Carrier 40MBABQ36XA3 Air Handler Heat Pump Ductless System User Manual
- June 15, 2024
- Carrier
Table of Contents
Carrier 40MBABQ36XA3 Air Handler Heat Pump Ductless System
Product Information
The 40MBAB Air Handler Unit is a ductless system available in sizes 18 to 60. It is designed for air conditioning purposes and is suitable for both light commercial and non-light commercial applications. The unit is equipped with an indoor fan coil unit type A, which functions as an air handler.
This service manual provides detailed information for servicing, repairing, and maintaining the indoor units. It includes an appendix on page 36 that contains troubleshooting data. The manual also provides a table of contents on page 1 for easy navigation.
Model Number Nomenclature:
KBTUH | 18 | 24 | 30 | 36 | 36 | 48 | 60 |
---|---|---|---|---|---|---|---|
V-PH-HZ | 208/230-1-60 | 208/230-1-60 | 208/230-1-60 | 208/230-1-60 | 208/230-1-60 | ||
208/230-1-60 | 208/230-1-60 | ||||||
ID MODEL NO. | 40MBABQ18XB3 | 40MBABQ24XB3 | 40MBABQ30XB3 | 40MBABQ36XB3 | |||
40MBABQ36XA3 | 40MBABQ48XA3 | 40MBABQ60XA3 |
Specifications are subject to change without notice.
Note: The unit requires a main electrical disconnect switch to be in the OFF position before installation, modification, or servicing. Additionally, only trained and qualified installers and service mechanics should handle the unit.
Product Usage Instructions
- Ensure the main electrical disconnect switch is in the OFF position before installing, modifying, or servicing the unit. If there are multiple disconnect switches, lock out and tag each switch with a suitable warning label.
- Only trained and qualified installers and service mechanics should perform the installation, start-up, and servicing of the air conditioning equipment. Untrained personnel can perform basic maintenance tasks such as coil cleaning, but all other operations should be handled by trained service personnel.
- When working on the equipment, always observe the precautions mentioned in the literature and on tags, stickers, and labels attached to the equipment.
- Follow all safety codes and wear safety glasses and work gloves. Keep a quenching cloth and fire extinguisher nearby when brazing. Exercise caution when handling, rigging, and setting bulky equipment.
- Read the manual thoroughly and follow all the warnings or cautions provided in the literature and attached to the unit. Consult local building codes and the National Electrical Code (NEC) for any special requirements.
- Take note of the safety-alert symbol ( ) on the unit and in the instructions or manuals. Be alert to the potential for personal injury when encountering this symbol. Familiarize yourself with the signal words used: DANGER, WARNING, and CAUTION.
- Never use air or gases containing oxygen for leak testing or operating refrigerant compressors, as this can lead to an explosion. Only use approved methods and materials for these purposes.
40MBAB Air Handler Unit Ductless System Sizes 18 to 60
SAFETY CONSIDERATIONS
These words are used with the safety-alert symbol. DANGER identifies the most
serious of hazards which will result in severe personal injury or death.
WARNING signifies hazards which could result in personal injury or death.
CAUTION is used to identify unsafe practices which may result in minor
personal injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability, or
operation.
WARNING
ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in
personal injury or death. Before installing, modifying, or servicing the unit,
the main electrical disconnect switch must be in the OFF position.
There may be more than 1 disconnect switch. Lock out and tag switch with a
suitable warning label.
Installing, starting up, and servicing air-conditioning equipment can be
hazardous due to unit pressures, electrical components, and equipment location
(roofs, elevated structures, etc.).
Only trained, qualified installers and service mechanics should install,
start-up, and service this equipment.
Untrained personnel can perform basic maintenance functions such as coil
cleaning. All other operations should be performed by trained service
personnel only.
When working on the equipment, observe the precautions in the literature and
on tags, stickers, and labels attached to the equipment.
Follow all safety codes. Wear safety glasses and work gloves. Keep a quenching
cloth and fire extinguisher nearby when brazing. Use care in handling,
rigging, and setting bulky equipment.
Read this manual thoroughly and follow all the warnings or cautions included
in the literature and attached to the unit. Consult local building codes and
the National Electrical Code (NEC) for special requirements.
Recognize safety information. This is the safety-alert symbol . When you see
this symbol on the unit and in instructions or manuals, be alert to the
potential for personal injury. Understand these signal words: DANGER, WARNING,
and CAUTION.
WARNING
EXPLOSION HAZARD Failure to follow this warning could result in death, serious
personal injury, and/or property damage.
Never use air or gases containing oxygen for leak testing or operating
refrigerant compressors. Pressurized mixtures of air or gases containing
oxygen can lead to an explosion.
CAUTION
EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in equipment
damage or improper operation. Do not bury more than 36 in. (914 mm) of
refrigerant pipe in the ground. If any section of pipe is buried, there must
be a 6 in. (152 mm) vertical rise to the valve connections on the outdoor
units. If more than the recommended length is buried, refrigerant may migrate
to the cooler buried section during the extended periods of unit shutdown.
This causes refrigerant slugging and could possibly damage the compressor at
start-up.
INTRODUCTION
This service manual provides the necessary information to service, repair, and maintain the indoor units. This manual contains an “APPENDICES” on page 36 with data required to troubleshoot issues. Use the “TABLE OF CONTENTS” on page 1 to locate a desired topic.
Specifications subject to change without notice.
40MBAB: Service Manual
MODEL NUMBER NOMENCLATURE
Table 1 — Unit Sizes
KBTUH 18 24 30
V-PH-HZ
36
208/230-1-60
36
48
60
ID MODEL NO. 40MBABQ18XB3 40MBABQ24XB3 40MBABQ30XB3 40MBABQ36XB3 40MBABQ36XA3 40MBABQ48XA3 40MBABQ60XA3
INDOOR UNIT
40 MB
A
B
Q
24
X
A
3
40 = INDOOR UNIT
MB = MODEL
INDOOR FAN COIL UNIT TYPE A = AIR HANDLER
MAJOR SERIES
VOLTAGE 3 = 208/230-1-60
A = Light Commercial B = Non Light Commercial
UNIT TYPE Q = Heat Pump
NOMINAL CAPACITY 18 – 1 1/2 TON 24 – 2 TONS 30 – 2 1/2 TONS 36 – 3 TONS 48 – 4
TONS 60 – 5 TONS
MAXIMUM NUMBER OF FAN COIL UNITS CONNECTED TO THE OUTDOOR UNIT A = 1:1
21
22
V
10001
Week of Manufacture
Sequential Serial Number
Year of Manufacture
V = ALL MODELS
Use of the AHRI Certified TM Mark indicates a manufacturer’s participation in
the program For verification of certification for individual products, go to
www.ahridirectory.org.
Manufacturer reserves the right to change, at any time, specifications and
designs without notice and without obligations. 2
40MBAB: Service Manual
AUXILLIARY CONTACTS FOUND ON THE MAIN BOARD
Work Terminal Port CN23 – Normally Open Dry Contact (Output)
· The WORK terminal port is linked to the unit’s indoor blower · When the
indoor blower is off, the contact is open · When the indoor blower is running,
the contact is closed · There is no voltage from CN23, power is provided from
the external control system and not from the unit. · The contacts are rated at
250VAC and 10 AMP maximum · If an active 24V signal output is required, G and
C ports (thermostat connections) may be used instead.
