Anybus 40-SER-ETH-A Communicator Common Ethernet Instruction Manual
- June 15, 2024
- Anybus
Table of Contents
- General Safety
- Intended Use
- Installation
- DIN-Rail Mounting
- Pin Connector
- RJ45 Connector
- Pin Connector
- Pin D-Sub Connector
- Technical Specifications
- CE Compliance
- UL Ordinary Locations (OrdLoc)
- For Information in Other Languages
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Anybus 40-SER-ETH-A Communicator Common Ethernet
General Safety
CAUTION
This equipment contains parts that can be damaged by electrostatic discharge
(ESD). Use ESD prevention measures to avoid damage.
CAUTION
To avoid system damage, the equipment should be connected to ground.
CAUTION
If this equipment is used in a manner not specified by the manufacturer, the
protection provided by the equipment may be impaired.
Intended Use
The intended use of this equipment is as a communication interface and gateway. The equipment receives and transmits data on various physical layers and connection types.
Model Identification
Hardware description | Model ID |
---|---|
Serial to Ethernet. With rotary switches | 40-SER-ETH-A |
Serial to Ethernet. Without rotary switches | 40-SER-ETH-B |
Serial to Profibus. With rotary switches | 40-SER-PDP-A |
Serial to Profibus. Without rotary switches | 40-SER-PDP-B |
Ethernet to Profibus. With rotary switches | 40-ETH-PDP-A |
Ethernet to Profibus. Without rotary switches | 40-ETH-PDP-B |
Ethernet to Ethernet. With rotary switches | 40-ETH-ETH-A, 40-ETH-ETH-A-60* |
Ethernet to Ethernet. Without rotary switches | 40-ETH-ETH-B, 40-ETH-ETH-B-60* |
*Other CPU mount option.
Installation
Make sure that you have all the necessary information about the capabilities and restrictions of your local network environment before installation.
- Tightening torque for 3-pin and 7-pin connector: 0.5-0.8 Nm.
- Use minimum 90 °C copper (Cu) wire only.
- Equipment to be supplied by Class 2 Power Source in accordance with the NEC.
- The equipment is considered as open type and shall be installed in a suitable end enclosure providing mechanical protection.
- Use in Overvoltage Category I Pollution Degree 2 Environment conforming to EN 60664-1.
- This equipment is designed to comply as Class III equipment according to 61010-2-201.
DIN-Rail Mounting
Pin Connector
| Pin|
Data
---|---|---
1| RS232 Rx Input
2| RS232 Tx Output
3| Functional Earth (FE)
4| Signal GND
5| RS485- B
6| RS485+ A
7| +5 V OUT
RJ45 Connector
| Pin| Data| Pin| Data
---|---|---|---|---
1| TD+| 5| N/A
2| TD-| 6| RD-
3| RD+| 7| N/A
4| N/A| 8| N/A
Pin Connector
**** | Pin | Data |
---|---|---|
1 | 12-30 VDC | |
2 | Ground (GND) | |
3 | Functional Earth (FE) |
Pin D-Sub Connector
**** | Pin | Data |
---|---|---|
1 | Shield | |
3 | B-line | |
4 | Request to Send (RTS) | |
5 | GND bus | |
6 | +5 V bus cut | |
8 | A-line | |
2, 7, 9 | NC |
Technical Specifications
Model identification| 40-SER-ETH-A
40-SER-ETH-B
| 40-SER-PDP-A
40-SER-PDP-B
| 40-ETH-PDP-A
40-ETH-PDP-B
| 40-ETH-ETH-A
40-ETH-ETH-B
40-ETH-ETH-A-60
40-ETH-ETH-B-60
---|---|---|---|---
Configuration connector| RJ45
Upper connector| 7-pin screw connector| RJ45 x 2
Lower connector| RJ45 x 2| 9-pin D-sub| RJ45 x 2
Power connector| 3-pin screw connector
Power supply| 12-30 VDC, Reverse voltage protection and short circuit
protection
Power consumption| Typical: 160 mA @ 24 V Max: 400 mA @ 12 V
Storage temperature| -40 to +85 °C
Operating temperature| -25 to +70 °C
Humidity| EN 600068-2-78: Damp heat, +40°C, 93% humidity for 4 days
EN 60068-2-30: Damp heat, +25°C – +55°C, 95% RH, 2 cycles
Vibration| See datasheet
Housing material| Plastic, See datasheet for details
Protection class| IP20
Product weight| 150 g
Dimensions| 27 x 144 x 98 mm (W x H x D) with connectors included
Mounting| DIN-rail
CE Compliance
This product is in compliance with the EMC Directive 2014/30/EU and the RoHS Directive 2011/65/EU with amendment 2015/863 through conformance with applicable standards. The full text of the Declaration of Conformity is available at www.anybus.com/support.
UKCA Compliance
This product is in compliance with the Electromagnetic Compatibility Regulations 2016. The full text of the Declaration of Conformity is available at www.anybus.com/support.
Disposal and Recycling
You must dispose of this equipment properly according to local laws and regulations. Because this equipment contains electronic components, it must be disposed of separately from household waste. When this equipment reaches its end of life, contact local authorities to learn about disposal and recycling options, or return the equipment to HMS. For more information, see www.anybus.com.
UL Ordinary Locations (OrdLoc)
This equipment is certified for use in ordinary locations in compliance with the following standards:
- UL 61010-1 SAFETY REQUIREMENTS FOR ELECTRICAL EQUIPMENT FOR MEASUREMENT, CONTROL, AND LABORATORY USE – PART 1: GENERAL REQUIREMENTS – Edition 3
- UL 61010-2-201 STANDARD FOR SAFETY REQUIREMENTS FOR ELECTRICAL EQUIPMENT FOR MEASUREMENT, CONTROL, AND LABORATORY USE – PART 2-201: PARTICULAR REQUIREMENTS FOR CONTROL EQUIPMENT – Edition 2
- CSA C22.2 NO. 61010-1 SAFETY REQUIREMENTS FOR ELECTRICAL EQUIPMENT FOR MEASUREMENT, CONTROL, AND LABORATORY USE. PT. 1, GENERAL REQUIREMENTS – Edition 3
- CSA C22.2 NO. 61010-2-201 SAFETY REQUIREMENTS FOR ELECTRICAL EQUIPMENT FOR MEASUREMENT, CONTROL, AND LABORATORY USE – PART 2-201: PARTICULAR REQUIREMENTS FOR CONTROL EQUIPMENT – Edition 2
The certification number for the OrdLoc certified equipment is: E214107
According to the standards listed above, the equipment is certified with the
following marking:
For Information in Other Languages
To download a language version of this Safety and Compliance Information: 1.
Find the product article number on the product cover. 2.
Scan the QR code to access
www.anybus.com/support. 3. Enter the product
article number to search for the product specific support web page.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>