SIEMENS ET 134-22 Low Temperature Detection Thermostat Instructions
- June 14, 2024
- SIEMENS
Table of Contents
Technical Instructions
Document No. 155-016P25
ET 134-22
April 12, 2018
Powers™ Controls
Low Temperature Detection
Thermostat
Description
The electric Low Temperature Detection Cut-out and Alarm Thermostat is a remote bulb instrument which opens an electrical circuit to stop the supply fan motor and/or closes an outside air damper when the temperature at the sensing element falls below the setting of the instrument. Simultaneously, it closes a circuit to indicate an alarm condition.
Features
- Manual reset
- Easy temperature setting with adjusting screw on top of enclosure
- Mounting bracket and two screws included
- Main and separate reverse-acting auxiliary contacts
Product Number
134-1504
Warning/Caution Notations
WARNING
Personal injury or loss of life may occur if a procedure is not performed as
specified.
CAUTION
Equipment damage or loss of data may occur if you do not follow a procedure as
specified.
Application
This instrument should only be used on those applications where the ambient temperature to which the instrument case and bellows are exposed remains above the temperature setting of the thermostat. This thermostat should be used in areas protected from the weather.
Prerequisites
WARNING:
This low temperature detection thermostat is designed for use only as an
operating control. Where an operating control failure would result in personal
injury and/or loss of property, it is the installer’s responsibility to add
devices (safety, limit controls) or systems (alarm, supervisory systems) that
protect against, or warn of control failure.
CAUTION:
The switch contact position (LINE-M2) may be in either an open or closed state
upon receipt due to possible exposure to freezing temperatures during
shipping. It is strongly recommended that the reset button be manually pressed
down and released before initial use to restore the switch position to a
normal operating state before proceeding to installation; otherwise, the unit
could remain in the tripped state.
Specifications
Switch Action| Main (LINE-M2) contacts open on temperature drop,
simultaneously auxiliary contacts close
---|---
Range| 15 to 55°F (-9 to 13°C)
Maximum bulb temperature| 400°F (204°C)
Minimum differential| 5°F (2.8°C) Non-adjustable
Sensing element| Vapor filled
Bulb length| 1/8-inch OD × 20 feet (6 m)
Reset action| Manual
Electrical rating| See Table 1
Weight| 2.4 lb (1.1 kg)
Dimensions| See Figures 2 and 5
Approvals| UL file SA 10816
CSA file LR948
Operation
This thermostat incorporates a temperature sensing element of the vapor-filled
type which actuates a heavy duty contact through a rugged link mechanism.
Any one-foot length of the element subjected to temperatures below the
temperature setting of the thermostat will actuate the thermostat switch
mechanism regardless of the temperature being sensed by the remainder of the
element. This makes the thermostats ideal for protecting large coils where
air stratification could cause freezing conditions in a localized area.
The thermostat has a main and auxiliary contact unit. The main load circuit
(LINE-M2) opens on temperature drop and simultaneously, an auxiliary or alarm
circuit (LINE-Ml) closes on temperature drop.
NOTE: The reset button must be manually pressed down and released to
resume normal fan system operation.
Electrical Ratings
Table 1.
Pole Number | Line-M2 (Main) | Line-M1 (Auxiliary) |
---|---|---|
Motor Rating | 120V | 208V |
AC Full Load Amps | 16.0 | 9. |
AC Locked Rotor Amps | 96.0 | 55. |
AC Non-Ind Amps | 16.0 | 9. |
Pilot Duty-Both Poles:
125 VA, 24 to 600 Vac
57.5 VA, 120 to 300 Vdc
Mounting and Installation
General Guidelines
- Locate the sensing element in the downstream side of the coil.
- Locate the case and bellows where the ambient temperature is always warmer than the setpoint.
- Install the thermostat so that the reset button is readily accessible and the element bellows points down.
- Install as much of the bulb as possible in a horizontal plane. If too much of the bulb is vertical, it will not operate properly.
- Avoid sharp bends or kinks in the sensing element.
Large walk-in Ducts
(Figure 1)
- Attach the mounting bracket to the thermostat with the two round head screws provided.
- Mount the two perforated steel strap hangers inside the duct with the wide part of the hanger strap parallel to the air flow.
- Drill a hole in the side of the duct. With the bulb still coiled, thread the bulb through the hole using a rotary movement.
- Mount the thermostat on the outside of the duct.
- Carefully uncoil the bulb avoiding sharp bends or kinks in the sensing element.
- Mount the bulb in a horizontal, serpentine manner, attaching the bulb to the strap as shown in detail in Figure 1.
The installation is complete.
NOTE: For an alternate method of mounting, use coil clips (Part Number 356-115) in the fins to hold the bulb in a horizontal, serpentine pattern.
Limited Access Ducts
(Figure 2)
- Attach the mounting bracket to the thermostat with the two round head screws provided.
- Attach a mounting flange (Part Number 808-412) on the opposite side of the duct (near the bottom) from where the thermostat will be mounted.
- Mount a second flange on an 8-inch by 4-inch sheet metal plate. Cut an access opening for the bulb on the duct diagonally across from the duct-mounted flange. Drill mounting screw holes for the sheet metal plate.
- Cut a length of copper tubing to fit diagonally across the duct. Stretch out the bulb and wrap it around the tubing. See Figure 2.
- Insert the tubing and bulb through the access hole and into the duct-mounted flange. Fasten the 8-inch by 4-inch sheet metal plate to the duct.
- Mount the thermostat on the outside of duct.
Wiring
WARNING:
Disconnect the power supply before wiring connections are made to avoid
possible electrical shock or damage to the equipment.
Make all wiring connections using copper conductors only and in accordance
with the National Electrical Code and local regulations. Loads exceeding the
rating of the thermostat should be handled by means of a relay or motor
starter.
An opening for 1/2-inch conduit is provided in the bottom of the thermostat
enclosure.
See Figure 3 for a typical wiring diagram.
CAUTION:
Use terminal screws furnished (#8-32 × 1/4-inch binder head screw).
Longer terminal screws can interfere with switch mechanism and damage the
switch.
Adjustment
After mounting the thermostat, adjust the temperature setting using the
setpoint adjusting screw on the top of the enclosure. See Figure 4.
Observe a complete operating cycle to be sure that all components function
correctly.
Calibration
There is no field calibration required for the thermostat.
Troubleshooting
Observe a complete operating cycle to be sure that all components function
correctly.
Service
There is no servicing of the thermostat. Replace if inoperative.
Dimensions
Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as design improvements are introduced. Powers is a trademark of Siemens Industry, Inc. Product or company names mentioned herein may be the trademarks of their respective owners. © 2018 Siemens Industry, Inc.
Siemens Industry, Inc.
Building Technologies Division
1000 Deerfield Parkway
Buffalo Grove, IL 60089
+ 1 847-215-1000
Your feedback is important to us. If you have
comments about this document, please send them to
SBT_technical.editor.us.sbt@siemens.com
Document No. 155-016P25
Printed in the USA
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>