Fig. 1 — Auxiliary Contacts
ALARM Terminal Port CN33 – Normally Open DRY CONTACT (OUTPUT):
· Allows the terminal port to connect to an external ALARM interface or
annunciator · There is no voltage from CN33, power is provided from the ALARM
system and not from the unit. · The contacts are rated at 250VAC and 10 AMP
maximum · When the unit experiences a problem, the contact closes, and the
ALARM is triggered.
Fig. 2 — Auxiliary Contacts
Manufacturer reserves the right to change, at any time, specifications and
designs without notice and without obligations. 3
40MBAB: Service Manual
WATER LEVEL Switch Terminal Port CN5 – SWITCH INPUT:
· To enable this switch, jumper J1 must be removed · A field supplied float
switch can be directly connected to CN5 · CLOSED contacts = normal · OPEN
contacts = overflow · When an overflow condition occurs, a signal is sent to
the system to turn it off · Alarm EE appears.
Fig. 3 — Auxiliary Contacts
UV LED terminal port CN43 – OUTPUT 24VAC:
· The UV LED port is linked to the unit’s fan · When the fan is running, the
relay is closed and there is an output of 24VAC through the contacts that can
be used to power a compatible UV LED LIGHT · May also be used to power a pilot
relay with 24VAC coil to control other peripherals
Fig. 4 — Auxiliary Contacts
Manufacturer reserves the right to change, at any time, specifications and
designs without notice and without obligations. 4
40MBAB: Service Manual
Auxiliary Contacts found on the 24V interface Board:
Remote control (ON-OFF) terminal port CN2 and jumper JR1 – INPUT: · Remove the
jumper JR1 to enable the ON-OFF function · When the remote switch is off
(OPEN); the unit is OFF · When remote switch is on (CLOSE); the unit is ON ·
When the remote switch is close/open, the unit responds to the demand within 2
seconds · When the remote switch is on, you can use the included remote
controller or wired controller to operate the unit as normal. · When the
remote switch off, the unit will not respond to the command from the remote
controller or wired controller and a CP code is displayed on the
board.
Fig. 5 — Auxiliary Contacts
Manufacturer reserves the right to change, at any time, specifications and
designs without notice and without obligations. 5
B CD BCD BCD BCD BCD
345 345 345 345
34 5
40MBAB: Service Manual
ROTARY AND DIP SWITCHES
Micro-Switch Setting:
FOR SETTING NETADDRESS
S1+S2
EF 0 1 2
ON
67 9A
8
12
CODE
0~F
NETADDRESS
0~15
F A C T O R YS E T T I N G
67 9A
EF 0 1 2
ON
8
12
0~F
16~31
EF 0 1 2
ON
67 9A
8
12
0~F
32~47
67 9A
EF 0 1 2
ON
8
12
0~F
48~63
Fig. 6 –Net Address Micro-switch S1 and dial-switch S2 are for address setting
when the user wants to control the unit with a central controller.
Range: 00-63
Fig. 7 — Unit Configuration
24V THERMOSTATS SETTING
CODE FACTORY SETTI
EF 0 1 2
S3
8
0~F
67 9A
ON
SW1
12 34 ON~OFF
ON
SW2
12 34 ON~OFF
ON
SW3
12 34 ON~OFF
ON
SW4
12 34 ON~OFF
ON
S4
12
ON~OFF
Fig. 8 — Unit Configuration Factory Settings
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 6
40MBAB: Service Manual
CONNECTORS (CONT.)
Table 2 — Unit Configuration Settings
DIAL CODE
FEATURES
S3
Electric heating turns on outdoor T4 temperature
SW1-1 SW1-2 SW1-3 SW1-4 SW2-1 SW2-2 SW2-3
SW2-4
SW3-1
SW3-2
SW3-3 SW3-4 S4-1 S4-2
Whether 24V control selection Cold wind protection option Single
cooling/heating and cooling options Set machine.single internal machine The
first group controls the electric heating to turn on the temperature
difference Whether the electric heating is delayed Electric auxiliary heating
delay start time
Electric heating/compressor allow opening limit
Continuous running time when the 1.8°F (1°C) set temperature is not reached
Cooling and heating Y2 signal setting temperature adjustment value A
Hysteresis of the second group of electric heating Reserve Default ON Default
ON
ON
OFF (DEFAULT)
0 (zero) means that the temperature protection is not turned on.
1 through F maps to -4°F through 46°F (-20°C through 8°C).
Each increment represents 3.6°F (2°C).
YES
NO
NO
YES
Cooling
Heating and Cooling
Indoor unit
KIT
1.8°F (1°C)
3.6°F (2°C)
YES 30 minutes Compressor allowed to operate to low limit set by S3
NO 15 minutes Electric heating allowed to operate to high limit set by S3
E-square value (0.5 hour)
1.5 hours
1.8°F (1°C)
3.6°F (2°C) /
Short circuit W1 and W2 DH is off by default
3.6°F (2°C)
5.4°F (3°C) /
W1, W2 separate DH on
SW4-1 SW4-2 SW4-3
000 is the default 000/001/010/011/100/101/110/111, internal machines with different abilities, electric heating and PSC classification for use
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 7
40MBAB: Service Manual
WIRING
Use the following steps to wire the indoor unit.
NOTE: Wiring in this section is for the base unit ONLY.
1. Prepare the cable for connection. a. Using wire strippers, strip the
insulation from both ends of the signal cable to reveal about 1/2 in (12mm) of
wire. b. Strip the insulation from both ends of the wires. c. Use a wire
crimper to crimp the fork terminals to the ends of the wires.
2. Open the indoor unit’s front panel. Use a screwdriver to remove the cover
of the electric control box on the indoor unit.
3. Thread the power cable and the signal cable through the wire outlet.
4. Connect the fork terminals to the terminals. Match the wire colors/ labels
with the labels on the terminal block.
5. Firmly screw the fork terminals of each wire to its corresponding
terminal. Refer to the serial number and wiring diagram located on the cover
of the electric control box.
L1 L2 S
Pass the belt through the hole of the ferrite core (Magnetic Ring to secure it
to the cable
Fig. 10 — Ferrite Core (Magnetic Ring)
The main power is supplied to the outdoor unit. When disconnecting the power
of the outdoor unit, the indoor unit would lose power. A disconnect switch is
not required on the indoor unit side on the wiring between the outdoor and
indoor unit. A 3 pole disconnect (purchased separately) may be used for extra
protection between the indoor and outdoor Unit.
Circuit Breaker (purchased separately)
(purchased separately)
3 Pole Disconnect (purchased separately)
Fig. 11 — Wiring Connection of Indoor Unit
The Auxiliary Heater must have a separate branch electric circuit with a
field-supplied disconnect switch located within sight from, and readily
accessible from, the unit.
Circuit Breaker
Fig. 9 — Control Box and Wiring Diagram
CAUTION
While connecting the wires, strictly follow the wiring diagram. The
refrigerant circuit can become very hot. Keep the interconnection cable away
from the copper tube.
6. Clamp down the cable with the cable clamp. The cable must not be loose or
put strain on the fork terminals.
