NAVAC Recovery Unit For Flammable Refrigerants User Manual

June 13, 2024
NAVAC

NAVAC-Logo

NAVAC-Recovery-Unit-For-Flammable-Refrigerants-Product

CERTIFICATIONS

Certified and tested according to:

  • EN IEC 60079-0:2018
  • EN IEC 60079-7:2015+A1:2018
  • EN 60079-11 :2012
  • EN IEC 60079-15:2019
  • EN ISO 80079-36:2016
  • EN ISO 80079-37:2016

Design reference standard:

  • UL 1963: Fourth Edition
  • CSA-C22.2 No.120-13
  • UL 121201: Ninth Edition
  • CSA-C22.2 No.213-17

NAVAC-Recovery-Unit-For-Flammable-Refrigerants-02

CE Denotes that this product complies with ATEX directives

Certificate No. is CSANe 22ATEX1032X
NAVAC-Recovery-Unit-For-Flammable-Refrigerants-01| Specific marking for explosion protection
3| Zone 2
G| Gas
Ex| Denotes explosion protection
ec| Increased safety
ic| Intrinsic safety
nC| Sealed device
h| Constructional safety
IIA| Typical gas – R290, R600a etc.
T4| 135°C (275°F)
Ge| EPL – Equipment Protection Level

Specific Conditions Of Use:

  1. Provision shall be made external to the equipment that ensures that the circuits are limited to over voltage category II as defined in EN 60664-1.
  2. In the final use, the OFP port shall comply with at least IP20.
  3. Maximum recovery weight of refrigerant not exceed 80kg one time. After the working, the machine shall be stopped and ensured the refrigerant to be cooling.
  4. Equipment shall not be installed in a location where the external conditions are conducive to the build-up of electrostatic charge on such surfaces. In addition, the equipment shall only be cleaned with a damp cloth.
  5. Equipment shall be operated such that the supply cable is protected from mechanical damage. The cable shall not be subjected to tension or torque.

Warning:

  1. WARNING- DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE MAY BE PRESENT
  2. WARNING – DO NOT CONNECT OR DISCONNECT WHEN ENERGIZED

GENERAL SAFETY

Use information

  • In order to prolong the life cycle of the recovery unit, please read the manual carefully before using to fully understand the safety, specification as well as operating procedure of the recovery unit.
  • Please check the product received is same as you ordered.
  • Please check the product if there is any damage during transportation.
  • Contact with local distributor if the above problem is found.
  • Please read the manual carefully and use the unit according to the product operating procedures.

Safety indication
warning
This mark indicates procedures that must be strictly observed to prevent hazards to people.

Notice
This mark indicates procedures must be strictly observed to prevent damage or destruction of the unit.

Matters needing attention
warning

  • For recovering only HVAC/R refrigerants from sealed HVAC/R systems. Warranty VOIDED if used for any other purposes.
  • Only a qualified technician should operate this recovery unit.
  • Before starting the equipment, make sure that it is well grounded.
  • If using electrical extension cord, the cord must be in good condition and properly connected and grounded.
  • Only a qualified electrician can do the wire connection according to the technical standard and circuit diagram.
  • The power must be cut off and no display in LCD before inspecting or repairing.
  • If the original power supply cord is damaged, an OEM replacement may be ordered through your NAVAC distributor.
  • Please check the capacity of your power supply, ammeter, electrical wires and circuit before use.
  • Only authorized refillable refrigerant tanks can be used. The setting of the pressure limiting device shall not be lower than 45 bar(653psi). Do not overfill the recovery tank, maximum at 80% capacity to make sure that there is enough space for liquid expansion. Overfilling of the tankmay cause a violent explosion.
  • Always wear safety goggles and protective gloves while working with refrigerants to protect your skin and eye from hurting by refrigerant gases or liquid.
  • Do not use this equipment near flammable li quid or gasoline.
  • A digital scale is needed to prevent overfilling.
  • Be sure that the place where you are working is thoroughly ventilated.

Before connecting, be sure to turn on the recovery unit to check:

  1. If the fan is working properly (if there’s air blowing out from the condenser side).
  2. Connect the check valve to the outlet port and close the check valve. Keep the inlet port open to atmosphere. Turn the knob to the “FAST” position and start the machine. The pressure on the outlet side should rise to 560Psi (38.6bar) within 65secs. After that, the high pressure switch protection switch is on, and the machine will automatically shut down.

