operations on the user’s site.
6. It is necessary to choose the place where the inlet and outlet air of the indoor unit is even.
7. It is necessary to avoid the places where there are other electrical products, power switch plugs and sockets, kitchen cabinet, bed, sofa and other valuables right under the lines on two sides of the indoor unit.

22

INSTALLATION MANUAL—Important considerations for R32/R290

The maximum charge and the required minimum floor area
m1 = (4 m3) x LFL , m2 = (26 m3)) x LFL, m3 = (130 m3 )x LFL Where LFL is the lower flammable limit in kg/ m3 R290 LFL is 0.038 kg/ m3,R32 LFL is 0.038 kg/ m3. For the appliances with a charge amount m1 < M = m2: The maximum charge in a room shall be in accordance with the following:m = max 2 5 x (LFL)(5/4) x h x (A)1/2 The required minimum floor area Amin to install an appliance with refrigerant charge M (kg) shall be in accordance with following: Amin = (M/ (2 5 x (LFL)(5/4) x h )) 2 Where: mmax is the allowable maximum charge in a room, in kg; M is the refrigerant charge amount in appliance, in kg; Amin is the required minimum room area, in m2; A is the room area, in m2; LFL is the lower flammable limit, in kg/m3; h is the installation height of the appliance,in meters for calculating mmax or A , min 1 8 m for wall mounted;

Table GG.1 – Maximum charge (kg)

Category

LFL (kg/m3)

h0 (m) 4

7

Floor area (m2)

10

15

20

30

50

0.6 0.05 0.07 0.08 0.1 0.11 0.14 0.18

R290

1 0.08 0.11 0.13 0.16 0.19 0.2 0.3

0.038 1.8 0.15 0.2

0.24 0.29 0.34 0.41 0.53

2.2 0.18 0.24 0.29 0.36 0.41 0.51 0.65

0.6 0.68 0.9 1.08 0.32 1.53 1.87 2.41

R32

0.306 1 1.14 1.51 1.8

2.2

2.54 3.12 4.02

1.8 2.05 2.71 3.24 3.97 4.58 5.61 7.254

2.2 2.5

3.31 3.96 4.85 5.6

6.86 8.85

Table GG.2 – Minimum room area (m2)

Category

LFL (kg/m3)

h0 (m)

Charge amount (M) (kg) Minimum room area (m2)

R290 R32

0.038 0.306

0.152kg 0.6 1 1.8 2.2
1.224kg 0.6 1 1.8 2.2

0.228kg 82 30 9 6 1.836kg 29 10 3 2

0.304kg 146 53 16 11 2.448kg 51 19 6 4

0.456kg 328 118 36 24 3.672kg 116 42 13 9

0.608kg 584 210 65 43 4.896kg 206 74 23 15

0.76kg 912 328 101 68 6.12kg 321 116 36 24

0.988kg 1514 555 171 115 7.956kg 543 196 60 40

21

INSTALLATION MANUAL—Important considerations for R32/R290
Important Considerations
The air conditioner you buy must be installed by professional personnel and the Installation manual is used only for the professional installation personnel! The
installation specifications should be subject to our after-sale service regulations. When filling the combustible refrigerant, any of your rude operations may cause serious injury or injuries to human body or bodies and object or objects. A leak test must be done after the installation is completed. It is a must to do the safety inspection before maintaining or repairing an air conditioner using combustible refrigerant in order to ensure that the fire risk is reduced to minimum. It is necessary to operate the machine under a controlled procedure in order to ensure that any risk arising from the combustible gas or vapor during the operation is reduced to minimum. Requirements for the total weight of filled refrigerant and the area of a room to be equipped with an air conditioner (are shown as in the following Tables GG.1 and GG.2)
20

25
23

INSTALLATION MANUAL—Installation of the Indoor unit

Before starting installation, decide on the position of the indoor and outdoor units, taking into account the minimum space reserved around the units
Do not install your air conditioner in a wet room such as a bathroom or laundry etc
The installation site should be 250cm or more above the floor.
To install, proceed as follows:
Installation of the mounting plate

