Honeywell TH6320U2008 Programmable Thermostat User Manual
- June 16, 2024
- Honeywell
Table of Contents
Honeywell TH6320U2008 Programmable Thermostat User Manual
Package Includes
- T6 Pro Thermostat
- UWP™ Mounting System
- Decorative Cover Plate
- Screws and Anchors
- 2 AA Batteries
- Thermostat Literature
Optional Cover Plate Installation
NOTE
If the Optional Cover Plate is not required, see “UWP Mounting System
installation” on the next page. Use the Optional Cover Plate when you need to
cover the paint gap from the old thermostat. Different cover plates are
depending on when the thermostat was manufactured.
For the square cover plate
- Separate the Cover Plate from the Mounting Plate.
- Mount the Mounting Plate onto the wall using any of the 8 screw holes. Insert and tighten the mounting screws supplied with Cover Plate Kit. Do not over-tighten. See Figure 2. Make sure the Mounting Plate is level.
- Attach the UWP by hanging it on the top hook of the Mounting Plate and then snapping the bottom of the UWP in place. See Figure 3.
- Snap the Cover Plate onto the Mounting Plate. See Figure 4.
For the rectangular cover plate
Mount the Cover Plate on the wall using any of the 6 screw holes. Insert
and tighten the mounting screws supplied with the Cover Plate. Do not over-
tighten. See Figure 1. Make sure the Cover Plate is level. Attach the UWP by
hanging it on the top hook of the Cover
- Plate and then snapping the bottom of the UWP in place. See Figure 2.
- If there are no existing wall anchors:
- Position the Cover Plate on the wall. Level and mark hole positions. See Figure 1.
- Drill holes at marked positions, and then lightly tap supplied wall anchors into the wall using a hammer.
- if your box contains red anchors, drill 7/32” (5.6 mm) holes.
- If your box contains yellow anchors, drill 3/16” (4.8 mm) holes.
- Use 2x supplied screws (#8 1-1/2” (38 mm) for red anchors and #6 1-1/2” (38 mm) for yellow anchors).
UWP Mounting System Installation
- Before starting, turn the power off at the breaker box or switch. Open the package to find the UWP. See Figure 1.
- Position the UWP on the wall. Level and mark hole positions. See Figure 2.
- Drill holes at marked positions, and then lightly tap supplied wall anchors into the wall using a hammer.
- If your box contains red anchors, drill 7/32” holes.
- If your box contains yellow anchors, drill 3/16” holes.
- Pull the door open and insert the wires through the wiring hole of the UWP. See Figure 3.
- Place the UWP over the wall anchors. Insert and tighten mounting screws supplied with the UWP. Do not over-tighten. Tighten until the UWP no longer moves. Close the door. See Figure 4.
Power options
Setting Slider Tabs
Set R Slider Tab.
- Use a built-in jumper (R Slider Tab) to differentiate between one or two transformer systems.
- If there is only one R wire, and it is connected to the R, Rc, or RH terminal, set the slider to the up position (1 wire).
- If there is one wire connected to the R terminal and one wire connected to the Rc terminal, set the slider to the down position (2 wires).
NOTE: Slider Tabs for U terminals should be left in place for T6 Pro models.
Wiring terminal designations
S
| Input for wired indoor or outdoor sensors (TH6320U and
TH6220U only)
| | L/A
– A
| Heat Pump fault input (Common (C) wire required for LA/A)
---|---|---|---|---
S| O/B| Changeover valve
Y
| ****
Compressor contactor (stage 1)
| AUX – W2| Auxiliary heat Heat (stage 2)
Y2| Compressor contactor (stage 2)| E| Emergency Heat
G| Fan| W| Heat (stage 1)
C
| 24VAC common. For 2 transformer systems, use common wire from cooling transformer.| ****
K
| ****
Unused
U| ****
Unused
| R| 24VAC power from heating transformer
U| Rc| 24VAC power from cooling transformer
Note
Not all terminals may be used, depending on the system type that is being
wired. The most commonly used terminals are shaded. The terminal can be jumped
using the Slider Tab. See “Setting Slider Tabs” above.
Wiring conventional systems: forced air and Hydronics
Shaded areas below apply only to TH6320U/TH6220U or as otherwise noted.
