BEA LO21 Lock-Out Relay for Swing Doors Instruction Manual
- June 13, 2024
- BEA
Table of Contents
BEA LO21 Lock-Out Relay for Swing Doors Instruction Manual
DESCRIPTION
- Red LED
- Green LED
- DIP switches
ANSI/BHMA 156.10-2005 requires the use of a sensor or photo beam on the
swing side of the door when using a header-mounted, safety sensor (e.g.
Bodyguard or DK12). For more information, reference the ANSI 156.10 standard.
TECHNICAL SPECIFICATIONS
Power Supply: 12 – 24 VAC / 15 – 24 VDC
Operating Frequency: 4 MHz (microprocessor)
Power Consumption: 10 mA at rest (50 mA max)
Output: 2 x SPST relays
Max. Voltage (relay contact): 60 VDC, 120 VAC
Max. Current (both relay contcats): 2A DC, 0.5A AC
Specifications are subject to change without prior notice.
All values measured in specific conditions.
PRECAUTIONS
CAUTION
- Shut off all power going to header before attempting any wiring procedures.
- The door control system and the header cover profile must be correctly grounded.
- Maintain a clean and safe environment when working in public areas.
- Constantly be aware of pedestrian traffic around the door area.
- Always stop pedestrian traffic through the doorway when performing tests that may result in unexpected reactions by the door.
- ESD (electrostatic discharge): Circuit boards are vulnerable to damage by electrostatic discharge. Before handling any board, ensure you dissipate your body’s ESD charge.
- Always check placement of all wiring before powering up to ensure that moving door parts will not catch any wires and cause damage to equipment.
- Ensure compliance with all applicable safety standards (i.e. ANSI A156.10) upon completion of installation.
- DO NOT attempt any internal repair of the components. All repairs and/or component replacements must be performed by BEA, Inc. Unauthorized disassembly or repair:
- May jeopardize personal safety and may expose one to the risk of electrical shock.
- May adversely affect the safe and reliable performance of the product resulting in a voided warranty.
- Always test the proper operation of the installation before leaving the premises.
- Only trained and qualified personnel are recommended to install and set up the sensor
MOUNTING & WIRING
All LO21 wiring must be accomplished with the module unplugged. If the red / white striped and white wires (data wires) touch each other when power is applied, damage to the unit will result.
WIRING TO MICRO CELL
*If using safety beams, blue and green wires must be wired in parallel with the Bodyguard/DK-12 connection to the SAF and COM of the door control.
If using dry contact safety beams, such as BEA’s Microcell, remember these changes:
- Power the safety beams with the same transformer that is used for the LO21.
- The black/white striped wire is not used and should be taped off.
- The gray and purple wires of the LO21 go to the NO and COM dry contacts of the safety beams.
HYDRAULIC UNIT / AC MOTOR
If AC voltage is > 50 VAC, use the provided 10,000 Ohm resistor to wire in- line with the red wire. Below are examples of a Keane Monroe Series 2000 swing-door operator.
WIRING TO HYDRAULIC UNIT
WIRING TO AC MOTOR
SETUP / PROGRAMMING
VERIFY OPERATION
-
Upon powering, verify red LED when door is in closing cycle. If it does not:
- DC units: Reverse the red and black wires from LO21 to motor.
- AC units: Verify AC power is being switched on and off at point of connection for red and black wires.
- Safety beams present: Verify green LED illuminates and turns off when beams are blocked (and unblocked, respectively).
-
If Bodyguard learns “door closed,” but not “door open”:
a. Place door in open position.
b. Using BEA remote control, unlock Bodyguard and press Magic Wand and then “2” .
c. If Bodyguard does not flash green, improper data is being sent for “door open” position (see below for correct voltage).
0 VDC = closed door / 8 VDC = closing door / 12 VDC = open door
d. Verify voltages as listed above, and refer to the Bodyguard User’s Guide, if necessary. -
Adjust Time Delay, if necessary, by changing DIP switch settings. These can be set for a time delay of 0 – 31 seconds. See following page for specific DIP switch settings.
- Time Delay begins when motor starts rotating to close door. Time Delay DOES NOT stop counting if motor rotation stops. Time Delay is only interrupted when door reactivates or safety beams are broken.
