VALLOX 51K MV Ventilation Units User Manual

June 15, 2024
VALLOX

Table of Contents

VALLOX 51K MV Ventilation Units User Manual

SAFETY

Safe and appropriate handling requires knowledge of the basic safety regulations, and of the intended use of the ventilation system. Read this manual before operating the ventilation unit. Please keep the manual for later reference. If you lose the manual, it can be downloaded from our website.

This user manual contains all the information necessary for safe operation of the system. All persons who operate and maintain the ventilation system must follow the instructions provided in this manual. Furthermore, all local accident prevention regulations must be observed.

INSTALLATION

Installation and setup should only be carried out by a qualified specialist. Electrical installations and connections must only be carried out by an electrician and in compliance with local regulations.

WARRANTY

The guarantee and liability exclude damage resulting from:

  • Inappropriate use of the ventilation system or the control unit
  • Incorrect or inappropriate installation, setup or use
  • Neglect of instructions concerning transportation, installation, use, or maintenance
  • Structural or electronic modifications or changes made to the software

INTENDED USE

All Val lox ventilation units have been designed to provide appropriate and continuous ventilation so as to present no threat to health and to maintain structures in good condition.

DISPOSAL OF THE VENTILATION UNIT

Do not dispose of electronic devices with household waste. Follow local laws and regulations on safe and ecological disposal of the product.

NOTE
For further information, go to www.vallox.com

WARNING
The unit is not intended for use by children under 8 years of age or by persons with reduced sensory, physical or mental capabilities, or whose lack of knowledge and experience do not ensure safe operation of the unit.
Such persons can use the unit under supervision, or by following the instructions of someone who is responsible for their safety.
Children must be supervised and not be allowed to play with the device.

SAFETY SIGNS USED IN THE INSTRUCTIONS

DANGER
Indicates a hazard that will result in death or serious injury if not avoided.
WARNING
Indicates a hazard that can result in death or serious injury if not avoided.
CAUTION
Indicates a hazard that can result in minor or moderate injury if not avoided.
IMPORTANT
Indicates a hazard that can result in damage to property or loss of data if not avoided.
NOTE
Indicates essential information about the product.
TIP
Provides additional information about the use of the pro

NSTALLATION OPTIONS

  • Vallox 51 MV and 51K MV can only be mounted on the wall. There are two unit models, left- (L) and right-handed (R). In the right-handed version, outdoor air comes into the unit from the right. In the left-handed version, outdoor air comes into the unit from the left. The location of the filters, bypass damper, and heating radiator is also mirrored in the left-handed model.

NOTE
The standard equipment and available accessories vary from country to country.

SYSTEM DESCRIPTION

System description

  1. Internet
  2. WLAN
  3. Router
  4. WLAN/LAN
  5. Additional switch
  6. Sensor

VENTILATION UNIT CONTROL

Ventilation unit control options.
Operation of the Vallox ventilation unit can be controlled by the following means:

  • Through a My Vallox control panel installed in the building.
  • Through the My Vallox Home local area network connection and the My Vallox Home/Cloud user interface.
  • Through the My Vallox Cloud service and the My Vallox Home/Cloud user interface.
  • Through a remote monitoring service or building automation that uses voltage signals or Modbus messages.

In addition to the integrated humidity and carbon dioxide sensor, ventilation can also be adjusted automatically by using the optional carbon dioxide, humidity, or VOC (air quality) sensor. When these are used, ventilation remains optimal even when the dwelling is unoccupied. Each user can use the week clock to adjust the ventilation to fit their individual lifestyle.

The ventilation unit’s integrated humidity and carbon dioxide sensors adjust ventilation automatically according to the need. In addition, ventilation can be automated by using optional carbon dioxide, humidity or air quality (VOC) sensors.

Changing the ventilation mode

Vallox 51 MV
The Vallox 51 MV ventilation unit is controlled by using the My Vallox control panel. Press the left button of the control panel (see the Figure) repeatedly until the desired status is shown as the middle option on the display.

At home
Use this mode when the dwelling is occupied.

Away
Use this mode when the dwelling is unoccupied, e.g. during a trip or other long absence.

Boost
Use this mode to increase the ventilation rate, e.g. when there are more people than usual in the dwelling or elsewhere on the premises.

Custom
Use this mode when, for example, you are making a fire in the fireplace. The mode is primarily used to create momentary overpressure in the dwelling.

IMPORTANT
Prolonged overpressure can result in damage to the structures of the building.

IMPORTANT
Apartment-specific ventilation units allows residents to adjust the ventilation efficiency. Ventilation is controlled based on the need e.g. through the cooker hood, ventilation control panel, or a separate control centre. In order to ensure that the indoor air presents no harm to health and remains optimal also for the structures of the building, ventilation must be kept on without disruptions. It is recommended that ventilation be left turned on during long holidays also. This keeps the indoor air fresh and prevents humidity from condensing in the ventilation ducts and structures. It also reduces the risk of moisture damage.

Vallox 51K MV

The Vallox 51K MV ventilation unit is controlled by using the Val lox Capture cooker hood that is connected to the unit. The cooker hood is designed to be used above the cooker top, as a general extraction valve in the kitchen, and as a ventilation system control panel.

Front panel buttons
The front panel of the cooker hood has four buttons and four signal lights.
panel buttons

Position of the damper
The damper is opened by pressing the damper button (light turns on). The damper is closed (light turns off) by pressing the damper button or automatically after one hour (without a timer or 45-120 min when programmed).

