CPVAN SM11 Smoke Alarm Instruction Manual

June 15, 2024
CPVan

CPVAN SM11 Smoke Alarm

Product Profile

Battery non-replacement

Alarm Application scenario

DIMENSION

Thank you for purchasing our smoke alarm device. Please read this manual carefully to ensure proper use and store it in a safe place for future reference.

Product Specifications

  • Power: DC 3V
  • Battery Package: CR14505 Lithium Battery,1600mAh(sealed in)
  • Operation Current: <1 OuA (standby); <70mA (alarm)
  • Alarm Volume: >85 dB(A) at 3 meters
  • Alarm Sensitivity: 0.09 – 0.17 dB/m
  • Low Battery: 2.6 ± 0.1 V
  • Silence Time: approx. 1 o minutes
  • Comply to Standard EN14604:2005/AC: 2008

Packing List

  • 1 x Photoelectric smoke alarm
  • 1 x Mounting bracket
  • 1 x Screw Kit (install option 1)
  • 1 x 3M Adhesive (install option 2)
  • 1 x User manual

Installation Instructions

  1. At first, you should install an alarm in the bedroom and walkway. If there are several bedrooms in the house, please install an alarm in every bedroom.
  2. install an alarm above the stairway and on every floor of the house.
  3. Smoke, heat, and burning things will spread horizontally after rising to the ceiling, so install the alarm in the middle of the ceiling.
  4. lf the alarm can not be installed in the middle of the ceiling, install it keeping 300mm away from the corners. (see figure).
  5. lf the alarm is installed in the wall, it should keep 100mm away from the ceiling.
  6. lf the length of the room or the hall is beyond 30 feet, you need to install several alarms there.
  7. When the wall or ceiling is slanting, the alarm needs to be installed a minimum of 500mm away from the highest wall or ceiling point in the room (see Figure 2).

Locations to Avoid

  1. High-humidity areas such as kitchens, and bathrooms;
  2. Next to air outlets, fans, and central heating;
  3. Dusty, dirty areas or areas with insects;
  4. High-temperature and easily polluted places;
  5. Places with difficult access, making it difficult to operate the test function;
  6. Within 1. Sm from lamps;
  7. Next to doors or windows;
  8. ln the top of rooms with sloping roofs, the corner of the room or other dead-air spaces.

Mounting Alarms

  1. Twist off the mounting bracket from the alarm.
  2. Put the bracket on the installation position and mark the screw holes on the ceiling or the wall.
  3. Drill two mounting holes in the marked place with an electric drill (The diameter of the drill hole is 5mm) and insert two plastic anchor plugs with a hammer.
  4. Screw the mounting bracket to the ceiling or the wall (Refer to Figure 3).
  5. Attach the alarm to the mounting bracket and turn clockwise to lock the alarm

WARNING: The installation instructions must be followed strictly in case of any injury.

How to Power up & off the device

The device is turned off by default before leaving the factory, Before the device can be used normally, the product must be activated.

  • Power Up— Press the test button over 1 O seconds, when the red LED indicator lights up, release the test button, and the alarm will power up and work normally.
  • Power Off— lf you go to power up the device, Press the test button over 1 O second, when the red LED indicator blinks twice, release the test button, the alarm is powered off, and Work is suspended.

Test your Alarm

Test the unit to ensure proper operation by pressing the cover, the alarm will sound if the unit is working well. If no sounds, you can refer to the “Troubleshooting” section for a solution.

CAUTION

  1. DO NOT test your alarm using an open flame. This may damage the smoke alarm, or ignite combustible materials and start a structural fire.
  2. DO NOT stand close to the alarm when the alarm is sounding. Exposure at close range may be harmful to your earnings, so step away when testing.
  3. Weekly Test: test this smoke alarm once a week.

LED Indicators

  1. Normal status: GREEN LED Flashes once every 60 seconds.
  2. Test status: Red LED flashes once every second.
  3. Hush/Silence mode: Red LED flashes once every 8 seconds.
  4. Low Battery status: Red LED flashes once every 60 seconds and 1 beep every 60 seconds.
  5. Fault status: the alarm will deliver beeps every 40 seconds.

Silence Mode

will be paused the unit alarming for approximately 1 O minute. The red LED will flash once every 8 seconds, it indicates the smoke alarm device is running into the silence mode. The silence feature is to be used only when a known alarm condition, such as smoke from cooking activates the alarm. The smoke alarm device will automatically reset after approximately 1 O minutes, if after this period, particles of combustion are still present, the alarm will sound again.

CAUTION: Before using the alarm silence (silence), identify the source of the smoke and be certain a safe condition exists.

Maintenance and Cleaning

There are a few simple steps you need do to keep it working properly.

  1. Test the alarm once a week.
  2. Do not paint the alarm. Paint will seal the vents and interfere with the sensor’s ability to detect smoke.
  3. Never attempt to disassemble the alarm to clean the inside. This will damage the alarm.

Clean the alarm at least once a month to remove dust, dirt, or debris., Use a vacuum cleaner with a soft brush, to vacuum all sides, and covers of smoke alarm device.
If there is a defective battery or other failures, you can refer to “Troubleshooting” for a solution, if there are still failures during the warranty, you can return them to your retailer.

Trouble Shooting

Problem Method of disposal
The alarm does not sound when testing 7. Please check whether the alarm is

powered up.
Red LED flashes and the alarm delivers one beep every 60 seconds| ****

7. The battery is low.


The alarm delivers one beep every 40 seconds

| 7. clean the alarm. please refer to the

“maintenance and cleaning” section.


Nuisance alarms are triggered intermittently or when residents are cooking, taking showers, etc

| ****

7. Press the silence button.

2. Clean the alarm. Please refer to the “maintenance and cleaning” section. 3. Move the alarm to a new location.

Warranty Information

We usually provide 12 month’s warranty after you install our smoke and heat alarm products, if you want to extend 24 months, just contact us via email:

During the specified warranty period, we will repair or replace, at its discretion any defective Smoke Alarms that are returned to the retailer. Please include your name, address, and phone number along with a brief description of what is wrong with the unit. Damage from neglect, abuse, or failure to adhere to any of the enclosed instructions will result in termination of the warranty, and the unit will not be replaced or repaired. This warranty shall not apply to the alarm if it has been damaged, modified, abused or altered after the date of purchase or if it fails to operate due to improper maintenance.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals