Carrier 30HXC Controller Retrofit Kit Instructions

June 15, 2024
Carrier

30HXC Controller Retrofit Kit

Product Information

Specifications

  • Product Name: 30HXC Carrier Controller Retrofit ComfortLink
    Series 6

  • Model Number: 30HX70000801

  • Manufacturer: Carrier

  • Country of Origin: USA

Safety Considerations

Installation and servicing of air-conditioning equipment can be
hazardous due to system pressure and electrical components. Only
trained and qualified service personnel should install, repair, or
service air-conditioning equipment.

Untrained personnel can perform basic maintenance functions of
cleaning coils and filters and replacing filters. All other
operations should be performed by trained service personnel.

When working on air-conditioning equipment, observe precautions
in the literature, tags and labels attached to the unit, and other
safety precautions that may apply.

Follow all safety codes. Wear safety glasses and work gloves. It
is important to recognize safety information. This is the
safety-alert symbol . When you see this symbol on the unit and
in instructions or manuals, be alert to the potential for personal
injury.

Warnings

This product can expose you to chemicals including lead and lead
components, which are known to the State of California to cause
cancer and birth defects or other reproductive harm. For more
information, go to www.P65Warnings.ca.gov.

Electrical shock can cause personal injury and death. Shut off
all power to this equipment during installation and service. There
may be more than one disconnect switch. Tag all disconnect
locations to alert others not to restore power until work is
completed.

Caution

UNIT DAMAGE HAZARD This unit uses a microprocessor-based
electronic control system. Do not use jumpers or other tools to
short out components or to bypass or otherwise depart from
recommended procedures. Any short-to-ground of the control board or
accompanying wiring may destroy the electronic modules or
electrical components.

Introduction

This document is to be used in conjunction with the 30HX
Installation Instructions as a supplement. It provides specific
information and instruction for the retrofitting of series 6 and
later ComfortLink controls to Carrier controls.

Required Items

See Table 1 for kit contents and part numbers.

Table 1 — 30HX Carrier Controller Retrofit Kit

30HX70000801

PART NO. DESCRIPTION QTY
2004275074 CIOB Mounting Bracket Assembly 1
2005071674 Remote Connectivity Assembly 1
2005071731 Carrier Controller PIC6 Panel Assembly 1
2004350103 PIC6 Low Voltage Control Schematic – CPM 1
2004275076 PIC6 Low Voltage Control Schematic – CIOBE 1
2004350104 PIC6 Low Voltage Control Schematic – AUX 1
2005097654 Drill Template 1
2004275068 Wire Harness 1
2005092737 Wire Harness 1
2004304262 Wire Harness 1
HY08ZZ045 Ethernet Cable 1
AL56AU166 #8-18 x 1/2 in. Mounting Screws 4

Product Usage Instructions

Retrofit Instructions – Step 1: Remove Power

Shut off all power to the unit before proceeding with the
retrofitting process.

Frequently Asked Questions (FAQ)

Q: Can untrained personnel perform any maintenance functions on

the product?

A: Yes, untrained personnel can perform basic maintenance
functions such as cleaning coils and filters and replacing filters.
However, all other operations should be performed by trained
service personnel.

Q: What should I do if I see the safety-alert symbol?

A: When you see the safety-alert symbol on the unit and in
instructions or manuals, be alert to the potential for personal
injury and follow the specified safety precautions.

30HXC Carrier Controller Retrofit ComfortLink Series 6 and Later

Instructions for Carrier Controller Retrofit Kit
30HX70000801

CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . 1 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 REQUIRED ITEMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 RETROFIT INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . 2 Step 1 — Remove Power . . . . . . . . . . . . . . . . . . . . . . 2 Step 2 — Remove Boards . . . . . . . . . . . . . . . . . . . . . 2 Step 3 — Drill New Holes . . . . . . . . . . . . . . . . . . . . . . 2 Step 4 — Mount Boards . . . . . . . . . . . . . . . . . . . . . . . 5 Step 5 — Connect Harnesses and Wiring . . . . . . . . 7 Step 6 — Replace the Panel Assembly . . . . . . . . . . . 8 Step 7 — Install Remote Connectivity Assembly . . 8 APPENDIX A — CARRIER CONTROLLER SYSTEM
MENU STRUCTURE . . . . . . . . . . . . . . . . . . . . . . . 13 APPENDIX B — 30HXC UNIT CONFIGURATION . . 41
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. It is important to recognize safety information. This is the safety-alert symbol . When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices, which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.

WARNING
This product can expose you to chemicals including lead and lead components, which are known to the State of California to cause cancer and birth defects or other reproductive harm. For more information, go to www.P65Warnings.ca.gov.
WARNING
Electrical shock can cause personal injury and death. Shut off all power to this equipment during installation and service. There may be more than one disconnect switch. Tag all disconnect locations to alert others not to restore power until work is completed.
CAUTION
UNIT DAMAGE HAZARD This unit uses a microprocessor-based electronic control system. Do not use jumpers or other tools to short out components or to bypass or otherwise depart from recommended procedures. Any short-to-ground of the control board or accompanying wiring may destroy the electronic modules or electrical components.
INTRODUCTION
This document is to be used in conjunction with the 30HX Installation Instructions as a supplement. It provides specific information and instruction for the retrofitting of series 6 and later ComfortLink controls to Carrier controls.
REQUIRED ITEMS
You will need the following items: · Safety glasses · Gloves · Power tool with drill · 1/16 in. (.0625 in.) drill bit · 11/64 in. (.164 in.) drill bit · 30HX Carrier Controller Retrofit Kit P/N 30HX70000801.
See Table 1 for kit contents and part numbers

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Catalog No. 04-53300257-01

Printed in U.S.A.

Form No. 30HX-18SI Rev. A

Pg 1

12-23

Replaces: NEW

.
Table 1 — 30HX Carrier Controller Retrofit Kit 30HX70000801

PART NO. 2004275074 2005071674 2005071731 2004350103 2004275076 2004350104 2005097654 2004275068 2005092737 2004304262 HY08ZZ045 AL56AU166

DESCRIPTION CIOB Mounting Bracket Assembly Remote Connectivity Assembly Carrier Controller PIC6 Panel Assembly PIC6 Low Voltage Control Schematic – CPM PIC6 Low Voltage Control Schematic – CIOBE PIC6 Low Voltage Control Schematic – AUX Drill Template Wire Harness Wire Harness Wire Harness Ethernet Cable #8-18 x 1/2 in. Mounting Screws

QTY 1 1 1 1 1 1 1 1 1 1 1 4

RETROFIT INSTRUCTIONS Step 1 — Remove Power
Shut off all power to unit.

WARNING
Electrical shock can cause personal injury and death. Shut off all power to this equipment during installation and service. There may be more than one disconnect switch. Tag all disconnect locations to alert others not to restore power until work is completed.
Step 2 — Remove Boards
1. Remove the Main Base Board (MBB) from the unit shown in Fig. 1. Leave wiring harness in control panel for future use in Step 5.
2. Remove the electronic expansion valve (EXV) board from the unit shown in Fig. 1. Leave wiring harness in control panel for future use in Step 5.
Step 3 — Drill New Holes
1. Attach the drill hole template (P/N 2005097654) in the open location where the MBB and EXV boards used to be, shown in Fig. 1. Drill hole template (P/N 2005097654) has an adhesive backing that will permanently adhere to the panel wall.
2. Using a power tool, drill out the hole pattern shown in Fig. 2. For hole numbers 1-4, use a 1/16 in. (.0625 in.) bit. For hole number 5, use an 11/64 in. (.164 in.) bit.

2

Electronic Expansion Valve (EXV)

Main Base Board (MBB)

3

Fig. 1 — MBB and EXV Board Positions

NOTE: Dimensions are in millimeters [inches].
Fig. 2 — Drill Hole Template (P/N 2005097654) 4

Step 4 — Mount Boards
1. Mount CIOB mounting bracket assembly (P/N 2004275074), shown in Fig. 3, in the recently drilled hole pattern in Step 3.

Align the pre-installed stud on the I/O bracket assembly into hole 5 to hold the assembly in place.
2. Use the 4 provided #8-18 x 1/2 in. mounting screws (P/N AL56AU166) to firmly mount the assembly into place using the 4 mounting holes circled in Fig. 4.

CIOB1 CIOB2

Fig. 3 — I/O Board Bracket Assembly (P/N 2004275074) 5

Mounting Holes
Mounting Holes
Fig. 4 — I/O Board Bracket Assembly Mounting Holes 6

Step 5 — Connect Harnesses and Wiring
1. Connect the harnesses to the corresponding connectors as shown in Fig. 5 and 6. The harnesses connected to the I/O boards will indicate what connectors to plug into the old MBB/EXV connections.
IMPORTANT: Use caution while connecting harnesses as they are similar and could be easily connected improperly.

2. From the pre-wired relays at the top of the panel, connect the black wiring to TB5 and TB2 as labeled on each wire. See callouts for TB5 and TB2 in Fig. 7.

TB5 TB2

Fig. 5 — Harness Connections

Fig. 7 — TB5 and TB2

Fig. 6 — Harness Connection Wires with Labels 7

Step 6 — Replace the Panel Assembly
1. Remove the ComfortLink subpanel assembly shown in Fig. 8 by disconnecting the Navigator from TB3, CB1-9, FUSE 1-2, and SW1-2; keep the screws for installing the Carrier Controller panel assembly.
2. Install Carrier Controller panel assembly (P/N 2005071731) into the place from where the ComfortLink assembly was removed (shown in Fig. 9), using the ComfortLink assembly screws.
3. Connect all wiring for TB3, CB1-9, FUSE 1-2, SW1-2 and I/O Board. I/O Board Bracket Assembly (P/N 2004275074) connections include the Power Input, LEN, and CB6.
ComfortLink Subpanel Assembly

Fig. 8 — Panel Assembly (Navigator, TB3, CB1-9, FUSE 1-2, SW1-2)

Fig. 9 — Carrier Controller Panel Assembly Replacing ComfortLink Assembly
Step 7 — Install Remote Connectivity Assembly
1. Attach the remote connectivity assembly (P/N 2005071674) to the bottom of the Carrier Controller panel assembly (P/N 2005071731) using nuts that are provided on the panel assembly (P/N 2005071731) as shown in Fig. 10 and 11.
2. Connect the harness (P/N 2005092742) to TB4 (120-v power; this is already connected to the Remote Connectivity Assembly) and connect the ethernet cable (P/N HY08ZZ045) to the PIC6 ethernet port J15 to Sierra modem ethernet port.
3. Install harness (P/N 2005092737); this harness connects the AUX board J6 to TB5 and is labeled as such.
4. Harness (P/N 2004275068) can make up to 3 CPM board connections depending on the tonnage of the unit. Disconnect existing plugs (PL1, PL2, PL3) from the CPM boards and replace with new harness plugs (CPM-A1, CPM-A2, CPM-B1).
For additional information please refer to the Carrier Controller control schematic shown in Fig. 12-14.