In normal circumstances, the damper must be closed (the signal light is off), which boosts the extract air flow from other premises.

The damper must be open (the signal light is turned on) when the user wants to increase the extract air flow from the cooker hood e.g.

  • when the cooker top or the oven is used for cooking;
  • the load in the kitchen is exceptional due to the use of strong detergents, presence of a large number of people, or similar.

Cooker hood light
Turn the light on or off by pressing the light switch. The light is dimmable. Adjust the brightness by pressing the light switch until the brightness is adequate.

Ventilation modes
Select the mode by pressing the fan speed button repeatedly until the signal light indicates the desired ventilation mode:

Away mode
Use this mode when the dwelling is unoccupied, e.g. during a trip or other long absence.

At home mode
Use this mode when the dwelling is occupied.

Boost mode
Use this mode to enhance ventilation, e.g. when there are more people than usual in the apartment.

Selection button
The selection button is roughly 3 cm to the left from the damper button. The selection button is not marked on the front panel.

CAUTION

  • Neglecting the cleaning of the grease filter can cause a fire hazard.
  • The outer surfaces of the hood can become hot when the cooker or the oven is turned on.
  • Flaming is forbidden underneath the cooker hood.
  • Always follow the instructions provided on adjusting the efficiency of ventilation.
  • Enable a sufficient supply air flow into the room if the cooker hood and non-electric devices are used simultaneously

NOTE
The unit reminds the user of the need to change the filters with the red signal light of the Vallox Capture cooker hood.

To set off the filter reminder, close the damper and then open-close-open- close. Press at a less than one second interval.

Connecting the ventilation unit to the cloud service

The ventilation unit can be connected to the My Vallox Cloud service. The cloud service allows for controlling ventilation remotely also, using e.g. a smartphone or tablet. Also the unit software is updated automatically through the cloud service. To connect to the cloud service, the ventilation unit must be connected to the Internet via LAN and registered with the cloud service. At the same time you create a My Vallox Cloud account for yourself. Read more about the service at www.myvallox.com.

NOTE
For the My Vallox Cloud/ Home instructions, please go to vallox. techmanuals.info/ Vallum/ENG/help/ web help

Brightness of the light

To adjust the brightness of the light:

  1. Turn on the light, close the damper, and set the ventilation to the Away mode.
  2. Press the selection button for roughly 10 seconds until the setting mode signal light starts to flash.
  3. Adjust the brightness of the light by pressing the light button until the brightness is adequate.
  4. To save the setting, press the selection button for roughly 3 seconds until the setting mode signal light stops to flash.

To read about the other functions of the selection button, go to our website, www.vallox.com

Guard function

The cooker hood has a guard function that is activated when the temperature of the cooker hood exceeds +60 °C or after a sudden increase in temperature (> 8 °C/min). In such a case, all signal lights and the LED light of the cooker hood will flash, the controlled fan or ventilation unit turns off, and the damper closes. If this kind of alarm is noticed before fire damage, it can be acknowledged by pressing any of the cooker hood buttons.

MAIN PARTS

Vallox 51 MV
Main parts
R model in the figure. In the L model, the parts are mirrored.

Heat recovery cell: 2a
Extract air fan : 3a
Supply air fan : 3c
Fine filter for supply air: 4a
Coarse filter for supply air : 4b
Coarse filter for extract air: 4c
Bypass damper of the HR cell : 5a
Post-heating resistor: 6a
Ceiling bushing for electric wires: 9a
Control panel: 10b
Internal humidity sensor: 11a
Internal carbon dioxide sensor: 11a
Carbon dioxide sensor (optional): 11c
Humidity sensor (optional): 11d
VOC sensor (Optional): 11e

MAIN PARTS

Vallox 51K MV

R model in the figure. In the L model, the parts are mirrored.

Heat recovery c: 2a
Extract air fan: 3a
Supply air fan: 3c
Fine filter for supply air : 4a
Coarse filter for supply air: 4b
Coarse filter for extract air: 4c
Bypass damper of the HR cell: 5a
Post-heating resistor: 6a
Ceiling bushing for electric wires: 9a
Control panel: 10b
Internal humidity sensor: 11a
Internal carbon dioxide sensor: 11a
Carbon dioxide sensor (optional): 11c
Humidity sensor (optional): 11d
VOC sensor (Optional): 11e
Cooker hood: 12a
Damper button: 12b
Fan speed adjustment: 12c
Light switch: 12d

MOUNTING ON THE WALL

NOTE
Avoid mounting the unit on a hollow, echoing partition wall or on a bedroom wall, or prevent the conduction of sound. The minimum distance between the top of the unit and the finished ceiling surface is 30 mm. Note that during mounting the unit rises 10 mm higher than the final height.

Mount the ventilation unit onto the wall with a mounting plate, as shown in the figures below. Make sure that the unit is horizontally level after mounting

Vallox 51K MV must be mounted so that the clearance between the bottom of the cooker hood and the cooker top is at least 426 mm in case of an electric stove and 650 mm in case a gas stove. The clearance is 134 mm (i.e. the height of the cooker hood) more between the bottom of the ventilation unit and the cooker top.

