Mean Well EDR-150-24 Series 150W Single Output Industrial Owner’s Manual

June 15, 2024
MEAN WELL

Mean Well EDR-150-24 Series 150W Single Output Industrial

Product Information

  • The EDR-150-24 is an economical slim DIN rail power supply series that provides up to 156W of power at 230VAC input.
  • It is designed to be installed on TS-35/7.5 or TS-35/15 mounting rails.
  • The power supply has a width of 40mm, allowing for space-saving installation inside cabinets.
  • It features universal AC input with a range of 90VAC to 264VAC and conforms to BS EN/EN61000-3-2 (80% Load), which is the European Union regulation for harmonic current.

Features

  • Universal AC input / Full range
  • Protections: Short circuit / Overload / Over voltage
    • Over temperature
  • Cooling by free air convection
  • Can be installed on DIN rail TS-35/7.5 or 15
  • UL 508 (industrial control equipment) approved
  • BS EN/EN61000-6-2(BS EN/EN50082-2) industrial immunity level
  • 100% full load burn-in test
  • 2 years warranty

Applications

  • Industrial control system
  • Semiconductor fabrication equipment
  • Factory automation
  • Electro-mechanical apparatus

GTIN CODE

Description

  • EDR-150-24 is one economical slim DIN rail power supply series, providing up to 156W at 230VAC input.
  • This series is adapt to be installed on TS-35/7.5 or TS-35/15 mounting rails.
  • The body is designed 40mm in width, which allows space saving inside the cabinets.
  • The entire series adopts the full range AC input from 90VAC to 264VAC and conforms to BS EN/EN61000-3-2(≤80% Load), the norm the European Union regulates for harmonic current.
  • EDR-150-24 is designed with metal housing that enhances the unit’s power dissipation.
  • With working efficiency up to 87%, the entire series can operate at the ambient temperature between -20°C and 60°C under air convection.
  • It is equipped with constant current mode for over-load protection, fitting various inductive or capacitive applications.
  • The complete protection functions and relevant certificates for industrial control apparatus (UL508, TUV BS EN/EN62368-1, and etc.) make EDR-150-24 a very competitive power supply solution for industrial applications.

Model Encoding

SPECIFICATION

MODEL EDR-150-24







OUTPUT

| DC VOLTAGE| 24V
RATED CURRENT| 6.5A / 230VAC       5.2A / 115VAC
CURRENT RANGE| 0 ~ 6.5A / 230VAC      0 ~ 5.2A / 115VAC
RATED POWER| 156W / 230VAC      125W / 115VAC
RIPPLE & NOISE (max.) **Note.2| 150mVp-p
VOLTAGE ADJ. RANGE| 24 ~ 28V
VOLTAGE TOLERANCE Note.3| ±1.0%
LINE REGULATION| ±0.5%
LOAD REGULATION| ±1.0%
SETUP, RISE TIME| 1500ms, 60ms/230VAC        3000ms, 60ms/115VAC at full load
HOLD UP TIME (Typ.)**| 16ms/230VAC         10ms/115VAC at full load




INPUT

| VOLTAGE RANGE Note.6| 90 ~ 264VAC       127 ~ 370VDC [DC input operation possible by connecting AC/L(+), AC/N(-)]
FREQUENCY RANGE| 47 ~ 63Hz
EFFICIENCY (Typ.)| 87%
AC CURRENT (Typ.)| 2.6A/115VAC        1.7A/230VAC
INRUSH CURRENT (Typ.)| 20A/115VAC        35A/230VAC
LEAKAGE CURRENT| <1mA / 240VAC




PROTECTION

| ****


OVERLOAD Note.7

| 105 ~ 130% rated output power

Protection type : Constant current limiting, recovers automatically after fault condition is removed / 230VAC

105 ~ 150% rated output power

Protection type : Constant current limiting, recovers automatically after fault condition is removed / 115VAC


OVER VOLTAGE

| 29 ~ 33V
Protection type : Shut down o/p voltage, re-power on to recover
OVER TEMPERATURE| Shut down o/p voltage, re-power on to recover




ENVIRONMENT

| WORKING TEMP.| -20 ~ +60℃ (Refer to “Derating Curve”)
WORKING HUMIDITY| 20 ~ 95% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +85℃, 10 ~ 95% RH
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 50℃)
VIBRATION| Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6



SAFETY & **EMC**

(Note 4)

| SAFETY STANDARDS| UL508, TUV BS EN/EN62368-1, EAC TP TC 004, BSMI CNS14336-1 approved;(meet BS EN/EN60204-1)
WITHSTAND VOLTAGE| I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
ISOLATION RESISTANCE| I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25℃/ 70% RH


EMC EMISSION

| Compliance to BS EN/EN55032 (CISPR32) Class A, BS EN/EN61000-3-2, Class A (≦80% Load), BS EN/EN61000-3-3, EAC TP TC 020, CNS13438 Class A


EMC IMMUNITY

| Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11, BS EN/EN55035, BS EN/EN61000-6-2 (BS EN/EN50082-2),

heavy industry level, EAC TP TC 020


OTHERS

| MTBF| 2717.1K hrs min.     Telcordia SR-332 (Bellcore) ; 472.5K hrs min.      MIL-HDBK-217F (25℃)
DIMENSION| 40125.2113.5mm (WHD)
PACKING| 0.6Kg; 20pcs/13Kg/1.16CUFT







NOTE

| 1.  All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.

2.  Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.

3.  Tolerance : includes set up tolerance, line regulation and load regulation.

4.  The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.

5.  Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power. In case the adjacent device is a heat source, 15mm clearance is recommended.

6.  Derating may be needed under low input voltage. Please check the derating curve for more details.

7.  Hiccup mode at 90~100VAC, recovers automatically after fault condition is removed.

8.  The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).

※ Product Liability Disclaimer:For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx

Block Diagram

Derating Curve

Static Characteristics

Mechanical Specification

Dimensions

Installation Instruction

  • This series fits DIN rail TS35/7.5 or TS35/15.
  • For installation details, please refer to the Instruction manual.

Installation Manual

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

MEAN WELL User Manuals

Related Manuals