MEAN WELL TDR-960-24 3 Phase Industrial DIN RAIL with PFC Function Owner’s Manual
- June 15, 2024
- MEAN WELL
Table of Contents
MEAN WELL TDR-960-24 3 Phase Industrial DIN RAIL with PFC Function
Product Information
Specifications
- Model: TDR-960-24, TDR-960-48
- DC Voltage Rated Current:- TDR-960-24: 24V, 40A (Current Range: 0 ~ 40A)
- TDR-960-48: 48V, 20A (Current Range: 0 ~ 20A)
 
- Rated Power: 960W
- Ripple & Noise (max.):- TDR-960-24: 180mVp-p
- TDR-960-48: 250mVp-p
 
- Output Voltage Adjustment Range: 24 ~ 28V
- Line Regulation
- Load Regulation
- Setup, Rise Time:- 1000ms, 100ms/400VAC at full load
- 800ms, 100ms/500VAC at full load
 
- Hold Up Time (Typ.):- 12ms / 400VAC at full load
- 14ms / 500VAC at full load
 
- Voltage Range:- Note.4 Three-Phase: 340 ~ 550VAC (Dual phase operation possible)
- 480 ~ 780VDC
 
- Frequency Range
- Power Factor (Typ.):- 47 ~ 63Hz PF0.88/400VAC
- PF0.86/500VAC at full load
 
- Efficiency (Typ.): 94%
- AC Current (Typ.):- 2A/400VAC
- 1.4A/500VAC
 
- Inrush Current (Typ.): COLD START 60A
- Leakage Current Overload: 100M Ohms / 500VDC / 25/ 70% RH
- EMC Emission: Compliance to BS EN/EN55032 (CISPR32), BS EN/EN61204-3 Class B, BS EN/EN61000-3-2,-3, EAC TP TC 020
- EMC Immunity MTBF: Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11, BS EN/EN55035, BS EN/EN61000-6-2 (BS EN/EN50082-2), BS EN/EN61204-3, heavy industry level, EAC TP TC 020 647.1K hrs min. Telcordia SR-332 (Bellcore) ; 59.5K hrs min. MIL-HDBK-217F (25)
- Dimension: 110125.2150mm (WHD)
- Packing: 2.47Kg ; 6pcs/15.8Kg/1.47CUFT
FAQ
- Q: What is the input voltage range for the TDR-960 series?- A: The input voltage range is Three-Phase 340 ~ 550VAC (Dual-phase operation possible) or 480 ~ 780VDC.
 
- Q: What is the rated power of the TDR-960 series?- A: The rated power is 960W.
 
- Q: What is the efficiency of the TDR-960 series?- A: The efficiency is approximately 94%.
 
- Q: What is the weight of the TDR-960 series?- A: The weight is 2.47 kg.
 
- Q: What is the dimension of the TDR-960 series?- A: The dimension is 110125.2150mm (WHD).
 
Features :
- Three-Phase 340 ~ 550VAC wide range input (Dual phase operation possible)
- Width only 110mm
- Built-in active PFC function compliance to BS EN/ EN61000-3-2
- High efficiency 94.5% and low power dissipation
- Protections: Short circuit / Overload / Over voltage / Over temperature
- Cooling by free air convection
- Built-in constant current limiting circuit
- Can be installed on DIN rail TS-35/7.5 or 15
- UL508(industrial control equipment)approved
- BS EN/EN61000-6-2(BS EN/EN50082-2) industrial immunity level
- Current sharing up to 3840W(3+1)
- Built-in DC OK relay contact
- 100% full load burn-in test
- 3 years warranty
SPECIFICATION
| MODEL | TDR-960-24 | TDR-960-48 | 
|---|
OUTPUT
|  DC VOLTAGE|  24V| 48V
RATED CURRENT|  40A| 20A
CURRENT RANGE|  0 ~ 40A| 0 ~ 20A
RATED POWER|  960W| 960W
RIPPLE & NOISE (max.) **Note.2|  180mVp-p| 250mVp-p
VOLTAGE ADJ. RANGE|  24 ~ 28V| 48 ~ 55V
VOLTAGE TOLERANCE Note.3|  ±1.0%| ±1.0%
LINE REGULATION|  ±0.5%| ±0.5%
LOAD REGULATION|  ±1.0%| ±1.0%
SETUP, RISE TIME|  1000ms, 100ms/400VAC                800ms,
100ms/500VAC at full load
HOLD UP TIME (Typ.)**|  12ms / 400VAC              14ms / 500VAC at full
load  
INPUT
|  VOLTAGE RANGE **Note.4|  Three-Phase 340 ~ 550VAC (Dual phase
operation possible) 480 ~ 780VDC
FREQUENCY RANGE|  47 ~ 63Hz
POWER FACTOR (Typ.)|  PF≧0.88/400VAC                PF≧0.86/500VAC at
full load
EFFICIENCY (Typ.)|  94%| 94.5%
AC CURRENT (Typ.)|  2A/400VAC               1.4A/500VAC
INRUSH CURRENT (Typ.)|  COLD START 60A
LEAKAGE CURRENT**|  <3.5mA / 530VAC  
PROTECTION
|  OVERLOAD|  105 ~ 130% rated output power
Protection type : Constant current limiting, unit will shut down after 3 sec.
,re-power on to recover
OVER VOLTAGE|  29 ~ 33V| 56 ~ 65V
Protection type : Shut down o/p voltage, re-power on to recover
OVER TEMPERATURE|  Shut down o/p voltage, recovers automatically after
temperature goes down
FUNCTION|  DC OK REALY CONTACT RATINGS (max.)|
60Vdc/0.3A, 30Vdc/1A, 30Vac/0.5A resistive load
CURRENT SHARING|  Please refer to function manual  
ENVIRONMENT
|  WORKING TEMP. **Note.5|  -30 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY|  20 ~ 95% RH non-condensing
STORAGE TEMP., HUMIDITY|  -40 ~ +85℃, 10 ~ 95% RH non-condensing
TEMP. COEFFICIENT|  ±0.03%/℃ (0 ~ 50℃)
VIBRATION**|  Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X,
Y, Z axes; Mounting: Compliance to IEC60068-2-6  
SAFETY & EMC
(Note 6)
|  SAFETY STANDARDS|  UL508, AS/NZS62368.1, EAC TP TC 004 approved,
IEC62368-1 CB approved by SIQ; Design refer to BS EN/EN62368-1
WITHSTAND VOLTAGE|  I/P-O/P:3KVAC  I/P-FG:2KVAC  O/P-FG:0.5KVAC  O/P-DC
OK:0.5KVAC
ISOLATION RESISTANCE|  I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25℃/
70% RH
EMC EMISSION|  Compliance to BS EN/EN55032 (CISPR32), BS EN/EN61204-3
Class B, BS EN/EN61000-3-2,-3, EAC TP TC 020
EMC IMMUNITY|  Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11, BS
EN/EN55035, BS EN/EN61000-6-2 (BS EN/EN50082-2), BS EN/EN61204-3,
heavy industry level, EAC TP TC 020
OTHERS
|  MTBF|  647.1K hrs min.        Telcordia SR-332 (Bellcore) ; 59.5K hrs
min.         MIL-HDBK-217F (25℃)
DIMENSION|  110125.2150mm (WHD)
PACKING|  2.47Kg ; 6pcs/15.8Kg/1.47CUFT
NOTE|
- 
All parameters NOT specially mentioned are measured at 400VAC input, rated load and 25 C of ambient temperature. 
- 
Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 
- 
Tolerance : includes set up tolerance, line regulation and load regulation. 
- 
Dual-phase operation is allowed under certain derating to output load. 
 Please refer to derating curves for details.
- 
Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power. 
 In case the adjacent device is a heat source, 15mm clearance is recommended.
- 
The power supply is considered a component which h will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. 
- 
The ambient temperature derating of 3.5°C/1000m with fanless models and of 5°C/1000m with fan models for operating altitude higher than 2000m(6500ft). 
Product Liability Disclaimer: For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx
Mechanical Specification

Terminal Pin No. Assignment (TB1)
| Pin No. | Assignment | 
|---|---|
| 1 | FG | 
| 2 | AC/L3 | 
| 3 | AC/L2 | 
| 4 | AC/L1 | 
Terminal Pin No. Assignment (TB2)
| Pin No. | Assignment | 
|---|---|
| 1,2,3 | DC OUTPUT +V | 
| 4,5,6 | DC OUTPUT -V | 
Control Pin (CN205) : DINKLE ECH250R-04P or equivalent
| Pin No. | Assignment | Mating Housing | Wire Diameter | 
|---|---|---|---|
| 1 | P-(Current Share) | DINKLE ESC250V-04P | 
or equivalent (Including in the single package)
| 0.081~0.517mm2 (28~20AWG)
2| P+(Current Share)
3,4| DC OK Relay Contact  
Block Diagram

DC OK Relay Contact
| Contact Close | PSU turns on / DC OK. | 
|---|---|
| Contact Open | PSU turns off / DC Fail. | 
| Contact Ratings (max.) | 30V/1A resistive load. | 
Derating Curve
Output derating VS input voltage
Function Manual

Current sharing
- Parallel operation is available by connecting the units shown as below (P+,P- are connected mutually in parallel).
- The difference of output voltages among parallel units should be less than 0.2V.
- The total output current must not exceed the value determined by the following equation (Output current at parallel operation)=(The rated current per unit) x (Number of unit) x 0.9.
- In parallel operation 4 units is the maximum, please consult the manufacturer for other applications.
- The power supplies should be paralleled using short and large-diameter wiring and then connected to the load.
- When in parallel operation, the minimum output load should be greater than 5% of total output load. (Min. load >5% rated current per unit x number of unit)
- In parallel connection, maybe only one unit (master) operate if the total output load is less than 5% of rated load condition. The other PSUs (slaves) may go into standby mode and their output LEDs & relays will not turn on.
- Some minor noise may be heard at light load conditions under parallel operation. This is a normal phenomenon and the performance of the PSU will not be influenced.
MW Search : https://www.meanwell.com/serviceGTIN.aspx
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>