FUJITSU RQPL Package Heat Pump Instruction Manual

June 13, 2024
FUJITSU

Package Heat Pump

FUJITSU RQPL Package Heat Pump

RQPL
Nominal Sizes: 2 to 4 Tons [7.03 to 14.07 kW] 14 SEER Series

Manufactured for
Fujitsu General America, Inc.
Fairfield, NJ

  • Proper sizing and installation of equipment is critical to achieve optimal performance. Split system air conditioners and heat pumps must be matched with appropriate coil components to meet Energy Star. Ask your Contractor for details or visit www.energystar.gov.

Features and Benefits

  • Scroll compressor – for maximum efficiency and quiet operation.
  • Louvered condenser compartment – (2) protects the coil against yard hazards.
  • One-piece top with drip flange – (3) helps to keep water out of the unit.
  • Supply and return air openings – (4) feature a one-inch tall flange to prevent water migration into the ductwork.
  • Access panels have “weep holes” and channels – (5) to further manage water run-off.
  • Side and down discharge options – available on all models (Shipped horizontal flow standard).
  • Easily accessible blower section – (7) features a slide-out blower.
  • Conveniently located refrigerant connections – (8) for easy service diagnostics. Low pressure/loss of charge protection is standard on all models.
  • Condenser and evaporator coils – (9) feature enhanced fins for better heat transfer and rifled copper tubing for greater efficiency.
  • Supplemental electric heat strips – (10) up to 15 kW are available (field or factory installed) for periods of extreme cold temperatures. Single point wiring simplifies installation.
  • Easily accessible control box (12).
  • Thermal expansion valve – (13) is standard on all models and provides superior superheat control, reliability, and energy efficiency at all operating conditions.
  • Filter Drier – is standard on all models.
  • Rugged baserail – (15) included for improved installation and handling.
  • Reversing valve directs flow of refrigerant – and reverses the refrigerant flow when heating is required.

Package Heat Pump Features:

FUJITSU RQPL Package Heat Pump - Package Heat Pump
Features

Model Number Identification

R| Q| P| L| B024| J| K| 000| X X X
---|---|---|---|---|---|---|---|---
Brand| Product Category| Efficiency| Design Series| Cooling Capacity
(BTU) [kW]| Electrical Designation| Drive Package| Heating Capacity (Factory Installed)| Factory
Installed Options
R – Fujitsu| Q – Package Heat Pump| P – 14 SEER| L – R-410A| B024 – 24,000 [7.03] B025 – 24,000  [7.03] B030 – 30,000  [8.79] C036 – 36,000 [10.55] C042 – 42,000 [12.31] B049 – 48,000 [14.07]| J – 208-230V – 1PH – 60HZ
C – 208-230V – 3PH – 60HZ| K – Direct Drive| 000 – No Resistance Heat
005 – 05 kW Resistance Heat
(018-030)
010 – 10 kW Resistance Heat (024-048)
015 – 15 kW Resistance Heat (036-048)| (See Next Page)

[ ] Designates Metric Conversions

Available SKUs

Available Models
RQPL-B024JK
RQPL-B025JK
RQPL-B030JK
RQPL-C036CK
RQPL-C036JK
RQPL-C042CK
RQPL-C042JK
RQPL-B049CK
RQPL-B049JK

Options

Instructions for Factory Installed Option(s) Selection
Note: Two characters following the model number will be utilized to designate a factory-installed option or combination of options. If no factory option(s) is required, nothing follows the model number.
Step 1. After a basic rooftop model is selected, choose a two-character option code from the FACTORY INSTALLED OPTION SELECTION TABLE.

FACTORY INSTALLED OPTION CODES

Option Codes Low Ambient/High Pressure Tin Plated Hairpin Coil
AUA

Example: RQPL-B036JK000XX (where XX is factory installed option)
Example: No Options
RQPL-B036JK000
Note: Factory installed economizer is not available on these models.