7. Reattach the electric box cover.
Electrical heater unit power wires (DO NOT connect to
Electrical the indoor unit heater circuit breaker!) unit
Fig. 12 — Wiring Connection of Electric Heater (optional)
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 8
40MBAB: Service Manual
CONNECTION DIAGRAMS AND CONTROL METHODS
The air handler fan coil unit can be controlled mainly through the following
methods. · SCENARIO #1 Wired controller (Included, optional accessory) –
KSACN1001AAA:
Non-polarity controller used to operate all functions. The wired controller is
equipped with an infrared receiver and can be used in conjunction with the
wireless controller.
For this scenario to be enabled SW1-1 must be set to the OFF positions
(Default) · SCENARIO #1 Wireless controller (Included):
Hand-held wireless remote provides the same functionality as the wired
controller and can be used in conjunction with the wired controller. Refer to
the owner’s manual for the remote’s operational instructions.
For this scenario to be enabled SW1-1 must be set to the OFF position
(Default). · SCENARIO #2 Third party heat pump thermostat (Not Included):
Allows the control of the air handler via the built-in 24V interface. For this
scenario to be enabled SW1-1 must be set to the ON position.
Fig. 13 — Connection Methods for 18K-36K Residential Units
Fig. 14 — Connection Methods for 36K-60K Light Commercial Units
Manufacturer reserves the right to change, at any time, specifications and
designs without notice and without obligations. 9
40MBAB: Service Manual
WIRING DIAGRAMS
T1
T2A T2B
T2 Output:12VDC
Cn34 Output:220VAC
Cn15
WATER LEVEL SWITCH
Alarm
work
HEATER
UVLE D Output
ECM M
2
4(3) 3
CN4 3 CN4 6 CN6 CN2 9 Output:24VAC Output:5VDC Output:5VDC Output:5VDC
3
Cn1 2 Output:24VAC
CN2 3CN3 3 CN 5 CN21
Output:12VDC
Output:5VDC
J1
INDOOR UNIT MAINBOARD
Output:15VDC
DRY CONTACT
DRY CONTACT
Cn1 8 Y/ G
CN2 0 S1 S2
L and N :230VAC NL CN1 1
2
Output:24VAC Output:220VAC
CN9 CN2 2 Cn1 0
6
RE D TRAN S RE D
BLU E
RE D
2
Y/ G
BLAC K
RE D
COMMUNICATION TO OUTDOOR UNIT
2
L1 L2
TO OUTDOOR UNIT OR POWER
CN4 CN5 Cn 1
Output:24VAC Output:24VAC Output:+15VDC
CONTROLLE R
2 WIR E WIR E
Remot e Contro l
R C L
Output:+12VDC G Y1 Y/Y 2
4
ON/OF F CN 2
CN 7
Output:+15VDC
JR 1
Output:24VAC Output:24VAC Output:24VAC Output:24VAC CN 6 CN 9 CN1 0 CN1 1
B W W1
W2
E/AU X
DH
CN1 4
Output:+12VDC
Output:+5VDC CN 3 E Y X
24V THERMOSTAT
TCoomCmC.MBu s
48 5 POR T
CODE ECM T1 T2 T2A T2B
Fig. 15 — Wiring Diagram Sizes 18K/24K/30K/36K – Non Light-Commercial Models Table 3 — Wiring Diagram Sizes 18K/24K/30K/36K – Non Light-Commercial Models
Indoor ECM Motor Room Temperature Coil Temperature Sensor Indoor Coil Inlet Temperature Sensor Indoor Coil Outlet Temperature Sensor
PART NAME
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 10
40MBAB: Service Manual
WIRING DIAGRAMS (CONT)
T2 Output:12VDC
Cn34 Output:220VAC
Cn15
T1
WATER LEVEL SWITCH
Alarm
work
HEATER
UVLE D Output
ECM M
2
T2 A T2 B
4(3) 3
3
CN4 3 CN4 6 CN 6 CN2 9
Output:24VAC Output:5VDC Output:5VDC Output:5VDC
Cn1 2 Output:24VAC
CN2 3CN3 3 CN 5 CN2 1
Output:12VDC
Output:5VDC
J1
INDOOR UNIT MAINBOARD
Output:15VDC
DRY CONTACT
DRY CONTACT
Cn1 8 Y/ G
L and N :230VAC S and N :0-24VDC
N LS
CN1 1
3
Output:24VAC Output:220VAC
CN9 CN2 2 Cn1 0
6
RE D TRAN S RE D
BLU E
RE D
2
BLAC K YELLO W (WHITE )
RE D
2
L1 1L2 2S3 Y/ G
TO OUTDOOR UNIT
CN4 CN5 Cn 1
Output:24VAC Output:24VAC Output:+15VDC
2 WIR E WIRE CONTROLLER
Remote Control
4
Output:+12VDC ON/OFF
CN 2
CN 7 CN1 4
Output:+15VDC Output:+12VDC
R C L G Y1 Y/Y 2
B W W1
W2 E/AU X DH
JR 1
Output:24VAC Output:24VAC Output:24VAC Output:24VAC CN 6 CN 9 CN1 0 CN1 1
Output:+5VDC
CN 3 E Y X
24V THERMOSTAT
TCoomCmC.MBus
48 5 POR T
Fig. 16 — Wiring Diagram Sizes 36K – 60K Light Commercial Models
CODE ECM CAP FAN T1 T2 T2A T2B
Table 4 — Wiring Diagram Sizes 36K – 60K Light Commercial Models
Indoor ECM Motor Indoor Fan Capacitor Indoor Fan Motor Room Temperature Sensor Coil Temperature Sensor Indoor Coil Inlet Temperature Sensor Indoor Coil Outlet Temperature Sensor
PART NAME
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 11
40MBAB: Service Manual
REFRIGERANT LINES
General refrigerant line sizing 1. The outdoor units are shipped with a full
charge of R410A refrigerant. All charges, line sizing, and capacities are
based on runs of 25 ft. (7.6 m). For runs over 25 ft. (7.6 m), consult the
product data. 2. Minimum refrigerant line length between the indoor and
outdoor units is 10 ft. (3 m). 3. Refrigerant lines should not be buried in
the ground. If it is necessary to bury the lines, not more than 36 in. (914
mm) should be buried. Provide a minimum 6 in. (152 mm) vertical rise to the
service valves to prevent refrigerant migration. 4. Both lines must be
insulated. Use a minimum of ½ in. (12.7 mm) thick insulation. Closed-cell
insulation is recommended in all long-line applications. 5. Special
consideration should be given to isolating interconnecting tubing from the
building structure. Isolate the tubing so that vibration or noise is not
transmitted into the structure. 6. For piping runs greater than 25 ft. (7.6
m), add refrigerant up to the allowable length as specified in the product
data.
Refrigerant Coil Specifications
DUCTED INDOOR COIL
UNIT SIZE
Table 5 — Refrigerant Coil Specifications
Number of rows
Tube pitch (a)x row pitch (b)
Fin Spacing
Fin type Fin Material
Tube outside dia.