MOUNTING ON THE CEILING

Vallox 51 MV can be equipped with an optional ceiling mounting plate. To attach the ceiling mounting plate:

  • On rafter frames or other frame structure with M8 thread bars so that they withstand the weight of the unit.
  • Ensure that the installation plate is horizontally level, as this determines the position of the unit.
  • The top edge of the white covering strip of the ceiling mounting plate can be installed against the ceiling. Alternatively, a concealed mounting method can be used, in which case the ceiling can be 30 mm below the top of the white covering strip.

Insulate the ducts against condensation also between the unit and the ceiling mounting plate.

Mounting the ceiling mounting plate

  1. Fasten the thread bars on the rafter frames or other frame structure, and screw the nuts onto the bars.
  2. Lift the ceiling mounting plate in place.
  3. Push a rubber damper and a washer to each thread bar to the cup of the plate.
  4. Turn the nuts to make sure that the unit is horizontally level.
  5. Shorten the lower ends of the thread bars so that they will be at no more than 10 mm from the lower surface of the ceiling mounting plate.

NOTE
A space of at least 330 mm must be reserved in front of the unit for maintenance purposes

NOTE
Mount the ventilation unit in a place where the temperature does not fall below +10°C.

CAUTION
The ventilation unit is very heavy. Do not perform this procedure alone.

Installing the ventilation unit to the ceiling mounting plate

  1. Install the ceiling mounting plate with M8 thread bars so that it is horizontally level.
    Installing the ventilation
    NOTE
    The end of the thread bars must be 5 mm or less below the fastening nut. Do not fasten the ceiling mounting plate too tight to the ceiling. Ensure that the sliding bars move and restore to their original position by pulling from the operating levers (A).

The top edge of the white covering strip of the ceiling mounting plate can be installed against the ceiling. Alternatively, a concealed mounting method can be used, in which case the ceiling can be 30 mm below the top of the white covering strip.

  1. Ensure that the insulation washers are in place in the outlet collars below the ceiling mounting plate.

  2. The door of the unit must be removed when the Vallox 51 ventilation unit is installed onto the wall mounting plate.

  3. Lift the ventilation unit close to the ceiling mounting plate and feed the cables through the hole in the ceiling mounting plate on top of the ceiling. Alternatively, the cables can be fed between the ceiling mounting plate and the ventilation unit to the rear wall, to the area shown in the adjacent figure.
    NOTE
    Remember to make a service door in the ceiling so that the cables and the connection box can be accessed. The distance between the service door and the ceiling mounting plate must be around 500 mm.
    When the ventilation unit is lifted against the ceiling mounting plate, the unit locks in place. (Where needed, guide the mounting hooks on the ceiling mounting plate (B) to the grooves on the side panels of the ventilation unit).

There are operating levers (A) on the front bottom corners of the ceiling mounting plate. When the levers have been restored to the same level with the white covering strip of the ceiling mounting plate, the unit has been locked in place.

  1. Where required, the unit can be detached from the ceiling mounting plate. Remove the door of the unit. Lift the unit slightly upwards and pull simultaneously from both operating levers ( A) of the ceiling mounting plate to detach the unit from the ceiling mounting plate.

Attic floor penetration plate

The attic floor penetration plate (F) is optional. When an attic floor penetration plate is used, the airtightness of the vapour barrier must be ensured.
The minimum distance of the attic floor penetration plate from the rear wall is 5 mm. The minimum distance of the attic floor penetration plate from the side walls is 15 mm

EXTERNAL ELECTRICAL CONNECTIONS

External electrical connections are led to the ventilation unit through the ceiling bushing for electric wires. The length of the wires must enable pulling the fan chamber assembly out of the unit without having to disconnect any of the connections.
Connection

REMOVAL OF CONDENSING WATER

Vallox 51 MV
The Vallox Silent Klick siphon is installed in the bottom pool of Vallox 51 MV. The condensing water tube is led from the siphon e.g. to the siphon of the sink or to the floor drain. Alternatively, an elbow can be installed in the bottom pool, in which case the Vallox Silent Klick siphon is installed in the condensing water tube to enable maintenance measures.
Removal Condensing

NOTE
The Vallox Silent Klick siphon package is delivered with Vallox 51 MV and 51K MV. Installation instructions for the siphon are enclosed with the packaging, and can also be found online at www.vallox.com. When the alternative siphon installation method is used, the ring seal and the locking part must be moved to the pipe connection part that is mounted on the wall.

In Vallox 51K MV, an elbow is mounted on the bottom pool between the unit and the cooker hood. A condensing water tube is led from the elbow e.g. into the siphon of the sink or to the floor drain. The siphon must not be installed inside the cooker hood. Instead, it must be installed in the condensing water tube so as to enable maintenance measures. There are approx. 2 mm wide holes at the rear of the bottom of the Vallox 51K MV ventilation unit marking the position where the condensing water tube must be installed.

  1. Install the elbow at the bottom of the ventilation unit without the siphon (Figure 1). Install the siphon in the condensing water tube before the drain or odour trap (Figure 2). The Vallox Silent Klick siphon helps prevent noise disturbance caused by the removal of condensing water.

  2. The condensing water tube must be installed either directly backwards from the cooker hood through the wall, if there is a sewer connection behind the wall (see figure 2 for the dimensions of the tube location), or to the odour trap of the sink (Figure 2).

  3. The condensing water tube must be placed at an angle so that it always points downwards.

Observe in the figure:

  1. Elbow.
  2. Exit hole for the condensing water outlet.

INSTALLATION OF THE VALLOX CAPTURA COOKER HOOD

The Vallox Captura cooker hood is installed on the bottom of Vallox 51K MV.