General Data

NOMINAL SIZES 2-4 TONS [7.03-14.07 kW]

Model RQPL- Series B024JK B025JK B030JK C036CK
Cooling Performance 1 CONTINUED
Gross Cooling Capacity Btu [kW] 25,000 [7.32] 24,400 [7.15] 29,800 [8.73]

35,000 [10.25]
EER/SEER 2| 11.8/14| 12/14.3| 12/14.3| 11/14
Nominal CFM/AHRI Rated CFM [L/s]| 800/850 [378/401]| 800/850 [378/401]| 1000/1050 [472/495]| 1200/1300 [566/613]
AHRI Net Cooling Capacity Btu [kW]| 24,400 [7.15]| 23,800 [6.97]| 29,200 [8.56]| 34,200 [10.02]
Net Sensible Capacity Btu [kW]| 18,800 [5.51]| 17,800 [5.22]| 23,000 [6.74]| 27,500 [8.06]
Net Latent Capacity Btu [kW]| 5,600 [1.64]| 6,000 [1.76]| 6,200 [1.82]| 6,700 [1.96]
Net System Power kW| 2.07| 1.95| 2.48| 2.96
Heating Performance (Heat Pumps) 4| | | |
High Temp. Btuh [kW] Rating| 23,800 [6.97]| 23,600 [6.91]| 27,800 [8.15]| 33,000 [9.67]
System Power KW / COP| 1.99/3.5| 1.87/3.7| 2.26/3.6| 2.97/3.4
Low Temp. Btuh [kW] Rating| 13,800 [4.04]| 12,900 [3.78]| 15,500 [4.54]| 18,000 [5.27]
System Power KW / COP| 1.84/2.2| 1.69/2.24| 2.06/2.2| 2.72/2
HSPF (Btu/Watts-hr)| 8| 8| 8| 8
Compressor No./Type| 1/Scroll| 1/Scroll| 1/Scroll| 1/Scroll
Outdoor Sound Rating (dB) 3| 76| 76| 76| 76
Outdoor Coil—Fin Type| Louvered| Louvered| Louvered| Louvered
Tube Type| Rifled| Rifled| Rifled| Rifled
Tube Size in. [mm] OD| 0.375 [9.5]| 0.375 [9.5]| 0.375 [9.5]| 0.375 [9.5]
Face Area sq. ft. [sq. m]| 14.51 [1.35]| 14.51 [1.35]| 16.32 [1.52]| 16.32 [1.52]
Rows / FPI [FPcm]| 1 / 22 [9]| 1 / 22 [9]| 1 / 22 [9]| 2 / 22 [9]
Refrigerant Control| TX Valves| TX Valves| TX Valves| TX Valves
Indoor Coil—Fin Type| Louvered| Louvered| Louvered| Louvered
Tube Type| Rifled| Rifled| Rifled| Rifled
Tube Size in. [mm]| 0.375 [9.5]| 0.375 [9.5]| 0.375 [9.5]| 0.375 [9.5]
Face Area sq. ft. [sq. m]| 5.54 [0.51]| 5.54 [0.51]| 7.39 [0.69]| 7.39 [0.69]
Rows / FPI [FPcm]| 2 / 15 [6]| 2 / 15 [6]| 2 / 15 [6]| 2 / 15 [6]
Refrigerant Control| TX Valves| TX Valves| TX Valves| TX Valves
Drain Connection No./Size in. [mm]| 1/1 [25.4]| 1/1 [25.4]| 1/1 [25.4]| 1/0.75 [19.05]
Outdoor Fan—Type| Propeller| Propeller| Propeller| Propeller
No. Used/Diameter in. [mm]| 1/22 [558.8]| 1/22 [558.8]| 1/22 [558.8]| 1/22 [558.8]
Drive Type/No. Speeds| Direct/1| Direct/1| Direct/1| Direct/1
CFM [L/s]| 2700 [1274]| 2700 [1274]| 2700 [1274]| 2700 [1274]
No. Motors/HP| 1 at 1/3 HP| 1 at 1/3 HP| 1 at 1/3 HP| 1 at 1/3 HP
Motor RPM| 1075| 869| 1075| 1075
Indoor Fan—Type| FC Centrifugal| FC Centrifugal| FC Centrifugal| FC Centrifugal
No. Used/Diameter in. [mm]| 1/9×7 [229×178]| 1/9×7 [229×178]| 1/10×9 [254×229]| 1/10×9 [254×229]
Drive Type| Direct| Direct| Direct| Direct
No. Speeds| Multiple| Multiple| Multiple| Multiple
No. Motors| 1| 1| 1| 1
Motor HP| 1/3| 1/3| 1/2| 1/2
Motor RPM| 1050| 1050| 1050| 1050
Motor Frame Size| 48| 48| 48| 48
Filter—Type| Field Supplied| Field Supplied| Field Supplied| Field Supplied
Furnished| No| No| No| No
(NO.) Size Recommended in. [mm x mm x mm]| (1)1x20x20 [25x508x508]| (1)1x20x20 [25x508x508]| (1)1x24x24 [25x610x610]| (1)1x24x24 [25x610x610]
Refrigerant Charge Oz. [g]| 98 [2778]| 98 [2778]| 108 [3062]| 184 [5216]
Weights Net Weight lbs. [kg]| 391 [177]| 391 [177]| ** 444 [201]| 508 [230]
Ship Weight lbs. [kg]| 401 [182]| 401 [182]| 455 [206]| 519 [235]
See Page 10 for Notes.| | |
[   ] Designates Metric Conversions**