1H/1C System (1 transformer)
- R Power [1]
- Rc [R+Rc joined by Slider Tab] [2]
- Y Compressor contactor
- C 24VAC common [3]
- W Heat
- G Fan
Heat-only System
- R Power [1]
- Rc [R+Rc joined by Slider Tab] [2]
- C 24VAC common [3]
W Heat
- Heat-only System (Series 20) [5]
- R Series 20 valve terminal “R” [1]
- Rc [R+Rc joined by Slider Tab] [2]
- Y Series 20 valve terminal “W”
- C 24VAC common [3]
- W Series 20 valve terminal “B”
Heat-only System
- (power open zone valve) [5]
- R Power [1]
- Rc [R+Rc joined by Slider Tab] [2]
W Valve
- C 24VAC common [3]
- 1H/1C System (2 transformers)
- R Power (heating transformer) [1]
- Rc Power (cooling transformer) [1]
- Y Compressor contactor
- C 24VAC common [3, 4]
W Heat
- G Fan
- Heat-only System with Fan
- R Power [1]
- Rc [R+Rc joined by Slider Tab] [2]
- C 24VAC common [3]
- W Heat
- G Fan
Cool-only System
- R Power [1]
- Rc [R+Rc joined by Slider Tab] [2]
- Y Compressor contactor
- C 24VAC common [3]
- G Fan
- 2H/2C System (1 transformer) [6]
- R Power [1]
- Rc [R+Rc joined by Slider Tab] [2]
- Y Compressor contactor (stage 1)
- C 24VAC common [3]
- W Heat (stage 1)
- G Fan
- W2 Heat (stage 2)
- Y2 Compressor contactor (stage 2)
NOTES
Wire specifications: Use 18- to 22-gauge thermostat wire. Shielded cable is
not required.
- Power supply. Provide disconnect means and overload protection as required.
- Move the R-Slider Tab on UWP to the R setting. For more information, see “Setting Slider Tabs” on page 3
- Optional 24VAC common connection.
- The common connection must come from the cooling transformer.
- In ISU set the Heat system type to Radiant Heat. Set the number of cool stages to 0.
- In Installer Setup, set the system type to 2Heat/2Cool Conventional.
Wiring heat pump systems
Shaded areas below apply only to TH6320U/TH6220U or as otherwise noted.
- 1H/1C Heat Pump System
- R Power [1]
- Rc [R+Rc joined by Slider Tab] [2]
- Y Compressor contactor
- C 24VAC common [3]
- O/B Changeover valve [7]
- W Do not use this terminal for heat pump applications!
- 2H/1C Heat Pump System [8]
- R Power [1]
- Rc [R+Rc joined by Slider Tab] [2]
- Y Compressor contactor
- C 24VAC common [3]
- O/B Changeover valve [7]
- G Fan
Aux Auxiliary heat
- E Emergency heat
- L Heat pump fault input
- W Do not use this terminal for heat pump applications!
- 2H/2C Heat Pump System
- (TH6320U only) [9]
- R Power [1]
- Rc [R+Rc joined by Slider Tab] [2]
- Y Compressor contactor (stage 1)
- C 24VAC common [3]
- O/B Changeover valve [7]
G Fan
- Y2 Compressor contactor (stage 2)
- L Heat pump fault input
- W Do not use this terminal for heat pump applications!
- 3H/2C Heat Pump System
- (TH6320U only) [10]
- R Power [1]
- Rc [R+Rc joined by Slider Tab] [2]
- Y Compressor contactor (stage 1)
- C 24VAC common [3]
- O/B Changeover valve [7]
- G Fan
- Aux Auxiliary heat
E Emergency heat
- Y2 Compressor contactor (stage 2)
- L Heat pump fault input
- W Do not use this terminal for heat pump applications!
- Dual Fuel System (TH6320U / TH6220U only)
- R Power [1]
- Rc [R+Rc joined by Slider Tab] [2]
Y Compressor contactor (stage 1)
- C 24VAC common [3]
- O/B Changeover valve [7]
- Aux Auxiliary heat
- E Emergency heat
- Y2 Compressor contactor (stage 2 – if
- needed) [11]
- L Heat pump fault input
- S Outdoor sensor
- W Do not use this terminal for heat pump applications!