8

Fig. 10 — Remote Connectivity Assembly (P/N 2005071674)

Fig. 11 — Carrier Controller Panel Assembly (P/N 2005071731)

9

10

From drawing 2004275076

Fig. 12 — Carrier Controller PIC6 (24V) Control Schematic 30HX076-271, CIOB1

11

From drawing 2004275076

Fig. 13 — Carrier Controller PIC6 (24V) Control Schematic 30HX076-271, CIOB2

Fuse Replacement Table

FUSE DESIGNATION

TYPE

VOLTAGE AMPERAGE

FU2

SC-15 600

15

FU4

FNQ-R-1 600

1

NOTES:
1. Field-supplied control conductors to be at least 18 AWG (American Wire Gauge) or larger. The control cabinet should only be used for low voltage field wiring (50-v maximum).
2. Each digital output loop shall be limited to a maximum of 1A AC RMS steady-state at 24 VAC. Light load relay is recommended and the coil voltage of relay is 24 VAC. Power supply shall be provided by customer-fused transformer.
3. Each discrete input loop is powered by internal 24 VAC power supply. Field-optional contacts or switch must have 24 VAC rating. Maximum current is 60 mA. Nominal current is 10 mA. Switches with gold-plated bifurcated contacts are recommended.
4. The analog inputs support 5k/10k NTC thermistors, 0/4-20 mA sensors, and 5 vdc sensors. For details, refer to the Controls, Operations, and Troubleshooting Manual and match with software.
5. Each analog output loop supports 0/4-20 mA or 0/2-10 vdc voltage output. The analog output loop is powered by IOB board. Do not supply external power. For details, refer to the Controls, Operations, and Troubleshooting Manual and match with software.
6. Dry type contact, rated switching load 230 VAC/5A or 24 vdc/5A. 7. Ground shields at signal generating devices. 8. All field interlock contacts must have a minimal rating or 2A at 24 VAC
sealed. 9. If chilled water pump interlock is used, remove jumper across associated
terminal blocks. 10. Factory-installed wiring must meet requirements of UL 60335 / UL 1995;
any field-installed wiring must also follow the appliance codes. All wiring must be rated 75°C.

Fig. 14 — Carrier Controller PIC6 (24V) Control Schematic 30HX076-271, LEN Bus Wiring 12

APPENDIX A — CARRIER CONTROLLER SYSTEM MENU STRUCTURE

SETTING UP THE USER INTERFACE
The Carrier Controller control is a 4.3-inch color touch screen that can quickly display alarms, unit operating status and other information. It supports network connections and language customization (users can choose the display language for controlling parameters). If the display is not used for a long time, it will be black and enter the screen saver state, but the controller is still running, and the operating mode remains unchanged. If the user touches the screen, the screen will be light again and the welcome page will be displayed.

ICON

Table B — Common Buttons

INTERFACE

ICON

Login Interface

INTERFACE

Login: Advanced Access

Exit: Reset user access

Parameter Interface

BUTTONS
See Tables A and B for button details.

Table A — Buttons above the Main Interface

ICON

INTERFACE

ALTERNATE ICON

INTERFACE

Save changes

Cancel changes

Navigation Button

Previous page (when menu exceeds one page)

Next page (when menu exceeds one page)

Home

Back

Main menus

System menus

Not logged in

Logged in

Unit is off No alarm

Unit is running or in standby
Alert
Alarm

Wrencha

Question Marka

NOTE(S): a. This icon appears when the menus are viewed through an internet connection.

SETTINGS
General Features
The Carrier Controller includes a standard 4.3-inch touch screen for system control. Its controls can be operated via a touch screen or a web interface. See “Web Interface” on page 18. The navigation menus for the two connection methods (Carrier Controller user interface and web browser) are the same. Only two web pages can be authorized to be used at the same time. NOTE: Some features are not available when using the web browser interface. The Carrier Controller provide access to the following interfaces: · Main interface · System menu interface · User login interface · Start/Stop interface · Alarm interface · Main menu interface · Configuration menu interface · Maintenance menu interface · Trend visualization interface
Main Interface
The main interface provides an overview of system control, monitoring the evaporator and condenser circuits (Fig. A). It provides the current operating status of the unit, including unit load, condenser and evaporator pump status, and pre-defined set point parameters. The default unit of the parameter is metric. Use the following buttons:
.
Return to the main menu
Go to the Home Screen and access all unit functions

Return to the previous display menu

13

APPENDIX A — CARRIER CONTROLLER SYSTEM MENU STRUCTURE (CONT)
DATE AND TIME INTERFACE The date and time interface allows the user to change the system time, date, summer time, time zone, and other configurations.
Click the Date/Time button to display the Date/Time interface, as shown in Fig. C.

LEGEND 1 — Circuit operation status 2 — Unit load percentage 3 — Setpoint (click to enter the setpoint page after logging in) 4 — Pump running status, click to enter the pump status interface 5 — Evaporator inlet and outlet temperatures 6 — Condenser inlet and outlet temperatures 7 — Unit status information
Fig. A — Main Interface Screen
These screens can display an information message in the band at the bottom:

Message

Status

COMMUNICATION FAILURE!

Equipment controller did not respond while reading the table content.

ACCESS DENIED!

Equipment controller does not allow accessing one of the table data blocks.

LIMIT EXCEEDED!

The value entered exceeds table limits.

Save changes?

Modifications have been made. The web interface waits to confirm exit by pressing Save or Cancel.

Force or Auto command was rejected

HIGHER FORCE IN EFFECT!

by the equipment controller because the interface force level is lower than

the equipment controller’s level.

System Configuration Menu Interface

Press the button at the top right of the main interface to enter
the system configuration menu interface (Fig. B). Through this interface, the user can access software and hardware system information and configuration interface such as CPU load, network configuration, date and time configuration, language and unit system configuration, and brightness configuration.

Fig. C — Date/Time Interface Screen LANGUAGE AND UNIT SYSTEM INTERFACE The language and unit system interface allows the user to select the controller language and change the system metric (imperial or metric) (Fig. D). Access the interface from the System Configuration screen by clicking the Language Units Config button . The selection under this page does not need to be saved. The settings will take effect after exiting the current page.
Fig. D — Language and Unit System Interface

Fig. B — System Configuration Screen 14

APPENDIX A — CARRIER CONTROLLER SYSTEM MENU STRUCTURE (CONT)
NETWORK PORT CONFIGURATION INTERFACE The 4.3-inch controller is equipped with J5 as the Ethernet port eth0 (Fig. E). Users can enter the network interface by clicking the
button in the system menu to modify the IP setting. The default IP address of the eth0 network port is 169.254.1.1.

Fig. G — User Login Screen for Factory Level
For Service Login and Factory Login, scan the QR code and enter the password. See Fig. H and I.

Fig. E — Network Port Configuration Interface

Click the up and down buttons to switch the screen.

When the modification is complete, click to cancel the change.
USER LOGIN INTERFACE

to confirm or

Access the login menu interface by clicking the Login button in the upper right corner of the screen (Fig. F).
NOTE: The setpoint interface, configuration menu, and reset alarm interface in the main menu require the user to log in before they are visible on the touch screen.

Fig. H — Factory Login Screen with QR code

Fig. F — User Login Interface Screen Click the user login button to enter the user login interface (Fig. G). Enter password to get more control option permissions (default password = 11). After the password is entered, click on
the button in the bottom right corner to complete the current
access. Click on the button in the bottom right corner to cancel the current access.

Fig. I — Service Login Screen with QR code
On/Off Screen
UNIT START-UP
With the unit in Local Off mode, press to display the list of operating modes (Fig. J). Select the required mode.

15

APPENDIX A — CARRIER CONTROLLER SYSTEM MENU STRUCTURE (CONT)

Fig. J — Unit Start-up Screen
NOTE: After entering the menu, the current selection mode is the last operating mode.

Local On Local Schedule Network
Remote

Unit is in local control mode and allowed to start.
Unit is in local control mode. It is allowed to start if it is within the occupation period.
Unit is controlled by network commands. It is allowed to start if it is within the occupation period.
Unit is controlled by external commands. It is allowed to start if it is within the occupation period.

UNIT STOP

To stop the unit, press the button. The Confirm Stop button will display, as shown in Fig. K.

Fig. L — Main Menu Interface

GENERAL PARAMETERS
General parameters can be accessed through the general parameter interface (Fig. M). Go to the main menu and click the General Pa-

rameters button

to access the General Parameters screen.

Click the up and down buttons to switch the screen.

Fig. K — Confirm Stop Button Click the Confirm Stop button to confirm that the unit is down or click the Back button to return to the previous display. Once the unit is shut down, return to the main interface. (See “Main Interface” on page 13.).
Main Menu Interface
The main control parameters are accessible through the main menu interface, including general parameters, input and output status (Fig. L). Access the main menu by clicking the main menu
button in the upper left corner of the main interface. (See “Main Interface” on page 13.).

Fig. M — General Parameters Screen
TREND GRAPH INTERFACE The trend interface makes it easy to monitor user- selected parame-
ters (Fig. N). On the main menu, click the trend button to access the trend interface. Select the desired parameter and press Save . After the parameter setting is completed, click the lower right button to enter the trend graph interface (Fig. O).

Fig. N — Trend Interface 16

APPENDIX A — CARRIER CONTROLLER SYSTEM MENU STRUCTURE (CONT)

Click the up and down buttons to switch the screen.

When the modification is complete, click to cancel the change.

to confirm or

Configuration Menu Interface
The configuration menu provides access to a range of user-modifiable parameters, such as pump configuration, schedule menus, and more (Fig. Q). The configuration menu is password protected and is not visible until the user is logged in. (See “User login interface” on page 15.)

Fig. O — Trend Graph Interface

Click the Settings button trend display.

to adjust the set time and date of the

Click

to move the timeline, or click

the beginning or end of the selected period.

to move to

Click the Zoom In button or the Zoom Out button to zoom in or out on the view.
Click the Refresh button to reload the data.
SETPOINT INTERFACE
The setpoint interface provides the function to modify the target setpoint (Fig. P).
NOTE: The setpoint interface requires the user to log in before entering the login, which can be accessed through the main menu, or directly by clicking the setpoint button on the main interface to enter the page.

Fig. Q — Configuration Menu
GENERAL CONFIGURATION INTERFACE Take the General configuration interface as an example (Fig. R).
Click the General Configuration button in the general configuration menu to access the general configuration interface.

Fig. P — Setpoint Interface

Fig. R — General Configuration Interface

Click the up and down buttons to switch the screen.

When the modification is complete, click to cancel the change.

to confirm or

17

APPENDIX A — CARRIER CONTROLLER SYSTEM MENU STRUCTURE (CONT)

TIME SCHEDULE INTERFACE
The time schedule interface is located in the configuration menu. The interface control consists of two schedules. The first (OCCPC02S) is used to control the unit’s power on/off (Fig. S), and the second (OCCPC02S) is used to control the dual setpoint.
Go to the Configuration menu and click the Schedule menu button

Modbus TCP Configuration
For Modbus TCP, set the connection configuration as follows (Fig. T): 1. Set BMS RS485 Port Option to “0”. 2. Set Modbus TCP Enable to “Enable”.

to access the Schedule screen.

Set the schedule; the selected period is displayed by the green

band on the timeline. Click change.

to confirm or

to cancel the

1. Selection of the applicable days for the time schedule 2. Modification of the period start and end schedules 3. Save 4. Cancel 5. Previous period 6. Next period
Fig. S — Setpoint Schedule Screen
Web Interface
Users can connect to the controller using a web browser. Access the Carrier Controller interface by entering the unit IP address in the address bar of web browser. The default IP address of the unit is 169.254.1.1, and the address of the web browser address bar is https://169.254.1.1. This IP address can be modified in the web interface and the address of the web browser address bar should be changed accordingly. NOTE: Only authorize two network interfaces at the same time. NOTE: For safety reasons, the start/stop of the unit cannot be controlled via the network interface. All other operations, including monitoring unit operating parameters or unit configuration, can be achieved through the web interface. For security reasons, the web server is disabled by default. Before using HTTP to activate HTTP connections, make sure your network is protected from malicious attacks and any other security threats. Without comprehensive network security, open access is not available.
IMPORTANT: Carrier does not assume any responsibility or legal liability arising from security breaches.
NOTE: When two users are connected at the same time, neither has priority, and the last modified content is saved in the system.

