Mean Well EDR-150-24 Series 150W Single Output Industrial Owner’s Manual
- June 15, 2024
- MEAN WELL
Table of Contents
Mean Well EDR-150-24 Series 150W Single Output Industrial
Product Information
- The EDR-150-24 is an economical slim DIN rail power supply series that provides up to 156W of power at 230VAC input.
- It is designed to be installed on TS-35/7.5 or TS-35/15 mounting rails.
- The power supply has a width of 40mm, allowing for space-saving installation inside cabinets.
- It features universal AC input with a range of 90VAC to 264VAC and conforms to BS EN/EN61000-3-2 (80% Load), which is the European Union regulation for harmonic current.
Features
- Universal AC input / Full range
- Protections: Short circuit / Overload / Over voltage- Over temperature
 
- Cooling by free air convection
- Can be installed on DIN rail TS-35/7.5 or 15
- UL 508 (industrial control equipment) approved
- BS EN/EN61000-6-2(BS EN/EN50082-2) industrial immunity level
- 100% full load burn-in test
- 2 years warranty
Applications
- Industrial control system
- Semiconductor fabrication equipment
- Factory automation
- Electro-mechanical apparatus
GTIN CODE
- MW Search: https://www.meanwell.com/serviceGTIN.aspx.
Description
- EDR-150-24 is one economical slim DIN rail power supply series, providing up to 156W at 230VAC input.
- This series is adapt to be installed on TS-35/7.5 or TS-35/15 mounting rails.
- The body is designed 40mm in width, which allows space saving inside the cabinets.
- The entire series adopts the full range AC input from 90VAC to 264VAC and conforms to BS EN/EN61000-3-2(≤80% Load), the norm the European Union regulates for harmonic current.
- EDR-150-24 is designed with metal housing that enhances the unit’s power dissipation.
- With working efficiency up to 87%, the entire series can operate at the ambient temperature between -20°C and 60°C under air convection.
- It is equipped with constant current mode for over-load protection, fitting various inductive or capacitive applications.
- The complete protection functions and relevant certificates for industrial control apparatus (UL508, TUV BS EN/EN62368-1, and etc.) make EDR-150-24 a very competitive power supply solution for industrial applications.
Model Encoding
SPECIFICATION
| MODEL | EDR-150-24 | 
|---|
OUTPUT
|  DC VOLTAGE|  24V
RATED CURRENT|  6.5A / 230VAC       5.2A / 115VAC
CURRENT RANGE|  0 ~ 6.5A / 230VAC      0 ~ 5.2A / 115VAC
RATED POWER|  156W / 230VAC      125W / 115VAC
RIPPLE & NOISE (max.) **Note.2|  150mVp-p
VOLTAGE ADJ. RANGE|  24 ~ 28V
VOLTAGE TOLERANCE Note.3|  ±1.0%
LINE REGULATION|  ±0.5%
LOAD REGULATION|  ±1.0%
SETUP, RISE TIME|  1500ms, 60ms/230VAC        3000ms, 60ms/115VAC at full
load
HOLD UP TIME (Typ.)**|  16ms/230VAC         10ms/115VAC at full load  
INPUT
|  VOLTAGE RANGE Note.6|  90 ~ 264VAC       127 ~ 370VDC [DC input
operation possible by connecting AC/L(+), AC/N(-)]
FREQUENCY RANGE|  47 ~ 63Hz
EFFICIENCY (Typ.)|  87%
AC CURRENT (Typ.)|  2.6A/115VAC        1.7A/230VAC
INRUSH CURRENT (Typ.)|  20A/115VAC        35A/230VAC
LEAKAGE CURRENT|  <1mA / 240VAC  
PROTECTION
| ****
OVERLOAD Note.7
| 105 ~ 130% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed / 230VAC
105 ~ 150% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed / 115VAC
OVER VOLTAGE
|  29 ~ 33V
Protection type : Shut down o/p voltage, re-power on to recover
OVER TEMPERATURE|  Shut down o/p voltage, re-power on to recover  
ENVIRONMENT
|  WORKING TEMP.|  -20 ~ +60℃ (Refer to “Derating Curve”)
WORKING HUMIDITY|  20 ~ 95% RH non-condensing
STORAGE TEMP., HUMIDITY|  -40 ~ +85℃, 10 ~ 95% RH
TEMP. COEFFICIENT|  ±0.03%/℃ (0 ~ 50℃)
VIBRATION|  Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X,
Y, Z axes; Mounting: Compliance to IEC60068-2-6  
SAFETY & **EMC**
(Note 4)
|  SAFETY STANDARDS|  UL508, TUV BS EN/EN62368-1, EAC TP TC 004, BSMI
CNS14336-1 approved;(meet BS EN/EN60204-1)
WITHSTAND VOLTAGE|  I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
ISOLATION RESISTANCE|  I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25℃/
70% RH  
EMC EMISSION
| Compliance to BS EN/EN55032 (CISPR32) Class A, BS EN/EN61000-3-2, Class A (≦80% Load), BS EN/EN61000-3-3, EAC TP TC 020, CNS13438 Class A
EMC IMMUNITY
| Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11, BS EN/EN55035, BS EN/EN61000-6-2 (BS EN/EN50082-2),
heavy industry level, EAC TP TC 020
OTHERS
|  MTBF|  2717.1K hrs min.     Telcordia SR-332 (Bellcore) ; 472.5K hrs
min.      MIL-HDBK-217F (25℃)
DIMENSION|  40125.2113.5mm (WHD)
PACKING|  0.6Kg; 20pcs/13Kg/1.16CUFT  
NOTE
| 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.
5. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power. In case the adjacent device is a heat source, 15mm clearance is recommended.
6. Derating may be needed under low input voltage. Please check the derating curve for more details.
7. Hiccup mode at 90~100VAC, recovers automatically after fault condition is removed.
8. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).
※ Product Liability Disclaimer:For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx
Block Diagram
Derating Curve
Static Characteristics
Mechanical Specification
Dimensions
Installation Instruction
- This series fits DIN rail TS35/7.5 or TS35/15.
- For installation details, please refer to the Instruction manual.
Installation Manual
- Please refer to: http://www.meanwell.com/manual.html.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>