NOMINAL SIZES 2-4 TONS [7.03-14.07 kW]

Model RQPL- Series C036JK C042CK C042JK B049CK
Cooling Performance 1 CONTINUED
Gross Cooling Capacity Btu [kW] 35,000 [10.25] 41,000 [12.01] 41,000
[12.01] 47,500 [13.92]
EER/SEER 2 11/14 11/14 11/14 11.5/14
Nominal CFM/AHRI Rated CFM [L/s] 1200/1300 [566/613] 1400/1375 [661/649]
1400/1375 [661/649] 1600/1600 [755/755]
AHRI Net Cooling Capacity Btu [kW] 34,200 [10.02] 40,000 [11.72] 40,000
[11.72] 46,000 [13.48]
Net Sensible Capacity Btu [kW] 27,500 [8.06] 30,100 [8.82] 30,100 [8.82]

34,650 [10.15]
Net Latent Capacity Btu [kW]| 6,700 [1.96]| 9,900 [2.9]| 9,900 [2.9]| 11,350 [3.33]
Net System Power kW| 2.96| 3.69| 3.69| 4
Heating Performance (Heat Pumps)| | | |
High Temp. Btuh [kW] Rating| 33,000 [9.67]| 40,000 [11.72]| 40,000 [11.72]| 46,000 [13.48]
System Power KW / COP| 2.97/3.4| 3.77/3.38| 3.77/3.38| 3.87/3.48
Low Temp. Btuh [kW] Rating| 18,000 [5.27]| 24,800 [7.27]| 24,800 [7.27]| 26,200 [7.68]
System Power KW / COP| 2.72/2| 3.36/2.18| 3.36/2.18| 3.55/2.2
HSPF (Btu/Watts-hr)| 8| 8| 8| 8
Compressor No./Type| 1/Scroll| 1/Scroll| 1/Scroll| 1/Scroll
Outdoor Sound Rating (dB) 5| 76| 76| 76| 78
Outdoor Coil—Fin Type| Louvered| Louvered| Louvered| Louvered
Tube Type| Rifled| Rifled| Rifled| Rifled
Tube Size in. [mm] OD| 0.375 [9.5]| 0.375 [9.5]| 0.375 [9.5]| 0.375 [9.5]
Face Area sq. ft. [sq. m]| 16.32 [1.52]| 16.32 [1.52]| 16.32 [1.52]| 16.32 [1.52]
Rows / FPI [FPcm]| 2 / 22 [9]| 2 / 22 [9]| 2 / 22 [9]| 2 / 22 [9]
Refrigerant Control| TX Valves| TX Valves| TX Valves| TX Valves
Indoor Coil—Fin Type| Louvered| Louvered| Louvered| Louvered
Tube Type| Rifled| Rifled| Rifled| Rifled
Tube Size in. [mm] OD| 0.375 [9.5]| 0.375 [9.5]| 0.375 [9.5]| 0.375 [9.5]
Face Area sq. ft. [sq. m]| 7.39 [0.69]| 7.39 [0.69]| 7.39 [0.69]| 7.39 [0.69]
Rows / FPI [FPcm]| 2 / 15 [6]| 2 / 15 [6]| 2 / 15 [6]| 2 / 15 [6]
Refrigerant Control| TX Valves| TX Valves| TX Valves| TX Valves
Drain Connection No./Size in. [mm]| 1/0.75 [19.05]| 1/1 [25.4]| 1/1 [25.4]| 1/1 [25.4]
Outdoor Fan—Type| Propeller| Propeller| Propeller| Propeller
No. Used/Diameter in. [mm]| 1/22 [558.8]| 1/22 [558.8]| 1/22 [558.8]| 1/22 [558.8]
Drive Type/No. Speeds| Direct/1| Direct/1| Direct/1| Direct/1
CFM [L/s]| 2700 [1274]| 3700 [1746]| 3700 [1746]| 3000 [1416]
No. Motors/HP| 1 at 1/3 HP| 1 at 1/3 HP| 1 at 1/3 HP| 1 at 1/3 HP
Motor RPM| 1075| 1200| 1200| 1075
Indoor Fan—Type| FC Centrifugal| FC Centrifugal| FC Centrifugal| FC Centrifugal
No. Used/Diameter in. [mm]| 1/10×9 [254×229]| 1/10×9 [254×229]| 1/10×9 [254×229]| 1/10×9 [254×229]
Drive Type| Direct| Direct| Direct| Direct
No. Speeds| Multiple| Multiple| Multiple| Multiple
No. Motors| 1| 1| 1| 1
Motor HP| 1/2| 3/4| 3/4| 3/4
Motor RPM| 1050| 1050| 1050| 1075
Motor Frame Size| 48| 48| 48| 48
Filter—Type| Field Supplied| Field Supplied| Field Supplied| Field Supplied
Furnished| No| No| No| No
(NO.) Size Recommended in. [mm x mm x mm]| (1)1x24x24 [25x610x610]| (1)1x24x24 [25x610x610]| (1)1x24x24 [25x610x610]| (1)1x24x24 [25x610x610]
Refrigerant Charge Oz. [g]| 184 [5216]| 188.8 [5352]| 188.8 [5352]| 177 [5018]
Weights Net Weight lbs. [kg]| 508 [230]| 500 [227]| 510 [231]| 500 [227]
Ship Weight lbs. [kg]| 519 [235]| 511 [232]| 521 [236]| 511 [232]
See Page 10 for Notes.| | | [   ] Designates Metric Conversions