Fig. T — Modbus TCP Configuration
Modbus RTU Configuration
For Modbus RTU, set the connection configuration as follows (Fig. U): 1. Set BMS RS485 Port Option to “2”. 2. Set Modbus TCP Enable to “Disable”. 3. Set Modbus Server UID to the Modbus Master address. 4. Set Modbus RTU Parity Option to “0”. 5. Set Modbus RTU Stop Bit to “2”. 6. Set Modbus RTU Baudrate to “0”.
Fig. U — Modbus RTU Configuration

18

APPENDIX A — CARRIER CONTROLLER SYSTEM MENU STRUCTURE (CONT)

BACnet IP Configuration

BACnet MS/TP Configuration

For BACnet IP, set the connection configuration as follows (Fig. V):

1. Set BMS Port RS485 Option to “0”.

2. Set BACnet/IP Enable to “Enable”.

3. Set BACnet IP port name to the used port.

4. Set the BACnet Network and Identifier.

5. The IP subnet mask of BACnet client (usually a computer) shall be the same as the subnet mask of chiller controller. When controller initializes BACnet module, the subnet mask of controller IP will be used. For example:

PC IP=172.24.237.249

subnet mask =255.255.254.0

Controller IP=172.24.237.175 subnet mask =255.255.254.0

6. Set ALC Auto ID Scheme to “Disable”.

For BACnet MS/TP, set the connection configuration as follows (Fig. W):
1. Set Port RS485 Option to “1”.
2. Set BACnet/IP Enable to “Disable”.

Fig. W — BACnet MS/TP Configuration
Detailed Menu Structure
The menu structure is shown in Fig. X.

Fig. V — BACnet IP Configuration

Home

Back

Main Menu

SYS Menu

User Login

Main Menu

Start/Stop

Alarm Menu

General Parameters

Temperatures

Pressures

Inputs Status

Outputs Status

Pump Status

Run Times

Mode

Setpoint Table

Configuration Menu
Legend Basic Configuration (no password) User Login visible (password 11)

Trend
Fig. X — Menu Structure 19

APPENDIX A — CARRIER CONTROLLER SYSTEM MENU STRUCTURE (CONT)
MAINMENU Menu
NOTE: Because specific sets may not contain certain features, some parameters may appear in the table that cannot be configured.

ICON

DISPLAYED TEXTa

DESCRIPTION

ASSOCIATED TABLE

General Parameters

General Parameters

GENUNIT

Temperatures

Temperatures

TEMP

Pressures

Pressures

PRESSURE

Inputs Status

Inputs Status

INPUTS

Outputs Status

Outputs Status

OUTPUTS

Pump Status

Pump Status

PUMPSTAT

Run Times

Run Times

RUNTIME

Mode

Modes

MODES

Setpoint Table

Setpoint Table

SETPOINT

Configuration Menu

Configuration Menu

CONFIG

Trendb
NOTE(S): a. Depends on the selected language (English by default). b. The trend menu is displayed as a single image.

Trendings

Trendings

20

APPENDIX A — CARRIER CONTROLLER SYSTEM MENU STRUCTURE (CONT)

GENUNIT — General Parameters

NAME
1 CTRL_TYP
2 unitstat 3 strtstop 4 CHIL_S_S 5 CHIL_OCC 6 min_left 7 loc_occ 8 HEATCOOL
9 HC_SEL
10 SP_SEL 11 SP_OCC 12 CAP_T 13 CAP_A 14 CAP_B

STATUS
0 to 3 0=Local, 1=Network 2=Remote, 3=Local Sched

OFF_ON
DSABLE_ENABLE
NO_YES

NO_YES

0 to 4 0=Cooling, 1=Heating 2=Cool Heat Reclaim 3=Heat Heat Reclaim 4=Heat Reclaim Only
0 to 2 0=Auto, 1=Spt1, 2=Spt2
NO_YES


15 SP

16 CTRL_PNT
17 cpnt_min
18 cpnt_max 19 TOT_CURR 20 CURR_A 21 CURR_B 22 CURR_LIM
23 NEMSTOP
24 DEM_LIM 25 ms_stsp

­40.00 to 93.33 ­40 to 200
­40.00 to 93.33 ­40 to 200
­20.00 to 93.33 ­4 to 200



0 to 4500
0 to 3 0=Local, 1=Network 2=Remote, 3=Local Sched

NOTE(S): a. Depends on the selected language (English by default).

DEFAULT
0
0 OFF DSABLE NO
0 NO 0
0
1
YES 0 0 0
­17.78 0
­17.78 0
­20.00 ­4
67.22 153
0 0 0 0
0
— —

UNIT

— — — — min — —


— % % % °C °F °C °F °C °F °C °F A A A A

— —

DISPLAYED TEXTa
Control Type
Unit Run State Unit Start Stop State Net:Cmd Start/Stop Net:Cmd Occupied Minutes Left To Start Local Schedule Occupied Cooling/Heating Status
Cooling/Heating Select
Setpoint Select Setpoint Occupied? Percent Total Capacity Percent Capacity Cir A Percent Capacity Cir B Current Setpoint
Control Point
Control Point Min Limit
Control Point Max Limit Actual Chiller Current Actual Current Cir A Actual Current Cir B Chiller Current Limit
Control Type

21

APPENDIX A — CARRIER CONTROLLER SYSTEM MENU STRUCTURE (CONT)

TEMP — Temperature

NAME 1 COOL_EWT 2 COOL_LWT 3 COND_EWT 4 COND_LWT 5 SCT_A 6 SST_A 7 SET_A1 8 SET_A2 9 DGT_A1 10 DGT_A2 11 AVGDGT_A 12 CPTMP_A1 13 CPTMP_A2 14 SCT_B 15 SST_B 16 SET_B1 17 SET_B2 18 DGT_B1 19 DGT_B2 20 AVGDGT_B 21 CPTMP_B1 22 CPTMP_B2 23 SPACETMP 24 CHWSTEMP 25 CHWSHEAT

UNIT °C / °F °C / °F °C / °F °C / °F °C / °F °C / °F °C / °F °C / °F °C / °F °C / °F °C / °F °C / °F °C / °F °C / °F °C / °F °C / °F °C / °F °C / °F °C / °F °C / °F °C / °F °C / °F °C / °F °C / °F °C / °F

NOTE(S): a. Depends on the selected language (English by default).

DISPLAYED TEXTa Cooler Entering Fluid Cooler Leaving Fluid Condenser Entering Fluid Condenser Leaving Fluid Saturate Cond Temp Cir A Saturate Evap Temp Cir A Saturate Eco Temp Cir A1 Saturate Eco Temp Cir A2 Disch Gas Temp Cir A1 Disch Gas Temp Cir A2 Average Disch Gas Temp A Motor Temp Cir A1 Motor Temp Cir A2 Saturate Cond Temp Cir B Saturate Evap Temp Cir B Saturate Eco Temp Cir B1 Saturate Eco Temp Cir B2 Disch Gas Temp Cir B1 Disch Gas Temp Cir B2 Average Disch Gas Temp B Motor Temp Cir B1 Motor Temp Cir B2 Optional Space Temp Sys Chilled Water Supply Sys Heated Water Supply

PRESSURE — Pressures

NAME 1 DP_A 2 SP_A 3 OP_A1 4 OP_A2 5 DOP_A1 6 DOP_A2 7 ECOP_A1 8 ECOP_A2 9 DP_B 10 SP_B 11 OP_B1 12 OP_B2 13 DOP_B1 14 DOP_B2 15 ECOP_B1 16 ECOP_B2

UNIT kPa / PSI kPa / PSI kPa / PSI kPa / PSI kPa / PSI kPa / PSI kPa / PSI kPa / PSI kPa / PSI kPa / PSI kPa / PSI kPa / PSI kPa / PSI kPa / PSI kPa / PSI kPa / PSI

NOTE(S): a. Depends on the selected language (English by default).

Discharge Pressure A Suction Pressure A Oil Pressure A1 Oil Pressure A2 Oil Pressure Diff A1 Oil Pressure Diff A2 Eco Pressure A1 Eco Pressure A2 Discharge Pressure B Suction Pressure B Oil Pressure B1 Oil Pressure B2 Oil Pressure Diff B1 Oil Pressure Diff B2 Eco Pressure B1 Eco Pressure B2

DISPLAYED TEXTa

22

APPENDIX A — CARRIER CONTROLLER SYSTEM MENU STRUCTURE (CONT)

INPUTS — Inputs Status

NAME 1 ONOFF_SW 2 HC_SW 3 SETP_SW 4 LIM_SW1 5 LIM_SW2 6 OIL_L_A 7 OIL_L_B 8 PWR_A 9 PWR_B 10 SP_RESET 11 LIM_ANAL 12 REM_LOCK 13 ICE_SW 14 OCC_OVSW 15 HP_SW_A1 16 HP_SW_A2 17 HP_SW_B1 18 HP_SW_B2 19 CURRE_A1 20 CURRE_A2 21 CURRE_B1 22 CURRE_B2 23 EMSTOP 24 TQ_TMP_A 25 TQ_RES_A 26 TQ_POS_A 27 TQ_TMP_B 28 TQ_RES_B 29 TQ_POS_B

STATUS OFF_ON COOL_HEAT OPEN_CLOSE OPEN_CLOSE OPEN_CLOSE OPEN_CLOSE OPEN_CLOSE OPEN_CLOSE OPEN_CLOSE — — OPEN_CLOSE OPEN_CLOSE OPEN_CLOSE OPEN_CLOSE OPEN_CLOSE OPEN_CLOSE OPEN_CLOSE — — — — OPEN_CLOSE — — 0 to 100 — — 0 to 100

NOTE(S): a. Depends on the selected language (English by default).

DEFAULT OFF COOL OPEN OPEN OPEN OPEN OPEN OPEN OPEN 0 0 OPEN OPEN OPEN OPEN OPEN OPEN OPEN 0 0 0 0
CLOSE 0 0 0 0 0 0

UNIT — — — — — — — — — mA mA — — — — — — — A A A A — — — % — — %

DISPLAYED TEXTa Remote On/Off Switch Remote Heat/Cool Switch Remote Setpoint Switch Limit Switch 1 Limit Switch 2 Oil Level Input A Oil Level Input B Power Feedback Input A Power Feedback Input B Reset SP 4-20mA Sgnl Limit 4-20mA Signal Remote Interlock Ice Done Storage Switch Occupied Override Switch High Pressure Switch A1 High Pressure Switch A2 High Pressure Switch B1 High Pressure Switch B2 Compressor A1 Current Compressor A2 Current Compressor B1 Current Compressor B2 Current Unit Emergency Switch TQ FB Temperature Cir A TQ FB Resistance Cir A TQ Position Cir A TQ FB Temperature Cir B TQ FB Resistance Cir B TQ Position Cir B

23

APPENDIX A — CARRIER CONTROLLER SYSTEM MENU STRUCTURE (CONT)

OUTPUTS — Outputs Status

NAME 1 CP_A1 2 OILSL_A1 3 LDR_1_A1 4 LDR_2_A1 5 MC_1_A1 6 MC_2_A1 7 CP_A2 8 OILSL_A2 9 LDR_1_A2 10 LDR_2_A2 11 MC_1_A2 12 MC_2_A2 13 OILPMP_A 14 ALARM_A 15 WTVAL_A 16 SHUNT_A 17 TQ_CMD_A 18 CP_B1 19 OILSL_B1 20 LDR_1_B1 21 LDR_2_B1 22 MC_1_B1 23 MC_2_B1 24 CP_B2 25 OILSL_B2 26 LDR_1_B2 27 LDR_2_B2 28 MC_1_B2 29 MC_2_B2 30 OILPMP_B 31 ALARM_B 32 WTVAL_B 33 SHUNT_B 34 TQ_CMD_B 35 CAPT_010 36 RUN 37 ALARM 38 ALERT 39 SHUTDOWN 40 ELECBFAN

STATUS OFF_ON OFF_ON OFF_ON OFF_ON OFF_ON OFF_ON OFF_ON OFF_ON OFF_ON OFF_ON OFF_ON OFF_ON OFF_ON NORMAL_ALARM 0 to 100 OFF_ON 0 to 100 OFF_ON OFF_ON OFF_ON OFF_ON OFF_ON OFF_ON OFF_ON OFF_ON OFF_ON OFF_ON OFF_ON OFF_ON OFF_ON NORMAL_ALARM 0 to 100 OFF_ON 0 to 100 — OFF_ON OFF_ON OFF_ON OFF_ON OFF_ON

NOTE(S): a. Depends on the selected language (English by default).