  1. Remove the plug from the feedthrough seal of the condensing water tube of the cooker hood ( Figure 1).

  2. Lift the cooker hood and fit the hooks at the rear of the cooker hood into the holes at the bottom of the ventilation unit. Push in place (Figure 2).

  3. Ensure that the feedthrough seal of the condensing water tube sits firmly around the tube.

  4. Lift the front of the cooker hood to fit the mountings into the penetrations in the bottom of the ventilation unit (Figure 3).

  5. Fasten the M5 hexagon screws (2) through the mountings (Figure 4).}

Lead the power cord and the control cable up along the cable channel (Figure 3). Wind approx. half a metre of thecables behind the cooker hood so that it can be removed for  maintenance purposes where required. Move the metal cover backwards so that it covers the opening between the cooker hood and the wall (Figure 5).

CAUTION
The minimum clearance between the bottom edge of the cooker hood and an electric stove is 426 mm.

MEASURING AND ADJUSTING THE AIR FLOWS OF THE VENTILATION UNIT

The accessories delivered with the unit include four (4) air flow measuring tubes. These can be inserted in the ducts to allow for easier ventilation adjustment.
Adjustment Ventilation Unit

MEASURING AND ADJUSTING THE AIR FLOWS OF THE COOKER HOOD

Standard ventilation

The volume flow rate of the air inside the cooker hood is measured with the damper closed and, where required, adjusted based on the static pressure loss and the performance scheme of the cooker hood.

  • Measure the static pressure loss of the cooker hood by pushing the probe through the hole in the damper (see the figure).
  • Determine the volume flow rate from the performance scheme based on the measured pressure and the number of open holes in the damper.

Adjustment:

  • Cover the required number of holes in the damper with the magnetic strip that is delivered with the cooker hood.

STANDARD VENTILATION OF THE COOKER HOOD

Damper in the closed position

Adjustment position| Holes of the damper open
2| 2
3| 3
4| 4
5| 5
6| 6
7| 7
8| 8

**Standard ventilation (settings 2-8)

**

Air flow measurement points
Air flow measuring tubes are placed in the ventilation ducts in accordance with the instructions. The standard air flow from the cooker hood is measured past the damper. The fan curves indicate the total pressure accounted for by duct losses.

A Supply air
B Extract air
C Cooker hood extract air
D Supply air fan
E Extract air fan

R model in the figures. In the L model, the order of the ducts is mirrored.

DIMENSIONS AND DUCT OUTLETS

Vallox 51 MV

There are two condensing water discharge outlets at the bottom. The condensing water outlet or siphon is connected to a free, not plugged, discharge outlet.
A. The condensing water outlet /siphon is connected here in case of a right-handed unit
B. The condensing water outlet /siphon is connected here in case of a left-handed unit

**Vallox 51K MV

**

Dimensions

**R model

L model

**

Duct outlets
Inner diameter of the female collar: 125mm

  1. Supply air from the unit to the apartment
  2. Extract air from the apartment to the unit
  3. Exhaust air flowing outdoors from the unit
  4. Outdoor air to the unit

Locations of supports for HR cell

Vallox 51 MV
R model

L model

Vallox 51K MV
**R model

L model

**

  1. Supply air
  2. Extract air
  3. Coarse filter
  4. Fine filter
  5. Upper support of the cell
  6. Lower support of the cell

BEFORE BEGINNING MAINTENANCE WORK

WARNING
Always disconnect the power plug before starting maintenance on the ventilation unit. The unit has no safety switch that would switch the power off when the door of the unit is opened.

REPLACING THE FILTERS

The Vallox ventilation unit has three filters:

  • Coarse filter for supply air filters insects, heavy pollen  and other relatively large foreign objects out of the outdoor air.
  • Fine filter for supply air filters microscopic pollen and dust particles out of the supply air.
  • Coarse filter for extract air filters the extract air and keeps the heat recovery cell clean.

The filter replacement interval depends on the ambient particle concentration. It is recommended that the filters be replaced every spring and autumn, or at the very least once a year.

To replace the filters:

  1. Disconnect the ventilation unit from the mains electricity supply.

  2. Open the door of the unit.
    CAUTION
    The door is heavy.

  3. Remove the old filters (A, B, C) and discard them.

  4. Install the new filters (A, B, C).

  5. Close the door of the unit.

  6. Plug the ventilation unit back into the mains.

  7. The filters have now been successfully replaced.

IMPORTANT
If the power cord is damaged, the manufacturer, its service representative or other person with similar qualifications must replace it to avoid danger

NOTE
The service space in  front of the ventilation unit must be at least 330 mm.

TIP
Using original Vallox  filters ensures that the ventilation unit remains in top condition, giving the best results. To select and order filter packages, please go to: filters.vallox.com

CLEANING THE HEAT RECOVERY CELL

Check that the heat recovery cell is clean roughly once a year, or whenever the filters are being replaced. Clean by washing as required.
Replacing Filter

Cleaning the heat recovery cell:

  1. Disconnect the ventilation unit from the mains electricity supply.

  2. Open the door of the ventilation unit by undoing the finger screws and by lifting the door off.
    CAUTION
    The door is heavy.

  3. Pull out the black upper support of the cell (E) located above the cell.

  4. Lift and pull the cell (D) out of the unit.
    IMPORTANT
    Handle the cell carefully! Do not lift the cell by the layers. The cell layers are very thin and easily damaged.

  5. If the cell is dirty, clean it by immersing it in warm water, to which a small amount of a mild detergent has been added.

  6. Rinse the cell clean with a water spray. Do not use a high-pressure cleaner.

  7. When all the water has drained from between the layers, reassemble the ventilation unit in the reverse order.

  8. Close the door.

  9. Plug the ventilation unit back into the mains. The heat recovery cell has now been cleaned.

CONDENSING WATER

In the heating season, the extract air humidity condenses to water. In new buildings, the volume of condensing water can be high. Condensed water must be able to freely leave the unit.

At some time before the heating season begins (e.g. during autumn maintenance), check that the siphon or the condensing water outlet in the bottom pool are not clogged. To check this, pour some water into the pool. Clean as required.

NOTE
Some condensing water may have accumulated in the bottom pool of the unit; this is normal and requires no corrective action.

WARNING
Water must at all times be kept out of the electrical system.

CLEANING THE FANS

Check the cleanliness of the fans when servicing the filters and the heat recovery cell. Clean the fans as required.

Removing and cleaning the fans

**To clean the fans:

**

  1. Disconnect the ventilation unit from the mains electricity supply.

  2. Undo the door screws to open the door of the Vallox ventilation unit.

  3. Lift the door off.
    CAUTION
    The door is heavy.

  4. If the length of the cables that are led out of the unit through the ceiling bushing (G) and connected to the connection card (F) in the electric box prevents moving the fan chamber sufficiently far from the ventilation unit, disconnect the cables. Pull these cables out of the unit through the ceiling bushing.

  5. Detach outdoor and extract air temperature sensors from the ceiling mounts. Remove the round feedthrough rubbers (H) from the slots on the intermediate walls of the unit by pulling.

  6. Undo the earthing screw (K) on the upper left corner of the electric box.

  7. Release the damper motor (J) by placing an orange magnet (I) on the magnet icon on the damper motor. Observe the location of the magnet so that you will be able to return it to its original location after maintenance. Remove the bar from the joint of the damper. Turn the crank of the damper motor so that the bar comes off from the bypass damper and turn the damper into the cell bypass position.

  8. Pull out the upper support of the cell (E). Lift and pull the cell (D) out of the unit.

  9. Pull the fan chamber (M) out of the unit (contains the fans, electric box, and the bypass duct incl. the damper motor).

  10.  The fans are mounted on the fan chamber by means of three screws (L). Do not undo the earthing screw at the bottom edge on the rear wall side.

  11. Disconnect the quick connectors of the fan cable.

  12. Clean the fans. The fan can be cleaned with compressed air (wear protective goggles) or by brushing it gently.

  13. To reassemble the ventilation unit, follow the above steps in reverse order.

NOTE! Remember to reconnect the bar of the damper motor into the joint of the damper and to lock the connection with the orange magnet. Ensure that the sensors and their feedthrough rubbers are in correct locations. Also ensure that all the connections have been correctly implemented and the earthing screw is in place in the left corner.

IMPORTANT
The fans are extremely sensitive to external shocks. It is recommended that the fans be cleaned in place, i.e. without attempting to remove them. Handle the fan blades carefully. It is recommended that the fans be cleaned by a professional.

CLEANING THE GREASE FILTER OF THE COOKER HOOD

Keep the cooker hood clean. Wipe outer surfaces regularly with water containing a small amount of a mild detergent. Clean off any grease stains immediately. Do not use abrasive or corrosive detergents or tools.

Keep the grease filter clean to ensure an adequate extract air flow. The grease filter must be washed with warm water and detergent or in a dishwasher at least 1-2 times a month.

Removing and mounting the grease filter

  1. Pull the locking device of the grease filter towards the front edge of the cooker hood while pulling the grease filter downwards until it comes off.

  2. Clean the grease filter either by washing it with hot water and hand-washing detergent or in a dishwasher.
    Removing and mounting

  3. Mount the grease filter back in place. Push the front edge of the filter onto the shelf of the cooker hood and lift the rear edge in place with the locking device pressed down.

NOTE! Ensure that the locking device points downwards.

WARNING
Neglecting the cleaning of the grease filter can cause a fire hazard.

Light
The cooker hood has a long-lasting LED lighting module. If the light is not working, contact a servicing company.