NOMINAL SIZES 2-4 TONS [7.03-14.07 kW]

Model RQPL- Series B049JK

Cooling Performance 1
Gross Cooling Capacity Btu [kW] EER/SEER2
Nominal CFM/AHRI Rated CFM [L/s] AHRI Net Cooling Capacity Btu [kW] Net Sensible Capacity Btu [kW] Net Latent Capacity Btu [kW] Net System Power kW| 47,500 [13.92] 11.5/14
1600/1600 [755/755] 46,000 [13.48] 34,650 [10.15] 11,350 [3.33] 4

Heating Performance (Heat Pumps)4
High Temp. Btuh [kW] Rating
System Power KW / COP
Low Temp. Btuh [kW] Rating
System Power KW / COP
HSPF (Btu/Watts-hr)| 46,000 [13.48] 3.87/3.48
26,200 [7.68] 3.55/2.2
8
Compressor
No./Type| 1/Scroll
Outdoor Sound Rating (dB)3| 78
Outdoor Coil—Fin Type
Tube Type
Tube Size in. [mm] OD
Face Area sq. ft. [sq. m] Rows / FPI [FPcm] Refrigerant Control| Louvered
Rifled
0.375 [9.5] 16.32 [1.52] 2 / 22 [9] TX Valves
Indoor Coil—Fin Type
Tube Type
Tube Size in. [mm] Face Area sq. ft. [sq. m] Rows / FPI [FPcm] Refrigerant Control
Drain Connection No./Size in. [mm]| Louvered
Rifled
0.375 [9.5] 7.39 [0.69] 2 / 15 [6] TX Valves
1/1 [25.4]
Outdoor Fan—Type
No. Used/Diameter in. [mm] Drive Type/No. Speeds
CFM [L/s] No. Motors/HP
Motor RPM| Propeller
1/22 [558.8] Direct/1
3000 [1416] 1 at 1/3 HP
1075
Indoor Fan—Type
No. Used/Diameter in. [mm] Drive Type
No. Speeds
No. Motors
Motor HP
Motor RPM
Motor Frame Size| FC Centrifugal
1/10×9 [254×229] Direct
Multiple
1
3/4
1075
48
Filter—Type
Furnished
(NO.) Size Recommended in. [mm x mm x mm]| Field Supplied
No
(1)1x24x24 [25x610x610]
Refrigerant Charge Oz. [g]| 177 [5018]
Weights
Net Weight lbs. [kg] Ship Weight lbs. [kg]| 510 [231] 521 [236]

General Data Notes

NOTES:

  1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. AHRI capacity is net and includes the effect of fan motor heat. Units are suitable for operation in CFM range shown in airflow tables. Units are certified in accordance with the Unitary Air Conditioner Equipment certification program, which is based on AHRI Standard 210/240 or 360.
  2. EER and/or SEER are rated at AHRI conditions and in accordance with DOE test procedures.
  3. Outdoor Sound Rating shown is tested in accordance with AHRI Standard 270.
  4. Heating Performance is rated at 47° F ambient, 70° F entering dry bulb for High Temp rating and 17° F ambient, 70° F entering dry bulb for Low Temp rating. Performance ratings do include the effect of fan motor heat.

Gross Systems Performance Data

ENTERING INDOOR AIR @ 80°F [26.7°C] dbE

wbE| 71°F [21.7°C]| 67°F [19.4°C]| 63°F [17.2°C]
CFM [L/s]| 940 [444]| 850 [401]| 760 [359]| 940 [444]| 850 [401]| 760 [359]| 940 [444]| 850 [401]| 760 [359]
DR ➀| .15| .13| .11| .15| .13| .11| .15| .13| .11
OUT DOOR
DRY BULB
TEMPERATURE °F [°C]| 75 [23.9]| Total BTUH [kW] Sens BTUH [kW] Power| 29.9 [8.76] 19.2 [5.63] 1.5| 29.4 [8.62] 18.4 [5.39] 1.5| 28.8 [8.44] 17.5 [5.13] 1.5| 28.6 [8.38] 22.0 [6.45] 1.5| 28.0 [8.21] 21.0 [6.15] 1.5| 27.5 [8.06] 20.1 [5.89] 1.5| 27.6 [8.09] 23.3 [6.83] 1.5| 27.1 [7.94] 22.3 [6.54] 1.5| 26.6 [7.80] 21.2 [6.21] 1.5
80 [26.7]| Total BTUH [kW] Sens BTUH [kW] Power| 29.7 [8.70] 19.0 [5.57] 1.6| 29.1 [8.53] 18.1 [5.30] 1.6| 28.6 [8.38] 17.3 [5.07] 1.6| 28.3 [8.29] 21.8 [6.39] 1.6| 27.8 [8.15] 20.8 [6.10] 1.6| 27.3 [8.00] 19.9 [5.83] 1.6| 27.3 [8.00] 23.1 [6.77] 1.6| 26.8 [7.85] 22.1 [6.48] 1.6| 26.4 [7.74] 21.0 [6.15] 1.6
85 [29.4]| Total BTUH [kW] Sens BTUH [kW] Power| 29.0 [8.50] 18.6 [5.45] 1.7| 28.5 [8.35] 17.8 [5.22] 1.7| 27.9 [8.18] 16.9 [4.95] 1.7| 27.6 [8.09] 21.4 [6.27] 1.7| 27.2 [7.97] 20.5 [6.01] 1.7| 26.7 [7.83] 19.5 [5.71] 1.7| 26.7 [7.83] 22.7 [6.65] 1.7| 26.2 [7.68] 21.7 [6.36] 1.7| 25.7 [7.53] 20.7 [6.07] 1.7
