KYORITSU KEW 6516 Multifunction Installation Tester Instruction Manual
- June 13, 2024
- KYORITSU
Table of Contents
MULTIFUNCTON INSTALLATION TESTER
KEW 6516 / 6516BT
KEW 6516 Multifunction Installation Tester
A Iot of Testing Power in the hands of Electrical Installation Professionals!
Insulation | Loop | RCD |
---|---|---|
100/250/500/1000V | 2/20/200/2000Ω | 10/30/100/300/500/1000mA |
PSC | PFC | Earth |
2000A/20kA | 2000A/20kA 2000A/50kA | 20/200/2000Ω |
ACV | Continuity | Phase rotation |
300/600V | 20/200/2000Ω | |
Frequency | SPD (Varistor) | PAT |
Communication interface
KYORITSU ELECTRICAL INSTRUMENTS
WORKS, LTD.
www.kew-Itd.co.jp
Operation in 3 simple steps
Set the rotary dial to your testing range.
Connect the instrument to the installation under test.
Press the test button.
Hands free testing
By remote probe or using the Lockdown function of the test button.
Large LCD
All the test data is shown in one large colored screen.
Anti-Trip Technology (with 2 & 3
wire)
For no trip LOOP L-PE testing on all RCDs.
With 3wire (L, N, PE), to get the best accuracy readings.
With 2 wire only, very useful in case of no Neutral (i.e. 3-phase motor
lines).
HELP Key
HELP function will show instrument according to how to connect the the
function selected.
0.001 resolution
Thanks to high test current of 25A, the Loop Impedance Phase to Earth is
measured with high resolution of 0.001 ohm. This can be useful when testing in
the main switchboard closer to the transformer.
Wide variety of RCDs can be
tested
Type AC, A, F, B (General & Selective) EV and Variable
RCDs. Single and Auto test, Ramp test and Contact voltage.
PAT test
PAT test (PAT = Portable Appliance Tester) It is possible to check the
insulation resistance and earth bond continuity of portable appliances for
class I and II.
Zs/Ra Limit
The verification of safety
requirement on an electrical installation is simplified by using Zs/Ra Limit
function.
This function will automatically check if the measured loop impedance for TN
(or earth loop for TT) is low enough to trip (disconnect) the MCB / Fuse / RCD
giving the result of PASS(v) or FAIL (x) on the display.
SPD test
SPD (Surge Protection Device) which contains varistor can be tested measuring
the tripping voltage without damage it. Connectivity
KEW 6516 can download the test data by connecting the USB adapter (Model
8212-USB) and then print complete Test Reports by a PC.
While KEW 6516BT can transfer the test datatoa Tablet or Smartphone via
Bluetooth. Such test data can be saved, shared and sent by email. The USB
adapter can also be ordered as an option. KEW 6516 and
KEW 6516BT come complete with everything you need for testing an electrical
installation
Accessories
Optional Accessories
MODEL7272
2 cord reels with test leads,
2 spikes, an earth test lead,
a carrying case. MoDEL 8259
Adapter for measurement terminal terminal [red, yellow, green/1 se] MFT and EVSE ADAPTER Kits
KEW 6516-EV2: KEW 6516×1, KEW 8802×1
KEW 6516BT-EV2: KEW 6516BTx1, KEW 8602×1
KEW 6516 / 6516BT Specifications
Insulation resistance
Test voltage | 100V | 250V | 500V | 1000V | Max.1000V |
---|---|---|---|---|---|
Measuring ranges | 2.000/20.00/200.0MΩ | ||||
(Auto-ranging) | 20.00/200.0/1000MΩ | ||||
(Auto-ranging) | 20.00/200.0/2000MΩ | ||||
(Auto-ranging) | 0-1000V(goes up by1V) | ||||
Accuracy | ±2%rdg±6dgt (2.000/20.00MΩ) | ||||
±5%rdg±6dgt (200.0MΩ) | ±2%rdg±6dgt (20.00/200.0MΩ) | ||||
±5%rdg±6dgt (1000MΩ) | ±2%rdg±6dgt (20.00/200.0MΩ) | ||||
±5%rdg±6dgt (2000MΩ) | ±5%rdg±5dgt | ||||
Rated current | 1.0-1.2mA @0.1MΩ | 1.0-1.2mA @0.25MΩ | 1.0-1.2mA @0.5MΩ | ||
1.0-1.2mA @1MΩ | – | ||||
Short circuit current | 1.5mA max | – |
Loop impedance
Function | LOOP ATT | LOOP HIGH |
---|---|---|
L-PE/L-N(3wire) | L-PE(2wire) | L-PE(0.01ΩRes) |
Rated voltage | 100-260V(50/60Hz) | 48-260V(50/60Hz) |
100-260V(50/60Hz) | 48-500V(50/60Hz) | |
Impedance range | 20.00/200.0/2000Ω | |
(Auto-ranging) | 20.00/200.0/2000Ω | |
(Auto-ranging) | 2.000Ω | 20.00Ω |
Accuracy | ±3%rdg±6dgt | ±3%rdg±10dgt |
Nominal test current at 0Ω external loop: Magnitude/Duration at 230V |
L-N:6A/60ms
N-E:10mA| L-PE:15mA| 20Ω:6A/20ms
200Ω:0.5A/20ms
2000Ω:15mA/500ms| 25A/20ms| 6A/20ms
PSC/PFC
Range| 2000A/20kA(L-N(PSC)/L-PE(PFC))| 2000A/20kA(PFC)| 2000A/20kA(PFC)|
2000A/50kA(PFC)| 2000A/20kA(PSC)
---|---|---|---|---|---
Accuracy| PSC/PFC accuracy is derived from measured loop impedance
specification and measured voltage specification
RCD
Rated voltage | 100-260V(50/60Hz) |
---|---|
Function | x1/2, x1,x5,Ramp,Auto,Uc |
6/10/30/100/300/500/1000mA/variable
RCD type| AC(G/S)| A(G/S)| F(G/S)| B(G/S)| EV
Trip current setting| x1/2,x1,Uc| 10/30/100/300/500/1000mA(G)
10/30/100/300/500mA(S)
| 10/30/100/300/500mA| 10/30/100/300/500mA| 10/30/100/300mA| 6mA(×1 only)
x5| 10/30/100mA| 10/30/100mA| 10/30/100mA| 10/30mA| –
Ramp| 10/30/100/300/500mA| 10/30/100/300/500mA| 10/30/100/300/500mA|
10/30/100/300mA| 6mA
Accuracy| Trip current| x1/2| -8% – -2%| -10% – 0%| -10% – 0%| -10% – 0%| –
x1| +2% – +8%| 0% – +10%| 0% – +10%| 0% – +10%| 0% – +10%
x5| +2% – +8%| 0% – +10%| 0% – +10%| 0% – +10%| –
Ramp| -4% – +4%| -10% – +10%| -10% – +10%| -10% – +10%| -10% – +10%
Trip time| x1/2| 2000ms(G/S):±1%rdg±2ms| –
x1| 550ms(G):±1%rdg±2ms,1000ms(S):±1%rdg±2ms| 10.5s:±1%±2ms
x5| 410ms(G/S):±1%rdg±2ms| –
Continuity
Range | 20.00/200.0/2000Ω (Auto-ranging) |
---|---|
Open circuit voltage (DC) | 7-14V |
Measuring current | 200mA |
15mA | 15mA±3mA(short-circuit) |
Accuracy | ±2%rdg±8dgt |
Phase Rotation
Rated voltage | 48-600V(50/60Hz) |
---|---|
Remarks | Remarks Correct phase sequence: are displayed “1.2.3” and mark |
Reversed phase sequence: are displayed “3.2.1” and mark
Volts
Range | 300.0/600V(Auto-ranging) |
---|---|
Measuring ranges | Volts |
Frequency | 45-65Hz |
Accuracy | Volts |
Frequency | ±0.5%rdg±2dgt |
Earth
Range | 20.00/200.0/2000Ω(Auto-ranging) |
---|---|
Accuracy | ±2%rdg±0.08Ω(20.00Ω) |
±2%rdg±3dgt(200.0/2000Ω)
General
Applicable Standards| IEC 61010-1 CAT Ⅳ 300V / CATⅢ 600V Pollution degree 2,
IEC 61010-2-034, IEC 61557-1,2,3,4,5,6,7,10, IEC 60529(IP40), IEC 61326(EMC)
---|---
Communication Interface| USB, Bluetooth® 5.0¹, AndroidTM 5.0 or later, iOS
10.0 or later
Power source| LR6(AA)(1.5V) × 8
Dimension| 136(L) × 235(W) × 114(D)mm
Weight| 1350g (including batteries)
Accessories| Mains test lead², 7281(Test leads with remote control switch),
7246(Distribution board test lead), 7228A(Earth resistance test leads),
8041(Auxiliary earth spikes[2 spikes/1 set])
9084(Soft case), 9142(Carrying case), 9151(Shoulder strap), 9199(Shoulder pad), LR6(AA) × 8, Instruction manual, 8212-USB(USB adapter with “KEW Report(Software)”)*³, Calibration certificate
Optional Accessories| 8212-USB(USB adapter with”KEW Report(Software)”)*³, 8259(Adapter for measurement terminal), 7272(Precision measurement Cord set), 8017A(Extension prod long) 8601(EVSE ADAPTER), 8602(EVSE ADAPTER)
¹ 6516BT only
² 7187A:British plug, 7218A:(EU)European SCHUKO plug, 7221A(SA) South african plug, 7222A:(AU)Australian plug
*³ 8212-USB : Standard accessory for 6516, optional accessory for 6516BT
Bluetooth is a trademark or registered trademark of Bluetooth SIG. Inc.
Android is a trademark or registered trademark of Google Inc.
iOS is a trademark or registered trademark of Cisco Technology, Inc. in the
United States and other countries.
Safety Warnings :
Please read the “Safety Warnings” in the instruction manual supplied with the
instrument thoroughly and completely for correct use. Failure to follow the
safety rules can cause fire, trouble, electrical shock, etc. Therefore, make
sure to operate the instrument on a correct power supply and voltage rating
marked on each instrument.
For inquires or orders :
2-5-20, Nakane, Meguro-ku, Tokyo, 152-0031 Japan
Phone:+81-3-3723-0131
Fax:+81-3-3723-0152
www.kew-lItd.co.jp
@This leaf et was produced n September 2023.
The contents of this eaflet are subject to change without notice
KEW 6516/65 16BT-3E Seo.23 SS
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>