Nominal Tube Wall Tube Enhancement Tube Material
Coil length x height x width
Face area Number of circuits Metering Device High Burst Pressure Low Burst
Pressure Design (high/low) Burst Pressure Gas Pipe (size connection type)
Liquid Pipe (size connection type)
in mm FPI mm
inch mm mm (inch) (Yes/ No)
inch mm ft2
inch Psi (MPa) Psi (MPa)
Psi In (mm) In (mm)
18
24
30/36/48
60
3
4
5
0.83×0.53
21×13.37
20
1.3
1.3
1.3
1.3
Louvered
Gold hydrophilic aluminum
0.276
7
0.00945 (0.24)
Yes
Copper
16.34×13.23×1.58×2
16.34×21.5×2.11×2 16.34×21.5×2.63×2
415x336x40.11×2
41554653.482 41554666.852
3
4.88
4.88
6
10
14
No metering device in indoor unit – information provided in Outdoor Unit’s PSR
550(3.79)
340(2.34)
550/340
Ø1/2″ (12.7)
ø5/8″ (15.9)
ø5/8″ (15.9)
Ø7/8″ (22)
Ø1/4″ (6.35)
ø3/8″ (9.52)
ø3/8″ (9.52)
ø3/8″ (9.52)
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 12
40MBAB: Service Manual
TROUBLESHOOTING
WARNING
Turn off all power supplies or disconnect all wires to avoid electric shock.
While checking indoor/outdoor PCB, please equip oneself with anti-static
gloves or wrist strap to avoid damage to the board.
WARNING
Electricity remains in capacitors even when the power supply is off. Ensure
the capacitors are fully discharged before troubleshooting.
Test the voltage between P and N on back of the outdoor unit main PCB with a multimeter. If the voltage is lower than 36V, the capacitors are fully discharged.
Error Display (Indoor Unit)
When the indoor unit encounters a recognized error, an error code appears (see Table 6).
DISPLAY EH00 EL01 EL16 EH03 EH60 EH61 EH62 EH65 ELOC EH06 EH0E EC07 EC51 EC52 EC53 EC54 EC56 PC00 PC01 PC02 PC03 PC04 EC0d PC0L FL09
Table 6 — Error Display (Indoor Unit)
ERROR INFORMATION Indoor unit EEPROM parameter error Indoor / outdoor unit
communication error Communication malfunction between adapter board and
outdoor main board The indoor fan speed is operating outside of the normal
range (for some models) Indoor room temperature sensor T1 is in open circuit
or has short circuited Evaporator coil temperature sensor T2 is in open
circuit or has short circuited Evaporator coil temperature sensor T2B is in
open circuit or has short circuited Evaporator coil temperature sensor T2A is
in open circuit or has short circuited Refrigerant Leakage Detection (for some
models) Communication error between indoor two chips Water-level alarm
malfunction The outdoor fan speed is operating outside of the normal range
(for some models) Outdoor unit EEPROM parameter error Condenser coil
temperature sensor T3 is in open circuit or has short circuited Outdoor room
temperature sensor T4 is in open circuit or has short circuited Compressor
discharge temperature sensor TP is in open circuit or has short circuited
Evaporator coil outlet temperature sensor T2B is in open circuit or has short
circuited (for free match indoor units) IPM malfunction or IGBT over-strong
current protection Over voltage or over low voltage protection Top temperature
protection of compressor or High temperature protection of IPM module Low
pressure protection (for some models) Inverter compressor drive error Outdoor
unit malfunction Low ambient temperature protection Mismatch between the new
and old platforms
SOLUTION Page 16 Page 17 Page 32 Page 22 Page 22 Page 22 Page 22 Page 22 Page 23 -Page 24 Page 20 -Page 22 Page 22 Page 22 -Page 25 Page 26 Page 27 Page 28 Page 29 Page 30 Page 30 Page 32
For other errors: The display board may display a code or a code undefined by the service manual. Ensure the code is not a temperature reading.
DISPLAY EH63
Table 7 — Error Display on Two Way Communication Wired Controller
MALFUNCTION OR PROTECTION Communication error between wire controller and
indoor unit
The other error codes displayed on the wire controller are the same from those on the unit.
SOLUTION —
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 13
40MBAB: Service Manual
Quick Maintenance by Error Code
Review the following tables for common faulty parts associated with each error
code.
PART REQUIRING REPLACEMENT
Indoor PCB Outdoor PCB Indoor fan motor T1 sensor T2 Sensor T2B Sensor T2A
Sensor T3 Sensor T4 Sensor Reactor Compressor Additional refrigerant Water-
level switch Water pump
Table 8 — Quick Maintenance by Error Code
ERROR CODE
EH 00 EL 01 EH 03 EH 60 EH 61 EH 62
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
EH 65
x x x x x x x x x x x x
EL 0C
x x x x x x x x x x x x
EH 0E
x x x x x x x x x x x
EC 53
x x x x x x x x x x x x
PART REQUIRING REPLACEMENT Indoor PCB Outdoor PCB Outdoor fan motor T3 Sensor TP Sensor Pressure sensor Reactor Compressor IPM module board Low pressure protector Additional refrigerant
Table 9 — Quick Maintenance by Error Code
EC 54 EC 51 EC 5C EC 52 EC07/71/72/73 PC 00
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
PC 01
x x x x x x x x
PC 02
x x x x x x x x
PC 04
x x x x x x x
PC 03
x x x x x x x x
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 14
40MBAB: Service Manual
Quick Maintenance by Error Code (Cont.)
Table 10 — Quick Maintenance by Error Code
PART REQUIRING REPLACEMENT Indoor PCB Outdoor PCB Outdoor fan motor
EL 16 x
x
EH 0B
x x
PC 06 x
x
PC 08/44/ 49
x
T3 Sensor TP Sensor
x
x
x
x
x
x
x
Pressure sensor Reactor
x
x
x
x
x
x
x
Compressor IPM module board Data adapter board High pressure valve assembly
x
x
x
x
x
x
x
x
x
x
x
x
High pressure protector
x
x
x
x
Low pressure protector Additional refrigerant
x
x
x
x
x
x
x
PC 0A x
x x x x x x x x x
PC 0F x
x x x x
x x x x x x x
Table 11 — Quick Maintenance by Error Code
PART REQUIRING REPLACEMENT
PC 41
PC 43
PC 10/11/12
PC 30
PC 31
PC 40
Indoor PCB Outdoor PCB Outdoor fan motor T3 Sensor TP Sensor Pressure sensor Reactor Compressor IPM module board Data adapter board High pressure valve assembly High pressure protector Low pressure protector Additional refrigerant Electric control box
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
NOTE: For certain models, the outdoor PCB can not be removed separately. In this case, the outdoor electric control box should be replaced as a whole.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 15
40MBAB: Service Manual
DIAGNOSIS AND SOLUTION
EH00 – EEPROM Parameter Error Diagnosis and Solution
Description: Indoor or outdoor PCB main chip does not receive feedback from
the EEPROM chip. Recommended parts to prepare: · Indoor PCB · Outdoor PCB
Troubleshooting and Repair:
Shut o the power and turn it on 2 minutes later.
Is it s
displaying the
No
error code?
Yes
Replace the indoor main PCB (EH 00)/ outdoor main PCB (EC 51)
NOTE: The priority is EH00 followed by EC51.
The unit is operang normally.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 16
40MBAB: Service Manual
DIAGNOSIS AND SOLUTION (CONT.)
EL01 – Indoor and Outdoor Unit Communication Error Diagnosis and Solution
Description: Indoor unit can not communicate with the outdoor unit.