90 [32.2]| Total BTUH [kW] Sens BTUH [kW] Power| 28.0 [8.21] 18.1 [5.30] 1.8| 27.5 [8.06] 17.3 [5.07] 1.8| 27.0 [7.91] 16.5 [4.84] 1.8| 26.6 [7.80] 20.9 [6.13] 1.8| 26.2 [7.68] 20.0 [5.86] 1.8| 25.7 [7.53] 19.1 [5.60] 1.8| 25.6 [7.50] 22.2 [6.51] 1.8| 25.2 [7.39] 21.2 [6.21] 1.8| 24.7 [7.24] 20.2 [5.92] 1.8
95 [35]| Total BTUH [kW] Sens BTUH [kW] Power| 26.7 [7.83] 17.5 [5.13] 1.9| 26.3 [7.71] 16.7 [4.89] 1.9| 25.8 [7.56] 16.0 [4.69] 1.9| 25.4 [7.44] 20.4 [5.98] 1.9| 24.9 [7.30] 19.4 [5.69] 1.9| 24.5 [7.18] 18.5 [5.42] 1.9| 24.4 [7.15] 21.6 [6.33] 1.9| 24.0 [7.03] 20.7 [6.07] 1.9| 23.5 [6.89] 19.7 [5.77] 1.9
100 [37.8]| Total BTUH [kW] Sens BTUH [kW] Power| 25.4 [7.44] 16.9 [4.95] 2.0| 24.9 [7.30] 16.1 [4.72] 2.0| 24.5 [7.18] 15.4 [4.51] 2.0| 24.0 [7.03] 19.7 [5.77] 2.0| 23.6 [6.92] 18.8 [5.51] 2.0| 23.2 [6.80] 18.0 [5.28] 2.0| 23.0 [6.74] 21.0 [6.15] 2.0| 22.6 [6.62] 20.1 [5.89] 2.0| 22.2 [6.51] 19.1 [5.60] 2.0
105 [40.6]| Total BTUH [kW] Sens BTUH [kW] Power| 24.0 [7.03] 16.3 [4.78] 2.1| 23.6 [6.92] 15.5 [4.54] 2.1| 23.1 [6.77] 14.8 [4.34] 2.1| 22.6 [6.62] 19.1 [5.60] 2.1| 22.2 [6.51] 18.2 [5.33] 2.1| 21.8 [6.39] 17.4 [5.10] 2.1| 21.7 [6.36] 20.4 [5.98] 2.1| 21.3 [6.24] 19.5 [5.71] 2.1| 20.9 [6.13] 18.5 [5.42] 2.1
110 [43.3]| Total BTUH [kW] Sens BTUH [kW] Power| 22.7 [6.65] 15.6 [4.57] 2.2| 22.3 [6.54] 14.9 [4.37] 2.2| 21.9 [6.42] 14.2 [4.16] 2.2| 21.4 [6.27] 18.5 [5.42] 2.2| 21.0 [6.15] 17.6 [5.16] 2.2| 20.6 [6.04] 16.8 [4.92] 2.2| 20.4 [5.98] 19.7 [5.77] 2.2| 20.0 [5.86] 18.9 [5.54] 2.2| 19.6 [5.74] 18.0 [5.28] 2.2
115 [46.1]| Total BTUH [kW] Sens BTUH [kW] Power| 21.6 [6.33] 15.1 [4.43] 2.3| 21.2 [6.21] 14.4 [4.22] 2.3| 20.8 [6.10] 13.7 [4.02] 2.3| 20.2 [5.92] 17.9 [5.25] 2.3| 19.9 [5.83] 17.1 [5.01] 2.3| 19.5 [5.71] 16.3 [4.78] 2.3| 19.3 [5.66] 19.2 [5.63] 2.3| 18.9 [5.54] 18.3 [5.36] 2.3| 18.6 [5.45] 17.5 [5.13] 2.3

DR —Depression ratio
dbE —Entering air dry bulb
wbE —Entering air wet bulb
Total —Total capacity x 1000 BTUH
Sens —Sensible capacity x 1000 BTUH
Power —KW input

NOTES:
¿ When the entering air dry bulb is other than 80°F [27°C], adjust the sensible capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].
HEATING PERFORMANCE DATA—RQPL-024

IDB 60°F [15.5°C] 70°F [21.1°C] 80°F [26.7°C]
CFM [L/s] 940 [444] 850 [401] 760 [359]
[444]** 850 [401] 760 [359] 940 [444]

760 [359]
OUT DOOR
DRY BULB
TEMPERATURE
°F [°C]| 0 [-17.8]| Total BTUH [kW] Power| 8.9 [2.61] 1.4| 8.8 [2.58] 1.4| 8.7 [2.55] 1.4| 8.0 [2.34] 1.6| 7.9 [2.32] 1.6| 7.9 [2.32] 1.6| 6.5 [1.90] 1.8| 6.5 [1.90] 1.8| 6.5 [1.90] 1.9
5 [-15]| Total BTUH [kW] Power| 10.5 [3.08] 1.4| 10.4 [3.05] 1.4| 10.4 [3.05] 1.5| 9.6 [2.81] 1.6| 9.6 [2.81] 1.6| 9.5 [2.78] 1.6| 8.2 [2.40] 1.8| 8.1 [2.37] 1.9| 8.1 [2.37] 1.9
10 [-12.2]| Total BTUH [kW] Power| 12.1 [3.55] 1.4| 12.1 [3.55] 1.5| 12.0 [3.52] 1.5| 11.3 [3.31] 1.6| 11.2 [3.28] 1.6| 11.1 [3.25] 1.7| 9.8 [2.87] 1.9| 9.8 [2.87] 1.9| 9.7 [2.84] 1.9
15 [-9.4]| Total BTUH [kW] Power| 13.8 [4.04] 1.5| 13.7 [4.02] 1.5| 13.6 [3.99] 1.5| 12.9 [3.78] 1.6| 12.8 [3.75] 1.7| 12.7 [3.72] 1.7| 11.5 [3.37] 1.9| 11.4 [3.34] 1.9| 11.3 [3.31] 1.9
20 [-6.7]| Total BTUH [kW] Power| 15.4 [4.51] 1.5| 15.3 [4.48] 1.5| 15.2 [4.45] 1.5| 14.5 [4.25] 1.7| 14.4 [4.22] 1.7| 14.3 [4.19] 1.7| 13.1 [3.84] 1.9| 13.0 [3.81] 1.9| 12.9 [3.78] 1.9
25 [-3.9]| Total BTUH [kW] Power| 17.1 [5.01] 1.5| 16.9 [4.95] 1.5| 16.8 [4.92] 1.5| 16.2 [4.75] 1.7| 16.1 [4.72] 1.7| 15.9 [4.66] 1.7| 14.7 [4.31] 1.9| 14.6 [4.28] 1.9| 14.5 [4.25] 2.0
30 [-1.1]| Total BTUH [kW] Power| 18.7 [5.48] 1.5| 18.6 [5.45] 1.5| 18.4 [5.39] 1.6| 17.8 [5.22] 1.7| 17.7 [5.19] 1.7| 17.6 [5.16] 1.7| 16.4 [4.81] 1.9| 16.3 [4.78] 2.0| 16.1 [4.72] 2.0
35 [1.7]| Total BTUH [kW] Power| 20.3 [5.95] 1.5| 20.2 [5.92] 1.6| 20.0 [5.86] 1.6| 19.4 [5.69] 1.7| 19.3 [5.66] 1.7| 19.2 [5.63] 1.8| 18.0 [5.28] 2.0| 17.9 [5.25] 2.0| 17.8 [5.22] 2.0
40 [4.4]| Total BTUH [kW] Power| 22.0 [6.45] 1.6| 21.8 [6.39] 1.6| 21.7 [6.36] 1.6| 21.1 [6.18] 1.7| 20.9 [6.13] 1.8| 20.8 [6.10] 1.8| 19.6 [5.74] 2.0| 19.5 [5.71] 2.0| 19.4 [5.69] 2.0
45 [7.2]| Total BTUH [kW] Power| 23.6 [6.92] 1.6| 23.4 [6.86] 1.6| 23.3 [6.83] 1.6| 22.7 [6.65] 1.8| 22.6 [6.62] 1.8| 22.4 [6.56] 1.8| 21.3 [6.24] 2.0| 21.1 [6.18] 2.0| 21.0 [6.15] 2.1
50 [10]| Total BTUH [kW] Power| 25.2 [7.39] 1.6| 25.1 [7.36] 1.6| 24.9 [7.30] 1.6| 24.4 [7.15] 1.8| 24.2 [7.09] 1.8| 24.0 [7.03] 1.8| 22.9 [6.71] 2.0| 22.8 [6.68] 2.0| 22.6 [6.62] 2.1