Notice

  • Be sure the unit is working under the right power supply.
  • When using an extension cord it should be minimum 14 AWG and no longer than 25 feet, otherwise it may cause the voltage drop and damage the compressor.
  • The input pressure of the unit should not exceed 26bar(377.0psi).
  • The unit need to be laid in horizontally, otherwise it will lead to unexpected vibration, noise or  even abrasion.
  • Do not expose the equipment to sun or rain.
  • The ventilation opening of the unit must not be blocked.
  • If the overload protector pops, reposition it after 5 minutes.
  • When doing self purging operation, the knob must be turned slowly to “PURGE” to ensure the inlet pressure is less than 5 bar(72.5 psi).
  • If fluid hammer happens in the recovery, please turn the knob slowly to “SLOW” position and  do not let reading pressure drop to zero.
  • When you select fast model to start work. please monitor output pressure, if the output pressure increase fast to 27bar(391.6 psi),please turn to slow mode slowly and monitor the outlet pressure not exceeding 35bar(507.6 psi).
  • The equipment is intended for serving air-conditioning and refrigeration systems containing less than 200 lbs of high-pressure refrigerant.
  • The tank and hose used must comply with the local regulations.

ADDITIONAL SAFETY INSTRUCTION

Additional Safety Instructions for refrigeration systems containing Flammable refrigerants.

  • Except for existing occupational hazard procedures or other regulations that may be required by local, state or federal agencies, the following are additional safety recommendations when servicing refrigeration equipment that contain Class A2L, A2 or A3 refrigerants.

  • The area of service should be marked as Temporary Hazardous Zone. This will be an area with a radius of 3m centered on refrigeration equipment being serviced and should have no smoking and other hazardous signs posted. Local supervisor should be notified of the zone’s existence.
    NAVAC-Recovery-Unit-For-Flammable-Refrigerants-03

  • Ensure the refrigeration equipment’s power has been discontinued during maintenance work.

  • When connecting service equipment (such as vacuum pumps, scales, recovery units) to a power source, the connection must be made outside the Temporary Hazardous Zone.

  • Factory-equipped power cord of NRDDF is 3.2m, which can make sure the connection is made in the area free of ignitable concentrations. Do not change the power cord at will.

OPERATION MANUAL

  1. Do not mix different refrigerants together in one tank, otherwise they could not be separated or used.
  2. Before recovering the refrigerant, the tank should achieve the vacuum level: -29.6inHg , for purge non-condensable gases. Each tank was full of nitrogen when it was manufactured in the factory, thus the nitrogen should be evacuated before first use.
  3. The knob should be in the “Close” Position before operation. All the valves must be closed, the input and output fittings should be covered with protective caps when the unit is not in operation. The air/ moisture is harmful to the recovery result and will shorten the life span of the unit.
  4.  A filter drier should always be used and should be replaced regularly. And each type of refrigerant must have its own filter. For the sake of ensuring the normal operation of the unit, please use high quality filter drier specified by our company. A high quality filter drier will help protect machine .
  5. Special-caution is needed when recovering from system, and two dry filters are needed.
  6. The unit has an Internal High Pressure protector. If the pressure inside the system is above rated shut-off pressure (see specification), compressor will automatically shut off and the HP cutoff shows. To restart the compressor, please lower the internal pressure (Output gauge indicates lower than 35 bar/507.6 PSI), after the HP cutoff blinks, then Press the “START” button to restart the compressor. When high pressure protection initiates, please determine the cause and deal with it before restarting the unit.
    • The input valve of the refrigerant tank is closed-opening the valve will help solve the problem.
    • The connecting hose between the recovery unit and refrigerant tank is plugged -close all the valves and replace the connecting hose.
    • The temperature of the refrigerant tank is too high, causing high pressure- cool the tank down.

SPECIFICATION

NRDDF

Refrigerants| Category Ill : R12, R134a, R401C, R500, R1234yf, R600a
Category IV: R22, R401A, R401B, R402B, R407C, R407D, R408A, R409A, R411A, R411B, R412A, R502, R509, R290
Category V: R32, R402A, R404A, R407A, R407B, R410A, R507
Power| 115V, 60Hz
Motor| Brushless Motor, 1 HP
Motor Speed| 3000 RPM
Maximal Current Draw| 12A
Compressor| Oil-less, Air-cooled, Piston
High Pressure Protector| 38.5bar/3850kpa(558psi)
Operating Temperature| 32-104°F
Dimensions| 14.5×9.9×11.7 inch

Note: R-702, R-E170, R-1150, R-429A, R-432A, R-435A, R510Aaren􀀂compatible

PERFORMANCE DATA

NAVAC-Recovery-Unit-For-Flammable-Refrigerants-04A (Do not dispose through – typical waste streams)
IN ACCORDANCE WITH SECTION 608 OF THE CLEAN AIR ACT:
THIS EQUIPMENT HAS BEEN CERTIFIED BY UNDERWRITERS LABORATORIES INC. TO MEET EAP’S MINIMUM REQUIREMENT FOR RECOVERY EQUIPMENT INTENDED FOR USE WITH CATEGORY Ill, IV, AND V REFRIGERANTS OUTLINED IN AHRl-740-98, TABLE 4.

NRDDF UL Verified Test Results

Refrigerant| R22| R134a| R407C| R410A
Push/Pull Recovery (kg/min)| 7.73| 5.81| 7.75| 8.35
Liquid Recovery (kg/min)| 5.04| 3.56| 5.56| 6.55
Vapor Recovery (kg/min)| 0.29| 0.26| 0.28| 0.34
Final Recovery Vacuum (kPa)| 50.8| 50.8| 50.8| 50.8
Residual Trapped Refrigerant (kg)| 0.007| 0.006| 0.006| 0.005
High Temp (104°F) (kg/min)| 0.34| | |

INTRODUCTION OF OPERATION PANEL

NAVAC-Recovery-Unit-For-Flammable-Refrigerants-05

  • StarVStop: Starts and Stops recovery unit.

  • LP Switch: Hold for 3 seconds to switch between LP1, LP2, Lp3.

  • Units/Zero: Press to change units to lnHg, Kpa, Psi, Kg/I, Bar, Mpa.  Hold for 3 seconds to zero out readings.

  • Cancel Alarm: Hold for 3 seconds to mute recovery unit.

  • LP1: (Auto shutoff with manual restart)
    if the inlet pressure is lower than -20inHg for 20 seconds, the unit will shut down. “LP Cutoff” will be displayed.
    When LP  0 inHg you must press ST ART to restart the recovery unit

  • LP2: (Auto shutoff with automatic restart)
    if the inlet pressure is lower than -20inHg for 20 seconds, the unit will shut down. “LP Cutoff’ is displayed.
    When LP O inHg the unit will restart automatically.

  • LP3: (Continuous Run)
    The recovery unit will run continuously, no matter what the level the input pressure is(LP)

  • O.F.P Cutoff: Will light up when the recovery cylinder is 80% filled, or if the OFP cable is opened. The machine will stop running.

  • LP Cutoff: will light up when low pressure switch is activated for more than 20 seconds below -20 inHg.

  • HP Cutoff: Will light up when high pressure switch is activated above 560 Psi.

Restart: It will flash after an error has occurred and settled. Pressing “START’ will resume activity. Fault: Error Codes

  • E1: The pressure sensor is disconnected
  • Fault 2: Input voltage is too low
  • Fault 3: High input voltage
  • Fault 4: Overcurrent protection
  • Fault 7: Temperature protector open
  • Fault 8: Motor stalling
  • Mute: Audible alerts and beeps are turned off.
  • Fan: This icon rotates while the machine is running. When the machine stops, the icon

NAVAC-Recovery-Unit-For-Flammable-Refrigerants-06

  • Close: Inlet valve is closed
  • Recover: Input valve is partially opened
  • Fast: Input valve is fully opened
  • Purge: Input closed, and output is opened to allow the unit to remove most of the refrigerant  inside the recovery machine

PARTS DIAGRAM

NAVAC-Recovery-Unit-For-Flammable-Refrigerants-07

  1. O.F.P Adaptor Assy
  2. Left side Plate
  3. Fan
  4. Wind Guide Cover
  5. Motor
  6. Support Assy
  7. Top Plate
  8. Knob 18 Base
  9. Control Assy
  10. Valve Assy
  11. Cylinder
  12. Copper Pipe
  13. Coupling
  14. Compressor
  15. Condenser
  16. Rear Plate
  17. Right Side Plate
  18. Motor Control Board (MCB)
  19. Front Side Plate with Digital Manifold Gauge

