WATTS HKV2013AF Series 1 Inch Stainless Steel Heating Circuit Manifold
Product Information
The HKV2013AF Series heating manifold is a stainless steel heating circuit manifold with flow meters. It conforms to DIN EN 1264-4 standards for water- based surface embedded heating and cooling systems. The manifold is designed for distributing and regulating the flow rate in low-temperature floor heating or cooling systems.
Product Usage Instructions
- Ensure that all safety precautions are followed while using the product.
- Install the manifold according to the dimensions provided in the manual.
- Connect the primary circuit and end set to the manifold using the specified tightening torque.
- If required, connect an actuator to the manifold for control purposes.
- Use the flowmeter to monitor and regulate the flow rate in the heating circuit.
- Refer to the pressure-temperature diagram to understand the pressure and temperature limits for different media mixtures.
- Refer to the pressure loss diagram to determine the pressure loss in the manifold at different flow rates.
- If necessary, use optional accessories such as the ball valve set KH, end set Q1, or end set KFE90 for flushing, filling, draining, and venting purposes.
- Make sure to refer to the installation and operating manual for detailed instructions and additional information.
General information
Requirements
- The installer or user must read, understand and observe this installation and operating manual before carrying out any operation.
- The heating manifold may only be fitted, adjusted and maintained by trained specialist personnel. Trainees may only work on the product under the supervision of an experienced person. The manufacturer will only accept any liability in line with statutory provisions if the above instructions have been adhered to.
- All instructions in this installation and operating manual are to be observed when using this heating manifold. This manual is an integral part of the product and must be available to all users throughout its entire service life. This manual is protected by copyright and may not be altered without the manufacturer’s permission.
Product conformity
The HKV2013AF Series heating manifold conforms to DIN EN 1264-4 “Water based
surface embedded heating and cooling systems”.
Product features
- Stainless steel round pipe manifold on mounting bracket
- G 1 male thread with flat sealing on both sides.
- Shut-off flow meter with particularly low pressure loss.
- Regulating and shut-off valve with M30 × 1.5 adaptation.
- Fastening, air vent key and sticker set for identifying the heating circuit included in delivery.
- In option: Ball valve and end set for flushing, filling and venting.
Safety
Safety notices
-
WARNING
WARNING indicates a danger arising through incorrect behaviour (e.g. misuse, disregarding notices, etc.) that may cause serious physical injury or death. -
CAUTION
CAUTION indicates a potentially dangerous situation that may cause minor or slight injuries if the appropriate safety precautions are not in place. -
NOTICE
NOTICE indicates a situation that may cause material damage if the corresponding precautions are not taken. -
Intended use
The manifolds are used for distributing and regulating the flow rate in low temperature floor heating or cooling systems.
Foreseeable misuse
The following is regarded as foreseeable misuse:
- operating the heating circuit manifold contrary to the specifications;
- making modifications to the heating circuit manifold not agreed with the manufacturer;
- using replacement or wear parts not approved by the manufacturer.
Technical specification
Hydraulic data|
---|---
Max. operating pressure| 10 bar (see Pressure-temperature diagram)
Medium temperature| from -10 to 80 °C (see Pressure-temperature diagram)
Media| Water or water with glycol as per VDI 2035
Connections|
Primary circuit and end set| G 1 male thread
Heating circuit| G ¾ eurocone male thread
Tightening torque| G ¾ screw fittings 25-30 Nm 25-30 Nm; G1 screw fittings 55
Nm
Connection for actuator| M30 x 1.5 / closing point 11.8 mm / stroke 2.5
Manifold|
Manifold| Stainless steel 1.4301
Flowmeter| CW617N, PPS
O-rings| EPDM
Flat seals| AFM/2
End set (optional)| CW617N
Pressure-temperature diagram
Pressure loss diagram
Dimensions
| | | | | | Outlets| | | | |
---|---|---|---|---|---|---|---|---|---|---|---
| 2| 3| 4| 5| 6| 7| 8| 9| 10| 11| 12
L1 = HKV| 160| 210| 260| 310| 360| 410| 460| 510| 560| 610| 660
| | | | | | | | | | |
L2 = HKV + KFE90 (C)| 209| 259| 309| 359| 409| 459| 509| 559| 609| 659| 709
L3 = HKV + Q1 (B)| 219| 269| 319| 369| 419| 469| 519| 569| 619| 669| 719
| | | | | | | | | | |
L4 = KH (A) + HKV + KFE90 (C)| 271| 321| 371| 421| 471| 521| 571| 621| 671|
721| 771
L5 = KH (A) + HKV + Q1 (B)| 281| 331| 381| 431| 481| 531| 581| 631| 681| 731|
781
Components overview
Components
- Manifold supply
- Flow meter with shut-off function
- Wall brackets
- Manifold return
- Heating circuit connection
- Control valve with protective cap
Optional accessories
- A Ball valve set KH
- B End set Q1: Flushing, filling, draining, venting
- C End set KFE90: Flushing, filling, draining, venting
Installation and commissioning
Hot water!
