Diablo DSP-10-LV Loop Detector User Guide

June 13, 2024
Diablo

Diablo-logo

Diablo DSP-10-LV Loop Detector

WIRING
The pin assignments for the detector and the optional wiring harness are:

Pin Wire Color Function
1 Black DC + or AC Line
2 White DC – or AC Neutral
3 Orange Relay B N.O.
4 Green Chassis Ground
5 Yellow Relay A Common
6 Blue Relay A N.O.
Pin Wire Color Function
--- --- ---
7 Gray Loop
8 Brown Loop
9 Red Relay B Common
10 Pink or White/Black Relay A N.C.
11 Violet or White/Red Relay B N.C.

DIP SWITCHES

1 Function
OFF Detect Immediately on Entry
ON 2 Second Detect Delay on Entry
2 3
--- ---
OFF OFF
ON OFF
OFF ON
ON ON
4 Function
--- ---
OFF Normal Sensitivity
ON Sensitivity Boost During Detect
5 6
--- ---
OFF OFF
ON OFF
OFF ON
ON ON
5 6
--- ---
OFF OFF
ON OFF
OFF ON
ON ON
8 Function
--- ---
OFF Inductive Loop
ON Free Exit Probe (Magnetometer)
9 10
--- ---
OFF OFF
ON OFF
OFF ON
ON ON

SENSITIVITY

The factory default is 5 and should work for most installations.

Setting| 0| 1| 2| 3| 4| 5| 6| 7| 8| 9
---|---|---|---|---|---|---|---|---|---|---
%ΔL/L| 0.48| 0.32| 0.24| 0.16| 0.12| 0.08| 0.06| 0.04| 0.03| 0.02
Response| 70 ms ± 10 ms| 140 ms ± 20 ms

INDICATORS

Green Power LED
Steady on when operating normally. See fault table for a flashing condition.

Fault Display for Current Fault Display for Prior Fault
Low Voltage 2 Hz with 50% duty cycle NONE
Open Sensor 1 flash ON every 2 seconds 1 flash OFF every 2 seconds
Shorted Sensor 2 flashes ON every 2 seconds 2 flashes OFF every 2 seconds
Large Change 3 flashes ON every 2 seconds 3 flashes OFF every 2 seconds

Red Detect A LED
The LED will turn on when a vehicle is over the loop detection area. If delay is programmed, the LED will blink slowly during the delay interval. If extension is programmed, the LED will blink fast during the extension interval.

FAIL-SAFE or FAIL-SECURE

There are three jumpers internal to the detector that are used to select Fail- Safe or Fail-Secure modeof operation for the Relay A output. This setting determines what states the relay output should be in if a loop failure is detected. Fail-Safe operation has the relay activated. Fail-Secure has the relay deactivated. Most applications that are not high security will use the Fail-Safe mode of operation. The detector is shipped in the Fail-Safe mode from the factory. Additional information is available at the Diablo Controls website www.diablocontrols.com or contact technical support at 866-395-6677.