Recommended parts to prepare: · Signal wires · Magnet ring · Indoor PCB ·
Outdoor PCB Troubleshooting and Repair:
XYE Communication:
Power off, then restart the unit 2 minutes later.
Yes
Check whether there is any interference.
Are there too many lamps, power transformers?
Yes
Is the signal wire too long?
No
Check whether the signal wire is
shield cable or whether the
No
shield cable is ground.
Yes
Check whether the wire has the correct polarity; P to P, Q to Q, or E to E.
No
Yes
Check whether the signal wire is broken.
Yes
No
Check whether the signal wires
No
are inserted on the PCB firmly.
Yes
Replace the indoor main PCB. Is the error resolved?
No
Replace the outdoor main PCB.
Remove the interference or add a magnet ring on the power wire.
Use a shield cable grounding.
Correct the connection .. Replace the signal wire. Pull out and re-insert.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 17
40MBAB: Service Manual
DIAGNOSIS AND SOLUTION (CONT.)
(S) Current Loop Communication:
Power off, then restart the unit af ter 2 minutes.
Does the error code disappear?
Yes
No
Solved
Check t he w iring connection bet ween indoor and out door
unit, are t hey good?
No
Correct the connection or change w ires
Yes
Measure the DC voltage between N/L2 and S (Black pin to S , Red pin to N/L2).
The value is alt ernative from negat ive to posit ive
The value is fixed and close to 0
Check t he w iring connection from indoor terminal t o indoor
PCB, are t hey good?
Repalce indoor PCB
The value is alw ays posit ive
For unit s with only one PCB
Check t he w iring connection from outdoor terminal t o outdoor PCB and wiring bet ween PCBs if t here is more t han 1 PCB
For unit s with main PCB and IPM board both
Check t he AC volt age of L, N output t o IPM board, is it same No
as pow er input?
Yes Unplug all the high voltage components connected t o main PCB such as 4
way valve, heater, AC f an one by one t o check their resist ance. Is there
any component
short circuit?
No
Check t he DC 5V, 12V from IPM board t o main PCB, are t hey normal?
No
Replace main PCB
Replace out door PCB Yes
Replace short-circuited
Yes
component and main
PCB
Yes
Replace short-circuited
component and outdoor
Yes
PCB
No
Unplug elect ronic expansion valve. Check if t he DC 5V, 12V to main
PCB are OK
Yes
Replace coil of elect ronic expansion valve
Yes
Check if t he pow er LED is on?
No
Unplug all the high voltage components connected t o main PCB such as 4 way
valve, heater, AC f an one by one t o check their resist ance. Is there any
component
short circuit? No
Unplug elect ronic expansion valve. Check if pow er LED is on?
No
Replace IPM board
Note: For certain models, outdoor PCB could not be removed separately. In this case, the outdoor electric control box should be replaced as a whole.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 18
40MBAB: Service Manual
REMARKS: · Use a multimeter to test the DC voltage between the 2 port (or S or
L2 Terminal) and the 3 port (or N or S Terminal) of the outdoor unit. · The
red pin of the multimeter connects with the 2 port (or S or L2 port) while the
black pin is for the 3 port (or N or S Terminal). · When the unit is normal
running, the voltage is moving alternately as positive values and negative
values. · If the outdoor unit malfunctions, the voltage remains a positive
value. · If the indoor unit malfunctions, the voltage does not change.
S and N or
L2 and S or
2 and 3
· Use a multimeter to test the reactor resistance which does not connect with
the capacitor. · The normal value should be around zero ohm. Otherwise, the
reactor has malfunctioned.
NOTE: The figures and values are for reference only, actual condition and
specific value may vary.
Manufacturer reserves the right to change, at any time, specifications and
designs without notice and without obligations. 19
40MBAB: Service Manual
DIAGNOSIS AND SOLUTION (CONT.)
EH03 / EC07 – Fan Speed Is Operating Outside of Normal Range / EC 71 Over
Current Failure of Outdoor DC Fan Motor / EC73 Zero-speed failure of outdoor
DC fan motor Diagnosis and Solution
Description: When the indoor / outdoor fan speed operates at too low or too
high a speed for a certain time, the unit ceases operation and the LED
displays the failure.
Recommended parts to prepare: · Connection wires · Fan assembly · Fan motor ·
PCB Troubleshooting and Repair:
Power off. Restart the unit after 2 minutes.
Does a problem remain?
NO
YES
Shut off the power supply. Rotate the fan by hand.
The unit is operating normally.
Does it turn easily?
NO
YES Check the fan motor wiring.
Inspect the unit for an obstruction and remove.
Is it improperly wired?
YES Measure the voltage for the fan motor from the PCB.
Ensure the proper connections.
Is it within normal parameters?
NO
Replace the main PCB.
YES Replace the fan motor.
NOTE: For certain models, the outdoor PCB cannot be removed separately. In this case, the outdoor electric control box should be replaced as a whole.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 20
40MBAB: Service Manual
Index:
1. Indoor DC Fan Motor (control chip is on PCB) Power on the unit and when
the unit is in the STANDBY mode, measure the pin1&pin2 voltage of CN15, and
pin3 of CN34 in the fan motor connector. If the voltage value is not in the
range shown in Table 12, the PCB has an issue and needs to be replaced.
Table 12 — CN34
NO.
COLOR
SIGNAL
VOLTAGE
1
/
/
2
Black
GND
3
Orange
PWM
5-12VDC
4
Blue
FG
0-12DVC
Table 13 — CN15
NO.
COLOR
SIGNAL
VOLTAGE
1
Yellow
208/230VAC
2
Black
208/230VAC
3
Yellow-Green
GND
2. Outdoor DC Fan Motor (control chip is in outdoor PCB)
Release the UVW connector. Measure the resistance of U-V, U-W, V-W. If the
resistance is not equal to each other, the fan motor has an issue and needs to
be replaced. Otherwise the PCB has an issue and needs to be replaced.
Fig. 17 — Outdoor DC Fan Motor
Manufacturer reserves the right to change, at any time, specifications and
designs without notice and without obligations. 21
40MBAB: Service Manual
DIAGNOSIS AND SOLUTION (CONT.)
EH60/EH61/EH62/EH65/EC53/EC52/EC54 – Open Circuit or Short Circuit of
Temperature Sensor Diagnosis and Solution
Description: If the sampling voltage is lower than 0.06V or higher than 4.94V,
the LED displays the failure. Recommended parts to prepare: · Connection wires
· Sensors · PCB Troubleshooting and Repair:
Check the connection between the temperature sensor and the PCB.
Is it properly wired?
YES Measure the sensor’s
resistance value.
NO
Ensure the proper connections.
Is it within acceptable parameters?
NO
Replace the sensor.
YES Replace the indoor PCB ((EH XX)
or the outdoor PCB (EC XX))
NOTE: The priority is EC 52 >EC 53 > EC54 > EC55 > EC 56 > EH 60 > EH61 > EH62
EH 65.
Fig. 18 — Test NOTE: For certain models, the outdoor PCB could not be removed
separately. In this case, the outdoor electric control box
should be replaced as a whole. Figure 18 and the value within are for
reference only. The actual appearance and value may vary.
Manufacturer reserves the right to change, at any time, specifications and
designs without notice and without obligations. 22
40MBAB: Service Manual
DIAGNOSIS AND SOLUTION (CONT.)