DEFAULT OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF
NORMAL 0
OFF 0
OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF NORMAL
0 OFF
0 0 OFF OFF OFF OFF OFF

UNIT — — — — — — — — — — — — — — % — % — — — — — — — — — — — — — — % — % V — — — — —

DISPLAYED TEXTa Comp Start Relay A1 Oil Solenoid Output A1 Loader 1 Output A1 Loader 2 Output A1 Motor Cool 1 Output A1 Motor Cool 2 Output A1 Comp Start Relay A2 Oil Solenoid Output A2 Loader 1 Output A2 Loader 2 Output A2 Motor Cool 1 Output A2 Motor Cool 2 Output A2 Oil Pump Output Cir A Alarm Relay State Cir A Water Valve Pos Cir A Shunt Trip Output A TQ PWM Cmd Cir A Compressor Start Relay B Oil Solenoid Output B1 Loader 1 Output B1 Loader 2 Output B1 Motor Cool 1 Output B1 Motor Cool 2 Output B1 Comp Start Relay B2 Oil Solenoid Output B2 Loader 1 Output B2 Loader 2 Output B2 Motor Cool 1 Output B2 Motor Cool 2 Output B2 Oil Pump Output Cir B Alarm Relay State Cir B Water Valve Pos Cir B Shunt Trip Output B TQ PWM Cmd Cir B Chiller Capacity Run Relay State Alarm Relay State Alert Relay State Shutdown Relay State Electrical Box Fan

PUMPSTAT — Pump Status

NAME 1 SET_FLOW 2 CPUMP_1 3 CPUMP_2 4 ROTCPUMP 5 COOLFLOW 6 HPUMP_1 7 HPUMP_2 8 ROTHPUMP 9 CONDFLOW 10 flow_ok

STATUS NO_YES OFF_ON OFF_ON NO_YES OPEN_CLOSE OFF_ON OFF_ON NO_YES OPEN_CLOSE NO_YES

NOTE(S): a. Depends on the selected language (English by default).

DEFAULT NO OFF OFF NO
OPEN OFF OFF NO CLOSE NO

24

UNIT — — — — — — — — — —

DISPLAYED TEXTa Cooler Flow SP Out Cooler Pump #1 Cmd Cooler Pump #2 Cmd Rotate Cooler Pumps ? Cooler Flow SW Status Condenser Pump #1 Cmd Condenser Pump #2 Cmd Rotate Condenser Pumps? Condenser Flow Switch Flow Switch Has Set OK?

APPENDIX A — CARRIER CONTROLLER SYSTEM MENU STRUCTURE (CONT)

RUNTIME — Run Times

NAME 1 HR_MACH 2 st_mach 3 hr_cp_a1 4 st_cp_a1 5 hr_cp_a2 6 st_cp_a2 7 hr_cp_b1 8 st_cp_b1 9 hr_cp_b2 10 st_cp_b2 11 hr_cpum1 12 hr_cpum2 13 hr_hpum1 14 hr_hpum2 15 lst_cpa1 16 lst_cpa2 17 lst_cpb1 18 lst_cpb2 19 lsp_cpa1 20 lsp_cpa2 21 lsp_cpb1 22 lsp_cpb2 23 lr_cp_a1 24 lr_cp_a2 25 lr_cp_b1 26 lr_cp_b2 27 s_cp_a1 28 s_cp_a2 29 s_cp_b1 30 s_cp_b2 31 s_cir_a 32 s_cir_b

STATUS — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — —

NOTE(S): a. Depends on the selected language (English by default).

DEFAULT 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

UNIT hours
— hours
— hours
— hours
— hours
— hours hours hours hours min min min min min min min min min min min min sec sec sec sec sec sec

DISPLAYED TEXTa Machine Operation Time Machine Starts Number Compressor A1 Hours Compressor A1 Starts Compressor A2 Hours Compressor A2 Starts Compressor B1 Hours Compressor B1 Starts Compressor B2 Hours Compressor B2 Starts Cooler Pump #1 Hours Cooler Pump #2 Hours Cond Pump #1 Hours Cond Pump #2 Hours Comp A1 Last Start Time Comp A2 Last Start Time Comp B1 Last Start Time Comp B2 Last Start Time Comp A1 Last Stop Time Comp A2 Last Stop Time Comp B1 Last Stop Time Comp B2 Last Stop Time Comp A1 Last Run Time Comp A2 Last Run Time Comp B1 Last Run Time Comp B2 Last Run Time Comp A1 On Seconds Comp A2 On Seconds Comp B1 On Seconds Comp B2 On Seconds Cir A On Seconds Cir B On Seconds

25

APPENDIX A — CARRIER CONTROLLER SYSTEM MENU STRUCTURE (CONT)

MODES — Modes

NAME 1 m_state 2 shut_nor 3 shut_rcy 4 shut_alm 5 str_rdy 6 str_rcy 7 rcysh_cm 8 nrysh_cm 9 fst_act 10 spt2_act 11 rst_act 12 dem_act 13 ramp_act 14 alm_act 15 over_act 16 fail_a1 17 fail_a2 18 fail_b1 19 fail_b2 20 fail_a 21 fail_b 22 cpmprot 23 cpmpprs 24 hpmprot 25 hpmpprs 26 dly_min 27 slv_act 28 ice_act 29 ice_term 30 ice_rcy 31 sp_used 32 cprun_a1 33 cprun_a2 34 cprun_b1 35 cprun_b2 36 cirrun_a 37 cirrun_b 38 currp_a1 39 currp_a2 40 currp_b1 41 currp_b2 42 pref_a1 43 pref_a2 44 pref_b1 45 pref_b2

STATUS 0 to 3
NO_YES NO_YES NO_YES NO_YES NO_YES NO_YES NO_YES NO_YES NO_YES NO_YES NO_YES NO_YES NO_YES NO_YES
0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 0 to 2 NO_YES NO_YES NO_YES NO_YES 0 to 15 NO_YES NO_YES 0 to 1 NO_YES 0 to 2 NO_YES NO_YES NO_YES NO_YES NO_YES NO_YES 0 to 100 0 to 100 0 to 100 0 to 100 0 to 2 0 to 2 0 to 2 0 to 2

NOTE(S): a. Depends on the selected language (English by default).

DEFAULT 0 NO NO NO NO NO NO NO NO NO NO NO NO NO NO 0 0 0 0 0 0 NO NO NO NO 1 NO NO 0 NO 0 NO NO NO NO NO NO 0 0 0 0 0 0 0 0

UNIT — — — — — — — — — — — — — — — — — — — — — — — — — min — — — — — — — — — — — % % % % — — — —

DISPLAYED TEXTa Machine State Normal Shutdown Recycle Shutdown Alarm Shutdown Startup Ready Recycle Startup Recycle Shutdown Done NonRecycle Shutdown Done Fast Loading Active Second Setpoint In Use Setpoint Reset In Effect Demand Limit Active Ramp Loading Unit Alarm Active Override Active Compressor A1 Fail Compressor A2 Fail Compressor B1 Fail Compressor B2 Fail Circuit A Fail Circuit B Fail Cooler Pump Rotation Cooler Pump Period Start Cond Pump Rotation Cond Pump Period Start Actual Off to On Delay Master Slave Active Ice Building Ice Build Terminated Ice Build Recy Startup Current SetPoint Used Comp A1 is running Comp A2 is running Comp B1 is running Comp B2 is running Circuit A is running Circuit B is running Comp A1 Current Per Comp A2 Current Per Comp B1 Current Per Comp B2 Current Per Prelub Pump Fail A1 Prelub Pump Fail A2 Prelub Pump Fail B1 Prelub Pump Fail B2

26

APPENDIX A — CARRIER CONTROLLER SYSTEM MENU STRUCTURE (CONT)

SETPOINT — Setpoint Table

1 csp1

NAME

2 csp2

3 ice_sp

4 cramp_sp

5 hsp1

6 hsp2

7 hramp_sp

8 mc_sp

9 w_sct_sp
10 lim_sp1 11 lim_sp2 12 lim_sp3
13 hr_sp

14 hr_db

STATUS
­28.89 to 26.00 ­20 to 78.8
­28.89 to 26.00 ­20 to 78.8
­28.89 to 26.00 ­20 to 78.8
0.11 to 11.11 0.2 to 20
26.67 to 76.67 80 to 170
26.67 to 76.67 80 to 170
0.11 to 11.11 0.2 to 20
37.78 to 121.11 100 to 250
26.67 to 60.00 80 to 140
0 to 100
0 to 100
0 to 100
30.00 to 63.00 86 to 145.4
1.00 to 10.00 1.8 to 18

NOTE(S): a. Depends on the selected language (English by default).

DEFAULT
6.67 44
6.67 44
6.67 44
0.56 1
37.78 100
37.78 100
0.56 1
75.00 167
40.00 104
100
100
100
50.00 122
5.00 9

UNIT
°C °F
°C °F
°C °F
°C °F
°C °F
°C °F
^C ^F
°C °F
°C °F
%
%
%
°C °F
°C °F

DISPLAYED TEXTa Cooling Setpoint 1 Cooling Setpoint 2 Cooling Ice Setpoint Cooling Ramp Loading Heating Setpoint 1 Heating Setpoint 2 Heating Ramp Loading Motor Temp Setpoint Water Val Condensing Stp Switch Limit Setpoint 1 Switch Limit Setpoint 2 Switch Limit Setpoint 3 Heat Recovery Setpoint HR Setpoint Deadband

27

APPENDIX A — CARRIER CONTROLLER SYSTEM MENU STRUCTURE (CONT) CONFIG Menu

ICON

DISPLAYED TEXTa
General Configuration

DESCRIPTION
General Configuration

ASSOCIATED TABLE
GEN_CONF

Pump Configuration

Pump Configuration

PUMPCONF

Reset Configuration

Reset Configuration

RESETCFG

Schedule Menu

Schedule Menu

SCHEDULE

Holiday Menu

Holiday Menu

HOLIDAY

Broadcast Menu
NOTE(S): a. Depends on the selected language (English by default).

Broadcast Menu

GENCONF — General Configuration

NAME
1 prio_cir
2 ewt_opt 3 seq_typ 4 ramp_sel 5 cramp_sp
6 hramp_sp 7 off_on_d
8 lim_sel
9 ice_buil 10 shortcyc 11 curr_ful 12 curr_sel

STATUS
0 to 2 0=Auto, 1=A Prio 2=B Prio
NO_YES
NO_YES
NO_YES
0.11 to 1.11 0.2 to 2
0.11 to 1.11 0.2 to 2
1 to 15
0 to 2 0 = None 1 = Switch Control 2 = 4-20mA Control
NO_YES
NO_YES

DSABLE_ENABLE

NOTE(S): a. Depends on the selected language (English by default).