TECHNICAL SPECIFICATIONS

Product title| Vallox 51 MV R Vallox 51 MV L| |
---|---|---|---
Air volumesSupply air Extract air| 46 dm³/s, 100 Pa51 dm³/s, 100 Pa| Fans Supply air Extract air| 0.035 kW 0.35 A EC0.035 kW 0.35 A EC
Post-heating| Electrical resistor, 900 W| Electrical connection| 230 V, 50 Hz, 4.24 A power plug
Pre-heating| –| Enclosure protection class| IP34
Additional heating| –| Heat recovery bypass| Automatic
FiltersSupply air Extract air| ISO Coarse > 75% + ISO ePM₁ ISO Coarse > 75%| |
Specific energy consumption (SEC)in a cold climatein a temperate climate| A+ A| Efficiencies Annual efficiency Supply air efficiencySpecific Fan Power (SFP)| 77%84%1.04 kW/m3/h (33 dm3/s)
Dimensions (w x h x d)| 598 x 668 x 349 mm| Weight| 45 kg
Working point defined in the Ecodesign Directive (2009/125/EC), Southern Finland, Helsinki-Vantaa TRY year 2012.
Product title| Vallox 51K MV R Vallox 51K MV LVallox Captura white hoodVallox Captura stainless steel hood| |
Air volumesSupply air Extract air| 46 dm³/s, 100 Pa51 dm³/s, 100 Pa| FansSupply air Extract air| 0.035 kW 0.35 A EC0.035 kW 0.35 A EC
Post-heating| Electrical resistor, 900 W| Electrical connection| 230 V, 50 Hz, 4.24 A 2 x power plug
Pre-heating| –| Enclosure protection class| IP34
Additional heating| –| Heat recovery bypass| Automatic
FiltersSupply air Extract air| ISO Coarse > 75% + ISO ePM₁ ISO Coarse > 75%| |
Specific energy consumption (SEC)in a cold climate a temperate climate| A+ A| Operating efficiencies Annual efficiency Supply air efficiency Specific Fan Power (SFP)| 77%84%1.04 kW/m3/h (33 dm3/s)
Dimensions (w x h x d)| 598 x 802 x 349 mm| Weight| 51 kg
Working point defined in the Ecodesign Directive (2009/125/EC), Southern Finland, Helsinki-Vantaa TRY year 2012.

AIR FLOWS AND SOUND VALUES

**FAN INPUT POWER

SUPPLY/EXTRACT AIR VOLUMES

**

Sound values

| Sound power level in the supply air duct (one duct) by octave band Lw, dBAdjustment position| Sound power level in the extract air duct (one duct) by octave band Lw, dBAdjustment position
---|---|---
Adjustment position (%)| 10| 20| 30| 40| 50| 60| 70| 80| | 100| 10| 20| 30| 40| 50| 60| 70| 80| | 100
Medium frequency of the octave bandHz| 63| 57| 61| 64| 65| 68| 70| 73| 79| | 81| 60| 58| 58| 61| 64| 64| 71| 70| | 72
125| 51| 54| 58| 60| 62| 64| 66| 68| | 69| 51| 52| 54| 54| 57| 59| 60| 62| | 62
250| 45| 50| 55| 57| 62| 61| 64| 66| | 66| 30| 34| 38| 40| 45| 45| 47| 49| | 50
500| 40| 46| 51| 53| 57| 59| 63| 66| | 68| 31| 38| 40| 42| 45| 49| 51| 56| | 56
1000| 32| 39| 45| 47| 51| 55| 59| 64| | 64| 21| 26| 30| 33| 36| 40| 42| 45| | 46
2000| 20| 30| 37| 41| 44| 47| 49| 52| | 52| 14| 15| 20| 24| 28| 30| 33| 35| | 36
4000| 18| 22| 29| 35| 40| 44| 47| 50| | 51| 18| 17| 17| 17| 18| 20| 22| 24| | 25
8000| 21| 21| 23| 27| 33| 38| 43| 47| | 47| 21| 21| 21| 21| 21| 21| 21| 21| | 21
LW, dBLWA, dB(A)| 58| 62| 66| 67| 70| 72| 75| 80| | 82| 61| 59| 59| 62| 65| 65| 72| 71| | 73
42| 47| 52| 54| 59| 60| 64| 67| | 68| 38| 40| 42| 43| 46| 49| 52| 55| | 55
| Vallox 51 MV, Vallox 51K MV (no standard extraction through the hood in the kitchen)Sound pressure level coming through the envelope of the unit in the room in which it is installed (10m² sound absorption)
Adjustment position
Adjustment position (%)| 10| 20| 30| 40| 50| 60| 70| 80| | 100
LpA, dB (A)| 21| 24| 28| 29| 32| 35| 38| 40| | 40
| Vallox 51K MV (standard extraction 8 dm³/s through the hood in the kitchen)Sound pressure level coming through the envelope of the unit in the room in which it is installed (10m² sound absorption)
Adjustment position
Adjustment position (%)| | 22| | 40| | | | | |
LpA, dB (A)| | 28| | 32| | | | | |

INTERNAL ELECTRICAL CONNECTION

Vallox 51 MV / Vallox 51K MV
Connection

A Motherboard
B
  1. Extract air fan tacho (WT)
  2. GND (GN)
  3. Extract air fan PWM (YE)
  4. Supply air fan tacho (WT)
  5. GND (GN)
  6. Supply air fan PWM (YE)

C|

  1. Extract air
  2. Outdoor air
  3. Supply air
  4. Exhaust air
  5. Supply air from the HR cell

D| LAN
MB_A| External Modbus A signal
---|---
MB_B| External Modbus B signal
+24V| +24V voltage (DC)
GND| Digital and analog ground potential
RS_A| Local hardware Modbus A signal
RS_B| Local hardware Modbus B signal
NTC| External temperature sensor connector
D/I1| Digital input 1
D/I2| Digital input 2
11V1| 11.1 V operating voltage
AN/I| Analog input 0-10VDC
RM/I| 24V relay input
RM/O| 24V relay output
T| Supply air fan
---|---
P| Extract air fan
M| Damper motor
AHS| Post-heating control
CO2| Internal carbon dioxide sensor
%RH| Internal humidity sensor
R1| Post-heating resistor with 90°C and 130°C overheating protection

