SONBEST RS485 explosion proof carbon dioxide sensor User Manual

June 5, 2024
SONBEST

RS485 explosion proof carbon dioxide sensor

 SD9770B User Manual http://www.sonbus.com/

SD9770B

RS485 explosion proof carbon dioxide sensor

User Manual

File Version: V21.2.25

SD9770B using the standard RS485 bus MODBUS-RTU protocol,easy access to PLC,DCS and other instruments or systems for monitoring carbon dioxide state quantities.The internal use of  high-precision sensing core and related devices to ensure high reliability and excellent long-term  stability,can be customized RS232,RS485,CAN,420mA,DC0~5V\10V,ZIGBEE,Lora,WIFI,GPRS and  other output methods.

Shanghai Sonbest Industrial Co., Ltd Page1

 SD9770B User Manual http://www.sonbus.com/

 Technical Parameters

Technical parameter

|

Parameter value

---|---

CO2 range

|

0~5000ppm

CO2 accuracy

|

±100ppm

Communication Interface

|

RS485

Default baud rate

|

9600 8 n 1

Power

|

DC9~24V 1A

Display

|

LCD

Running temperature

|

-40~80°C

Working humidity

|

5%RH~90%RH

Product Size

How to wiring?

Shanghai Sonbest Industrial Co., Ltd Page2

 SD9770B User Manual http://www.sonbus.com/

Application solution

Shanghai Sonbest Industrial Co., Ltd Page3

 SD9770B User Manual http://www.sonbus.com/

 How to use?

Communication Protocol

The product uses RS485 MODBUS-RTU standard protocol format, all operation or reply commands  are hexadecimal data. The default device address is 1 when the device is shipped, the default baud rate is  9600, 8, n, 1

1. Read Data (Function id 0x03)

 Inquiry frame (hexadecimal), sending example: Query 1# device 1 data, the host computer sends the

Shanghai Sonbest Industrial Co., Ltd Page4

 SD9770B User Manual http://www.sonbus.com/

command:01 03 00 00 00 01 84 0A .

Device ID

|

Function id

|

Start Address

|

Data Length

|

CRC16

---|---|---|---|---

01

|

03

|

00 00

|

00 01

|

84 0A

For the correct query frame, the device will respond with data:01 03 02 00 79 79 A6 , the resp onse  format is parsed as follows:

Device ID

|

Function id

|

Data Length

|

data 1

|

Check Code

---|---|---|---|---

01

|

03

|

02

|

00 79

|

79 A6

Data Description: The data in the command is hexadecimal. Take data 1 as an example. 00 79 is  converted to a decimal value of 121. If the data magnification is 100, the actual value is 121/100=1.21.  Others and so on.

 2. Data Address Table

Address

|

Start Address

|

Description

|

Data type

|

Value range

---|---|---|---|---

40001

|

00 01

|

carbon dioxide

|

read

|

0~65535

40101

|

00 64

|

model code

|

read/write

|

0~65535

40102

|

00 65

|

total points

|

read/write

|

1~20

40103

|

00 66

|

Device ID

|

read/write

|

1~249

40104

|

00 67

|

baud rate

|

read/write

|

0~6

40105

|

00 68

|

mode

|

read/write

|

1~4

40106

|

00 69

|

protocol

|

read/write

|

1~10

3 read and modify device address

(1) Read or query device address

If you don’t know the current device address and there is only one device on the bus, you can use the  command FA 03 00 64 00 02 90 5F Query device address.

Device ID

|

Function id

|

Start Address

|

Data Length

|

CRC16

---|---|---|---|---

FA

|

03

|

00 64

|

00 02

|

90 5F

FA is 250 for the general address. When you don’t know the address, you can use 250 to get the real  device address, 00 64 is the device model register.

For the correct query command, the device will respond, for example the response data is: 01 03 02  07 12 3A 79, the format of which is as shown in the following table:

Device ID

|

Function id

|

Start Address

|

Model Code

|

CRC16

---|---|---|---|---

01

|

03

|

02

|

55 3C 00 01

|

3A 79

Response should be in the data, the first byte 01 indicates that the real address of the current device is,  55 3C converted to decimal 20182 indicates that the current device main model is 21820, the last two bytes  00 01 Indicates that the device has a status quantity.

(2) Change device address

For example, if the current device address is 1, we want to change to 02, the command is:01 06 00 66  00 02 E8 14 .

Device ID

|

Function id

|

Start Address

|

Destination

|

CRC16

---|---|---|---|---

01

|

06

|

00 66

|

00 02

|

E8 14

After the change is successful, the device will return information: 02 06 00 66 00 02 E8 27 , its format  is parsed as shown in the following table:

Device ID

|

Function id

|

Start Address

|

Destination

|

CRC16

---|---|---|---|---

01

|

06

|

00 66

|

00 02

|

E8 27

Shanghai Sonbest Industrial Co., Ltd Page5

 SD9770B User Manual http://www.sonbus.com/

 Response should be in the data, after the modification is successful, the first byte is the new device  address. After the general device address is changed, it will take effect immediately. At this time, the user  needs to change the query command of the software at the same time.

4 Read and Modify Baud Rate

(1) Read baud rate

The device default factory baud rate is 9600. If you need to change it, you can change it according to  the following table and the corresponding communication protocol. For example, read the current device’s  baud rate ID, the command is:01 03 00 67 00 01 35 D5 , its format is parsed as follows.

Device ID

|

Function id

|

Start Address

|

Data Length

|

CRC16

---|---|---|---|---

01

|

03

|

00 67

|

00 01

|

35 D5

Read the baud rate encoding of the current device. Baud rate encoding: 1 is 2400; 2 is 4800; 3 is 9600;  4 is 19200; 5 is 38400; 6 is 115200.

For the correct query command, the device will respond, for example the response data is: 01 03 02  00 03 F8 45, the format of which is as shown in the following table:

Device ID

|

Function id

|

Data Length

|

Rate ID

|

CRC16

---|---|---|---|---

01

|

03

|

02

|

00 03

|

F8 45

coded according to baud rate, 03 is 9600, ie the current device has a baud rate of 9600.

(2)Change the baud rate

For example, changing the baud rate from 9600 to 38400, ie changing the code from 3 to 5, the  command is: 01 06 00 67 00 05 F8 1601 03 00 66 00 01 64 15 .

Device ID

|

Function id

|

Start Address

|

Target Baud Rate

|

CRC16

---|---|---|---|---

01

|

03

|

00 66

|

00 01

|

64 15

Change the baud rate from 9600 to 38400, changing the code from 3 to 5. The new baud rate will take  effect immediately, at which point the device will lose its response and the baud rate of the device should  be queried accordingly. Modified.

5 Read Correction Value

(1) Read Correction Value

When there is an error between the data and the reference standard, we can reduce the display error  by adjusting the correction value. The correction difference can be modified to be plus or minus 1000, that  is, the value range is 0-1000 or 64535 -65535. For example, when the display value is too small, we can  correct it by adding 100. The command is: 01 03 00 6B 00 01 F5 D6 . In the command 100 is hex 0x64 If  you need to reduce, you can set a negative value, such as -100, corresponding to the hexadecimal value of  FF 9C, which is calculated as 100-65535=65435, and then converted to hexadecimal to 0x FF 9C. The  correction value starts from 00 6B. We take the first parameter as an example. The correction value is read and modified in the same way for multiple parameters.

Device ID

|

Function id

|

Start Address

|

Data Length

|

CRC16

---|---|---|---|---

01

|

03

|

00 6B

|

00 01

|

F5 D6

For the correct query command, the device will respond, for example the response data is: 01 03 02  00 64 B9 AF, the format of which is as shown in the following table:

Device ID

|

Function id

|

Data Length

|

Data value

|

CRC16

---|---|---|---|---

01

|

03

|

02

|

00 64

|

B9 AF

In the response data, the first byte 01 indicates the real address of the current device, and 00 6B is the  first state quantity correction value register. If the device has multiple parameters, other parameters  operate in this way. The same, the general temperature, humidity have this parameter, the light generally

Shanghai Sonbest Industrial Co., Ltd Page6

 SD9770B User Manual http://www.sonbus.com/

does not have this item.

(2) Change correction value

 For example, the current state quantity is too small, we want to add 1 to its true value, and the current  value plus 100 correction operation command is:01 06 00 6B 00 64 F9 FD .

Device ID

|

Function id

|

Start Address

|

Destination

|

CRC16

---|---|---|---|---

01

|

06

|

00 6B

|

00 64

|

F9 FD

After the operation is successful, the device will return information: 01 06 00 6B 00 64 F9 FD, the  parameters take effect immediately after successful change.

Disclaimer

This document provides all information about the product, does not grant any license to intellectual  property, does not express or imply, and prohibits any other means of granting any intellectual property  rights, such as the statement of sales terms and conditions of this product, other issues. No liability is  assumed. Furthermore, our company makes no warranties, express or implied, regarding the sale and use  of this product, including the suitability for the specific use of the product, the marketabi lity or the infringement liability for any patent, copyright or other intellectual property rights, etc. Product  specifications and product descriptions may be modified at any time without notice.  Contact Us

Company: Shanghai Sonbest Industrial Co., Ltd

Address:Building 8,No.215 North east road,Baoshan District,Shanghai,China Web: http://www.sonbest.com
Web: http://www.sonbus.com
SKYPE: soobuu
Email: sale@sonbest.com
Tel: 86-021-51083595 / 66862055 / 66862075 / 66861077
Shanghai Sonbest Industrial Co., Ltd Page7