DEFAULT
0
NO NO NO 0.56 1 0.56 1 1
0
NO NO 100 DSABLE

UNIT

— — — ^C ^F ^C ^F min

— — — —

BROADCAST
DISPLAYED TEXTa Cir Priority Sequence Entering Fluid Control Staged Loading Sequence Ramp Loading Select Cold Ramp Setpoint Heat Ramp Setpoint Unit Off to On Delay Demand Limit Type Select Ice Mode Enable short cycle management Full Current Limit Value Current Limit Select

28

APPENDIX A — CARRIER CONTROLLER SYSTEM MENU STRUCTURE (CONT)

PUMPCONF — Pump Configuration

NAME
1 hpumpseq
2 cpumpseq
3 pump_del 4 pump_per 5 pump_loc 6 stopheat 7 stopcool

STATUS
0 to 4 0 = No Pump 1 = One Pump Only 2 = Two Pumps Auto 3 = Pump#1 Manual 4 = Pump#2 Manual
0 to 4 0 = No Pump 1 = One Pump Only 2 = Two Pumps Auto 3 = Pump#1 Manual 4 = Pump#2 Manual
24 to 3000
DSABLE_ENABLE
DSABLE_ENABLE
DSABLE_ENABLE
DSABLE_ENABLE

NOTE(S): a. Depends on the selected language (English by default).

DEFAULT
0
0
48 DSABLE ENABLE DSABLE DSABLE

RESETCFG — Reset Configuration

NAME
1 cr_sel
2 hr_sel
3 dt_cr_no 4 dt_cr_fu 5 v_cr_no 6 v_cr_fu 7 spacr_no 8 spacr_fu 9 cr_deg 10 dt_hr_no 11 dt_hr_fu 12 v_hr_no 13 v_hr_fu 14 spahr_no 15 spahr_fu 16 hr_deg

STATUS
0 to 4 0=None, 1=Delta 2=4-20mA Control 3=Space Temp Cooling
0 to 4 0=None, 1=Delta 2=4-20mA Control 3=Space Temp Cooling
0.00 to 13.89 0 to 25
0.00 to 13.89 0 to 25
0 to 20
0 to 20
­10.00 to 51.67 14 to 125
­10.00 to 51.67 14 to 125
­16.67 to 16.67 ­30 to 30
0.00 to 13.89 0 to 25
0.00 to 13.89 0 to 25
0 to 20
0 to 20
­10.00 to 51.67 14 to 125
­10.00 to 51.67 14 to 125
­16.67 to 16.67 ­30 to 30

NOTE(S): a. Depends on the selected language (English by default).

DEFAULT
0
0
0.00 0
0.00 0 0 0
­10.00 14
­10.00 14 0.00 0 0.00 0 0.00 0 0 0
­10.00 14
­10.00 14 0.00 0

UNIT —

DISPLAYED TEXTa
Condenser Pumps Sequence


hours — — — —

Cooler Pumps Sequence
Pump Auto Rotation Delay Pump Sticking Protection Flow Checked If Pump Off Cooler Pump Off In Heat Cond Pump Off In Cool

UNIT


^C ^F ^C ^F mA mA °C °F °C °F ^C ^F ^C ^F ^C ^F mA mA °C °F °C °F °C °F

DISPLAYED TEXTa
Cooling Reset Select
Heating Reset Select
Delta T No Reset Value Delta T Full Reset Value Current No Reset Value Current Full Reset Value Space T No Reset Value Space T Full Reset Value Cooling Reset Deg. Value Delta T No Reset Value Delta T Full Reset Value Current No Reset Value Current Full Reset Value Space T No Reset Value Space T Full Reset Value Heating Reset Deg. Value

29

APPENDIX A — CARRIER CONTROLLER SYSTEM MENU STRUCTURE (CONT)

SCHEDULE — Schedule Menu

ICON

NAME

Time schedule 1OCCPC01S

Time schedule 2OCCPC02S

NOTE(S): a. Depends on the selected language (English by default).

DISPLAYED TEXTa Unit start/stop schedule Unit setpoint schedule

HOLIDAY — Holiday Menu

ICON

NAME

HOLDY_01

HOLDY_02

HOLDY_03

HOLDY_04

HOLDY_05

HOLDY_06

HOLDY_07

HOLDY_08

HOLDY_09

HOLDY_10

HOLDY_11

HOLDY_12

HOLDY_13

HOLDY_14

HOLDY_15

HOLDY_16

NOTE(S): a. Depends on the selected language (English by default).

DISPLAYED TEXTa Holiday 1 Holiday 2 Holiday 3 Holiday 4 Holiday 5 Holiday 6 Holiday 7 Holiday 8 Holiday 9 Holiday 10 Holiday 11 Holiday 12 Holiday 13 Holiday 14 Holiday 15 Holiday 16

BROADCAST — Broadcast Configuration

STATUS DEFAULT DISPLAYED TEXTa

DESCRIPTION

0 to 2

2

Activate

Broadcast: 0 = Broadcast disabled 1 = Holidays, OAT and time/date broadcast 2 = Stand-alone OAT broadcast (daylight saving time and holiday determined without broadcasting through the bus)

OAT Broadcast

0 to 239

0

Bus

Bus number of the unit with outdoor temperature sensor

0 to 239

0

Element

Element number of the unit with outdoor temperature sensor

disable/enable disable Daylight Savings Select Summer/winter time activation (daylight saving selection)

Daylight Savings Select ­ Summer time (entering)

1 to 12

3

Month

Month

1 to 7

7

Day of Week (1=Monday) Day of the week (1 = Monday)

1 to 5

5

Week Number of Month Week of the month

Daylight Savings Select ­ Winter time (leaving)

1 to 12

10

Month

Month

1 to 7

7

Day of Week (1=Monday) Day of the week (1 = Monday)

1 to 5

5

Week Number of Month Week of the month

NOTE(S): a. Depends on the selected language (English by default).

30

APPENDIX A — CARRIER CONTROLLER SYSTEM MENU STRUCTURE (CONT) ALARMS Menu

ICON

DISPLAYED TEXTa

DESCRIPTION

ASSOCIATED TABLE

Reset Alarms

Reset Alarms

ALARMRST

Current Alarms

Current Alarms

CUR_ALM

Alarm Historic

Alarm Historic

ALMHIST1

Major Alarm Historic

Major Alarm Historic

NOTE(S): a. Depends on the selected language (English by default).

ALARMRST — Reset Alarms

NAME 1 RST_ALM 2 ALM 3 alarm_1c 4 alarm_2c 5 alarm_3c 6 alarm_4c 7 alarm_5c 8 alarm_1 9 alarm_2 10 alarm_3 11 alarm_4 12 alarm_5

STATUS 0 to 1 0 to 0 0 to 0 0 to 0 0 to 0 0 to 0 0 to 0 0 to 0 0 to 0 0 to 0 0 to 0 0 to 0

NOTE(S): a. Depends on the selected language (English by default).

DEFAULT 0 0 0 0 0 0 0 0 0 0 0 0

UNIT — — — — — — — — — — — —

ALMHIST2
DISPLAYED TEXTa Alarm Reset Alarm State Current Alarm 1 Current Alarm 2 Current Alarm 3 Current Alarm 4 Current Alarm 5 Jbus Current Alarm 1 Jbus Current Alarm 2 Jbus Current Alarm 3 Jbus Current Alarm 4 Jbus Current Alarm 5

31

APPENDIX A — CARRIER CONTROLLER SYSTEM MENU STRUCTURE (CONT)

CONTROL OPERATION
This section identifies important control functions such as unit start and stop, cooling control, and more. It also describes how to perform key operations of the control system.
Start/Stop Control
Table C summarizes the unit control type and stop or go status with regard to the following parameters.
· Operating type: this is selected using the start/stop button on the front of the user interface.
LOFF Local off
L-C Local on
L-SC Local schedule
REM Remote
CCN CCN Network
· Remote start/stop contacts: these contacts are used when the unit is in remote operating type (Remote).
· CHIL_S_S: this network command relates to the unit start/stop when the unit is in network mode.
· Start/Stop schedule: occupied or unoccupied status of the unit as determined by the unit start/stop program (Schedule 1).
· Network emergency shutdown: if this CCN or BACnet/IP (option) command is activated, it shuts the unit down whatever the active operating type.

· CCN emergency shutdown: if this CCN command is activated, it shuts the unit down whatever the active operating type.
· General alarm: the unit is totally stopped due to failure.
Unit Stop Function
This function controls the unit compressor capacity reduction. If there is an alarm or a demand to stop it forces the compressors to the minimum capacity before stopping them.
This stop sequence is not followed if there is a unit protection alarm such as “water heat exchanger frost protection” or “low saturated suction temperature”.
Evaporator Water Pump Control
The unit can control the evaporator water pump. The pump is turned on when this option is configured (see PUMPCONF configuration sub-menu) and when the unit is in one of the on modes described above or in delay mode. Since the minimum value for the delay at start-up is 1 minute (configurable between 1 and 15 minutes), the pump will run for at least one minute before the first compressor starts.
The pump is kept running for 20 seconds after the unit goes to stop mode. It is turned off if the unit is shut down due to an alarm, unless the fault is a frost protection fault.
The control provides a means to automatically start the pump each day at 14.00 for 2 seconds when the unit is off. Starting the pump periodically for a few seconds increases the lifetime of the pump bearings and the tightness of the pump seal.

Table C — Unit Control Type and Status

ACTIVE OPERATING TYPE

LOFF L-C L-SC REM CCN MAST CHIL_S_S

————

————

— — — — Active —

Off

— — — — Active —

— — — — — Active Off

— Active

— — — — Active —

On

— — — — — Active On

Active — — — — —

— — Active — — —

— Active

— Active — — — —

— — Active — — —

— Active

— — — Active — —

— — — Active — —

— Active

— Active

— — — Active — —

— Active

REMOTE START/ STOP CONTACT
— — — — — — — — — — — — — — Open — Open — Closed Closed

PARAMETER STATUS

MASTER CONTROL
TYPE

START-STOP TIME SCHEDULE

Unoccupied

CCN

CCN

Unoccupied

Occupied

CCN

Occupied

Unoccupied

Local

Unoccupied

Occupied

Local

Occupied

Unoccupied

Remote

Remote

Unoccupied

Occupied

Remote

Occupied

CCN EMERGENCY SHUTDOWN
Active — — — — —
Disabled Disabled
— — — Disabled Disabled Disabled — — — — Disabled Disabled

GENERAL ALARM
— Yes — — — — No No — — — No No No — — — — No No

CONTROL UNIT TYPE MODE

Off

Off

CCN

Off

CCN

Off

CCN

Off

CCN

Off

CCN

On

CCN

On

Local

Off

Local

Off

Local

Off

Local

On

Local

On

Local

On

Remote Off

Remote Off

Remote Off

Remote Off

Remote On

Remote On

32

APPENDIX A — CARRIER CONTROLLER SYSTEM MENU STRUCTURE (CONT)

Condenser Water Pump Control

ACTIVE SETPOINT

Control of the condenser water pump is the same as for the evaporator water pump. See “Evaporator Water Pump Control” on page 32. There is only one condenser pump.
Control Point
The control point represents the water temperature that the unit must satisfy.
In cooling mode the evaporator outlet water is controlled by default, but the evaporator inlet water can also be controlled (requires a Service configuration modification).
In heating mode the condenser outlet water is controlled by default, but the condenser inlet water can also be controlled (requires a Service configuration modification).
Control point = active setpoint + reset.

Two setpoints can be selected. Usually, the second cooling setpoint is used for unoccupied periods. Depending on the current operation type, the active setpoint can be selected by choosing the item in the table Status Genunit, with the volt-free user contacts, with network commands or with the setpoint timer program (schedule 2).
Table D summarizes the possible selections depending on the control types (local, remote or network) and the following parameters:
· Setpoint select in local control: item “Setpoint select” in the table Status Genunit permits selection of the active setpoint, if the unit is in local operating type.
· Control contacts 2: status of control contact 2.
· Schedule 2 status: schedule for setpoint selection.