WIRING DIAGRAM

Front Side Plate with Digital Manifold Gauge

Graphics Code ITEM
HS High pressure sensor
M Motor
MCB Motor control board
XS Socket
DCB Digital gauge control board
LS L ow pressure sensor
OFP Over filling protector
TP Temperature protector
HP High pressure switch

OPERATING INSTRUCTION

Refrigerant hoses exhaust

NAVAC-Recovery-Unit-For-Flammable-Refrigerants-09

Preparation
It’s required to use hoses with ball valves on this recovery machine. Connect the hose correctly and firmly (see diagram above)

  1. Check the refrigeration device and make sure the gas valve and liquid valve are closed.

  2. Check the refrigerant tank and make sure the gas valve and liquid valve are closed.

  3. Open the gas valve and liquid valve of the manifold gauge.

  4. Open the ball valves on the recovery machine outlet and valves on the hose connected to the outlet

  5. Power on the recovery machine, the LCD screen will display the inlet and outlet pressures.

  6. Turn the knob to “FAST’.
    Start

  7. Start the vacuum pump and let it run until the recovery machine’s display (low pressure) shows above -20inHg.

  8. Close the ball valve of the vacuum pump hose which is connected to the refrigerant tank.

  9. Tum the knob to “Close”.

  10. Connect the recovery machine outlet to the refrigerant tank with a hose.

Recovery mode

NAVAC-Recovery-Unit-For-Flammable-Refrigerants-09

Preparation
Connect the hoses correctly and firmly. (Please refer to the connection diagram) Make sure all valves are closed.

  1. Switch off the power of refrigerant equipment.

  2. Open the vapor and liquid valves of refrigerant equipment.

  3. Open the vapor valve of the refrigerant tank.

  4. Open the ball valves on the hose connected to the recovery machine outlet
    Start operation

  5.  Press the ‘START’ button to start machine.

  6.  Turn the knob to “Recover”.

  7. If recover liquid refrigerant, please open the liquid valve of the manifold gauge.

  8. If recover vapor refrigerant, please open the vapor valve of the manifold gauge.

  9. Recovery is completed when machine enters into a vacuum. In Automatic shutoff this would be at 20inHg

  10. When recovery is completed, you can run self-purging right away without powering off.

Notice

  1. If slowly liquid turn hammer the knob happens to “Slow’ in the position, recovery, let the please  reading of the low-pressure gauge drops until liquid hammer stops. Do not let the reading drop to zero, otherwise the inlet port will not pump.
  2. If it is difficult to start, tum to “CLOSE” when liquid, turn to “PURGE” when vapor, then press “START” to restart the machine, and turn to the required position.

Self-purge mode

NAVAC-Recovery-Unit-For-Flammable-Refrigerants-09

Notice
The unit must be purged every time after use;
Liquid refrigerant remained may expand and damage the components and pollute the environment.

Start operation

  1.  The machine stops automatically after recovery finished based on LP cutoff setting.

  2. Turn the knob to “Close”, press “START” button to start the machine.

  3. Turn the knob to “Purge” and start self purging.

  4. The self purging mode will be finished when machine automatic stops or runs to certain vacuum level.
    Finish operation

  5. Turn the knob to “Close”.

  6. After confirming the machine has stopped, unplug the power cord from the charger to the power socket first, then unplug the cord from the charger to the recovery machine to avoid sparks.

  7. Close the ball valves at both ends of the outlet hose.

  8. Close the vapor valve of the tank.

  9. Remove all the hoses and recycle them properly.

Liquid push/pull mode

AMW-90 Countertop Microwave Ovens

Notice
An electronic scale is needed to monitor the recovery process to prevent overfilling.

Preparation
Connect the hoses correctly and firmly. (Please refer to the connection diagram) Make sure all valves are closed.

  1. Turn the knob to “FAST’.

  2. Connect Those 11 to the vacuum pump.

  3. Start the vacuum pump to pump the vacuum.

  4. Let the vacuum pump run for 20 secs, close the ball valve on[hose 11, turn off the vacuum pump, and remove the hose from the vacuum pump.