NOTES
Wire specifications: Use 18- to 22-gauge thermostat wire. Shielded cable is
not required.
- Power supply. Provide disconnect means and overload protection as required.
- Move the R-Slider Tab on UWP to the R setting. For more information, see “Setting Slider Tabs” on page 3
- Optional 24VAC common connection.
- In Installer Setup, set the system type to 2Heat/2Cool Conventional.
- In Installer Setup, set the changeover valve to O (for cool changeover) or B (for heat changeover).
- In ISU set the Heat system type to the Heat pump. 1 compressor and 1 stage of backup heat.
- In ISU set the Heat system type to the Heat pump. 2 compressors and 0 stages of backup heat.
- In ISU set the Heat system type to Heat pump. 2 compressors and 1 stage of backup heat.
- Dual fuel with Y2 only for TH6320U
Thermostat mounting
- Push excess wire back into the wall opening.
- Close the UWP door. It should remain closed without bulging.
- Align the UWP with the thermostat, and push gently until the thermostat snaps in place.
- Turn the power on at the breaker box or switch.
Set the time and date
Time
- Press Menu on your thermostat.
- Press or to go to TIME. Press Select.
- Press or to choose between 12 or 24 hours.
- Press Select.
- Use or adjust the hour. Press Select.
- Use or adjust the minutes. Press Select to exit the Time menu.
Date
- If previously setting time, continue to Step 2. If at the Home screen, press Menu on your thermostat.
- Press or to go to DATE. Press Select.
- Use or adjust the year. Press Select.
- Use the or to adjust the month. Press Select.
- Use the or to adjust the day. Press Select to save and exit the Date menu.
System operation settings
- Press the Mode button to cycle to the next available System mode.
- Cycle through the modes until the required System mode is displayed and leave it to activate.
NOTE: Available System modes vary by model and system settings.
System modes
- Auto
- Heat
- Cool
- Em Heat
- Off
**Fan operation settings
**
-
Press the Fan button to cycle to the next available Fan mode.
-
Cycle through the modes until the required Fan mode is displayed and leave it to activate.
NOTE: Available Fan modes vary with system settings.
Fan modes:- Auto: The fan runs only when the heating or cooling system is on.
- On: The fan is always on.
- Circ: The fan runs randomly about 33% of the time.
Alerts or Reminders
- Press Menu, and then press until the display shows ALRT.
- Press Select to display which alert(s) are present.
- The word SNZE (SNOOZE) appears.
- Press Select again to snooze the reminder for 7 days.
- To clear the alert, press Select, and then press go to CLER (Clear).
- Press Select to clear the reminder. Some alerts cannot be snoozed or cleared.
- Please call your local heating and cooling professional if this occurs. The heating and cooling system may require service.
Installer setup (ISU)
- Press and hold the CENTER and buttons for approximately 3 seconds to enter the advanced menu.
- Press Select to enter ISU.
- Press Select to cycle through menu setup options.
- Press to change values or select from available options.
- Press Select and confirm your settings or press Back to ignore changes and return to the ISU menu screen to continue editing another setup option.
- To finish the setup process and save your settings, press Home and return to the Home screen.
NOTE: A complete list of all setup (ISU) parameters and options starts below and continues through page 10.
Advanced setup options (ISU)
NOTE: Depending on system settings, not all options may be available.
# ISU| ISU Name| ISU Options (factory default
in bold)
---|---|---
120| Scheduling Options| 0 = Non-Programmable
2 = 5-2 Programmable
3 = 5-1-1 Programmable
4 = 7-Day Programmable
125| Temperature Indication Scale| 0 = Fahrenheit
1 = Celsius
130| Outdoor Sensor
(TH6320U / TH6220U only)
| 0 = None
1 = Wired Outdoor Sensor
200| Heating System Type| 1 = Conventional Forced Air Heat
2 = Heat Pump 3 = Radiant Heat
5 = None (Cool Only)
205| Heating Equipment Type| Conventional Forced Air Heat:
1 = Standard Efficiency Gas Forced Air
2 = High Efficiency Gas Forced Air
3 = Oil Forced Air
4 = Electric Forced Air 5 = Hot Water Fan Coil
Heat Pump:
7 = Air to Air Heat Pump
8 = Geothermal Heat Pump
Radiant Heat:
9 = Hot Water Radiant Heat
12 = Steam
218| Reversing Valve O/B| 0 = O (O/B in Cool)
1 = B (O/B in Heat)
220| Cool Stages / Compressor Stages 200=Conv / 200=HP| 0, 1 , 2
Note: Only 1 compressor stage available on TH6210U model. Only 1 compressor stage available on TH6220U model if configured for heat pump.