LOCAL OPERATING MODE
HEATING/COOLING OPERATING MODE
Cooling Cooling Cooling Cooling Cooling Cooling Heating Heating Heating Heating

Table D — Active Setpoint

LOCAL SETPOINT SELECTION
csp 1 csp 2 auto auto auto auto hsp 1 hsp 2 auto auto

PARAMETER STATUS
ICE STORAGE CONFIGURATIONa
— — Activated Activated — Deactivated — — — —

ICE STORAGE CONTACT STATUSa — — Open Closed
— — — — —

REMOTE OPERATING MODE

PARAMETER STATUS

HEATING/COOLING OPERATING MODE

LOCAL SETPOINT SELECTION

ICE STORAGE CONFIGURATIONa

Cooling Cooling Cooling Cooling Cooling Cooling Heating Heating NETWORK OPERATING MODE

csp control — — — — — — —

— — — Activated Activated Activated — —
PARAMETER STATUS

HEATING/COOLING OPERATING MODE

LOCAL SETPOINT SELECTION

ICE STORAGE CONFIGURATIONa

Cooling Cooling Cooling Cooling Heating Heating

Activated

Activated

NOTE(S): a. Only with energy management option.

ICE STORAGE CONTACT STATUSa — — — — Open Closed — —
ICE STORAGE CONTACT STATUSa — — Open Closed — —

SCHEDULE 2 STATUS — —
Unoccupied Unoccupied
Occupied Unoccupied
— — Occupied Unoccupied
CONTROL CONTACT 2
— csp 1 (open) csp 2 (closed)
Open Closed Closed Open Closed
CONTROL CONTACT 2
Occupied Unoccupied Unoccupied Unoccupied Occupied Unoccupied

ACTIVE SETPOINT
Cooling setpoint 1 Cooling setpoint 2 Ice storage setpoint Cooling setpoint 2 Cooling setpoint 1 Heating setpoint 2 Heating setpoint 1 Heating setpoint 2 Heating setpoint 1 Heating setpoint 2
ACTIVE SETPOINT
Control setpoint Cooling setpoint 1 Cooling setpoint 2 Cooling setpoint 1 Ice storage setpoint Cooling setpoint 2 Heating setpoint 1 Heating setpoint 2
ACTIVE SETPOINT
Cooling setpoint 1 Cooling setpoint 2 Ice storage setpoint Cooling setpoint 2 Heating setpoint 1 Heating setpoint 2

33

APPENDIX A — CARRIER CONTROLLER SYSTEM MENU STRUCTURE (CONT)

RESET
Reset means the active setpoint is modified so that less machine capacity is required (in cooling mode the setpoint is increased, in heating mode it is decreased). This modification is in general a reaction to a drop in the load. For the Carrier Controller control system, the reset source can be configured in the menu Status RESETCFG: it can be based on the outdoor temperature (gives a measure of the load trends for the building) or used with the energy management option at the reset setpoint. In response to a drop in the space temperature or to a drop in T, the cooling setpoint is normally reset upwards to optimize unit performance.

In the three cases the reset parameters, i.e. slope, source and maximum value, are configurable in the Setpoint menu.
Reset is a linear function based on three parameters:
· A reference at which reset is zero (space temperature or T – no reset value).
· A reference at which reset is maximum (space temperature or T – full reset value).
· The maximum reset value.
See Fig. Y.

Fig. Y — Reset Example in Cooling Mode for the Space Temperature
LEGEND A — Maximum reset value B — Space temperature for zero reset C — Space temperature for maximum reset D — Building load

34

APPENDIX A — CARRIER CONTROLLER SYSTEM MENU STRUCTURE (CONT)

Demand Limit
Generally, demand limit is used by an energy management system in order to restrict the unit electricity consumption.
The PIC6 control system for 30HX provides two methods of demand limit:
· By reference to a limiting signal from a user-controlled volt-free contact: the capacity of the unit cannot exceed the demand limit setpoint (which can be modified in the Setpoints menu) when the limit contact is closed.
· By reference to an external 0-10 vdc signal: the capacity of the unit cannot exceed the demand limit imposed by this external signal. It is a linear function and its parameters are configurable in the User1 menu (voltages at 0% limitation and 100% of limitation). This function is not available if Reset by reference to an external 0-10 vdc signal has already been selected.
Whatever the method used, demand limit is active in all operating types: Local, Remote or CCN. However, in Local operating type, demand limit can be disabled and in CCN operating type, demand limit can be controlled directly with the aid of CCN commands.
NOTE: A limitation value of 100% means that the unit may call upon the full array of its capacity stages.
Figure Z is an example of demand limit by an external 0-10 vdc signal. This example assumes that the limitation parameters are such that at 0 volt the authorized capacity shall be maximum capacity, and at 10 volts the authorized capacity shall be zero (this is the default configuration).
Capacity Control
This function adjusts the compressor capacity to keep the heat exchanger water temperature at its setpoint. The control system

continuously takes account of the temperature error with respect to the setpoint, as well as the rate of change in this error and the difference between entering and leaving water temperatures, in order to determine the optimum moment at which to add or withdraw capacity.
In addition, the high pressure or low pressure unloading functions can also affect the temperature control accuracy.
Compressors are started in a sequence designed to equalize the number of start-ups (value weighted by their operating time).
Saturated Condensing Temperature Control
Saturated condensing temperature control is assured if the threeway valve option is selected. The saturated condensing temperature is controlled based on a fixed setpoint that can be configured by via the SETPOINT table. The three-way valve control can be configured by the service department via the SERVICE table.
Determining the Lead Circuit
This function commands the start/stop sequence of the two refrigerant circuits called A and B. The circuit authorized to start first is the lead circuit. Three methods can be configured by the user in the Configuration menu:
· Auto mode: the control system determines the lead circuit so as to equalize the number of starts on each circuit (value weighted by the operating times of each circuit). Thus, the circuit with the least number of starts is always given precedence to start. The lead circuit is stopped last.
· Circuit A as leader: Circuit A is always the lead circuit. It is the first to start and the last to stop.
· Circuit B as leader: Circuit B is always the lead circuit. It is the first to start and the last to stop.

Fig. Z — Demand Limit by 0-10 vdc Signal 35

APPENDIX A — CARRIER CONTROLLER SYSTEM MENU STRUCTURE (CONT)

Circuit Loading Sequence

High Current Load Shedding Function

Two circuit loading sequences are available. The choice of sequence can be configured by the user in the Configuration menu
· Balanced circuit loading: If this sequence is selected, the control system tries to keep the capacity of circuits A and B equal as the total load on the unit increases or decreases.
· Loading with priority given to one circuit: If this sequence is selected, the control system loads the lead circuit completely before the second circuit starts up. When there is a demand limit, the second circuit is unloaded first.
IMPORTANT: 30HX units use 06N twin screw compressors. The screw compressor efficiency is better at full load than at part load. By default, the ‘close control’* configuration is not validated, and the control will always try to optimize unit efficiency.

  • Temperature precision has priority over compressor capacity. This parameter is only accessible to Carrier Service.
    Compressor Start-Up Sequence in One Circuit
    The first compressor to start is the one with the least number of start-ups and operating hours. If both compressors are operating and the load decreases, the compressor that started first shuts down. This avoids cycling of the same compressor.
    EXV Control
    The electronic expansion valves (EXVs) control charging and the refrigerant flow in the evaporator, maintaining the optimum evaporator throttle and a correct discharge superheat. Opening the valve permits reduction of the throttle, and thus improves the heat exchange in the evaporator. This opening can be limited to maintain the condenser subcooling and correct superheat, avoiding liquid slugging at the compressors and ensuring operating stability.
    Motor Cooling Valve Control
    The temperature of the motor windings is controlled to a setpoint of 82°C. This is achieved by cycling of the motor cooling valves to allow the liquid refrigerant to flow across the motor windings, if necessary. On units equipped with economizers with plate heat exchangers, a thermostatic valve controls the necessary refrigerant flow entering this heat exchanger and continuously flowing over the motor windings. All refrigerant used for motor cooling returns to the rotors through an orifice situated mid-way along the compression cycle and is compressed to the discharge pressure.
    Head Pressure Control on Water-Cooled Units
    The saturated condensing temperature is controlled by reference to a user- definable fixed setpoint.
    This temperature is maintained by using the valve to control the flow of water in each condenser circuit.
    High Pressure Load Shedding Function
    This function does not require an additional board. It prevents high pressure breaks on a circuit by the following means:
    · Preventing any capacity increase on the circuit once the high-pressure value has reached an initial threshold.
    · Shedding one or more capacity stages once a second protection threshold has been reached.
    In the event of capacity stages being shed, no capacity increase will be authorized on the circuit for a period of 5 minutes.
    NOTE: The last capacity stage cannot be shed by this protection function. An alarm is activated if the high pressure is still too high.

This function does not require an additional board. It prevents high current breaks on each compressor by the following means:
· Preventing any capacity increase on the compressor once the high current value has reached an initial threshold
· Shedding one or more capacity stages once a second protection threshold has been reached.
In the event of capacity stages being shed, no capacity increase will be authorized on the circuit for a period of 5 minutes.
Start-up Procedure — Prelubrication
This procedure describes the necessary procedures to ensure the lubrication of the compressor before start-up.
The control follows the sequence below:
For the lead compressor (the first compressor in the circuit to start):
1. Start the oil pump and measure the initial oil pressure.
2. Wait approximately 30 seconds.
3. Verify the oil solenoid valve tightness. – If oil pressure increases and the solenoid valve is not open, the oil solenoid valve failure alarm is activated and prelubrication is stopped. The procedure is aborted. – If not, the oil solenoid valve is activated.
4. Wait approximately 15 seconds.
5. If oil pressure increases, prelubrication is assured and the compressor can start.
6. If not, a further prelubrication cycle is started. Return to point 1.
NOTE: After three cycles, the low oil pressure alarm at pre-startup is activated, and prelubrication is also stopped.
For the lag compressor (one compressor in the circuit is already in operation).
1. Activate the oil solenoid valve.
2. Wait approximately 15 seconds.
3. If oil pressure increases, prelubrication is assured and the compressor can now start.
4. If not, the low oil pressure at start-up alarm is activated and the prelubrication is also stopped.
Time Schedule Function
The control includes two-time schedules.
The first schedule (schedule 1 OCCPC01S) allows automatic changeover of the unit from occupied to unoccupied mode: the unit is started during occupied periods.
The second schedule (schedule 2 OCCPC02S) allows automatic change of the active setpoint (if auto mode is selected) from the occupied setpoint to the unoccupied setpoint.
Cooling or heating setpoint 1 is active during occupied periods. Cooling or heating setpoint 2 is active during unoccupied periods.
Each time schedule consists of eight user configurable periods. Each of these periods can be validated as active or not active for each day of the week as well as for holiday periods. The day begins at 00:00 and ends at 23:59.
The schedule is in unoccupied mode unless a time period is active. If two periods coincide or are active on the same day, priority is given to the unoccupied period. Each of the eight periods can be displayed and modified using a sub-menu.The following table shows how to configure a period. The method is the same for time schedule 1 and 2.

36

APPENDIX A — CARRIER CONTROLLER SYSTEM MENU STRUCTURE (CONT)

SCHEDULE MENU
This function is used to define the start/stop time schedule and the setpoint selection time schedule.

· Operating status, compressors A and B · Unit completely stopped · Unit in operation

Name

Description

SCHEDULE1 Unit start/stop time schedule

SCHEDULE2 Unit setpoint selection time schedule

HOLIDAYS MENU

This function is used to define 16 holiday periods. Each period is defined by three parameters: month, start day and holiday period duration. During the holiday periods the controller is in occupied or unoccupied mode, depending on the periods validated as holidays. Each of these holiday periods can be displayed or modified using a sub-menu.

IMPORTANT: The Broadcast function must be active for the holiday function to operate, even if the unit is in autonomous mode (not connected to the CCN network).

Black Box Function
The Carrier Controller registers the values of around 20 predefined variables every 5 seconds. If an operation alarm appears, the control saves a data set of 180 registrations (168 preceding the alarm and 12 following it), for a duration of 15 minutes of unit operation.
Each registration is associated with a time schedule defined in hours, minutes and seconds. The control can store a maximum of 20 data sets in the memory. If the threshold of 20 data sets is reached, a rotary registration mechanism is triggered (a new data set deletes the oldest data set). The data sets can be recovered by a Carrier service technician, using the Carrier Pro-View tool that permits downloading them to a PC and later deleting them from the unit.
DIAGNOSTICS – TROUBLESHOOTING

Name

Description

HOLDY_01

Holiday period 1

HOLDY_02

Holiday period 2

HOLDY_03

Holiday period 3

HOLDY_04

Holiday period 4

HOLDY_05

Holiday period 5

HOLDY_06

Holiday period 6

HOLDY_07

Holiday period 7

HOLDY_08

Holiday period 8

HOLDY_09

Holiday period 9

HOLDY_10

Holiday period 10

HOLDY_11

Holiday period 11

HOLDY_12

Holiday period 12

HOLDY_13

Holiday period 13

HOLDY_14

Holiday period 14

HOLDY_15

Holiday period 15

HOLDY_16

Holiday period 16

Energy Management Option

This option requires the installation of an additional SIOB-BASE EMM type board. This board permits access to the following functions:

· Reset via 4-20 mA control.

· Ice storage contact: if ice storage control has been config-
ured (Configuration Menu General Configuration), this contact permits activation of the ice storage setpoint.

· User safety loop input: this contact is used for the customer safety loops that require a unit shut-down if it is closed.

· Occupancy control time schedule override contact: if this contact is closed, the unit enters the occupied mode for a configurable override time of 1 to 4 hours.

· Condenser water flow input.

· Demand limit setpoint contact and output.

This option also permits display of the following data:

· Current unit capacity via 0-10 vdc output

The Carrier Controller has many fault tracing aid functions. The local interface and its various menus give access to all unit operating conditions. If an operating fault is detected, an alarm is activated and an alarm code is stored in the Alarms menu, sub-menus “Reset alarms” and “Current alarm”.
Email Notification
The control system can define one or two recipients and notify the recipient by email whenever a new alarm occurs or resets all currently existing alarms. NOTE: Email notifications can only be set by a Carrier service technician.
Alarm Display
The control system quickly displays the status of the unit (Fig. AA). Once the alarm is activated, the icon clock on the touch screen lights up and shakes. · The LED flashes and shakes to indicate that the loop
is running, but there is a warning. · The indicator light is steady red and shakes to indi-
cate that the circuit has stopped due to a malfunction.
Fig. AA — Alarm Display

37

APPENDIX A — CARRIER CONTROLLER SYSTEM MENU STRUCTURE (CONT)

Click the button at the top right of the interface to enter the alarm information and alarm reset interface (Fig. AB).

A manual reset must be run from the Carrier Controller interface or the web via the “Reset alarms” menu, item RST_ALM. Alarm reset can be protected by a basic user level password.
NOTE: The reset alarm menu can only display up to the current 5 active unit alarm codes. The alarm can only be reset after the user has logged in.
Access the reset alarm menu (Fig. AD) by clicking the alarm but-

ton and selecting Reset Alarm .

Fig. AB — Alarm Information/Alarm Reset Interface
Current Alarm
The current alarm interface lists the currently active alarms, including the date and time the alarm occurred (Fig. AC). The controller displays up to 10 current alarms. Access the currently active alarm list by tapping alarm button
and selecting current alarm in the upper right corner of the screen. The current alarm screen displays.

Fig. AD — Reset Alarm Menu
Alarm History
The alarm history menu is divided into the last 50 alarms and the alarm information that has been resolved by the last 50 main alarm stores (Fig. AE). · Normal alarms are used to indicate pump failure, sensor
failure, network connection problems, etc. · Primary alarms are used to indicate process failure.
To access the alarm history menu, click alarm button and then
select either Alarm History or Primary Alarm History .

Fig. AC — Current Alarm Screen
Resetting Alarms
When the cause of the alarm has been corrected, the alarm can be reset either automatically on return to normal, or manually when action has been taken on the unit, depending on the type. Alarms can be reset even if the unit is running, service login is required.
This means that an alarm can be reset without stopping the machine. In the event of a power supply interrupt, the unit restarts automatically without the need for an external command. However, any faults active when the supply is interrupted are saved and may in certain cases prevent a circuit or a unit from restarting.

Fig. AE — Alarm History
Alarm Codes
Table E lists the general alarm codes.

38

APPENDIX A — CARRIER CONTROLLER SYSTEM MENU STRUCTURE (CONT)
Table E — Alarm Codes

ALARM ALARM NUMBER CODE

DESCRIPTION OF THE ALARM TEXT

RESET TYPE

1 15010 Sensor Fault-Cooler Entering Fluid Thermistor

Automatic if the temperature measured by the sensor returns to normal.

2 15020 Sensor Fault-Cooler Leaving Fluid Thermistor

As above

3 15030 Sensor Fault-Condenser Entering Fluid Thermistor

As above

4 15040 Sensor Fault-Condenser Leaving Fluid Thermistor

As above

5 15050 Sensor Fault-Out Door Temperature Thermistor

As above

6 15061 Sensor Fault-Master/Slave Cooled Fluid Thermistor

As above

7 15062 Sensor Fault-Master/Slave Heated Fluid Thermistor

As above

8 15073 Sensor Fault-Compressor A1 Discharge Gas Thermistor As above

9 15074 Sensor Fault-Compressor A2 Discharge Gas Thermistor As above

10 15075 Sensor Fault-Compressor B1 Discharge Gas Thermistor As above

11 15076 Sensor Fault-Compressor B2 Discharge Gas Thermistor As above

12 15081 Sensor Fault-Circuit A Motor Cooling TQ Feedback

As above

13 15082 Sensor Fault-Circuit B Motor Cooling TQ Feedback

As above

14 12011 Sensor Fault-Circuit A Discharge Transducer

Automatic, if the sensor measurement value returns to normal.

15 12012 Sensor Fault-Circuit B Discharge Transducer

As above

16 12021 Sensor Fault-Circuit A Suction Transducer

As above

17 12022 Sensor Fault-Circuit B Suction Transducer

As above

18 12033 Sensor Fault-Compressor A1 Oil Pressure Transducer As above

19 12034 Sensor Fault-Compressor A2 Oil Pressure Transducer As above

20 12035 Sensor Fault-Compressor B1 Oil Pressure Transducer As above

21 12036 Sensor Fault-Compressor B2 Oil Pressure Transducer As above

22 12043 Sensor Fault-Compressor A1 Eco Pressure Transducer As above

23 12044 Sensor Fault-Compressor A2 Eco Pressure Transducer As above

24 12045 Sensor Fault-Compressor B1 Eco Pressure Transducer As above

25 12046 Sensor Fault-Compressor B2 Eco Pressure Transducer As above

26 12051 Sensor Fault-Cir A Reclaim Pumpdown Press Transducer As above

27 12052 Sensor Fault-Cir B Reclaim Pumpdown Press Transducer As above

28 4013 Loss Communication With TCPM Board Number 1

Automatic, if communication is restored

29 4014 Loss Communication With TCPM Board Number 2

As above

30 4015 Loss Communication With TCPM Board Number 3

As above

31 4016 Loss Communication With TCPM Board Number 4

As above

32 4021 Loss Communication With SIOB Board Number 1

As above

33 4022 Loss Communication With SIOB Board Number 2

As above

34 4023 Loss Communication With SIOB EMM Board

As above

35 4051 Loss Communication With AUX Board Number 1

As above

36 4052 Loss Communication With AUX Board Number 2

As above

37 10020 Process Fault-Customer Interlock Failure

Automatic, if triggered during a shutdown

38 10030 Process Fault-Unit is in CCN Emergency Stop

As above

39 10040 No Factory Configuration

As above

40 10050 Factory Configuration Error

As above

41 10061 Process Fault-Circuit A High Discharge Pressure

As above

42 10062 Process Fault-Circuit B High Discharge Pressure

As above

43 10073 Process Fault-Compressor A1 Oil Solenoid

Automatic, if the same alarm has not tripped during the last 24 hours

44 10074 Process Fault-Compressor A2 Oil Solenoid

As above

45 10074 Process Fault-Compressor B1 Oil Solenoid

As above

46 10076 Process Fault-Compressor B2 Oil Solenoid

As above

47 10083 Process Fault-Prestart Compressor A1 Oil Pressure

As above

48 10084 Process Fault-Prestart Compressor A2 Oil Pressure

As above

49 10085 Process Fault-Prestart Compressor B1 Oil Pressure

As above

50 10086 Process Fault-Prestart Compressor B2 Oil Pressure

As above

51 10091 Process Fault-Circuit A Low Oil level

Manual

52 10092 Process Fault-Circuit B Low Oil level

Manual

53 10101 Process Fault-Circuit A Low SST

Manual

54 10102 Process Fault-Circuit B Low SST

Manual

55 10111 Process Fault-Circuit A High SST

Manual

56 10112 Process Fault-Circuit B High SST

Manual

57 10121 Process Fault-Circuit A Low DSH Temperature

Automatic, if the same alarm has not tripped during the last 24 hours

58 10122 Process Fault-Circuit B Low DSH Temperature

As above

59 10133 Process Fault-Comp A1 High Discharge Temperature Manual

60 10134 Process Fault-Comp A2 High Discharge Temperature Manual

61 10135 Process Fault-Comp B1 High Discharge Temperature Manual

62 10136 Process Fault-Comp B2 High Discharge Temperature Manual

63 10143 Process Fault-Comp A1 Max Oil Filter Diff Pressure

Manual

64 10144 Process Fault-Comp A2 Max Oil Filter Diff Pressure

Manual

65 10145 Process Fault-Comp B1 Max Oil Filter Diff Pressure

Manual

66 10146 Process Fault-Comp B2 Max Oil Filter Diff Pressure

Manual

39

APPENDIX A — CARRIER CONTROLLER SYSTEM MENU STRUCTURE (CONT)
Table E — Alarm Codes (cont)

ALARM ALARM NUMBER CODE

DESCRIPTION OF THE ALARM TEXT

RESET TYPE

67 10163 Process Fault-Compressor A1 Low Oil Pressure

Automatic, if the same alarm has not tripped during the last 24 hours

68 10164 Process Fault-Compressor A2 Low Oil Pressure

As above

69 10165 Process Fault-Compressor B1 Low Oil Pressure

As above

70 10166 Process Fault-Compressor B2 Low Oil Pressure

As above

71 10170 Process Fault-Cooler Freeze Protection

As above

72 10181 Process Fault-Circuit A Condenser Freeze Protection

Manual reset when saturated exhaust temperature is greater than 40°F; automatic reset in general

