MEAN WELL CSP-3000-120 3000W Power Supply with Single Output Owner’s Manual
- June 13, 2024
- MEAN WELL
Table of Contents
- MEAN WELL CSP-3000-120 3000W Power Supply with Single Output Owner’s
- Dimension
- Features
- Applications
- Description
- SPECIFICATION
- Block Diagram
- Function Manual
- Current Sharing
- Mechanical Specification
- Installation Manual
- Read More About This Manual & Download PDF:
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
MEAN WELL CSP-3000-120 3000W Power Supply with Single Output Owner’s
Manual
Dimension
Features
- AC input 180-264VAC
- Built-in active PFC function
- High efficiency up to 93%
- Forced air cooling by built-in DC fans
- Output voltage / current programmable
- Active current sharing up to 9000W(2+1)
- Built-in remote ON-OFF control/auxiliary power/ power OK signal
- Protections: Short circuit/ Overload/ Over voltage /Over temperature/ Fan failure
- Conformal coating
- 5 years warranty
Applications
- Factory control or automation apparatus
- Test and measurement instrument
- Laser related machine
- UV curing equipment
- Fish lamp
- Burn-in facility
GTIN CODE
MW Search: https://www.meanwell.com/serviceGTIN.aspx.
Description
CSP-3000 is a 3KW single-output enclosed type AC/DC power supply. This series operates for 180-264VAC input voltage and offers the models with the DC output mostly demanded from the industry. Each model is cooled by the built-in fan with fan speed control, working for the temperature up to 65 C. Moreover, CSP-3000 provides vast design flexibility by equipping various built-in functions such as output programming, active current sharing, remote ON-OFF control, auxiliary power, etc.
Model Encoding/ Order Information
SPECIFICATION
| MODEL | CSP-3000-120 | CSP-3000-250 | CSP-3000-400 | 
|---|
OUTPUT
|  DC VOLTAGE|  120V| 250V| 400V
RATED CURRENT|  25A| 12A| 7.5A
CURRENT RANGE|  0 ~ 25A| 0 ~ 12A| 0 ~ 7.5A
RATED POWER|  3000W| 3000W| 3000W
RIPPLE & NOISE (max.) Note.2| 800mVp-p| 1000mVp-p| 1200mVp-p
CONSTANT   CURRENT   REGION|  90 ~ 120V| 125 ~ 250V| 200 ~ 400V
VOLTAGE   TOLERANCE   Note.3|  ±1.0%| ±1.0%| ±1.0%
LINE REGULATION|  ±0.5%| ±0.5%| ±0.5%
LOAD REGULATION|  ±0.5%| ±0.5%| ±0.5%
SETUP, RISE TIME|  1000ms, 80ms / 230VAC at full load
HOLD UP TIME (Typ.)|  10ms at full load  
INPUT
|  VOLTAGE RANGE Note.4|  180 ~ 264VAC           254 ~ 370VDC
FREQUENCY RANGE|  47~63Hz
POWER FACTOR (Typ.)|  PF≧0.95/230VAC at full load
EFFICIENCY (Typ.)|  92%| 92.5%| 93%
AC CURRENT (Typ.)|  20A/180VAC        16A/230VAC
INRUSH CURRENT (Typ.)|  Cold start 60A/230VAC
LEAKAGE CURRENT|  <0.3mA / 240VAC  
PROTECTION
|  SHORT CIRCUIT|  Shut down and latch off o/p voltage, re-power on to
recover
OVER CURRENT|  105 ~ 120% rated output power
User adjustable continuous constant current limiting or constant current
limiting with delay shutdown after 3 seconds, re-power on to recover (Please
refer to the Function Manual)
OVERVOLTAGE|  127 ~ 150V| 265 ~ 315V| 420 ~ 500V
Protection type : Shut down o/p voltage, re-power on to recover
OVER TEMPERATURE|  Shut down o/p voltage, recovers automatically after
temperature goes down or re-power on to recover  
FUNCTION
|  OUTPUT VOLTAGE PROGRAMMABLE(PV)|  Please refer to the Function Manual.
OUTPUT   CONSTANT   CURRENT PROGRAMMABLE(PC)|  Please refer
to the Function Manual.
CURRENT SHARING|  Please refer to the Function Manual.
AUXILIARY POWER(AUX)| 12V@0.4A
REMOTE ON-OFF CONTROL|  Please refer to the Function Manual
ALARM SIGNAL OUTPUT|  Power OK signal. Please refer to the Function
Manual  
ENVIRONMENT
|  WORKING TEMP.|  -20 ~ +65℃ (Refer to “Derating Curve”)
WORKING HUMIDITY|  20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY|  -40 ~ +85℃, 10 ~ 95% RH non-condensing
TEMP. COEFFICIENT|  ±0.05%/℃ (0 ~ 50℃)
VIBRATION|  10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes  
SAFETY & EMC
(Note 5)
|  SAFETY STANDARDS|  UL62368-1,Dekra seal BS EN/EN62368-1, EAC TP TC004,
GB4943.1
WITHSTAND VOLTAGE|  I/P-O/P:3KVAC  I/P-FG:2KVAC  O/P-FG:0.5KVAC
ISOLATION RESISTANCE|  I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/
70% RH  
EMC EMISSION
|  Parameter|  Standard|  Test Level / Note
Conducted| BS EN/EN55032(CISPR32)| Class A
Radiated| BS EN/EN55032(CISPR32)| Class A
Harmonic Current| BS EN/EN61000-3-2| —–
Voltage Flicker| BS EN/EN61000-3-3| —–  
EMC IMMUNITY
|  BS EN/EN55035 ,BS EN/EN61000-6-2
Parameter|  Standard|  Test Level / Note
ESD| BS EN/EN61000-4-2| Level 3, 8KV air ; Level 2, 4KV contact
Radiated| BS EN/EN61000-4-3| Level 3
EFT / Burst| BS EN/EN61000-4-4| Level 3
Surge| BS EN/EN61000-4-5| Level 3, 2KV/Line-Earth ; Level 2, 1KV/Line-Line
Conducted| BS EN/EN61000-4-6| Level 3
Magnetic Field| BS EN/EN61000-4-8| Level 4
Voltage Dips and Interruptions| BS EN/EN61000-4-11| >95% dip 0.5 periods, 30%
dip 25 periods,>95% interruptions 250 periods
**OTHERS|  MTBF|  721.1K hrs min.       Telcordia SR-332 (Bellcore)
; 80.5K hrs min.       MIL-HDBK-217F (25℃)
DIMENSION|  278177.863.5mm (LWH)
PACKING**|
- 
All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25C of ambient temperature. 
- 
In the PV Mode: Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 
 3. Tolerance: includes set up tolerance, line regulation and load regulation.
- 
Turn off the output when input voltage is less than 160VAC. 
 The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on a 720mm’360mm metal plate with 1mm of thickness. The final equipment must be re- confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMl testing of component power supplies.” (as available on http://www.meanwell.com)
- 
The ambient temperature derating of 3.5 C/1000m with fanless models and of 5C/1000m with fan models for operating altitude higher than 2000m(6500ft 
|
Block Diagram