1. Always mount the rear panel horizontally and vertically 2. Drill 32 mm deep holes in the wall to fix the
plate; 3. Insert the plastic anchors into the hole; 4. Fix the rear panel on the wall with provided tapping screws 5. Be sure that the rear panel has been fixed firmly enough
to withstand the weight.
Note : The shape of the mounting plate may be different from the one above, but installation method is similar .
Drilling a hole in the wall for the piping
1. Make the piping hole ( 65) in the wall at a slight downward slant to the outdoor side.
2. Insert the piping-hole sleeve into the hole to prevent the connection piping and wiring from being damaged when passing through the hole. The hole must slope downwards towards the exterior
Note : Keep the drain pipe down towards the direction of the wall hole, otherwise leakage may occur.
Electrical connections—Indoor unit

Indoors

Outdoors 5mm

1. Open the front panel. 2. Take off the cover as indicated in the piciure ( by
removing a screw or breaking the hooks). 3. For the electrical connections, see the circuit diagram
on the right part of the unit under the front panel. 4. Connect the cable wires to the screw terminals by
following the numbering ,Use wire size suitable to the electric power input (see name plate on the unit) and according to all current national safety code requirements. The cable connecting the outdoor and indoor units must be suitable for outdoor use. The plug must be accessible also after the appliance has been installed so that it can be pulled out if necessary. An efficient earth connection must be ensured. If the power cable is damaged, it must be replaced by an authorised Service Centre.
Note:Optional the wires can been connected to the main PCB of indoor unit by manufacturer according to the model without terminal block.

25

INSTALLATION MANUAL—Installation of the Indoor unit

Refrigerant piping connection
The piping can be run in the 3 directions indicated by numbers in the picture . When the piping is run in direction 1or 3, cut a notch along the groove on the side of the indoor unit with a cutter. Run the piping in the direction of the wall hole and bind the copper pipes , the drain pipe and the power cables together with the tape with the drain pipe at the bottom, so that water can flow freely.
Do not remove the cap from the pipe until connecting it, to avoid dampness or dirt from entering. If the pipe is bent or pulled too often , it will become stiff . Do not bend the pipe more than three times at one point. When extending the rolled pipe, straighten the pipe by unwinding it gently as shown in the picture.

1 23

Shape the connection pipe

YES

NO

Extending the rolled pipe

Connections to the indoor unit
1. Remove the indoor unit pipe cap (check that there is no debris inside).
2. Insert the fare nut and create a flange at the extreme end of the connection pipe.
3. Tighten the connections by using two wrenches working in opposite directions.
4. For R32/R290 refrigerants, mechanical connectors should be outdoors.

torque wrench
The connectors should be outdoors

Indoor unit condensed water drainage
The indoor unit condensed water drainage is fundamental for the success of the installation.
1. Place the drain hose below the piping, taking care not to create siphons.
2. The drain hose must slant downwards to aid drainage. 3. Do not bend the drain hose or leave it protruding or
twisted and do not put the end of it in water . If an extension is connected to the drain hose , ensure that it is lagged when it passes into the indoor unit. 4. If the piping is installed to the right, the pipes, power cable and drain hose must be lagged and secured onto the rear of the unit with a pipe connection. 1) Insert the pipe connection into the relative slot. 2) Press to join the pipe connection to the base.
26

YES

NO

NO

INSTALLATION MANUAL—Installation of the Indoor unit

INSTALLATION OF THE INDOOR UNIT
After having connected the pipe according to the instructions, install the connection cables. Now install the drain pipe. After connection,lag the pipe, cables and drain pipe with the insulating material.
1. Arrange the pipes ,cables and drain hose well. 2. Lag the pipe joints with insulating material , securing
it with vinyl tape. 3. Run the bound pipe , Cables and drain pipe through
the wall hole and mount the indoor unit onto the upper part of the mounting plate securely. 4. Press and push the lower part of the indoor unit tightly against the mounting plate

