ActronAir MGW-CLDCS VRF Cloud Gateway User Manual
- June 15, 2024
- ActronAir
Table of Contents
ActronAir MGW-CLDCS VRF Cloud Gateway
VRF CLOUD GATEWAY
Operation Manual
- Model Numbers
- MGW-CLDCS
IMPORTANT NOTE
Please read this manual carefully before installing or operating your air
conditioning unit.
Safety Precautions
The Operation and Installation Manual of this product describes how to properly handle the product, prevent harm to others and prevent property losses, as well as how to use the product correctly and safely. Read the following carefully, make sure you understand the content (symbols and marks), and observe the precautions below
CAUTION
- Read the safety warnings carefully prior to installation.
- Be sure to observe the important safety precautions provided below. Meanings of labels:
- Warning Improper handling may lead to personal injury or material loss.
- Caution Indicates that the operations will be affected due to ignoring a precaution.
Icon description
WARNING
- This unit must be installed by professional technicians. Users are not allowed to install the unit themselves; otherwise, it may cause harm to you or others or damage the controller.
- Other electrical wiring work must be carried out by a professional technician according to the circuit diagram. All wiring work must comply with electrical safety specifications.
- It is forbidden to modify the use and function of the product without authorization.
CAUTION
- Do not install the product in a location where flammable gas can easily leak. Any leakage within the vicinity of the device may cause a fire.
- The wiring must be compatible with controller current.
- Be sure to check the wiring before powering on, because it is prohibited to install the machine while the power is on.
- In the event of any malfunction, please contact a professional technician. DO NOT disassem-ble or repair the unit without authorization.
- This equipment is not suitable for places where children gather.
Operation Instructions
Gateway Hardware
- MGW-CLDCS Gateway [hereinafter referred to as the “Gateway”] is used together with “Cloud Service” to upload VRF unit data to the cloud server through the Gateway.
- The model adapted are ECOFLEX ODU + 3rd generation IDU or ECOFLEX ODU + ECOFLEX IDU.
- The Gateway supports one RS-485 bus and is capable of taking in 8 refrigerant systems (the maximum IDU quantity is 64); Supports 1 DI port which is defined as an emergency stop interface; Supports 1 LAN port used for Web page configuration.
- The X port of the Gateway is connected to the X port of the ODU, and the Y port of the Gateway is connected to the Y port of the ODU.
- When multiple refrigerant systems are connected, they need to use different addresses.
Gateway Functions
Gateway Web
Gateway’s factory IP address is 192.168.1.200. Enter http://Gateway IP on
the browser to access the built-in Web page of the Gateway. The PC needs to be
in the same network segment as the Gateway.
In the address bar of the Chrome browser (*3), enter http://192.168.1.200. The
Web page of the Gateway is shown in the figure below:
Other browsers may be incompatible, preventing the Web function from working properly.
Settings
The parameters are described as follows
After modifying parameters, click “Save” to automatically restart the gateway.
Firmware
- Upgrade Gateway firmware: click “UpLoad” and select the correct firmware.
- The firmware is successfully imported when the progress bar displays 100%. The gateway automatically restarts and updates the firmware.
- Note : Must be connecter to the internet to get firmware update
Restore Factory Settings
When the factory configuration is restored, the gateway IP address, and server parameters are set to factory setting values.
Steps
-
Power off the Gateway, press and hold SW1 and turn on the power of Gateway;
-
Keep holding SW1 until the digital display shows “LL” and release SW1; when the digital display shows “FF”, the Gateway has been restored to factory configuration and automatically reset and restarted.
Emergency Stop
In the event of a short circuit connection of DI1 and M, the Gateway will start the emergency shutdown function.
Logic description of emergency stop: The Gateway uses continuous polling (*4) to obtain the information of the connected device. During the effective period of the emergency stop function, the Gateway determines that the IDU is locked in the on state according to the polling information, and will unlock the locked-on attribute of the corresponding IDU. -
If the IDU is on, the Gateway sends a shutdown command until the Gateway exits the emergency stop function (*5).
-
*The interval of Gateway polling depends on the number of devices connected, and usually takes five minutes to complete.
-
Exiting the emergency stop will not restore the IDU’s locked-on status, namely, the IDU which was originally locked on becomes unlocked.
Installation Instructions
Product Introduction
Product Dimensions
Installation Accessories
Please check that you have all the following parts.
Installation Method
Installing the Guide Rail
Mounting the Device on the Wall
actronair.com.au 1300 522 722
pyright 2023 Actron Engineering Pty Limited ABN 34 002767240. ®Registered
Trade Marks of Actron Engineering Pty Limited. ActronAir is constantly seeking
ways to improve the design of its products, therefore specification are
subject to change without notice.
Operation Manual – VRF CLOUD GATEWAY Document: 9590-3036-06 Ver. 1 230821