Static Characteristics
Derating Curve
Efficiency vs Load (400V Model)
DRIVING METHODS OF LED MODULE
I-V Operating Area(for PC mode only)
- 
CSP-3000-120CSP-3000-120 
- 
CSP-3000-250 
  
- 
CSP-3000-400 
Function Manual
- Output Voltage/Current Programming
- Mode Setting
 CN1:
|  CONDITION| MODE| FUNCTION
---|---|---|---
**** PIN5/PIN6| SHORT| PV MODE| Output Voltage Programming
OPEN| PC MODE| Output Current Programming  
The factory default settings: PV mode output max voltage pin5/pin6 short by jumper cap. When pull out the jumper cap,the default settings: PC mode output max constant current.

PV/PC Set adjustment
- Adjust the resistance(SVR2) can set output voltage or constant current point, the adjusting range is 20%-100% of max voltage or max constant current point.
- In the CN2, pin5/pin6 access external 10V voltage signal or 500-1KHz PWM signal can adjust the output voltage or constant current point.
 CN2:PIN5/PIN6 needs to operate with a 10V sinking signal or PWM signal, Max. sink current TmA.
  
| MODEL | 120V | 250V | 400V | 
|---|---|---|---|
| PV range | 18 ~ 120V(max.) | 37.5 ~ 250V(max.) | 60 ~ 400V(max.) | 
| PC range | 2.4 ~ 30A(max.) | 1.4~ 17A(max.) | 0.8 ~ 10A(max.) | 
Remote ON-OFF
- Remote ON-OFF is activated by the configuration with respect to CN1 as shown in the following diagram.
  