Severe scalding possible.
- Allow the product to cool before carrying out any maintenance, cleaning or work repair.
- Do not put hands into hot water when draining the product.
Pipe installation
- Cut the plastic, copper or multilayer pipe to length perpendicular and deburr / calibrate. Push the clamping ring nut over the pipe.
- Push the grab ring onto the pipe and insert the hose nozzle.
- Push the conical end of the pipe all the way into the connection on the manifold.
- Tighten the clamping ring nut by hand. Push the plastic, copper or multilayer pipe up to the stop.
- Hold the outlet screw connection using a 24 mm open-end wrench or spanner and tighten the clamping ring nut using a30 mm open-end spanner (approx. 25-30 Nm). Fit the pipe without any tensile, compressive or torsional forces. Do not exceed the max. torque stated in the installation instructions for the compression joint used.
Shutting off the heating circuit
- The valves on the return can be closed, e.g. for flushing and filling the heating circuit. To do this, put the protective cap on the valve and close it by turning it clockwise
- The flow meter can be closed with a air vent key. However, this is not necessary for filling and flushing the circuits. If the flow meter is shut off, the following opening sequence must be observed in order to avoid malfunction or damage. First, open the flow meter, then the control valve.
Flushing and filling the circuits
Material damage!
Opening shut-off valves quickly produces pressure surges.
Always open shut-off valves slowly and in a controlled manner.
All flow meters must be completely open.
The system pressure must not exceed 3 bar when flushing and filling.
- Close ball valves 1 and 2 on the manifold.
- Close all valves on the return using the protective caps.
- Attach the flushing and filling hose to the fill and drain valve 3 on the supply side; the discharge outlet on fill and drain valve 4 must be open.
- Completely open the valve on the circuit to be flushed using the protective cap.
- Flush the circuit with clear water.
- Once flushing is over, close the control valve and flush/fill the next circuit.
- Once the flushing and filling procedures are complete, remove the hose from the end set (fill and drain valves 3 and 4).
- When venting using the end set Q1 and KFE90, follow illustrations A and B on this page.
- The protective end caps are to be fully closed off once the system has been flushed and filled.
Adjusting the flow rate
Material damage!
Flowmeter must not be used to adjust the flow rate.
- Remove the protective cap on the relevant heating circuit and close the valve with a air vent key by turning it clockwise (= min. setting).
- Adjust the flow rate by turning the regulating spindle anticlockwise on the return valve. The actual value can be read from the flow meter. Do not use the flow meter to adjust the flow. Once all the circuits have been set, check the flow values and readjust if necessary.
- The fine thread of the adjusting spindle must not be visible above the edge of the AF19 hexagonal nut! Once it is closed, the valve is open (full flow) after 2.5 to 3 turns anticlockwise.
- The protective cap or the actuator should be screwed back on once the adjustment work is complete. This prevents the valves from accidental adjustment and from getting dirty.
Disposal
Dispose of the product and packaging by local laws and regulations or recycle
them
Warranty
WATTS products are tested extensively. WATTS therefore guarantees only the replacement or, at the sole discretion of WATTS, the free-of-charge repair of components of the supplied products where these, in the opinion of WATTS, exhibit verifiable manufacturing faults. Warranty claims due to defects or defects of title may be asserted within one (1) year of delivery/transfer of risk. Excluded from the warranty are damages attributable to normal use of the product or friction and damages resulting from modifications or non-authorized repairs on the products, for which WATTS rejects all claims for compensation (direct or indirect). (For more detailed information, please refer to our website.) In all cases, supply is subject to the General Terms and Conditions, which can be found at www.wattswater.eu/gtc/.
The descriptions and photographs contained in this product specification sheet
are supplied by way of information only and are not binding. Watts Industries
reserves the right to carry out any technical and design improvements to its
products without prior notice.
Warranty: all sales and contracts for sale are expressly conditioned on the
buyer’s assent to Watts terms and conditions found on its website
www.wattswater.eu/gtc/. Watts hereby objects
to any term, different from or additional to Watts terms, contained in any
buyer communication in any form, unless agreed to in writing and signed by an
officer of Watts.
Watts Industries Deutschland GmbH Godramsteiner Hauptstr. 167 • 76829 Landau •
Germany
Tel. +49 6341 9656 0 • Fax +49 6341 9656 560
WIDE@wattswater.com
www.wattswater.de
Watts contacts in Europe :
www.wattswater.eu/watts/contacts/
WattsWater.eu