EL0C – Refrigerant Leakage Detection Diagnosis and Solution
Description: If the sampling voltage is lower than 0.06V or higher than 4.94V,
the LED displays the failure. Recommended parts to prepare: · Indoor PCB ·
Additional Refrigerant Troubleshooting and Repair:
Power off, then restart the unit 15 minutes later.
Place your hands in front of the indoor air outlet.
Is cool or hot air blowing from the indoor
air outlet?
NO Check system for leaks.
NO
Are there any leaks?
NO Charge the refrigerant correctly (about 10% of the nameplate charge).
YES
Is T2 loose ?
NO
YES
Ensure proper connections.
Is T1 too close to the evaporator?
YES
Install correctly.
NO
Replace the indoor PCB.
YES
Repair the leak and recharge the refrigerant.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 23
40MBAB: Service Manual
DIAGNOSIS AND SOLUTION (CONT.)
EH0E – Water-Level Alarm Malfunction Diagnosis and Solution
Description: If the sampling voltage is not 5V, the LED displays the failure
code. Recommended parts to prepare: · Connection wires · Water-level switch ·
Water pump · Indoor PCB Troubleshooting and Repair:
Power off, then restart the unit 2 minutes lat er.
Does a problem
remain?
YES
Is the water-level switch
inserted properly? YES
Is the water level switch broken?
YES
Replace the indoor main PCB
NO The unit is operating normally.
NO
Insert the water-level switch properly
NO Replace the water-level switch
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 24
40MBAB: Service Manual
DIAGNOSIS AND SOLUTION (CONT.)
PC 00 – IPM malfunction or IGBT over-strong current protection Diagnosis and
Solution
Description: When the voltage signal that the IPM sends to the compressor
drive chip is abnormal, the LED displays “PC 00” and the AC turns off.
Recommended parts to prepare: · Connection wires · IPM module board · Outdoor
fan assembly · Compressor · Outdoor PCB
Troubleshooting and Repair:
Check the wiring between PCB and compressor.
Does an error exist?
NO Check the IPM.
Is it in working order?
YES Check the outdoor fan and the
outdoor unit ventilation.
Is it in working order? YES
Check the compressor resistance values.
Are they within acceptable parameters?
YES Replace the outdoor PCB.
YES NO NO
NO
Ensure proper connections or replace the wires and connectors.
Replace the IPM board or replace the outdoor PCB.
Refer to the “Fan Speed is Out of Control” malfunction solution.
Replace the compressor.
NOTE: For certain models, the outdoor PCB cannot be removed separately. In this case, the outdoor electric control box should be replaced as a whole.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 25
40MBAB: Service Manual
DIAGNOSIS AND SOLUTION (CONT.)
PC 01 – Over voltage or too low voltage protection / PC 10 – Outdoor unit low
AC voltage protection / PC 11 – Outdoor unit main control board DC bus high
voltage protection / PC 12 (Outdoor unit main control board DC bus high
voltage protection / 341 MCE error Diagnosis and Solution
Description: Abnormal increases or decreases in voltage are detected by
checking the specified voltage detection circuit. Recommended parts to
prepare: · Power supply wires · IPM module board · PCB · Reactor
Troubleshooting and Repair:
Check the power supply.
Is it in working order?
NO
YES Check the connections and wires .
Are they in working order?
NO
YES
Power on and measure the voltage between P and N.
Turn off the unit.
Ensure proper connections or replace the wires.
While the unit is in STANDBY mode, is the voltage between P and N and around
DC 310V, 340V or 380V? When the unit is started,
is it in 220V~400V?
NO
Replace the IPM board.
YES Check the reactor.
Is it in working order? YES
Replace the reactor.
NO
Replace outdoor PCB.
NOTE: For certain models, the outdoor PCB could not be removed separately. In this case, the outdoor electric control box should be replaced as a whole.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 26
40MBAB: Service Manual
DIAGNOSIS AND SOLUTION (CONT.)
PC 02 – Top temperature protection of compressor or High temperature
protection of IPM module Diagnosis and Solution
Description: For some models with overload protection, if the sampling voltage
is not 5V, the LED displays the failure. If the IPM module temperature is
higher than a certain value, the LED displays the failure code.
Recommended parts to prepare: · Connection wires · High pressure protector ·
IPM module board · System blocks · Outdoor PCB
Troubleshooting and Repair:
Check if the air flow system
of the indoor and outdoor units
Yes
is obstructed.
Clear the air inlet and outlet or the indoor and outdoor unit’s heat exchanger.
No
Turn off the power supply. Wait 10 minutes and turn back on.
Yes
Check if the compressor top temperature is higher than 194°F(90°C).
Yes
Check if the refrigerant system is normal.
Yes
Check if all the connection, especially the
No
connection of OLP (Over Load Protector) No Correct the connection.
sensor is good.
Yes
Measure the resistance between the two ports of
the OLP. Is it zero?
No
Replace the OLP.
No
Yes
Replace the outdoor control PCB.
Replace the outdoor control PCB.
Repair the refrigerant system.
Check the fastening screws on the PCB and IPM radiator.
Are they secure?
YES
NO
Tighten the screws and apply silicon grease.
Replace the outdoor control PCB.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 27
40MBAB: Service Manual
DIAGNOSIS AND SOLUTION (CONT.)
PC 03 – Low Pressure Protection Diagnosis and Solution
Description: If the sampling voltage is not 5V, the LED displays a failure
code. Recommended parts to prepare: · Connection wires · Low pressure
protector · Indoor fan assembly · Outdoor PCB Troubleshooting and Repair:
Low pressure protection
Are the low pressure protector and main control board wired
properly??
No
Reconnect the low pressure protector and main control board.
Yes
Is the low pressure protector broken? Method: Disconnect the plug.
Measure the resistance of the low pressure Yes protector. If the protector is
normal, the value is 0.
No
Replace the low pressure protector.
Is the outdoor ambient temperature too low ?
Yes
Stop the unit.
No
Is the valve core of the high pressure valve fully opened?
Yes
Is the indoor fan running properly in cooling mode?
Yes
No
Open the valve core of the high
pressure valve.
Refer to the solution to the malfunction No of fan speed being out of control.
Find
the cause and resolve the problem. .
Replace outdoor main board.
Is it in working order??
No
When the refrigerant level is not
su cient, does the system function properly after more refrigerant
No
is added?
Check whether the refrigerant system is functioning properly ..
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 28
40MBAB: Service Manual
DIAGNOSIS AND SOLUTION (CONT.)
PC 04 – Inverter compressor drive error Diagnosis and Solution
Description: An abnormal inverter compressor drive is detected by a special
detection circuit, including the communication signal detection, voltage
detection, compressor rotation speed signal detection.
Recommended parts to prepare: · Connection wires · IPM module board · Outdoor
fan assembly · Compressor · Outdoor PCB Troubleshooting and Repair:
Check the wiring between the PCB and compressor.
Is it improperly wired? NO
Check the IPM.
YES
Ensure proper connections or replace
the wires and connectors.
Is it functioning properly?
NO
YES
Check the outdoor fan and the outdoor unit ventilation.
Replace the IPM board or replace the outdoor PCB.
Is it functioning properly?
NO
Please refer to “Fan Speed Malfunction”
YES
Check the compressor resistance values.
Are they within acceptable parameters?
NO
Replace the compressor.
YES Replace the outdoor PCB.
NOTE: For certain models, the outdoor PCB could not be removed separately. In
this case, the outdoor electric control box should be replaced as a whole.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 29
40MBAB: Service Manual
DIAGNOSIS AND SOLUTION (CONT.)
EC 0d – Outdoor Unit Malfunction Diagnosis and Solution
Description: The indoor unit detects the outdoor unit has an error.
Recommended parts to prepare: · Outdoor unit Troubleshooting and Repair:
Is the main board displaying an error??
Yes
Refer to the prescribed steps for resolving the
issue.
WZZ,,then restart the unit 22
No
minutes later..Does the outdoor main board display an error code a few
minutes later?
Yes
DIAGNOSIS AND SOLUTION (CONT.)
PC 0L – Low ambient temperature protection Diagnosis and Solution
Description: It is a protection function. When the compressor is off, the
outdoor ambient temperature(T4) is lower than -31°F (35°C) for 10 second, the
unit stops and displays the failure code. When the compressor is on and the
outdoor ambient temperature(T4) is lower than -40°F for 10 seconds, the unit
stops and displays the failure code. When the outdoor ambient temperature(T4)
is no lower than -25°F for 10 seconds, the unit exits protection.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 30
40MBAB: Service Manual
DIAGNOSIS AND SOLUTION (CONT.)
EH 0b – Communication error between the two indoor chips Diagnosis and
Solution
Description: Indoor PCB main chip does not receive feedback from another chip.
Recommended parts to prepare: · Indoor main board · Adapter board adapter
Troubleshooting and Repair:
Shut off the power supply and turn it on 2 minutes later.
Is it still displaying the error code?
Yes
Check the connection wires between the adaptor board
and the main board. Is it connected properly?
No
Reconnect and retry. Does the error still appear?
Yes No
Replace the transfer board. Is the system running normally?
No
Replace the indoor main board.
Yes Yes
Trouble is resolved.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 31
40MBAB: Service Manual
DIAGNOSIS AND SOLUTION (CONT.)
EL 16 – Communication malfunction between adapter board and outdoor main board
Diagnosis and Solution
Description: The adapter PCB cannot detect the main control board. Recommended
parts to prepare: · Connection wires · Adapter board · Outdoor main PCB
Troubleshooting and Repair:
Power off, then restart the unit after 3 minutes.
Does a problem remain?
NO
YES Check the wirings and connections.
The unit is operating normally.
Are all the connections
NO
good?
YES
Replace the adapter main PCB.
Ensure proper connections.
Does the error still exist?
YES Replace the outdoor main control board.
NO
The problem is solved.
DIAGNOSIS AND SOLUTION (CONT.)
FL 09 – Indoor and outdoor mismatch malfunction Diagnosis and Solution
Description: Indoor and outdoor units are mismatched, the LED displays this
code. Replace the matching indoor or outdoor unit.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 32
40MBAB: Service Manual
DIAGNOSIS AND SOLUTION (CONT.)
P5 – Indoor Units Mode Conflict (Match with a Multi Outdoor Unit) Diagnosis
and Solution
Description: The indoor units cannot work in the COOLING and HEATING modes at
the same time. The HEATING mode has the priority. Suppose the indoor unit (A)
is working in the COOLING mode or the FAN mode and the indoor unit (B) is set
to the HEATING mode. The indoor unit (A) turns off and indoor unit (B) keeps
running in the HEATING mode. Suppose the indoor unit (A) is working in the
HEATING mode, and indoor unit (B) is set to COOLING mode or the FAN mode, then
indoor unit (B) changes to STANDBY and indoor unit (A) remains in the current
mode.
Table 14 — Indoor Units Mode Conflict
COOLING MODE HEATING MODE
FAN OFF
COOLING MODE No Yes No No
HEATING MODE Yes No Yes No
FAN No Yes No No
OFF No No No No
NOTE:
No: No mode conflict Yes: Mode conflict
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 33
40MBAB: Service Manual
DIAGNOSIS AND SOLUTION (CONT.)
Temperature Sensor Check
WARNING
Turn off all power supplies or disconnect all wires to avoid electric shock.
Operate after compressor and coil have returned to normal temperature in case
of injury.
1. Disconnect the temperature sensor from the PCB. 2. Measure the sensor’s
resistance value using a multi-meter. 3. Check the corresponding temperature
sensor resistance value.
Fig. 19 — Temperature Sensor Check NOTE: Figure 19 is for reference only. The
actual condition and specific value may vary according to temperature.
Manufacturer reserves the right to change, at any time, specifications and
designs without notice and without obligations. 34
40MBAB: Service Manual
Compressor Check
1. Disconnect the compressor power cord from the outdoor PCB. 2. Measure the
resistance value of each winding using a multi-meter. 3. Check the resistance
value of each winding using Figure 20.
Fig. 20 — Input Terminal (typical)
Manufacturer reserves the right to change, at any time, specifications and
designs without notice and without obligations. 35
40MBAB: Service Manual
APPENDICES
Appendix 1
Table 15 — Temperature Sensor Resistance Value Table for T1, T2, T3, T4 (°C–K)
°C
°F
K OHM
°C
°F
K OHM
°C
°F
K OHM
°C
° F
-20
-4
115.266
20
68
12.6431
60
140
2.35774
100
212
-19
-2
108.146
21
70
12.0561
61
142
2.27249
101
214
-18
0
101.517
22
72
11.5
62
144
2.19073
102
216
-17
1
96.3423
23
73
10.9731
63
145
2.11241
103
217
-16
3
89.5865
24
75
10.4736
64
147
2.03732
104
219
-15
5
84.219
25
77
10
65
149
1.96532
105
221
-14
7
79.311
26
79
9.55074
66
151
1.89627
106
223
-13
9
74.536
27
81
9.12445
67
153
1.83003
107
225
-12
10
70.1698
28
82
8.71983
68
154
1.76647
108
226
-11
12
66.0898
29
84
8.33566
69
156
1.70547
109
228
-10
14
62.2756
30
86
7.97078
70
158
1.64691
110
230
-9
16
58.7079
31
88
7.62411
71
160
1.59068
111
232
-8
18
56.3694
32
90
7.29464
72
162
1.53668
112
234
-7
19
52.2438
33
91
6.98142
73
163
1.48481
113
235
-6
21
49.3161
34
93
6.68355
74
165
1.43498
114
237
-5
23
46.5725
35
95
6.40021
75
167
1.38703
115
239
-4
25
44
36
97
6.13059
76
169
1.34105
116
241
-3
27
41.5878
37
99
5.87359
77
171
1.29078
117
243
-2
28
39.8239
38
100
5.62961
78
172
1.25423
118
244
-1
30
37.1988
39
102
5.39689
79
174
1.2133
119
246
0
32
35.2024
40
104
5.17519
80
176
1.17393
120
248
1
34
33.3269
41
106
4.96392
81
178
1.13604
121
250
2
36
31.5635
42
108
4.76253
82
180
1.09958
122
252
3
37
29.9058
43
109
4.5705
83
181
1.06448
123
253
4
39
28.3459
44
111
4.38736
84
183
1.03069
124
255
5
41
26.8778
45
113
4.21263
85
185
0.99815
125
257
6
43
25.4954
46
115
4.04589
86
187
0.96681
126
259
7
45
24.1932
47
117
3.88673
87
189
0.93662
127
261
8
46
22.5662
48
118
3.73476
88
190
0.90753
128
262
9
48
21.8094
49
120
3.58962
89
192
0.8795
129
264
10
50
20.7184
50
122
3.45097
90
194
0.85248
130
266
11
52
19.6891
51
124
3.31847
91
196
0.82643
131
268
12
54
18.7177
52
126
3.19183
92
198
0.80132
132
270
13
55
17.8005
53
127
3.07075
93
199
0.77709
133
271
14
57
16.9341
54
129
2.95896
94
201
0.75373
134
273
15
59
16.1156
55
131
2.84421
95
203
0.73119
135
275
16
61
15.3418
56
133
2.73823
96
205
0.70944
136
277
17
63
14.6181
57
135
2.63682
97
207
0.68844
137
279
18
64
13.918
58
136
2.53973
98
208
0.66818
138
280
19
66
13.2631
59
138
2.44677
99
210
0.64862
139
282
K OHM 0.62973 0.61148 0.59386 0.57683 0.56038 0.54448 0.52912 0.51426 0.49989
0.486 0.47256 0.45957 0.44699 0.43482 0.42304 0.41164 0.4006 0.38991 0.37956
0.36954 0.35982 0.35042 0.3413 0.33246 0.3239 0.31559 0.30754 0.29974 0.29216
0.28482 0.2777 0.27078 0.26408 0.25757 0.25125 0.24512 0.23916 0.23338 0.22776
0.22231
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 36
40MBAB: Service Manual
Appendix 2
Table 16 — Temperature Sensor Resistance Value Table for T5 (TP) (°C–K)
° C
° F
K OHM
° C
° F
K OHM
° C
° F
K OHM
° C
° F
-20
-4
542.7
20
68
68.66
60
140
13.59
100
212
-19
-2
511.9
21
70
65.62
61
142
13.11
101
214
-18
0
483
22
72
62.73
62
144
12.65
102
216
-17
1
455.9
23
73
59.98
63
145
12.21
103
217
-16
3
430.5
24
75
57.37
64
147
11.79
104
219
-15
5
406.7
25
77
54.89
65
149
11.38
105
221
-14
7
384.3
26
79
52.53
66
151
10.99
106
223
-13
9
363.3
27
81
50.28
67
153
10.61
107
225
-12
10
343.6
28
82
48.14
68
154
10.25
108
226
-11
12
325.1
29
84
46.11
69
156
9.902
109
228
-10
14
307.7
30
86
44.17
70
158
9.569
110
230
-9
16
291.3
31
88
42.33
71
160
9.248
111
232
-8
18
275.9
32
90
40.57
72
162
8.94
112
234
-7
19
261.4
33
91
38.89
73
163
8.643
113
235
-6
21
247.8
34
93
37.3
74
165
8.358
114
237
-5
23
234.9
35
95
35.78
75
167
8.084
115
239
-4
25
222.8
36
97
34.32
76
169
7.82
116
241
-3
27
211.4
37
99
32.94
77
171
7.566
117
243
-2
28
200.7
38
100
31.62
78
172
7.321
118
244
-1
30
190.5
39
102
30.36
79
174
7.086
119
246
0
32
180.9
40
104
29.15
80
176
6.859
120
248
1
34
171.9
41
106
28
81
178
6.641
121
250
2
36
163.3
42
108
26.9
82
180
6.43
122
252
3
37
155.2
43
109
25.86
83
181
6.228
123
253
4
39
147.6
44
111
24.85
84
183
6.033
124
255
5
41
140.4
45
113
23.89
85
185
5.844
125
257
6
43
133.5
46
115
22.89
86
187
5.663
126
259
7
45
127.1
47
117
22.1
87
189
5.488
127
261
8
46
121
48
118
21.26
88
190
5.32
128
262
9
48
115.2
49
120
20.46
89
192
5.157
129
264
10
50
109.8
50
122
19.69
90
194
5
130
266
11
52
104.6
51
124
18.96
91
196
4.849
12
54
99.69
52
126
18.26
92
198
4.703
13
55
95.05
53
127
17.58
93
199
4.562
14
57
90.66
54
129
16.94
94
201
4.426
15
59
86.49
55
131
16.32
95
203
4.294
16
61
82.54
56
133
15.73
96
205
4.167
17
63
78.79
57
135
15.16
97
207
4.045
18
64
75.24
58
136
14.62
98
208
3.927
19
66
71.86
59
138
14.09
99
210
3.812
K OHM 3.702 3.595 3.492 3.392 3.296 3.203 3.113 3.025 2.941 2.86 2.781 2.704 2.63 2.559 2.489 2.422 2.357 2.294 2.233 2.174 2.117 2.061 2.007 1.955 1.905 1.856 1.808 1.762 1.717 1.674 1.632
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 37
40MBAB: Service Manual
DISASSEMBLY INSTRUCTIONS
Electrical Parts (Anti-static gloves must be worn)
PROCEDURES
ILLUSTRATION
1. Remove the 2 screws of the upper cover plate assembly then remove it.
2. Remove 2 screws then unplug the plugs. 3. Pull out the electric control
box subassembly.
Manufacturer reserves the right to change, at any time, specifications and
designs without notice and without obligations. 38
40MBAB: Service Manual
DISASSEMBLY INSTRUCTIONS (CONT.)
Electrical Parts (Anti-static gloves must be worn) (CONT.)
PROCEDURES
ILLUSTRATION
4. Remove the 2 screws and 1 ground screw.
5. Unplug the plugs then remove the main control board subassembly.
6. Release the data transfer module control board screw (1) and remove the
board.
7. Release the 2 screws then remove the transformer.
Manufacturer reserves the right to change, at any time, specifications and
designs without notice and without obligations. 39
40MBAB: Service Manual
DISASSEMBLY INSTRUCTIONS (CONT.)
Fan Motor and Fan
PROCEDURES
ILLUSTRATION
1. Remove the 2 fan assembly screws.
2. Remove the fan assembly.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 40
40MBAB: Service Manual
DISASSEMBLY INSTRUCTIONS (CONT.)
Fan Motor and Fan (Cont)
PROCEDURES
ILLUSTRATION
3. Release the 3 nuts securing the fan motor then remove the fan motor.
4. Release the 1 nut securing the fan and then remove the fan.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 41
40MBAB: Service Manual
DISASSEMBLY INSTRUCTIONS (CONT.)
Evaporator
PROCEDURES
ILLUSTRATION
1. Remove the cover plate.
2. Remove the cover plate assembly screws (3).
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 42
40MBAB: Service Manual
DISASSEMBLY INSTRUCTIONS (CONT.)
Evaporator (Cont.)
PROCEDURES
ILLUSTRATION
3. Remove the evaporator (with a water collector assembly).
4. Remove the water collector assembly screws (2). 5. Release the evaporator and water collector assembly.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. 43
40MBAB: Service Manual
© 2022 Carrier. All rights reserved.
Edition Date: 09/22
Catalog No: SG-40MBAB-01
Replaces: NEW
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
44
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>