Example 2.2(A): Using external voltage source
Example 2.2(B): Using internal 12V auxiliary output
Example 2.2(C): Using internal 12V auxiliary output
Connection Method
|  Example 2.2(A)| Example 2.2(B)| Example 2.2(C)
---|---|---|---
SW Logic| Power supply output ON| SW Open(open)| SW Open(open)| SW
Close(short)
Power supply output OFF| SW Close(short)| SW Close(short)| SW Open(open)  
Alarm Signal Output
Alarm signal is sent out through “P OK” & “P OK GND” and P OK2 & P OK GND2 pins on CN1. Please acknowledge an external voltage source is required for this function.

Function| Description| Output of alarm(P OK, Relay Contact)| Output of alarm(P
OK2, TTL Signal)
---|---|---|---
__ P OK| The signal is “Low” when the power supply is above 80% of the rated
output voltage, or, say, Power OK| Low(0.5V max at 500mA)| Low(0.5V max at
10mA)
The signal turns to be “High” when the power supply is under 80% of the rated
output voltage, or, say, Power Fail| High or open(External applied voltage,
500mA max.)| High or open(External applied voltage, 10mA max.)  
Explanation of alarm

Select Overload Protection Type
- Insert the shorting connector on CN1 that is shown in Fig 4.1, the Overload Protection Type will be “constant current limiting with delay shutdown after 3 seconds, re-power on to recover”. This is the factory default.
- Remove the shorting connector on CN1 that is shown in Fig 4.2, the Overload Protection Type will be “continuous constant current limiting”.
  
Current Sharing
CSP-3000 has the built-in active current sharing function and can be connected in parallel, up to 3 units, to provide higher output power as exhibited below:
- The power supplies should be paralleled using short and large diameter wiring and then connected to the load.
- The difference in output voltages among parallel units should be less than 0.2V(Can Fine tune by SVR1).
- The total output current must not exceed the value determined by the following equation:
- 
- When out current<( 50% rate current)×(Number of unit), the current shared among units may not be fully balanced.
 
- Under parallel operation, the “PV/PC” function is not available.
- CS+/CS- on CN1 are connected mutually in parallel(Note:CS+/CS- do not reverse connection).
  
Mechanical Specification

Mounting Instruction
Hole No.| Recommended Screw Size| MAX. Penetration Depth  L|  Recommended
mounting torque
---|---|---|---
1| M4| 5mm| 7~10Kgf-cm  
Control Pin No. Assignment (CN1) : HRS DF11-10DP-2DS or equivalent
| Mating Housing | HRS DF11-10DS or equivalent | 
|---|---|
| Terminal | HRS DF11-**SC or equivalent | 
| Pin No. | Function | 
| --- | --- | 
| 1 | RCG | 
| 2 | P-OK-2 | 
| 3 | RC | 
| 4 | P-OK-GND-2 | 
| 5 | GND | 
| 6 | Mode | 
| 7 | P-OK | 
| 8 | CS+ | 
| 9 | P-OK GND | 
| 10 | CS- | 
Control Pin No. Assignment (CN2) : HRS DF11-8DP-2DS or equivalent
| Mating Housing | HRS DF11-8DS or equivalent | 
|---|---|
| Terminal | HRS DF11-**SC or equivalent | 
| Pin No. | Function | 
| --- | --- | 
| 1 | 12V AUXG | 
| 2 | 12V AUX+ | 
| 3 | NC | 
| 4 | NC | 
| 5 | PV/PC+ | 
| 6 | PV/PC- | 
| 7 | NC | 
| 8 | NC | 
Note: NC pins, please keep open circuit and do not connect to other pins/signals.
LED status indication
AC Input Terminal Pin No. Assignment

DC Output Terminal Pin No. Assignment

Installation Manual
Please refer to : http://www.meanwell.com/manual.html
Read More About This Manual & Download PDF:
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>