  5. Connect and repeat step 2, 3, 4

  6. Connect the hoses to the gas port of the system and the liquid port of the refrigeration tank.
    Start operation

  7. Open the vapor valve, liquid valve of the HVAC system.

  8. Open the ball valves on the connecting those 11 and  hose 21

  9. Open the vapor valve, liquid valve of the tank.

  10. Press “START’ button to start machine, then it starts liquid push/pull mode.
    If the reading on the scale keeps the same or changes slowly, it means liquid in HVAC system has been recovered and vapor recovery mode can be underway.

  11. Tum the knob slowly to “Purge” and start self purging mode for the liquid.

  12. Tum the knob to “Close”

  13. Close the vapor valve, liquid valve of the HVAC system.

  14. Close the vapor valve, liquid valve of the tank.

  15. Close the ball valves on the hose connecting the recovery machine outlet and the system.

  16. Close the ball valves on the hose connecting the refrigerant tank and the system.

  17. Reconnect the hoses, and start recovery mode for the vapor.
    Finish

TROUBLE SHOOTING

PROBLEM CAUSE SOLUTION

LCD does not work after power is on

|

  1. Power cord is damaged.                            1. Replace cord.
  2. Inner connection is loose.                         2. Check the connection.
  3. Connect to J6 is damaged.                        3. Replace the connect.
  4. Malfunction of circuit board.                      4. Replace MCB or DCN circuit board.
    Contact NAVAC tech support

Machine does not run after pressing START|

  • HP Cutoff, or OFP Cutoff works (screen shows.)
  • Fault 2 or Fault3
  • Fault 4 or Fault 8
  • Fault 7
  • Button is damaged.
  • 6. Circuit board is damaged.

|

  • Check if the connection between HP or OFP to DCB is good.
  •  Adjust to correct voltage.
  • If the voltage is correct, replace the MCB
  • If this happens only when starting the machine: for liquid recovery, turn the knob to “CLOSE”, for gas recovery, turn the knob to “PURGE”, press “START” again to start the machine,
  • and turn the knob to “FAST”.
  • Only when inlet pressure is too high or fluid hammer happens, turn the knob to “SLOW”
  • When error occurs at no load, power off the machine and check if the fan can be manually rotated. If yes, replace the control board. If not, send the machine back to the factory for repair.
  • Check if the connection between TP and MCB is good. If good, contact NAVAC tech support.
  •  Replace the front side plate with digital manifold gauge.

| Misoperation causes HP Cutoff.                1. Refer to section 6 of OPERATION MANUAL on
| Thermal protector is on and shows               page 3.
Machine stops after running a period of time| Fault 7. 2. When Fault 7 and Restart flash, press START.
Refrigerant is 80% in the tank, and          3. Replace the tank. When O.F.P Cutoff and
O.F.P Cutoff shows.                                        Restart flash, press START.
low pressure protection switch is on.  4. See refer to self-cleaning operation steps for
| self-cleaning.
E1 shows at LP or HP| Pressure sensor is not connected well or is open circuit.| Check if the connection between LS or HS to DCB is good. If good, replace pressure sensor.
Slow recovery rate|

  1. The pressure of the refrigerant tank        1. Cooling the tank help decrease the pressure. is too high.                                                    2. Turn the knob towards “FAST”.
  2. The valve is not open enough.                   3. Contact NAVAC tech support.
  3. Piston ring of compressor is damaged.

Not evacuate|

  • Connection hose is loose.
  • Machine leaks.

|

  • Tighten the connection hosed.
  • Contact NAVAC tech support.

Attention
If you have the compressor repaired in any circumstances, please do a leak test before use and make sure there’s no leak.

How to do the leak test:

  1. Block the outlet port with a ball valve, keep the inlet in connection with the atmosphere;
  2. Turn the knob to the “FAST” and start the machine. When the outlet pressure rises to 30bar, press the “STOP”, and then turn the knob to the “PURGE”.
  3. Leave it alone for 30 minutes. Check the reading of the low pressure gauge. If the pressure is higher than 15bar, then it passes the test. If it is lower than 13bar, there a leak; if it is between 13bar and 15bar, leave it for another 30 minutes. If the pressure drops s 3bar, then it passes the test

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals