JABLOTRON JA-151ST Wireless Combined Smoke And Heat Detector Owner’s Manual

June 15, 2024
JABLOTRON

JABLOTRON JA-151ST Wireless Combined Smoke And Heat Detector

JABLOTRON-JA-151ST-Wireless-Combined-Smoke-And-Heat-Detector-
product

Product Information

Specifications:

  • Power: Three AA batteries
  • Typical Lifetime: Not specified
  • Smoke Detection: Yes
  • Smoke Detector Sensitivity: Not specified
  • Heat Detection: Yes
  • Alarm Temperature: Not specified
  • Communication Band: Not specified
  • Effective Radiated Power (ERP): Not specified
  • Communication Range: Not specified
  • Dimensions: Not specified
  • Weight: Not specified
  • Operating Temperature Range: Not specified
  • Compliance: Also complies with Can be operated according to Recommended screw

Description:

  • The JA-151ST detector is a wireless combined smoke and heat detector with a built-in siren. It is specifically designed to detect fire hazards in the interior of residential or commercial buildings. The detector can also be installed in mobile homes or caravans. Please note that this product is not suitable for installation on industrial premises.
  • The detector is powered by three AA batteries and utilizes wireless communication. The installation of this detector must be carried out by a trained technician with a valid manufacturer’s certificate.
  • In the event of a fire hazard, the detector will indicate it through the built-in LED indicator and acoustic signaling.

Product Usage Instructions

Installation:

  1. Choose an appropriate location for the detector, ensuring it is within the recommended communication range.
  2. Fix the detector securely to the desired surface using the recommended screws.
  3. Ensure that the detector is installed by a trained technician with a valid manufacturer’s certificate.

Testing:
It is crucial to regularly test the functionality of the JA-151ST detector to ensure proper operation.

  1. Press and hold the test button on the detector for a few seconds.
  2. The LED indicator should flash, and the siren should sound to indicate that the detector is functioning correctly.

Maintenance:
Regular maintenance is essential to keep the JA-151ST detector in optimal condition.

  1. Replace the batteries as per the manufacturer’s instructions or when the low battery indicator is activated.
  2. Clean the detector periodically by gently wiping the exterior with a soft, dry cloth.

Frequently Asked Questions (FAQ):

  • Q: Can the JA-151ST detector be installed on industrial premises?
    A: No, this product is not designed for installation on industrial premises.

  • Q: How is the detector powered?
    A: The JA-151ST detector is powered by three AA batteries.

  • Q: What do the LED indicator and acoustic signaling indicate?
    A: The LED indicator and acoustic signaling are used to indicate a fire hazard detected by the detector.

Description

  • The JA-151ST detector uses wireless communication and it is powered by three AA batteries. The detector should be installed by a trained technician with a valid with a valid manufacturer’s certificate.
  • The detector indicates a fire hazard using the built-in LED indicator and acoustic signaling.
  • The JA-151ST consists of two independent detectors – an optical smoke detector and a heat detector. The optical smoke detector works on the principle of scattered light. It is very sensitive to large dust particles which are present in dense smoke. It is less sensitive to smaller particles generated by the combustion of liquids such as alcohol. That is why the fire detector also contains a built-in heat detector which has a slower reaction but is much better at detecting fire which generates only a small amount of smoke.

Technical specifications

  • Power 3 x Alkaline battery type LR6 (AA) 1.5 V/2.4 Ah
    Please note: Batteries are not included

  • Typical lifetime approx. 3 years

  • Smoke detection optical light scattering

  • Smoke detector sensitivity m = 0.11 ÷ 0.13 dB/m pursuant to EN 14604:2005, EN 54-7

  • Heat detection class A1 according to EN 54-5

  • Alarm temperature +60 °C to +65 °C

  • Communication band 868.1 MHz, Jablotron protocol

  • Effective Radiated Power (ERP) 10 mW

  • Communication range approx. 300 m (unrestricted area)

  • Dimensions diameter 126 mm, height 50 mm

  • Weight 150 g

  • Operating temperature range -10 °C to +65 °C

  • Also complies with EN 54-25, ETSI EN 300 220, EN 60950-1, EN 50130-4, and EN 55022.

  • Can be operated according to ERC REC 70-03

  • Recommended screw 2x ø 3.5 x 40 mm (countersunk head)

Contact Information

JABLOTRON ALARMS a.s.
Pod Skalkou 4567/33 | 466 01 | Jablonec n. Nisou I Czech Republic www.jablotron.com.