UNITRONICS IO-Link HUB Class A Device User Guide
- June 15, 2024
- UNITRONICS
Table of Contents
UNITRONICS®
IO-LINK
User Guide
UG_ULK-1616P-M2P6
(IO-Link HUB,16I/O,PN,M12,IP67)
1. Description
1.1 Agreement
The following terms/abbreviations are used synonymously in this document:
IOL: IO-Link.
LSB: least significant bit.
MSB: most significant bit.
This device: equivalent to “this product”, refers to the product model or series described in this manual.
1.2 Purpose
This manual contains all the information required to use the device correctly, including information on necessary functions, performance, usage, etc. It is suitable both for programmers and test/debugging personnel who debug the system themselves and interface it with other units (automation systems, other programming devices), as well as for service and maintenance personnel who install extensions or perform fault/error analysis.
Please read this manual carefully before installing this equipment and putting
it into operation.
This manual contains instructions and notes to help you step-by-step through
installation and commissioning. This ensures trouble-free. use of the product.
By familiarizing yourself with this manual, you will gain.
The following benefits:
- ensuring safe operation of this device.
- take advantage of the full capabilities of this device.
- avoid errors and related failures.
- reduce maintenance and avoid cost waste.
1.3 Valid Scope
The descriptions in this document apply to the IO-Link device module products of the ULKEIP series.
1.4 Declaration of Conformity
This product has been developed and manufactured in compliance with applicable
European standards and guidelines (CE, ROHS).
You can obtain these certificates of conformity from the manufacturer or your
local sales representative.
2. Safety Instructions
2.1 Safety Symbols
Read these instructions carefully and inspect the equipment before attempting
to install, operate, repair, or maintain it. The following special messages
may appear throughout this document or on the equipment to indicate status
information or to warn of potential hazards.
We divide the safety prompt information into four levels: “Danger”, “Warning”,
” Attention”, and “Notice”.
DANGER| indicates a severely hazardous situation which, if not avoided, will
result in death or serious injury.
---|---
WARNING| indicates a hazardous situation which, if not avoided, could result
in death or serious injury.
ATTENTION| indicates a hazardous situation which, if not avoided, could result
in minor or moderate injury.
NOTICE| used to prompt information not related to personal injury
This is the DANGER symbol, which indicates an electrical hazard exists which, if instructions are not followed, will result in personal injury.
This is a WARNING symbol, which indicates an electrical hazard exists which, if instructions are not followed, could result in personal injury.
This is the “Attention” symbol. Used to warn you of a potential personal
injury hazard. Observe all safety instructions following this symbol to avoid
injury or death.
This is the “Notice” symbol, which is used to warn the user of possible risks. Failure to observe this regulation may result in faulty of device.
2.2 General Safety
This equipment should only be installed, operated, serviced and maintained by qualified personnel. Qualified person is a person who has skills and knowledge concerning the construction and operation of electrical equipment, and its installation, and has received safety training to recognize and avoid the hazards involved.
There shall be a statement in the instructions that if the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
User modifications and/or repairs are dangerous and will void the warranty and release the manufacturer from any liability.
Product maintenance can only be carried out by our personnel. Unauthorized
opening and improper servicing of the product can result in extensive
equipment damage or possibly personal injury to the user.
In the event of a serious malfunction, discontinue use of the equipment. Prevent accidental operation of the device. If repairs are required, please return the device to your local representative or sales office.
It is the operating company’s responsibility to comply with locally applicable
safety regulations.
Store unused equipment in its original packaging. This provides the best
protection against impact and moisture for the device. Please ensure that the
ambient conditions comply with this relevant regulation.
2.3 Special Safety
A process started in an uncontrolled manner may endanger or be exposed to other equipment, therefore, before commissioning, make sure that the use of the equipment does not involve risks that may endanger other equipment or be endangered by other equipment risks of.
Power Supply
This device can only be operated with a current source of limited power, that
is, the power supply must have overvoltage and overcurrent protection
functions.
To prevent the power failure of this equipment, affecting the safety of other
equipment; or the failure of external equipment, affecting the safety of this
equipment.
3. Product Overview
The IO-Link master establishes the connection between the IO-Link device and the automation system. As an integral part of the I/O system, the IO-Link master station is either installed in the control cabinet, or directly installed on site as a remote I/O, and its encapsulation level is IP65/67.
- Designed for industrial environments, it is a system applied to automated lines.
- Compact structure, suitable for usage scenarios with limited installation conditions.
- IP67 high protection level, anti-interference design, suitable for demanding application environments.
As a special reminder, IP rating is not part of UL certification.
4. Technical Parameters
4.1 ULK-1616P-M2P6
4.1.1 ULK-1616P-M2P6 Specification
The technical specifications of ULK-1616P-M2P6 are as follows:
Basic Parameters
|
Full Series
---|---
Housing Material|
PA6 + GF
Housing Color|
Black
Protection Level|
IP67, Epoxy full potting
Dimensions (VV x H x D)|
155mmx53mmx28.7mm
Weight|
217g
Operating Temperature|
-25°C..70°C
Storage Temperature|
-40°C…85°C
Operating Humidity|
5%…95%
Storage Humidity|
5%…95%
Operating Atmospheric Pressure|
80KPa…106KPa
Storage Atmospheric Pressure|
80KPa…106KPa
Tightening Torque I/O)|
M12:0.5Nm
Application Environment:|
conforms to EN-61131
Vibration Test|
conforms to IEC60068-2
Impact Test|
conforms to IEC60068-27
Free Drop Test|
conforms to IEC60068-32
EMC|
conforms to IEC61000 -4-2,-3,-4
Certification|
CE, RoHS
Mounting Hole Size|
Φ4.3mm x4
Model | ULK-1616P-M2P6 |
---|---|
IOLINK Parameters | |
IO-LINK Device | |
Data Length | 2 bytes input/2 bytes output |
Minimum Cycle Time | |
Power Parameters | |
Rated Voltage | |
Total Current UI | <1.6A |
Total Current UO | <2.5A |
Port Parameters (input) | |
Input Port Postion | J1….J8 |
Input Port Number | up to 16 |
PNP | |
Input Signal | 3-wire PNP sensor or 2-wire passive signal |
Input Signal “0” | Low level 0-5V |
Output Signal “1” | High level 11-30V |
Switching Threshold | EN 61131-2 Type 1/3 |
Switching Frequency | 250HZ |
Input Delay | 20us |
Maximum Load Current | 200mA |
I/O connection | M12 Spin Female A coded |
Port Parameters (output) | |
Output Port Postion | J1….J8 |
Output Port Number | up to 16 |
Output Polarity | PNP |
Output Voltage | 24V (follow UA) |
Output Current | 500mA |
Output Diagnostic Type | point diagnosis |
Synchronization Factory | 1 |
Switching Frequency | 250HZ |
Load Type | Resistive, Pilot Duty, lungsten |
Short Circuit Protection | yes |
Overload Protection | yes |
I/O Connection | M12 Spin Female A coded |
4.1.2 ULK-1616P-M2P6 Series LED Definition
ULK-1616P-M2P6 LED is shown in the below figure.
-
IO-LINK LED
Green: No communication connection
Green flashing: communication is normal
Red: communication lost -
PWR LED
Green: module power supply is normal
Yellow: Auxiliary power supply (UA) is not connected (for modules with output function)
Off: Module power is not connected -
I/O LED
Green: channel signal is normal
Red: There is output when the port is short-circuited/overloaded/without UA power -
LEDA
-
LEDB
| Status| Solution
---|---|---
PWR| Green: Power OK|
Yellow: no UA power| Check if there is +24V on pin 2
Off: The module is not powered| Check power wiring
LINK| Green: No communication connection| Check the configuration of the
modules in the PLC
Green flashing: link is normal, data communication is normal|
Off: Link not established| Check the cable
Red: Communication with the master station is interrupted| Check the status of
the master station / view the connection line
IO| Green: channel signal is normal|
Red: There is output when the port is shortcircuited/overloaded/without UA
power| Check whether the wiring is correct/measure UA voltage/PLC program
Note: When the Link indicator is always off, if there is no abnormality in the
cable inspection and replacement of other modules, it indicates that the
product is working abnormally.
Please contact the manufacturer for technical consultation.
4.1.3 ULK-1616P-M2P6 Dimension
The size of the ULK-1616P-M2P6 is 155mm × 53mm × 28.7mm, including 4 mounting
holes of Φ4.3mm, and the depth of the mounting holes is 10mm, as shown in the
figure below:
5. Product Installation
5.1 Installation Precautions
To prevent product malfunction, malfunction, or negative impact on performance and equipment, please observe the following items.
5.1.1 Installation Site
Please avoid installing near devices with high heat dissipation (heaters, transformers, large-capacity resistors, etc.)
Please avoid installing it near equipment with serious electromagnetic
interference (large motors, transformers, transceivers, frequency converters,
switching power supplies, etc.).
This product uses PN communication.
Radio waves (noise) generated. by transceivers, motors, inverters, switching
power supplies, etc. may affect the communication between the product and
other modules.
When these devices are around, it may affect the communication between the
product and the module or damage the internal components of the module.
When using this product near these devices, please confirm the effects before
use.
When multiple modules are installed close to each other, The service life of
the modules may be shortened due to the inability to dissipate heat.
Please keep more than 20mm between the modules.
5.1.2 Application
Do not use AC power. Otherwise, there is a risk of rupture, seriously
affecting the safety of personal and equipment.
Please avoid wrong wiring. Otherwise, there is a risk of rupture and burnout.
It may affect the safety of personal and equipment.
5.1.3 Usage
Do not bend the cable within a radius of 40mm. Otherwise there is a risk of
disconnection.
If you feel that the product is abnormal, please stop using it immediately and
contact the company after cutting off the power.
5.2 Hardware Interface
5.2.1 ULK-1616P-M2P6 Interface Definition
Power Port Definition
1. ULK-1616P-M2P6 Power Port Definition
The power port uses a 5-pin connector, and the pins are defined as follows:
Power Port Pin Definition
Port
M12
Female & Male
Pin Definition
| Connection Type| M12, 5 pins, A-code Male|
Male
-
V+
-
Output: P24V
No output: N/C -
0V
-
C/Q
-
N/C
Allowable Input Voltage| 18…30 VDC (type.24VDC)
Maximum Current| 1A
Static Working Current lc| s80mA
Power Reverse Polarity Protection| yes
Tightening Torque (power port)| M12:0.5Nm
Protocol| IOLINK
Transfer Speed| 38.4 kbit/s (COM2)
Minimum Cycle Time| 55ms
|
|
|
|
|
|
2. IO Link Port Pin Definition
The IO-Link port uses a 5-pin connector, and the pins are defined as follows:
I/O Port Pin Definition
Port
M12
A-code
Female
|
Pin Definition
---|---
Input(In/Output)
|
Output
PNP
|
PNP
|
- 24V DC+
- Input (In/Output)
- 0V
- Input(In/Output)
- FE
|
- N/C
- Output
- 0V
- Output
- FE
Address Distribution
|
(-R)
Byte
| 1| 0| Byte| 1| 0
Bit0| J1P4| J5P4| Bit0| J1P4|
J5P4
Bit1
| J1P2| J5P2| Bit1| J1P2| J5P2
Bit2| J2P4| J6P4| Bit2| J2P4|
J6P4
Bit3
| J2P2| J6P2| Bit3| J2P2| J6P2
Bit4| J3P4| J7P4| Bit4| J3P4|
J7P4
Bit5
| J3P2| J7P2| Bit5| J3P2| J7P2
Bit6| J4P4| J8P4| Bit6| J4P4|
J8P4
Bit7
| J4P2| J8P2| Bit7| J4P2|
J8P2
Pin 5 (FE) is connected to the ground plate of the module. If the shielding layer of the connected temperature sensor needs to be grounded, please connect pin 5 to the shielding layer and ground the grounding plate of the module.
5.2.2 ULK-1616P-M2P6 Wiring Diagram
1. Output Signal
J1~J8 (DI-PNP)
2. Output Signal
J1~J8 (DI-PNP)
3. Input/Output Signal (self-adaptive)
J1~J8 (DIO-PNP)
5.2.3 ULK-1616P-M2P6 IO Signal Address Correspondence Table
1. Applicable Models: ULK-1616P-M2P6
Byte
| 0| Byte|
1
---|---|---|---
I 0.0/Q0.0| J5P4| I 1.0/Q1.0|
J1P4
I 0.1/Q0.1
| J5P2| I 1.1/Q1.1| J1P2
I 0.2/Q0.2| J6P4| I 1.2/Q1.2|
J2P4
I 0.3/Q0.3
| J6P2| I 1.3/Q1.3| J2P2
I 0.4/Q0.4| J7P4| I 1.4/Q1.4|
J3P4
I 0.5/Q0.5
| J7P2| I 1.5/Q1.5| J3P2
I 0.6/Q0.6| J8P4| I 1.6/Q1.6|
J4P4
I 0.7/Q0.7
| J8P2| I 1.7/Q1.7|
J4P2
The information in this document reflects products at the date of printing.
Unitronics reserves the right, subject to all applicable laws, at any time, at
its sole discretion, and without notice, to discontinue or change the
features, designs, materials and other specifications of its products, and to
either permanently or temporarily withdraw any of the forgoing from the
market.
All information in this document is provided “as is” without warranty of any
kind, either expressed or implied, including but not limited to any implied
warranties of merchantability, fitness for a particular purpose, or non-
infringement. Unitronics assumes no responsibility for errors or omissions in
the information presented in this document. In no event shall Unitronics be
liable for any special, incidental, indirect or consequential damages of any
kind, or any damages whatsoever arising out of or in connection with the use
or performance of this information.