Covered by vinyl tape

refrigerant pipe connection cable
connection cable 1 (for heat-pump)

insulation sleeve
refrigerant pipe

Probe

Condensed water

cable(for heat-pump) drain pipe

mounting plate

Sometimes, if the refrigerant piping is already embedded in the wall,or if you want to connecting the piping and wiring on the wall, do as below: 1.Gab both ends of the bottom plate, apply a little outward force to take off the bottom plate.
2.Hook the top of the indoor unit on the mounting plate without piping and wiring.
3.Lift the indoor unit opposite the wall, unfold the bracket on the mounting plate, and use this bracket to prop up the indoor unit, there will be a big space for operation.
4.Do the refrigerant piping, wiring, connect drainage hose, and wrap them as Step 4 to 7.
5.Replace the bracket of mounting plate.
6.Push down the bottom of indoor unit to let the snaps onto the bottom hooks of the mounting plate, and make sure it is hooked firmly.
7.Replace the bottom plate of the indoor unit.

Take off the bottom plate

Unfold the bracket on the mounting plate

27

INSTALLATION MANUAL—Installation of the outdoor unit
The outdoor unit should be installed on a solid wall and fastened securely. The following procedure must be observed before connecting the pipes and connecting cables : decide which is the best position on the wall and leave enough space to be able to carry out maintenance easily. Fasten the support to the wall using screw anchors which are particularly suited to the type of wall; Use a larger quantity of screw anchors than normally required for the weight they have to bear to aviod vibration during operation and remain fastened in the same position for years without the screws becoming loose. The unit must be installed following the national regulations. The outdoor unit should be installed on a solid wall and fastened securely, of on the ground on a flat/level surface like a concrete slab. The bolt size is M8*80mm.

Outdoor unit condensed water drainage (only for heat pump models)
The condensed water and the ice formed in the outdoor unit during heating operation can be drained away through the drain pipe
1. Fasten the drain port in the 25mm hole placed in the part of the unit as shown in the picture.
2. Connect the drain port and the drain pipe. Pay attention that water is drained in a suitable place.

drain port

drain pipe

28

INSTALLATION MANUAL—Installation of the outdoor unit

ELECTRICAL CONNECTIONS

1. Remove the handle on the right side plate of outdoor unit. 2. Connect the power connection cord to the terminal board.
Wiring should fit that of indoor unit. 3. Fix the power connection cord with wire clamp. 4. Confirm if the wire has been fixed properly. 5. An efficient earth connection must be ensured. 6. Recover the handle. 7.The appliance must be fitted with means for disconnection
from the supply mains having a contact separation in all poles that provide full disconnection under over voltage category III conditions, and these means must be incorporated in the fixed wiring in accordance with the wiring rules.

wiring diagram on the back of the cover
screw

CONNECTING THE PIPES

Screw the flare nuts to the outdoor unit coupling with the same tightening procedures described for the indoor unit.
To avoid leakage, pay attention to the following points:
1. Tighten the flare nuts using two wrenches. Pay attention not to damage the pipes.
2. If the tightening torque is not sufficient , there will probably be some leakage. With excessive tightening torque there will also be some leakage, as the flange could be damaged.
3. The surest system consists in tightening the connection by using a fix wrench and a torque wrench as below:

PIPE Size
1/4 ( 6.35)
3/8 ( 9.52)
1/2 ( 12)
5/8 ( 15.88)

Newton meter Pound-force foot Kilogram-force meter

[N x m]

(1bf-ft)

(kgf-m)