# ISU| ISU Name| ISU Options (factory default
in bold)
---|---|---
221| Heat Stages / Backup Heat Stages| Heat Stages: 1 , 2
Backup Heat Stages: 0, 1
230| Fan Control in Heat| 1 = Equipment Controls Fan
2 = Thermostat Controls Fan
253| Aux/E terminal control (Fixed to “0” setting on all models except TH6320U)| 0 = Drive both Aux & E together
1 = Aux and E independent
255| Backup Heat Source (Heat Pump Only)
(TH6320U / TH6220U only)
| 1 = Electric Forced Air
2 = Gas/Oil Forced Air (or Fossil Forced Air)
256| Emergency Heat Source (TH6320U only)| 1 = Electric Forced Air
2 = Gas/Oil Forced Air (or Fossil Forced Air)
260| External Fossil Fuel Kit
(TH6320U / TH6220U only)
| 0 = Thermostat Controls Backup Heat
1 = External Fossil Fuel Kit Controls Backup Heat
300| System Changeover| 0 = Manual
1 = Automatic
303| Auto Changeover Differential| 0 °F to 5 °F
0.0 °C to 2.5 °C
Note: Differential is NOT deadband. Resideo uses an advanced algorithm that fixes deadband at 0 °F. The differential setting is the minimum number of degrees from set-point needed to switch from the last mode running (heat or cool) to the opposite mode when the thermostat is in auto-changeover. This is more advanced than previous thermostats.
340| Backup Heat Droop| 0 = Comfort
2 = 2 °F
3 = 3 °F
4 = 4 °F
5 = 5 °F
6 = 6 °F
7 = 7 °F
8 = 8 °F
| 9 = 9 °F
10 = 10 °F
11 = 11 °F
12 = 12 °F
13 = 13 °F
14 = 14 °F
15 = 15 °F
Note: 0 (comfort) setting only available if backup heat
(ISU 255) is set to electric.
350| Upstage Timer for Backup Heat| 0 = Off
1 = 30 minutes
2 = 45 minutes
3 = 60 minutes
4 = 75 minutes
5 = 90 minutes
6 = 2 hours
7 = 3 hours
| 8 = 4 hours
9 = 5 hours
10 = 6 hours
11 = 8 hours
12 = 10 hours
13 = 12 hours
14 = 14 hours
16 = 16 hours
355| Compressor Lockout / Balance Point| — = Off
5 °F to 60 °F (in 5 °F increments)
-15.0 °C to 15.5 °C (in 2.5 °C or 3.0 °C increments)
Note: Use a wired sensor to set compressor lockout / balance point on TH6320U
/ TH6220U.
356| Outdoor Lockout Backup Heat| — = Off
5 °F to 65 °F (in 5 °F increments)
-15.0 °C to 18.5 °C (in 2.5 °C or 3.0 °C increments)
365| Compressor Cycle Rate (Stage 1)| 1 – 6
366| Compressor Cycle Rate (Stage 2)| 1 – 6
370| Heating Cycle Rate (Stage 1)| 1 – 12
371| Heating Cycle Rate (Stage 2)| 1 – 12
375| Heating Cycle Rate Auxiliary Heat| 1 – 12
378| Heating Cycle Rate Emergency Heat (TH6320U only)| 1 – 12
387| Compressor Protection| 0 = Off
1 – 5 minutes
# ISU| ISU Name| ISU Options (factory default
in bold)
---|---|---
425| Adaptive Intelligent Recovery| 0 = No
1 = Yes
Note: Adaptive Intelligent Recovery (AIR) is a comfort setting. Heating or cooling equipment will turn on earlier, ensuring the indoor temperature will match the setpoint at the scheduled time.
430| Minimum Cool Setpoint| 50 °F to 99 °F (50 °F)
10.0 °C to 37.0 °C (10.0 °C)
431| Maximum Heat Setpoint| 40 °F to 90 °F (90 °F)
4.5 °C to 32.0 °C (32.0 °C)
435| Keypad Lockout| Series 0-6 (setting on original T6 models):
0 = None
1 = Partial
2 = Full
| Series 7 (setting current T6 models):
0 = Disabled
1 = Enabled
Note: Due to customer feedback this feature was changed. On series 0-6 thermostats, you can lockout the thermostat from the ISU the same as you can from menu lockout.
For series 7 or later, this setting allows the contractor to enable or disable the lockout feature. When disabled, there is no lockout option under menu.
500| Is Indoor Temperature Sensor WIRED to your system? (TH6320U / TH6220U only)| 0 = No
1 = Yes
515| Indoor Sensor type
(TH6320U / TH6220U only)
| 0 = 10k
1 = 20k
520| Which Sensors will be used for TEMPERATURE Control? (Multiple Sensors are Averaged) TH6320U / TH6220U only)| 1 = Thermostat Only 2 = Wired Only
3 = Average
702| Number of Air Filters| 0 – 2
711| Air Filter 1 Replacement Reminder| 0 = Off
1 = 10 Run Time Days
2 = 20 Run Time Days
3 = 30 Run Time Days
4 = 45 Run Time Days
5 = 60 Run Time Days
6 = 90 Run Time Days
7 = 120 Run Time Days
8 = 150 Run Time Days
9 = 30 Calendar Days
| 10 = 45 Calendar Days
11 = 60 Calendar Days
12 = 75 Calendar Days
13 = 3 Calendar Months
14 = 4 Calendar Months
15 = 5 Calendar Months
16 = 6 Calendar Months
17 = 9 Calendar Months
18 = 12 Calendar Months
19 = 15 Calendar Months
712| Air Filter 2 Replacement Reminder| 0 = Off
1 = 10 Run Time Days
2 = 20 Run Time Days
3 = 30 Run Time Days
4 = 45 Run Time Days
5 = 60 Run Time Days
6= 90 Run Time Days
7 = 120 Run Time Days
8 = 150 Run Time Days
9 = 30 Calendar Days
| 10 = 45 Calendar Days
11 = 60 Calendar Days
12 = 75 Calendar Days
13 = 3 Calendar Months
14 = 4 Calendar Months
15 = 5 Calendar Months
16 = 6 Calendar Months
17 = 9 Calendar Months
18 = 12 Calendar Months
19 = 15 Calendar Months
1400| Backlighting| 0 = On Demand
1 = Continuous
Note: Common wire needed for continuous.
1401| Backlight brightness| 1 – 5
Note: Only displayed if continuous backlight selected.
1410| Clock Format| 12 / 24
1415| Daylight Saving Time| 0 = Off
1 = On
1420| Temperature Display Offset| -3 to 3F (0)
-1.5 to 1.5C (0)
Installer system test
To perform a System Test:
- Press and hold the CENTER and buttons for approximately 3 seconds to enter the advanced menu.
- Use to go to TEST. Press Select to enter System Test.
- Use to change between Heat, Cool, Fan, Em Heat, or Ver (thermostat version information). Press Select.
- Press to turn stages on one at a time, and press to turn them off.
- Use the Home button to exit the System Test.
System test
System test | System status |
---|
Shaded areas below apply only to TH6320U/TH6220U or as otherwise noted.
| 0| All Off
| 1| Heat Stage 1 on
Heat|
| 2| Heat Stage 2 also on
| 3| Heat Stage 3 also on
| 0| All Off
Cool| 1| Cool Stage 1 on
| 2| Cool Stage 2 also on
| 0| All Off
Em Heat|
| 1| Em Heat on
| 0| Fan Off
Fan| |
| 1| Fan On
System status
Shaded areas below apply only to TH6320U/TH6220U or as otherwise noted.