- must be set to ensure that red LED remains on for entire “door closing” cycle; red LED must turn off after door reaches jamb
- Time Delay must be adjusted as necessary when door speed is adjusted
DIP SWITCH SETTINGS
LO21 LED INDICATORS:
red LED = lockout time; LED is on when door is in “closing” cycle
green LED = signal detection from safety beams
TIP WHEN SETTING TIME DELAY:
If the red LED on the Bodyguard illuminates while the door is in “closing”
cycle, it is probably seeing the door at the last degree or two of closing.
Try increasing the time delay by one second.
* = DIP ON
TIME DELAY | 1 | 2 | 3 | 4 | 5 |
---|---|---|---|---|---|
1 | * | ||||
2 | * | ||||
3 | * | ||||
4 | * | ||||
5 | * | * | |||
6 | * | * |
7
(def)| | | | |
8| | | | |
9| | | | |
10| | | | |
11| | | | |
12| | | | |
13| | | | |
14| | | | |
15| | | | |
16| | | | |
17| | | | |
18| | | | |
19| | | | |
20| | | | |
21| | | | |
22| | | | |
23| | | | |
24| | | | |
25| | | | |
26| | | | |
27| | | | |
28| | | | |
29| | | | |
30| | | | |
31| | | | | *
TROUBLESHOOTING
Red LED does not illuminate during “closing” cycle OR red LED illuminates in
latch check| Red and black wires are reversed (polarity sensitive)| Reverse
the polarity of the moror wires.
---|---|---
AC motor application: in-line resistor not installed| Install in-line resistor
on red wire of LO21 (AC motors only).
Faulty input power or data| Check voltage supply to LO21 (12 – 24 VAC / 15 –
24 VDC).
Check voltage on orange, brown, red, and black wires.
Door will not open or close (green LED is on)| Lockout safety beams are
blocked|
- Remove any obstructions with safety beam path.
- Check all wiring related to safety beams.
- Test the safety beams for proper operation.
Faulty safety beam receiver or transmitter
Faulty power supply to safety beam
Faulty safety beam wiring
Door will not re-cycle open when activated during “closing” cycle| Lockout
time is not long enough (red LED goes out before door is fully closed)|
Increase lockout time. Refer to DIP switch chart.
Data wires reversed at Bodyguard/ DK-12| Reverse data wires at Bodyguard/DK12.
Check voltage on data wires (red and red/ white).
Green LED does not illuminate when safety beams are blocked| Faulty safety
beam receiver| Test the beams and LO21 with multimeter.
Faulty connection on purple and gray wire from LO21| Make contact with the
purple and gray wires. Green LED should illuminate.
Improper voltage reading on data lines at LO21| Incorrect wiring at LO21|
Verify correct polarity at terminals 6 and 7 on Bodyguard.
Faulty LO21| If data line voltage remains constant at LO21 for open and close
dpositions and all wiring verified, replace faulty LO21.
BEA, INC. INSTALLATION/SERVICE COMPLIANCE EXPECTATIONS
BEA, Inc., the sensor manufacturer, cannot be held responsible for incorrect installations or incorrect adjustments of the sensor/device; therefore, BEA, Inc. does not guarantee any use of the sensor/device outside of its intended purpose. BEA, Inc. strongly recommends that installation and service technicians be AAADM-certifi ed for pedestrian doors, IDA-certifi ed for doors/ gates, and factory-trained for the type of door/gate system. Installers and service personnel are responsible for executing a risk assessment following each installation/service performed, ensuring that the sensor/device system performance is compliant with local, national, and international regulations, codes, and standards. Once installation or service work is complete, a safety inspection of the door/gate shall be performed per the door/gate manufacturer’s recommendations and/or per AAADM/ANSI/DASMA guidelines (where applicable) for best industry practices. Safety inspections must be performed during each service call – examples of these safety inspections can be found on an AAADM safety information label (e.g. ANSI/DASMA 102, ANSI/DASMA 107, UL294, UL325, and International Building Code).
Visit website for available languages of this document.
Verify that all appropriate industry signage, warning labels, and placards are in place.
ech Support & Customer Service:
1-800-523-2462
General Tech Questions: techservices-us@BEAsensors.com
Tech Docs: www.BEAsensors.com
75.0061.09 LO21 20230417