SONBEST SM7901V Carrier Plate Probe Noise Module User Manual
- June 15, 2024
- SONBEST
Table of Contents
SM7901V
Carrier plate probe noise module
User Manual
File Version: V23.12.2
SM7901V Carrier Plate Probe Noise Module
SM7901V using the standard ,easy access to PLC,DCS and other instruments or systems for monitoring noise state quantities.The internal use of high- precision sensing core and related devices to ensure high reliability and excellent long-term stability, can be customized RS232, RS485, CAN, 4-20mA, DC0~5V\10V, ZIGBEE, Lora, WIFI, GPRS and other output methods.
Technical Parameters
Technical parameter | Parameter value |
---|---|
Brand | SONBEST |
Noise range | 30~130dB |
Noise accuracy | ±3% |
Interface | RS485/TTL/DC0-3V |
Power | DC5V 1A |
Running temperature | -30~85℃ |
Working humidity | 5%RH~90%RH |
Product Selection
Product DesignRS485, TTL, DC0-3V Multiple output methods, the products are divided into the following models depending on the output method.
Product model | output method |
---|---|
SM7901B | RS485 |
SM7901TTL | TTL |
Product Size
Wiring mode
PIN Definition
GND | Power supply negative |
---|---|
AD | Voltage output |
TXD | TTLsent |
RXD | TTL receives |
5V | Power supply positive pole |
5V | Power supply positive pole |
In the case of broken wires, wire the wires as shown in the figure. If the product itself has no leads, the core color is for reference.
How to use?
Used for environmental noise, workplace noise, construction noise, traffic
noise and social noise and other noise detection and measurement
Application solution
■ TTL application scheme
■ DCO-3V application
Product List
Communication Protocol
The product uses RS485 MODBUS-RTU standard protocol format, all operation or reply commands are hexadecimal data. The default device address is 1 when the device leaves the factory, and the m odule or NON-Recorder default baud rate is 9600,8,n,1 ,but data recorder default baud rate is 115200.
1. Read data (function code 0x03)
Inquiry frame (hexadecimal), sending example: query 1 data of 1# device, the
upper computer sends the command: 01 03 00 00 00 01 84 0A .
Address | Function Code | Start Address | Data Length | Check Code |
---|---|---|---|---|
01 | 03 | 00 00 | 00 01 | 84 0A |
For the correct query frame, the device will respond with data: 01 03 02 00 79 79 A6 , response format:
Configuration Address| Register Address| Register Description| Data Type|
Value Range
---|---|---|---|---
40001| 00 00| noise| Read Only| 0~65535
40101| 00 64| Model Code| Read/Write| 0~65535
40102| 00 65| total number of measuring points| read/write| 1~20
Data description: The data in the command is hexadecimal, take data 1 as an
example, 00 79 is converted to decimal value as 121, assuming the data
magnification is 10, the real value is 121/10=12.1, Others and so on.
2. Common data address table
40103 | 00 66 | device address | read/write | 1~249 |
---|---|---|---|---|
40104 | 00 67 | baud rate | read/write | 0~6 |
40105 | 00 68 | communication mode | read/write | 1~4 |
40106 | 00 69 | protocol type | read/write | 1~10 |
3 Read and modify device address
(1) Read or query device address
If you don’t know the current device address and there is only one device on
the bus, you can query the device address through the commandFA 03 00 66 00 01
71 9E .
Device Address | Function Code | Start Address | Data Length | Check Code |
---|---|---|---|---|
FA | 03 | 00 66 | 00 01 | 71 9E |
FA means 250 is the general address, when you don’t know the address, you can
use 250 to get the real device address, 00 66 is the device address register.
For the correct query command, the device will respond, for example, the
response data is: 0 1 03 02 00 01 79 84, and its format parsing is shown in
the following table:
Device Address | Function Code | Start Address | Model Code | Check Code |
---|---|---|---|---|
01 | 03 | 02 | 00 01 | 79 84 |
In the response data, the first byte 01 represents the real address of the
current device.
(2) Change device address
For example, if the current device address is 1 and we want to change it to
02, the command is: 01 06 00 66 00 02 E8 14.
Device Address | Function Code | Register Address | Target Address | Check Code |
---|---|---|---|---|
01 | 06 | 00 66 | 00 02 | E8 14 |
After the change is successful, the device will return the information: 02 06 00 66 00 02 E8 27 , and its format analysis is shown in the following table:
Device Address | Function Code | Register Address | Target Address | Check Code |
---|---|---|---|---|
02 | 06 | 00 66 | 00 02 | E8 27 |
In the response data, after the modification is successful, the first byte is
the new device address.
Generally, after the device address is changed, it will take effect
immediately. At this time, the user needs to change the query command of his
software accordingly.
4 Read and modify baud rate
(1) Read baud rate
The default factory baud rate of the device is 9600. If you need to change it,
you can change it according to the following table and the corresponding
communication protocol. Fo r example, to read the baud rate ID of the current
device, the command is: 01 03 00 67 00 01 35 D5 , the format is parsed as
follows.
Device Address | Function Code | Start Address | Data Length | Check Code |
---|---|---|---|---|
01 | 03 | 00 67 | 00 01 | 35 D5 |
Read the baud rate code of the current device. Baud rate code: 1 is 2400; 2 is
4800; 3 is 9600; 4 is 19200; 5 is 38400; 6 is 115200.
For the correct query command, the device will respond, for example, the
response data is: 01 03 02 00 03 F8 45, and its format analysis is shown in
the following table:
Device Address | Function Code | Data Length | Baud Rate Code | Check Code |
---|---|---|---|---|
01 | 03 | 02 | 00 03 | F8 45 |
According to the baud rate code, 03 is 9600, that is, the baud rate of the
current device is 9600.
(2) Change the baud rate
For example, change the baud rate from 9600 to 38400, that is, change the code
from 3 to 5, the command is: 01 06 00 67 00 05 F8 16.
Device Address | Function Code | Register Address | Target Baud Rate | Check Code |
---|---|---|---|---|
01 | 06 | 00 67 | 00 05 | F8 16 |
Change the baud rate from 9600 to 38400, that is, change the code from 3 to 5. The new baud rate will take effect immediately, and the device will lose response at this time, and the baud rate of the device needs to be checked accordingly Modified.
5 Read and modify correction value
(1) Read correction value
When there is an error between the data and the reference standard, we can
reduce the display error by adjusting the correction value. The correction
difference can be modified in a rang e of plus or minus 1000, that is, the
value range is 0-1000 or 64535 -65535. For example, when the displayed value
is too small by 100, we can correct it by adding 100. The command is: 01 03 00
6B 00 01 F5 D6 . In the command, 100 is hexadecimal 0x64 ;If you need to
reduce it, you can set a negative value, such as -100, the corresponding
hexadecimal value is FF 9C, the calculation method is 100 -65535=65435, and
then converted to hexadecimal, it is 0x FF 9C. Device The correction value
starts from 00 6B. We take the first parameter as an example to illustrate.
When there are multiple parameters, the correction value is read and modified
in the same way.
Device Address | Function Code | Start Address | Data Length | Check Code |
---|---|---|---|---|
01 | 03 | 00 6B | 00 01 | F5 D6 |
For the correct query command, the device will respond, for example, the response data is: 01 03 02 00 64 B9 AF, and its format parsing is shown in the following table:
Device Address | Function Code | Data Length | Correction Value | Check Code |
---|---|---|---|---|
01 | 03 | 02 | 00 64 | B9 AF |
In the response data, the first byte 01 represents the real address of the current device, and 00 6B is the first state correction value register. If the device has multiple parameters, other parameters operate in the same way as this The same, generally temperature and humidity have this parameter, and lighting generally does not have this parameter.
(2) Change the correction value
For example, if the current state is too small, we want to add 1 to its
real value, and add 100 to the current value. The correction operation command
is: 01 06 00 6B 00 64 F9 FD.
Device Address | Function Code | Register Address | Target Address | Check Code |
---|---|---|---|---|
01 | 06 | 00 6B | 00 64 | F9 FD |
After the operation is successful, the device will return the information: 01
06 00 6B 00 64 F9 FD, after the successful change, the parameters will take
effect immediately.
For example, the range is 30~130dB, the analog output is 0~3V DC0-3Vvoltage
signal, noise and DC0-3Vvoltage The calculation relationship is as shown in
the formula: C = (A2-A1) * (X-B1) / (B2-B1) + A1, where A2 is noise range
upper limit, A1 is the lower limit of the range, B2 is DC0 -3Vvoltage output
range upper limit, B1 is the lower limit, X is the currently read noise value,
and C is the calculated DC0-3Vvoltage value. The list of commonly used values
is as follows:
DC0-3Vvoltage(V) | noiseValue (dB) | Calculation Process |
---|---|---|
0 | 30.0 | (130-30)*(0-0)÷(3-0)+30 |
1 | 63.3 | (130-30)*(1-0)÷(3-0)+30 |
2 | 96.7 | (130-30)*(2-0)÷(3-0)+30 |
3 | 130.0 | (130-30)*(3-0)÷(3-0)+30 |
As shown in the above formula, when measuring 1.5V, current DC0-3Vvoltage is
50dB。
Disclaimer
This document provides all information about the product, does not grant any
license to intellectual property, does not express or imply, and prohibits any
other means of granting any intellectual property rights, such as the
statement of sales terms and conditions of this product, other issues. No
liability is assumed. Furthermore, our company makes no warranties, express or
implied, regarding the sale and use of this product, including the suitability
for the specific use of the product, the marketability or the infringement
liability for any patent, copyright or other intellectual property rights,
etc. Product specifications and product descriptions may be modified at any
time without notice.
Contact Us
Company: Shanghai Sonbest Industrial Co., Ltd
Address:Building 8, No.215 North east road, Baoshan District, Shanghai, China
Web: http://www.sonbest.com
Web: http://www.sonbus.com
SKYPE: soobuu
Email: sale@sonbest.com