Enerlites 62050-IG Isolated Ground Decorator Duplex Outlet Installation Guide
- June 14, 2024
- ENERLITES
Table of Contents
Installation Guide
Isolated Receptacle **Installation Diagram
**
Receptacle Instructions
NOTICE : For installation by a qualified person in accordance with
national and local electrical codes.
WARNING : Risk of Electric Shock or Death. Disconnect power before
installing.
CAUTION : USE COPPER CONDUCTORS ONLY; 20A, 10AWG to 12AWG.
-
Remove insulation from conductors 5/8 inch.
-
Side Wire: Wrap conductor securely around terminal screw.
Tighten terminal screws securely,9-12 pound ·inch(1.0-1.4N ·m) of torque. -
Back-wiring clamps accept up to No. 10 copper or copper- clad wire.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>