Enerlites 61501-TR Duplex Tamper Resistant Receptacle Diagram Installation Guide
- June 14, 2024
- ENERLITES
Table of Contents
Enerlites 61501-TR Duplex Tamper Resistant Receptacle Diagram Installation
Guide
Wiring Diagram
Receptacle instructions
NOTICE: For installation by a qualified person in accordance with national and local electrical codes.
WARNING: Risk of Electric Shock or Death. Disconnect power before installing.
CAUTION: USE COPPER CONDUCTORS ONLY; 15A, 12AWG to 14AWG.
-
Remove insulation from conductors 5/8 inch.
-
Side Wire: Wrap conductor securely around terminal screw.
Tighten terminal screws securely, terminal tightening torque is 14 in-lbf(1.6 N·m). -
Push-in terminals for use on 15 ampere branch circuits only and with No. 14 AWG solid copper conductors only.
Do not use push-in terminals on a 20 ampere branch circuit.