CABLE COLOURS

BK Black
BU Blue
BN Brown
WT White
GY Grey
YE Yellow
YEGN Yellow-green

EXTERNAL ELECTRICAL CONNECTION

Val lox Capture cooker hood
Vallox Captura cooker hood

CONTACT DATA: GUARD FUNCTION
NORMAL SITUATION = OPEN
ACTIVATED = CLOSED

HOUSE AUTOMATION:
NORMAL SITUATION = OPEN

ERROR SITUATION (HOOD OR VENTILATION
UNIT) = CLOSED ACTIVATED GUARD
FUNCTION = FLASHING

POSITION OF THE DAMPER:
DAMPER CLOSED = CONTACT OPEN
DAMPER OPEN = CONTACT CLOSED

EXTERNAL ELECTRICAL CONNECTION

Vallox 51 MV
Connection

NOTE!
The ventilation unit has 3 spare feedthroughs. Where needed, more holes can be added to the feedthrough or all the required low-current signals can be led from the unit by using only one cable and separated outside the unit.

POWER SUPPLY

POWER SUPPLYMaximum ≤6W
MyVallox Control 1W
MyVallox Touch 0.5 W.
%RH sensor 0.3W
CO2 sensor 1.2W
VOC sensor 2W
Voltage 24 VDC
MB_A External Modbus A signal
MB_B External Modbus B signal
+24V +24V voltage (DC)
GND Digital and analog ground potential
RS_A Local hardware Modbus A signal
RS_B Local hardware Modbus B signal
NTC External temperature sensor connector
D/I1 Digital input 1
D/I2 Digital input 2
11V1 11.1 V operating voltage
AN/I Analog input 0-10VDC
RM/I 24V relay input
RM/O 24V relay output

EXTERNAL ELECTRICAL CONNECTION

Vallox 51K MV
Connection

POWER SUPPLYMaximum ≤6W
MyVallox Control 1W
MyVallox Touch 0.5 W.
%RH sensor 0.3W
CO2 sensor 1.2W
VOC sensor 2W
Voltage 24 VDC
MB_A External Modbus A signal
MB_B External Modbus B signal
+24V +24V voltage (DC)
GND Digital and analog ground potential
RS_A Local hardware Modbus A signal
RS_B Local hardware Modbus B signal
NTC External temperature sensor connector
D/I1 Digital input 1
D/I2 Digital input 2
11V1 11.1 V operating voltage
AN/I Analog input 0-10VDC
RM/I 24V relay input
RM/O 24V relay output

EXTERNAL ELECTRICAL CONNECTION FOR CONTROLLING THE MLV DUCT RADIATOR

Connection

D/I2 Digital input 2
11V1 11.1 V operating voltage
AN/I Analog input 0-10VDC
RM/I 24V relay input
RM/O 24V relay output
P Circulation pump
V Solenoid valve

DUCT RADIATOR OPERATION

Always follow first and foremost the connection diagram provided by the HVAC designer or heat pump manufacturer. Also read the duct radiator manual.

The accompanying figure shows an example of the arrangement for connecting the heating/cooling radiator unit to the heat collection circuit.

Connect the radiator output pipe to the heat collection circuit return pipe. Direct the fluid returning from the radiator unit to the heat collection circuit return pipe. If you know that there is a large loss of internal pressure inside the heat pump, the heat pump should be bypassed. If this is done, the fluid circuit will come into operation when the heat pump comes to a halt. When this happens the pressure loss in the one-way bypass valve Y2 must be lower than the pressure loss in the heat pump.

Heating: The pump starts when the outdoor air temperature drops below the winter limit value set at the factory (-5 °C).
Cooling The supply air setpoint value for the active mode (for example, At home) controls the pump start-up. The pump starts when the supply air setting is below the temperature of the supply air that is blown into the apartment.

The duct radiator can be installed in both the supply air duct and the outdoor air duct. If the radiator is installed in the outdoor air duct, it can be used for both preheating and cooling. If the radiator is installed in the supply air duct, it can be used for heating or for cooling only.

The duct radiator can be set to function either automatically or manually:

  • Automatic – In summer, the supply air temperature will be maintained at the level specified in the temperature setting. In winter, the duct radiator will turn on, when the outdoor temperature falls below the winter setting.
  • Manual – In summer, the duct radiator will turn on, when the outdoor temperature rises above the summer setting. In winter, the duct radiator will turn on, when the outdoor temperature falls below the winter setting.

To prevent the risk of condensation in the supply air duct, you can set the adjustment of the supply air limit to automatic or manual:

  • Automatic – The supply air limit is adjusted automatically based on the dew point of the extract air. When the supply air temperature falls too low, the duct radiator will turn off.
  • Manual – The supply air limit can be set manually. When the supply air temperature falls down to the set value, the duct radiator will turn off.

If an external sensor is in use, it is selected from the settings of the external sensor whether it is used to control the outdoor air duct radiator or the supply air duct radiator. The temperature of the external sensor can be read from the service menu: menu > service menu > unit information page 5 ”External sensor”.

NOTE:
If the duct radiator is used in the supply air duct, it can only be used for cooling.

NOTE:
When used to control the outdoor air duct radiator, the external NTC sensor is installed in the outdoor air duct before the radiator. When used to control the supply air duct radiator, the external NTC sensor is installed after the radiator.

NOTE:
When selecting the relay (C), take account of the maximum allowed combined power supply (6W) of the circuit board in the external MV electrical box, if the relay power supply comes from the circuit board’s +24V connector.

NOTE:
Due to the risk of humidity damage, in a duct that has not been insulated for condensation the supply air temperature must not fall below +16 … 20 °C.

DUCT RADIATOR OPERATION CHART

In the outdoor air duct
In the outdoor air duct
In the supply air duct
In the supply air duct

A Ventilation unit
B Supply air
C Outdoor air
D Feed from the distribution board
E Air extraction
F Duct radiator (reverse connection)
G Heat pump
H Heat collection circuit
N External NTC sensor
P Circulation pump. Not included in the delivery. The pump should be suited

to pumping liquid colder than the surrounding air, due to risk of condensation (for example, Grundfos Magna 1 25-80)
---|---
V| Solenoid valve. Not included in the delivery. The valve that is chosen must be compatible with the heat collection circuit fluid (for example, Danfoss 032U161431, HVAC code 4122110).
K| K Condensing water tube. Not included in the delivery.
IP| De-aerator. Not included in the delivery.
S| External electrical junction box for the MV
N| External NTC sensor for Vallox MV ventilation units
C| 24 VDC relay/contactor for controlling the pump and the solenoid valve. Not included in the delivery. (For example, ABB CR-P024DC2)
Y| One-way valve. Not included in the delivery
Y2| One-way valve. Not included in the delivery. The pressure loss must be less than the pressure loss of the heat pump

EXPLODED VIEW AND SPARE PARTS LIST

Vallox 51 MV
Parts list

N O| PART| PRODUCT NO.| NO| PART| PRODUCT NO| NO| PART| PRODUCT NO.
---|---|---|---|---|---|---|---|---
1a| Door| 4106304| 3g| Fan chamber assembly, R Fan chamber assembly, L| 41050494105048| 11c| MyVallox carbon dioxide sensor (optional)| 949111
1c| Door screw (supplied together with the lock nut of the door screw)| 990715| 4a| Fine filter for supply air| | 11d| MyVallox humidity sensor (optional)| 946149
1d| Plastic screw Cover plug| 9901514105656| 4b| Coarse filter for supply air| | 11e| MyVallox VOC sensor (optional)| 949112
1e| Door screw cover panel| 4106644| 4c| Coarse filter for extract air| | 11g| NTC sensor kit| 4106207
1k| Lock nut of the door screw (supplied together with the door screw)| 990715| 5b| Bypass damper motor| 930621| 13a| Siphon Vallox Silent Klick| 3494701
2a| HR cell (aluminium) HR cell (enthalpy)| 4103227933156| 6a| Post-heating resistor, R model Post-heating resistor, L model| 41065434106544| 14b| Motherboard| 949032-1
2b| Lower support for HR cell| 4103427| 9a| Ceiling bushing for electric wires Ceiling feed-through seal| 950445950446| 14c| Glass tube fuse 63mA slow 5x20mm| 952490
2c| Upper support for HR cell| 4103238| 10a| MyVallox Control panel| 949033| 14d| RJ45 extension cable| 952196
3a 3c| Extract air fan Supply air fan| 4104020| 10b| MyVallox Touch control panel| 949090| 15c| Connection card| 949038
3f| Air flow control grille| 4104868| 11a| Internal humidity and carbon dioxide sensor| 4107971| | |

Vallox 51K MV
Parts list

NO| PART| PRODUCT NO.| NO| PART| PRODUCT NO| NO| PART| PRODUCT NO.
---|---|---|---|---|---|---|---|---
1a| Door| 4106304| 4b| Coarse filter for supply air| | 11c| MyVallox carbon dioxide sensor (optional)| 949111
1c| Door screw (supplied together with the lock nut of the door screw)| 990715| 4c| Coarse filter for extract air| | 11d| MyVallox humidity sensor (optional)| 946149
1d| Plastic screw Cover plug| 9901514105656| 4f| Grease filter| 2052310| 11e| MyVallox VOC sensor (optional)| 949112
1h| Cover door mounting strip| 3296000| 5b| Bypass damper motor| 930621| 11g| NTC sensor kit| 4106207
1k| Lock nut of the door screw (supplied together with the door screw)| 990715| 5g| Damper actuator| 930622| 13a| Siphon Vallox Silent Klick| 3494701
2a| HR cell (aluminium) HR cell (enthalpy)| 4103227933156| 5h| Damper assembly| 2131310| 14b| Motherboard Motherboard| 949032-1949041
2b| Lower support for HR cell| 4103427| 6a| Post-heating resistor, R model Post-heating resistor, L model| 41065434106544| 14c| Glass tube fuse 63mA slow 5x20mm| 952490
2c| Upper support for HR cell| 4103238| 9a| Ceiling bushing for electric wiresCeiling feed-through seal| 950445950446| 14d| RJ45 extension cable| 952196
3a 3c| Extract air fan Supply air fan| 4104020| 10a| MyVallox Control panel| 949033| 15c| Connection card| 949038
3f| Air flow control grille| 4104868| 10b| MyVallox Touch control panel| 949090| 16a| LED lightLight fixture frame| 9440302131500
3g| Fan chamber assembly, R Fan chamber assembly, L| 41050494105048| 10d| Front panel assembly white Front panel assembly stainless steel| 21319502131900| 16b| LED power source| 940028
4a| Fine filter for supply air| | 11a| Internal humidity and carbon dioxide sensor| 4107971| | |

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

VALLOX User Manuals

Related Manuals