18 – 20 30 – 35 45 – 50 60 – 65

24.4 – 27.1 40.6 – 47.4 61.0 – 67.7 81.3 – 88.1

2.4 – 2.7 4.1 – 4.8 6.2 – 6.9 8.2 – 8.9

connection pipes

flare nuts liquid tap
gas tap

indoor unit gas valve

liquid valve tap

service port nut

protection caps

29

INSTALLATION MANUAL—Installation of the outdoor unit

Air Vacuumizing
1.Use a spanner to take down the protective caps from the service port, low pressure valve and high pressure valve of the outdoor unit.
2.Connect the pressure hose of manifold gauge to the service port on the outdoor unit low pressure valve.
3.Connect the charge hose from the manifold gauge to the vacuum pump.
4.Open the low pressure valve of the manifold gauge and close the high pressure valve.
5.Turn on the vacuum pump to vacuumize the system. 6.The vacuuming time should not be less than 15
minutes, or make sure the compound gauge indicates -0.1 MPa (-76 cmHg) 7.Close the low pressure valve of the manifold gauge and turn off the vacuum. 8.Hold the pressure for 5 minutes, make sure that the rebound of compound gauge pointer does not exceed 0.005 Mpa. 9.Turn the low pressure valve counterclockwise for 1/4 turn with hexagonal wrench to let a little refrigerant fill in the system, and close the low pressure valve after 5 seconds and quickly remove the pressure hose. 10.Check all indoor and outdoor joints for leakage with soapy water or leak detector. 11.Fully open the low pressure valve and high pressure valve of the outdoor unit with hexagonal wrench. 12.Replace the protective caps of the service port, low pressure valve and high pressure valve of the outdoor unit. 13.Replace the valve cover.
Refrigerant Pressure Inspection
Air-returning Low-pressure Range of Refrigerant R290: 0.4-0.6Mpa; Air- exhausting High-pressure Range: 1.5-2.0Mpa; Air-returning Low-pressure Range of Refrigerant R32: 0.8-1.2Mpa; Air-exhausting High-pressure Range: 3.2-3.7Mpa; It means that the refrigerating system or refrigerant of an air conditioner is abnormal if the air-exhausting and air-returning pressure ranges of the detected compressor exceed the nor mal ranges to a large extent.
compound gauge
Low pressure valve
Service port
High pressure valve
Valve protective caps Pressure hose

service port

vacuum pump

Manifold gauge
Pressure gauge High pressure valve Low pressure valve
Charge hose

30

Vacuum pump

INSTALLATION MANUAL—Installation of the outdoor unit

BLEEDING

The air and humidity left inside the refrigerant circulation can cause compressor malfunction. After having connected the indoor and outdoor units, bleed the air and humidity from the refrigerant circulation using a vacuum pump.
(1) Unscrew and remove the caps from the 2 – way and 3-way valves.
(2) Unscrew and remove the cap from the service port. (3) Connect the vacuum pump hose to the service port. (4) Operate the vacuum pump for 10 – 15 minutes until
an absolute vacuum of 10 mm Hg has been reached. (5) With the vacuum pump still in operation , close the
low – pressure knob on the vacuum pump coupling. Stop the vacuum pump. (6) Open the 2 – way valve by 1/4 turn and then close it after10 seconds. Check all the joints for leaks using liquid soap or an electronic leak device. (7) Turn the body of the 2-way and 3-way valves. Disconnect the vacuum pump hose. (8) Replace and tighten all the caps on the valves.

3-way valve diagram
connect to indoor unit
open position spindle

Connect to outdoor unit
Valve core

needle service port cap

Indoor unit Refrigerant flow direction 3-way valve

2-way valve

Service port nut
(2) Turn (8) Tighten

(6) Open 1/4 turn

(7) Turn to fully open the valve

(7) Turn to fully open the valve
valve cap

Valve cap

(1) Turn (8) Tighten

(1) Turn (8) Tighten

INSTALLATION MANUAL— operation test

1. Wind insulating covering around the joints of the indoor unit and fix it with insulating tape.
2. Fix the exceeding part of the signal cable to the piping or to the outdoor unit.
3. Fix the piping to the wall ( after having coated it with insulating tape) using clamps or insert them into plastic slots.
4. Seal the hole in the wall through which the piping is passed so that no air or water can fill.
Indoor unit test
Do the ON/OFF and FAN operate normally? Does the MODE operate normally? Do the set point and TIMER function properly? Does each lamp light normally? Do the flap for air flow direction operate normally? Is the condensed water drained regularly?
Outdoor unit test
Is there any abnormal noise or vibration during operation? Could the noise , the air flow or the condensed water drainage disturb the neighbours? Is there any coolant leakage?
Note: the electronic controller allows the compressor to start only three minutes after voltage has reached the system.

Clamps insulating covering

piping (indoor)

insulating tape

piping

gasket

(outdoor)

wall

31

INSTALLATION MANUAL—Information for the installer
Pipe length and Additional refrigerant

Note: When the matching indoor unit model is TAC-18CHSD/TPH11-l or TAC- 24CHSD/TPH11-l, the connecting pipe needs to be connected with the pipe adapter placed in the carton of the multi outdoor unit.

Dedicated Distribution Device and Wire for Air Conditioner

Min. Circuit Ampacity of Air Conditioner (A)
8 8 and 10 10 and 15 15 and 24 24 and 28 28 and 32

Minimum Wire Cross-sectional Area(mm2) 0.75 1.0 1.5 2.5 4.0 6.0

Specification of Socket or Switch (A)
15 15 20 25 35 40

Fuse Specification (A)
15 15 25 40 45 55

Note: This table is only for reference, the installation shall meet the requirements of local laws and regulations.

32

INSTALLATION MANUAL—Information for the installer
WIRING DIAGRAM
For different models, the wiring diagram may be different. Please refer to the wiring diagrams pasted on the indoor unit and outdoor unit respectively. On indoor unit, the wiring diagram is pasted under the front panel;
Front panel Wiring diagram
Outdoor wiring diagram:
<FMA-36I4HD/DVO>
<FMA-42I5HD/DVO> Note: For some models the wires has been connected to the main PCB of indoor unit by manufacturer
without terminal block. 33

INSTALLATION MANUAL—Information for the installer
CABLE WIRES SPECIFICATION

INVERTER TYPE MODEL capacity (Btu/h)

N

Power supply cable

L

N L Connection supply cable 1

9k
1.5mm2 1.5mm2 1.5mm2 0.75mm2 0.75mm2 0.75mm2 0.75mm2

12k

18k

24k

sectional area

1.5mm2

2.5mm2

2.5mm2

1.5mm2 1.5mm2 0.75mm2

2.5mm2 2.5mm2 0.75mm2

2.5mm2 2.5mm2 0.75mm2

0.75mm2

0.75mm2

0.75mm2

0.75mm2

0.75mm2

0.75mm2

0.75mm2

0.75mm2

0.75mm2

28k
2.5mm2 2.5mm2 2.5mm2 1.5mm2 1.5mm2 1.5mm2 1.5mm2

220V Air conditioner (7k~30k) indoor unit fuse : 50T, 3.15A 110V Air conditioner (7k~12k) indoor unit fuse : 50T, 3.15A 125V Air conditioner (7k~12k) indoor unit fuse : 61T, 15A 250V Air conditioner (18k~24k) indoor unit fuse : 65TS, 25A

34

MAINTENANCE
When cleaning, you mustshut down the machineand cut offthe power supply formore than 5 minutes. Under no circumstances shouldthe air conditioner beflushed with water. Volatileliquid (e.g. thinner orgasoline) will damage theair conditioner , soonly use soft drycloth or wet cloth dipped withneutral detergent to clean the air conditioner. Pay attention to cleaningthe filter screen regularlyto avoid dust coveringwhich will affectthe filter screen effect. When the operating environment is dusty, the cleaning frequencyshould be increased appropriately. After removing the filterscreen, do not touchthe fins of theindoor unit to avoidscratching.

Clean the unit

wring it dry

Gentle wipe

the unit surface

Tip: Wipefrequently to keep airconditioner clean and goodappearance .

Disassembly and assembly of filter screen

Grasp the raised plastichandle on the filterscreen by hand, andthen pull the filterscreen out in thedirection deviating from the unit,so that the upperedge of the filterscreen is separated fromthe unit. The filter can beremoved by lifting thefilter upwards. When installing the filterscreen, first insert thelower end of thefilter screen into thecorresponding position of the unit, andthen squeeze the upperend of the filterscreen into the correspondingbuckling position of the unit body.
Plastic handle

Clean the filter screen

Opposite to the direction of taking out the filter screen

Take out the filter screen from the unit

Clean the filter screen with soapy water and air dry it

Replace the filter

Tip: When youfind accumulated dust inthe filter screen, pleaseclean the filter screenin time to ensurethe clean, healthy and efficientoperation inside the airconditioner.

Cleaning of inner air duct

First, loosen the knobon the middle oflouver and bendthe louver outwards to take itout. Then, grasp both sidesof bottom plate pushdownwards to take downthe bottom plate. Finally, loosen the buckle of deflector assemblywith your thumb andtake it out. Wipe the airduct and fan assemblywith a clean andwrung wet rag. Clean the removed partswith soapy water andair dry it. After cleaning, restore theremoved parts in turn.

Louver

Deflector assembly Bottom plate

Service and maintenance

When the air conditioneris not in usefor a long time,do the following work: Take outthe batteries of theremote controller and disconnectthe power supply ofthe air conditioner. When starting to useafter long-term shutdown: 1.Clean the unitand filter screen; 2.Check whether thereare obstacles at theair inlet and outletof indoor and outdoorunits; 3.Check whether thedrain pipe is unobstructed; Install the batteries ofthe remote controller andcheck whether the poweris on.

35

TROUBLESHOOTING

MALFUNCTION POSSIBLE CAUSES

The appliance does not operate
Strange odor Noise of running water A fine mist comes from the air outlet A strange noise can be heard
Insufficient airflow, either hot or cold
The appliance does not respond to commands
The display is off

Power failure/plug pulled out. Damaged indoor/outdoor unit fan motor. Faulty compressor thermomagnetic circuit breaker. Faulty protective device or fuses. Loose connections or plug pulled out. It sometimes stops operating to protect the appliance. Voltage higher or lower than the voltage range. Active TIMER-ON function. Damaged electronic control board. Dirty air filter. Back flow of liquid in the refrigerant circulation. This occurs when the air in the room becomes very cold, for example in the
COOLING or DEHUMIDIFYING/DRY modes.
This noise is made by the expansion or contraction of the front panel due to variations in temperature and does not indicate a problem.
Unsuitable temperature setting. Obstructed air conditioner intakes and outlets. Dirty air filter. Fan speed set at minimum. Other sources of heat in the room. No refrigerant. Remote control is not close enough to indoor unit. The batteries of remote control need to be replaced. Obstacles between remote control and signal receiver in indoor unit. Active LIGHT function. Power failure.

Switch off the air conditioner immediately and cut off the power supply in the event of:

Strange noises during operation. Faulty electronic control board. Faulty fuses or switches. Spraying water or objects inside the appliance. Overheated cables or plugs. Very strong smells coming from the appliance.

ERROR SIGNALS ON THE DISPLAY

In case of error, the display on the indoor unit shown the following error codes:

Display Description of the trouble

Display Description of the trouble

Indoor temperature sensor fault

Outdoor discharge temperature sensor fault

Indoor pipe temperature sensor fault

Outdoor IPM module fault

Outdoor pipe temperature sensor fault

Outdoor current detect fault

Refrigerant system leakage or fault

Outdoor PCB EEPROM fault

Malfunction of indoor fan motor

Outdoor fan motor fault

Outdoor air temperature sensor fault

Outdoor suction temperature sensor fault

36

Like us on Facebook
TCL Electronics Australia Pty Ltd
ABN 83 111 032 896 Telephone: 1300 738 149
[email protected] www.tcl.com/au

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

TCL User Manuals

Related Manuals