KYORITSU 8602 EVSE Adapter User Manual

June 13, 2024
KYORITSU

KYORITSU - logo EVSE ADAPTER
KEW 8602

KYORITSU 8602 EVSE Adapter

Dedicated adapter for EVSE (Electric Vehicle Supply Equipment)
Installation inspections, maintenance and troubleshooting

Compact adapter for complete testing of Mede 3 AC EVSE

KYORITSU 8602 EVSE Adapter KYORITSU ELECTRICAL INSTRUMENTS WORKS, LTD.
www.kew-Itd.co.jp

  • EVSE tests under various simulations
    CP State / PP State simulation
    CP, Error / PE Error simulation

  • Touch pad for PE voltage check

  • L1, L2, L3, N, PE measuring terminals for electrical tests of EVSE

  • CP signal terminals for CP signal monitoring

  • Mains socket for load current test (MAX. 10A) CAT I 300V rating

What you can do with
KEW 8602

KYORITSU 8602 EVSE Adapter - Parts

Test overview for EVSE using the KEW 6516 series
*Can be used with other insulation resistance testers, DMMs, etc.
Tests conducted under dead-line conditions (CP STATE A)

Insulation test (for cable)
By connecting the test leads to the adapter terminal, the insulation resistance of cables can be measured for both single phase and three phase EVSE. (*Insulation measurement between wires (N, L1, L2, L3) other than PE is not possible.)
Earth Continuity test (200mA)
It is possible to check continuity between the PE terminal of the adapter and the outer metal part or the earth of the electrical circuit.
Earth test (3-wire & 2-wire)
The resistance of the earth to which the EVSE is connected can be measured.

KYORITSU 8602 EVSE Adapter - Figure 3Tests conducted under live line conditions (CP STATE C, D)
Voltage
Voltage/frequency between each terminal can be measured.
Phase rotation
Phase rotation of three phase power supply can be measured.
Loop Impedance (Loop ATT function)
Loop impedance between Line-Earth can be measured.
Typical measuring instruments are designed to make Loop impedance measurements on circuits where RCDs are installed, at currents that do not trip the RCD, which is rated at 30mA.
However, the 6mA DC RCDs built into the EVSE often trip even at this current, so the KEW 6516 series has a dedicated EVSE range that measures Loop impedance at even lower currents. KYORITSU 8602 EVSE Adapter - Figure
4

RCD test
The EVSE’s built-in 6mA DC RCD can be tested for operation.
Polarity (+,-), x1/2, x1 and x5 tests can be auto tested.
Type AC, A, B and F RCDs can also be tested.
Connection to/Type 1 EVES
The EVSE of Type 1 can be tested by using the optional conversion adapter (KEW 8603).

Mains socket
Load current tests up to 10A can be carried out X with this socket.
*Sockets are available in EU and UK types.

® KEW 8602 Specification

Plug IEC 62196-2 Type 2
Rated voltage AC 250V Max.(Single-phase) AC 430V Max.(Three-phase)
Rated Frequency 50/60Hz

Rated voltage/
current of mains socket| AC 10A/250V
*8602(EU):Type E socket, 8602(UK):Type BF socket
Fuse rating| AC 10A/250V, 05x20mm
Operating temp. & humidity range| 0 — 40t, RH 80% or less (no condensation)
Storage temp. & humidity range| -10 — 50°C, RH 80% or less (no condensation)
Applicable standards| IEC 61010-1 CAT II 300V, IEC 61010-2-030, IEC 61851-1, IEC 60529(IP40)
Altitude| 2000m or less
Cable length| Approx. 250mm
Dimension| Unit: 172(L) x 105(W) x 57(D) mm Plug part: 175(L) x 60(W) x 53(D) mm
Weight| Approx. 840g
Accessories| 8930 (Fuse)
9202 (Carrying case) Instruction manual
Optional Accessories| 8603 (TYPE1 to TYPE2 conversion adapter)

Accessories

Measurable tests by KEW 8602 only or in combination with MFT (KEW 6516/6516BT)

| 8602 only| I 8602+6516 or 6516BT(MFT)
---|---|---
CP state| A, B, C, D
PP state| OPEN, 13A, 20A, 32A, 63A
Terminal| E, N, L1, L2, L3, CP
PE PRE-TEST| ✓
CP Error| ✓
PE Error| ✓
Mains socket| 10A/250V
Continuity| | ✓
Insulation| –| (between conductors and earth)
Earth| –| ✓
(2W, 3W)
Loop impedance| –| ✓
Volts| –| ✓
RCD| –| ✓
(AC, A, B, F, 6mA DC)
Phase rotation| –| ✓

Optional Accessories

Kits

KEW 6516-EV2
KEW 6516×1, KEW 8602×1
KEW 6516BT-EV2
KEW 6516BTx1, KEW 8602×1

KYORITSU 8602 EVSE Adapter - Figure 9

Safety Warnings

Please read the Safety Warmings in the instruction manual supplied with the instrument thoroughly and completely forecourt use. Faire to follow the safety riles can cause fie, trouble, lectica shock, etc. Therefore, make sure to operate  the instrument on a correct power supply and voltage rating marked on each instrument.

Wi For inquires or orders :

KYORITSU ELECTRICAL INSTRUMENTS WORKS, LTD.

2-5-20, Nakase, Meguro-ku, Tokyo, 152-0031 Japan
Phone:+81-3-3723-0131
Fax:+81-3-3723-0152

https://www.kew-ltd.co.jp/en/

KYORITSU - logoThis leaflet was produced in September 2023.
The contents of this leaflet are subject to change twithought notice.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals