KYORITSU 2433R Leakage Clamp Meters User Manual
- June 9, 2024
- KYORITSU
Table of Contents
KYORITSU 2433R Leakage Clamp Meters
MODEL 2433R
- Frequency Selector Switch to eliminate the effect of harmonics.
- Three AC current ranges: 40mA/400mA/400A.
- Resolution 0.01mA.
AC A (50/60Hz)| 40/400mA/400A
±1%rdg±5dgt (40/400mA)
±1%rdg±5dgt (0 – 300A)
±2%rdg (300.1 – 399.9A)
---|---
AC A (WIDE)| 40/400mA/400A
±2.5%rdg±10dgt [20Hz – 1kHz] (40/400mA)
±2.5%rdg±10dgt [40Hz – 1kHz] (0 – 300A)
±5%rdg [40Hz – 1kHz] (300.1 – 399.9A)
Maximum circuit voltage| 600V AC/DC (between line/neutral) 300V AC/DC (against
earth)
Conductor size| Ø40mm max.
Frequency response| 20Hz – 1kHz [40Hz – 1kHz:400A]
Effect of External Stray Magnetic Field| 10mA AC approx. in proximity to a
15mm- dia
conductor carrying 100A AC
Applicable standards| IEC 61010-1 CAT III 300V Pollution Degree 2
IEC 61010-2-032
Response Time| Approx. 2 seconds
Power source| Two R03 or equivalent (DC1.5V) batteries
Dimensions| 185(L) × 81(W) × 32(D)mm
Weight| 270g approx.
Included Accessories| 9052 (Carrying Case) R03 (1.5V) × 2 Instruction Manual
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>