73 10182 Process Fault-Circuit B Condenser Freeze Protection

As above

74 10090 Process Fault-Master/Slave Communication Failure

Automatic

75 10211 Process Fault-Cooler Pump #1 Fault

Manual

76 10212 Process Fault-Cooler Pump #2 Fault

Manual

77 10190 Process Fault-Cooler Flow Switch Failure

Manual

78 10221 Process Fault-Condenser Pump #1 Fault

Manual

79 10222 Process Fault-Condenser Pump #2 Fault

Manual

80 10200 Process Fault-Condenser Flow Switch Failure

Manual

81 10263 Process Fault-Compressor A1 High Current

Automatic

82 10264 Process Fault-Compressor A2 High Current

Automatic

83 10265 Process Fault-Compressor B1 High Current

Automatic

84 10266 Process Fault-Compressor B2 High Current

Automatic

85 10160 Process Fault-System Pump Failure

Automatic

86 10271 Process Fault-Circuit A Stop Fault

Manual

87 10272 Process Fault-Circuit B Stop Fault

Manual

88 10280 Process Fault-Water Exchanger Temp Sensors Swapped Manual

89 11031 Process Fault-Compressor A High Press SW protection Manual

90 11032 Process Fault-Compressor B High Press SW protection Manual

91 11040 Process Fault-Heat Reclaim Flow Switch Failure

Manual

92 11050 Process Fault-Unit Is In Emergency Stop

Manual

40

APPENDIX B — 30HXC UNIT CONFIGURATION
Table F — Menu Options

MENU

MENU ITEM

Options

TONNAGE 76 86 96 106 116 126 136 146 171 186 206 246 261 271

0=Auto

Cir Priority Sequence

1=A Prio

00000000000000

2=B Prio

Entering Fluid Control

No/Yes

No

Staged Loading Sequence

No/Yes

No

Ramp Loading Select

No/Yes

No

Cold Ramp Setpoint

Default=1

11111111111111

General

Heat Ramp Setpoint

Default=1

11111111111111

Configuration Unit Off to On Delay

Default=1

11111111111111

0=None

Demand Limit Type Select

1=Switch Control 2=4-20mA

0

0

0

0

0

0

0

0

0

0

0

0

0

0

Control

Ice Mode Enable

No/Yes

No

Short Cycle Management

No/Yes

No

Full Current Limit Value

Default=100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

Current Limit Select

Disable/Enable

Disable

41

APPENDIX B — 30HXC UNIT CONFIGURATION (CONT)
Table F — Menu Options (cont)

MENU

MENU ITEM

Options

TONNAGE 76 86 96 106 116 126 136 146 171 186 206 246 261 271

Unit Type

0=Cool Only 1=Heat Mach 2=Air Cooled

0 or 0 or 0 or 0 or 0 or 0 or 0 or 0 or 0 or 0 or 0 or 0 or 0 or 0 or 11111111111111

0=YLC

Factory Select

1=MTL

22222222222222

2=CLT

Unit Size

Variousa

76 86 96 106 116 126 136 146 171 186 206 246 261 271

Comp A1 Must Trip Amps

Variousa

unit specific

Comp A2 Must Trip Amps

Variousa

0000000000

unit specific

Comp B1 Must Trip Amps

Variousa

unit specific

Comp B2 Must Trip Amps

Various

00000000000000

0=None

VFD Option

1=Dnfoss 2=STEP

00000000000000

3=INOVANCE

0=Mueller

Circuit A EXV Type

Unipolar

0 or 0 or 0 or 0 or 0 or 0 or 0 or 0 or 0 or 0 or 0 or 0 or 0 or 0 or

1=Mueller Bipolar 1 1 1 1 1 1 1 1 1 1 1 1 1 1

2=ETS

0=Mueller

Circuit B EXV Type

Unipolar

0 or 0 or 0 or 0 or 0 or 0 or 0 or 0 or 0 or 0 or 0 or 0 or 0 or 0 or

1=Mueller Bipolar 1 1 1 1 1 1 1 1 1 1 1 1 1 1

2=ETS

Refrigerant Type

0=R134a 1=R515b 2=R513a

0 or 0 or 0 or 0 or 0 or 0 or 0 or 0 or 0 or 0 or 0 or 0 or 0 or 0 or 22222222222222

Factory

Factory Password

113

113 113 113 113 113 113 113 113 113 113 113 113 113 113

Parameters Mini Load Valve Select Disable/Enable

Disable

Cooler Pass Number

1 or 2

unit specific

0= No

Economizer

Economizer Select 1=TQ Ctrl w/o Kitb

unit specific

2=TQ Ctrl w/ Kit

3=TXV Control

TQ with Feebback

No/Yes

No

Cooler LWT On Circuit A

No/Yes

No

Max Compressor Frequency

60

60 60 60 60 60 60 60 60 60 60 60 60 60 60

Power Supply Voltage

Various

unit specific

Soft Starter Select

No/Yes

No

Wye Delta Start Select

No/Yesa

unit specific

0=None

1=4-20mA

2=0-10V

Cond Water Valve Opt

3=20-4mA 4=10-0V

00000000000000

5=2-10V

6=0-20mA

7=20-0mA

Cond Temp Sensor Option Disable/Enable

Disable

Energy Management Module

Disable/Enable

Disable

Master Slave Option

Disable/Enable

Disable

Heat Reclaim Option Disable/Enable

Disable

42

APPENDIX B — 30HXC UNIT CONFIGURATION (CONT)
Table F — Menu Options (cont)

MENU
Service Parameters

MENU ITEM
Cooler Fluid Type
Condenser Fluid Type
Flow Switch Setpoint Brine Freeze Setpoint Brine Minimum Fluid Temp Maximum Condensing
Temp Max Condensing Temp Diff
Capa Close Control Opt
Comp Sequence Sel
Z Multipier For SMZ Maximum Current Setpoint
Maximum Current Diff Head Pressure Diff Timer
Head Pressure Diff EXV Offset Circuit A EXV Offset Circuit B
Atmospheric Pressure
Swift Restart Selection EWT Probe On Cir A Side
Country Code VFD Auto Config Enable CIOB Debug Log Level
Brine Max Pos Offset Pmp 1 Service Time Cfg Pmp 2 Service Time Cfg HeatPmp Service Time Cfg Wfliter Service Time Cfg Ofil Service Time Cfg A1 Ofil Service Time Cfg A2 Ofil Service Time Cfg B1 Ofil Service Time Cfg B2

Options
0=WATER 1=BRINE
2=Low 3=Super Low
0=WATER 1=BRINE
2=Low 3=Super Low
0 Default=34 Default=38
Default=122
Default=5 Disable/Enable
0=Auto 1=Comp 1 Lead 2=Comp 2 Lead
Default=1 Default=80 Default=10 Default=90 Default=9 Default=0 Default=0
Default=14.69
Disable/Enable No/Yes
Default=86 Disable/Enable
0 Default=15
0 0 0 0 0 0 0 0

TONNAGE 76 86 96 106 116 126 136 146 171 186 206 246 261 271
00000000000000
00000000000000
00000000000000 34 34 34 34 34 34 34 34 34 34 34 34 34 34 38 38 38 38 38 38 38 38 38 38 38 38 38 38
122 122 122 122 122 122 122 122 122 122 122 122 122 122
55555555555555 Disable
00000000000000
11111111111111 80 80 80 80 80 80 80 80 80 80 80 80 80 80 10 10 10 10 10 10 10 10 10 10 10 10 10 10 90 90 90 90 90 90 90 90 90 90 90 90 90 90 99999999999999 00000000000000 00000000000000 14.6 14.6 14.6 14.6 14.6 14.6 14.6 14.6 14.6 14.6 14.6 14.6 14.6 14.6 99999999999999
Disable Yes
11111111111111 Enable
00000000000000 15 15 15 15 15 15 15 15 15 15 15 15 15 15 00000000000000 00000000000000 00000000000000 00000000000000 00000000000000 00000000000000 00000000000000 00000000000000

NOTE(S):
a. Please refer to Table G on page 44 and Table H on page 45 for specific configuration details. b. The TQ valve is not available in North America.

43

Unit Size 76 86 96 106 116 126 136 146 161 171 186 206 246 261 271

APPENDIX B — 30HXC UNIT CONFIGURATION (CONT)
Table G — Wye Delta Start Select = No (XL Starter)

Power Supply Voltage 575 380 460
380/415 575 380 460
380/415 575 380 460
380/415 575 380 460
380/415 575 380 460
380/415 575 380 460
380/415 575 380 460
380/415 575 380 460
380/415 575 380 460
380/415 575 380 460
380/415 575 380 460
380/415 575 380 460
380/415 575 380 460
380/415 575 380 460
380/415 575 380 460
380/415

Comp A1 Must Trip Amps 54 82 68 86 66 100 82 104 80 122 102 126 98 148 122 152 98 148 122 152 98 148 122 152 118 178 146 184 118 178 146 184 128 194 160 200 106 162 134 164 128 194 160 200 106 162 134 164 128 194 160 200 128 194 160 200 128 194 160 200

Comp A2 Must Trip Amps 0
0
0
0
0
0
0
0
0
0
0 60 90 74 92 88 134 110 136 106 162 134 164 128 194 160 200

Comp B1 Must Trip Amps 54 82 68 86 54 82 68 86 54 82 68 86 54 82 68 86 66 100 82 104 80 122 102 126 80 122 102 126 98 148 122 152 88 134 110 136 128 194 160 200 128 194 160 200 128 194 160 200 128 194 160 200 128 194 160 200 128 194 160 200

44

Unit Size 76 86 96 106 116 126 136 146

APPENDIX B — 30HXC UNIT CONFIGURATION (CONT)
Table H — Wye Delta Start Select = Yes (Wye-Delta Starter)

Power Supply Voltage 575 380 230
208/230 460 230
380/415 575 380 230
208/230 460 230
380/415 575 380 230
208/230 460 230
380/415 575 380 230
208/230 460 230
380/415 575 380 230
208/230 460 230
380/415 575 380 230
208/230 460 230
380/415 575 380 230
208/230 460 230
380/415 575 380 230
208/230 460 230
380/415

Comp A1 Must Trip Amps 54 82 136 152 68 142 86 66 100 166 184 82 174 104 80 122 202 224 102 210 126 98 148 246 272 122 252 152 98 148 246 272 122 252 152 98 148 246 272 122 252 152 118 178 294 326 146 306 184 118 178 294 326 146 306 184

Comp A2 Must Trip Amps 0 0 0 0 0 0 0 0

Comp B1 Must Trip Amps 54 82 136 152 68 142 86 54 82 136 152 68 142 86 54 82 136 152 68 142 86 54 82 136 152 68 142 86 66 100 166 184 82 174 104 80 122 202 224 102 210 126 80 122 202 224 102 210 126 98 148 244 272 122 252 152

45

Unit Size 161 171 186 206 246 261 271

APPENDIX B — 30HXC UNIT CONFIGURATION (CONT)
Table H — Wye Delta Start Select = Yes (Wye-Delta Starter) (cont)

Power Supply Voltage 575 380 230
208/230 460 230
380/415 575 380 230
208/230 460 230
380/415 575 380 230
208/230 460 230
380/415 575 380 230
208/230 460 230
380/415 575 380 230
208/230 460 230
380/415 575 380 230
208/230 460 230
380/415 575 380 230
208/230 460 230
380/415

Comp A1 Must Trip Amps 128 194 318 354 160 330 200 106 162 266 296 134 272 164 128 194 318 354 160 330 200 106 162 266 296 134 272 164 128 194 318 354 160 330 200 128 194 318 354 160 330 200 128 194 318 354 160 330 200

Comp A2 Must Trip Amps
0
0
0
60 90 150 166 74 154 92 88 134 220 244 110 226 136 106 162 266 296 134 272 164 128 194 318 354 160 330 200

Comp B1 Must Trip Amps 88 134 220 244 110 226 136 128 194 318 354 160 330 200 128 194 318 354 160 330 200 128 194 318 354 160 330 200 128 194 318 354 160 330 200 128 194 318 354 160 330 200 128 194 318 354 160 330 200

46

© 2023 Carrier

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Catalog No. 04-53300257-01

Printed in U.S.A.

Form No. 30HX-18SI Rev. A

Pg 48

12-23

Replaces: NEW

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals