MEAN WELL NDR-75-12 75W Series Single Output Industrial DIN RAIL Owner’s Manual

June 15, 2024
MEAN WELL

MEAN WELL NDR-75-12 75W Series Single Output Industrial DIN RAIL

Product Information

The 75W Single Output Industrial DIN RAIL (NDR-75 series) is a power supply unit designed for industrial control systems. It offers universal AC input and full range capabilities, making it suitable for various applications such as semiconductor fabrication equipment, factory automation, and electro- mechanical apparatus.

Key Features

  • Short circuit, overload, over voltage, and over temperature protections
  • Cooling by free air convection
  • Can be installed on DIN rail TS-35/7.5 or 15
  • UL 508 (industrial control equipment) approved
  • BS EN/EN61000-6-2(BS EN/EN50082-2) industrial immunity level
  • 100% full load burn-in test
  • 3 years warranty

Product Specifications

Model Encoding Output Voltage Output Wattage
NDR-75-12 12V 75.6W
NDR-75-24 24V 76.8W
NDR-75-48 48V 76.8W

Product Usage Instructions

1. Ensure that the power supply unit is installed on a DIN rail TS-35/7.5 or 15, following the provided installation instructions.

2. Connect the AC input to a universal AC source with a voltage range of 90-264VAC or a DC source with a voltage range of 127-370VDC.

3. Connect the output terminals of the power supply unit to the appropriate devices or equipment requiring power.

4. Before turning on the power supply unit, verify that all connections are secure and properly insulated.

5. Turn on the power supply unit using the power switch.

6. Monitor the output voltage and ensure it is within the desired range for your application.

7. In case of any abnormal conditions such as short circuit, overload, over voltage, or over temperature, the power supply unit will automatically protect the connected devices. Take necessary actions to resolve the issue and prevent damage to the equipment.

Note: For detailed information on installation, operation, and safety precautions, refer to the user’s manual provided with the product.

Features

  • Universal AC input / Full range
  • Protections: Short circuit / Overload / Over voltage
  • Over temperature
  • Cooling by free air convection
  • Can be installed on DIN rail TS-35/7.5 or 15
  • UL 508 (industrial control equipment) approved
  • BS EN/EN61000-6-2(BS EN/EN50082-2) industrial immunity level
  • 100% full load burn-in test
  • 3 years warranty

Applications

  • Industrial control system
  • Semiconductor fabrication equipment
  • Factory automation
  • Electro-mechanical apparatus

GTIN CODE

Description

  • NDR-75 is one economical slim 75W Din rail power supply series, adapt to be installed on TS-35/7.5 or TS-35/15 mounting rails.
  • The body is designed 32mm in width, which allows space saving inside the cabinets.
  • The entire series adopts the full range AC input from 90VAC to 264VAC and conforms to BS EN/EN61000-3-2, the norm the European Union regulates for harmonic current.
  • NDR-75 is designed with metal housing that enhances the unit’s power dissipation. With working efficiency up to 89%, the entire series can operate at the ambient temperature between -20°C and 70°C under air convection.
  • It is equipped with constant current mode for over-load protection, fitting various inductive or capacitive applications.
  • The complete protection functions and relevant certificates for industrial control apparatus (UL508, TUV BS EN/EN62368-1, and etc.) make NDR-75 a very competitive power supply solution for industrial applications.

Model Encoding

SPECIFICATIONS

MODEL NDR-75-12 NDR-75-24 NDR-75-48






OUTPUT

| DC VOLTAGE| 12V| 24V| 48V
RATED CURRENT| 6.3A| 3.2A| 1.6A
CURRENT RANGE| 0 ~ 6.3A| 0 ~ 3.2A| 0 ~ 1.6A
RATED POWER| 75.6W| 76.8W| 76.8W
RIPPLE & NOISE (max.) **Note.2| 80mVp-p| 120mVp-p| 150mVp-p
VOLTAGE ADJ. RANGE| 12 ~ 14V| 24 ~ 28V| 48 ~ 55V
VOLTAGE TOLERANCE Note.3| ±2.0%| ±1.0%| ±1.0%
LINE REGULATION| ±0.5%| ±0.5%| ±0.5%
LOAD REGULATION| ±1.0%| ±1.0%| ±1.0%
SETUP, RISE TIME| 1200ms, 60ms/230VAC        2000ms, 60ms/115VAC at full load
HOLD UP TIME (Typ.)**| 60ms/230VAC       12ms/115VAC at full load





INPUT

| VOLTAGE RANGE Note.6| 90 ~ 264VAC        127 ~ 370VDC [DC input operation possible by connecting AC/L(+), AC/N(-)]
FREQUENCY RANGE| 47 ~ 63Hz
EFFICIENCY (Typ.)| 85.5%| 88%| 89%
AC CURRENT (Typ.)| 1.45A/115VAC        0.9A/230VAC
INRUSH CURRENT (Typ.)| 20A/115VAC        35A/230VAC
LEAKAGE CURRENT| <1mA / 240VAC





PROTECTION

| ****

OVERLOAD

| 105 ~ 130% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed


OVER VOLTAGE

| 14 ~ 17V| 29 ~ 33V| 56 ~ 65V
Protection type : Shut down o/p voltage, re-power on to recover
OVER TEMPERATURE| Protection type : Shut down o/p voltage, re-power on to recover




ENVIRONMENT

| WORKING TEMP.| -20 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY| 20 ~ 95% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +85℃, 10 ~ 95% RH
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 50℃)
VIBRATION| Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6


SAFETY & EMC

(Note 4)

| SAFETY STANDARDS| UL508, TUV BS EN/EN62368-1, EAC TP TC 004 approved;(meet BS EN/EN60204-1)
WITHSTAND VOLTAGE| I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
ISOLATION RESISTANCE| I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25℃/ 70% RH
EMC EMISSION| Compliance to BS EN/EN55032 (CISPR32), BS EN/EN61204-3 Class B, BS EN/EN61000-3-2,-3, EAC TP TC 020


EMC IMMUNITY

| Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11, BS EN/EN55035, BS EN/EN61000-6-2 (BS EN/EN50082-2),

BS EN/EN61204-3, heavy industry level, EAC TP TC 020


OTHERS

| MTBF| 2757.3K hrs min.     Telcordia SR-332 (Bellcore) ; 486.2K hrs min.    MIL-HDBK-217F (25℃)
DIMENSION| 32125.2102mm (WHD)
PACKING| 0.51Kg; 28pcs/15.3Kg/1.22CUFT


NOTE

| 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.

2. Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.

3. Tolerance : includes set up tolerance, line regulation and load regulation.

4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.

5. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power. In case the adjacent device is a heat source, 15mm clearance is recommended.

6. Derating may be needed under low input voltage. Please check the derating curve for more details.

7. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).

※ Product Liability Disclaimer:For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx

Block Diagram

Derating Curve

Static Characteristics

Mechanical Specification

Dimensions

Installation Instruction

  • This series fits DIN rail TS35/7.5 or TS35/15.
  • For installation details, please refer to the Instruction manual.

Installation Manual