Specifications
- Temperature Ranges
- Heat: 40 °F to 90 °F (4.5 °C to 32.0 °C)
- Cool: 50 °F to 99 °F (10.0 °C to 37.0 °C)
- Working Ambient Temperature
- 32 °F to 120 °F (0 C° to 48.9 °C)
- Operating Ambient Temperature
- 37 °F to 102 °F (2.8 °C to 38.9 °C)
- Shipping Temperature
- -20 °F to 120 °F (-28.9 °C to 48.9 °C)
- Operating Relative Humidity
- 5% to 90% (non-condensing)
- Physical Dimensions in inches (mm) (H x W x D)
- 4-1/16” H x 4-1/16” W x 1-5/32” D
- 103.5 mm H x 103.5 mm W x 29 mm D
Electrical Ratings
Terminal | Voltage (50/60Hz) | Running Current |
---|---|---|
W Heating | 20-30 Vac | 0.02-1.0 A |
W2 (Aux) Heating | 20-30 Vac | 0.02-1.0 A |
E Emergency Heat | 20-30 Vac | 0.02-0.5 A |
Y Compressor Stage 1 | 20-30 Vac | 0.02-1.0 A |
Y2 Compressor Stage 2 | 20-30 Vac | 0.02-1.0 A |
G Fan | 20-30 Vac | 0.02-0.5 A |
O/B Changeover | 20-30 Vac | 0.02-0.5 A |
L/A Input | 20-30 Vac | 0.02-0.5 A |
Troubleshooting
If you have difficulty with your thermostat, please try the following suggestions. Most problems can be corrected quickly and easily.
Display is blank| • Check circuit breaker and reset if necessary.
• Make sure power switch for heating & cooling system is on.
• Make sure furnace door is closed securely.
• Make sure fresh AA alkaline batteries are correctly installed (see page 3).
---|---
Heating or cooling
system does not respond
| • Press Mode button to set system Heat (see page 7). Make sure the desired temperature is set higher than the inside temperature.
• Press Mode button to set system Cool (see page 7). Make sure the desired temperature is set lower than the inside temperature.
• Check circuit breaker and reset if necessary.
• Make sure power switch for heating & cooling system is on.
• Make sure furnace door is closed securely.
• Wait 5 minutes for the system to respond.
Temperature settings do not change| Make sure heating and cooling temperatures are set to acceptable ranges:
• Heat: 40 °F to 90 °F (4.5 °C to 32.0 °C)
• Cool: 50 °F to 99 °F (10.0 °C to 37.0 °C)
“Cool On” or “Heat On” is flashing| • Compressor protection feature
is engaged. Wait 5 minutes for the system to restart safely, without damage to
the compressor.
Aux heat runs in cooling| • For heat pump systems, verify there is
not a wire attached to W on UWP systems. See “Wiring heat pump systems” on
page 5.
Cool runs with a call for heat| • For heat pump systems, verify
there is not a wire attached to W on UWP systems. See “Wiring heat pump
systems” on page 5.
CAUTION: ELECTRICAL HAZARD
Can cause electrical shock or equipment damage. Disconnect power before
beginning installation.
CAUTION: EQUIPMENT DAMAGE HAZARD
Compressor protection is bypassed during testing. To prevent equipment damage,
avoid cycling the compressor quickly.
CAUTION: MERCURY NOTICE
If this product is replacing a control that contains mercury in a sealed tube,
do not place the old control in the trash. Contact your local waste management
authority for instructions regarding recycling and proper disposal.
CAUTION: ELECTRONIC WASTE NOTICE
The product and batteries should not be disposed of with other household
waste. Check for the nearest authorized collection centres or authorized
recyclers. The correct disposal of end-of-life equipment will help prevent
negative consequences for the environment and human health. FCC statement
available at: https://customer.resideo.com/en-US/support/residential/codes-
and-standards/FCC15105/Pages/default.aspx
Customer Assistance
For assistance with this product, please visit
customer.resideo.com.
Or call Resideo Customer Care toll-free at
1-800-468-1502
Resideo Technologies Inc.
1985 Douglas Drive North, Golden Valley, MN 55422
1-800-468-1502
www.resideo.com 33-00181EFS—19 M.S. Rev. 05-22 |
Printed in United States
2022 Resideo Technologies, Inc. All rights reserved. The Honeywell Home
trademark is used under license from Honeywell International, Inc. This
product is manufactured by Resideo Technologies, Inc. and its affiliates.
Download PDF:Honeywell TH6320U2008 Programmable Thermostat User Manual
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>