COOLING PERFORMANCE DATA—RQPL-025

ENTERING INDOOR AIR @ 80°F [26.7°C] dbE

wbE| 71°F [21.7°C]| 67°F [19.4°C]| 63°F [17.2°C]
CFM [L/s]| 930 [439]| 850 [401]| 760 [359]| 930 [439]| 850 [401]| 760 [359]| 930 [439]| 850 [401]| 760 [359]
DR ➀| .15| .17| .19| .15| .17| .19| .15| .17| .19
OUT DOOR DRY
BULB TEMPERATURE
°F [°C]| 75 [23.9]| Total BTUH [kW] Sens BTUH [kW] Power| 30.4 [8.9] 18.8 [5.5] 1.5| 29.9 [8.8] 17.5 [5.1] 1.4| 29.3 [8.6] 16.1 [4.7] 1.4| 28.5 [8.4] 22.1 [6.5] 1.5| 28.0 [8.2] 20.7 [6.1] 1.5| 27.5 [8.1] 19.2 [5.6] 1.4| 26.8 [7.9] 24.4 [7.2] 1.5| 26.4 [7.7] 23.0 [6.8] 1.5| 25.9 [7.6] 21.4 [6.3] 1.4
80 [26.7]| Total BTUH [kW] Sens BTUH [kW] Power| 29.6 [8.7] 18.2 [5.3] 1.5| 29.1 [8.5] 16.9 [5.0] 1.5| 28.5 [8.4] 15.5 [4.6] 1.5| 27.7 [8.1] 21.5 [6.3] 1.5| 27.2 [8.0] 20.1 [5.9] 1.5| 26.7 [7.8] 18.6 [5.5] 1.5| 26.0 [7.6] 23.8 [7.0] 1.6| 25.6 [7.5] 22.4 [6.6] 1.5| 25.1 [7.4] 20.8 [6.1] 1.5
85 [29.4]| Total BTUH [kW] Sens BTUH [kW] Power| 28.7 [8.4] 17.5 [5.1] 1.6| 28.2 [8.3] 16.3 [4.8] 1.6| 27.6 [8.1] 14.9 [4.4] 1.6| 26.8 [7.9] 20.9 [6.1] 1.6| 26.3 [7.7] 19.5 [5.7] 1.6| 25.8 [7.6] 18.1 [5.3] 1.6| 25.1 [7.4] 23.2 [6.8] 1.6| 24.7 [7.2] 21.8 [6.4] 1.6| 24.2 [7.1] 20.2 [5.9] 1.6
90 [32.2]| Total BTUH [kW] Sens BTUH [kW] Power| 27.7 [8.1] 16.9 [5.0] 1.7| 27.2 [8.0] 15.7 [4.6] 1.7| 26.7 [7.8] 14.4 [4.2] 1.7| 25.8 [7.6] 20.3 [6.0] 1.7| 25.4 [7.4] 19.0 [5.6] 1.7| 24.9 [7.3] 17.6 [5.2] 1.7| 24.1 [7.1] 22.4 [6.6] 1.7| 23.7 [6.9] 21.1 [6.2] 1.7| 23.3 [6.8] 19.7 [5.8] 1.7
95 [35]| Total BTUH [kW] Sens BTUH [kW] Power| 26.7 [7.8] 16.3 [4.8] 1.8| 26.2 [7.7] 15.1 [4.4] 1.8| 25.7 [7.5] 13.9 [4.1] 1.8| 24.8 [7.3] 19.6 [5.8] 1.8| 24.4 [7.2] 18.4 [5.4] 1.8| 23.9 [7.0] 17.0 [5.0] 1.8| 23.1 [6.8] 21.9 [6.4] 1.8| 22.7 [6.7] 20.6 [6.0] 1.8| 22.3 [6.5] 19.2 [5.6] 1.8
100 [37.8]| Total BTUH [kW] Sens BTUH [kW] Power| 25.6 [7.5] 15.8 [4.6] 1.9| 25.2 [7.4] 14.7 [4.3] 1.9| 24.7 [7.2] 13.5 [4.0] 1.9| 23.7 [6.9] 19.0 [5.6] 1.9| 23.3 [6.8] 17.8 [5.2] 1.9| 22.9 [6.7] 16.5 [4.8] 1.9| 22.0 [6.4] 21.3 [6.3] 1.9| 21.7 [6.4] 20.1 [5.9] 1.9| 21.3 [6.2] 18.7 [5.5] 1.9
105 [40.6]| Total BTUH [kW] Sens BTUH [kW] Power| 24.5 [7.2] 15.2 [4.5]2.0| 24.1 [7.1] 14.2 [4.2] 2.0| 23.6 [6.9] 13.0 [3.8] 2.0| 22.6 [6.6] 18.5 [5.4] 2.0| 22.2 [6.5] 17.3 [5.1] 2.0| 21.8 [6.4] 16.1 [4.7] 2.0| 20.9 [6.1] 20.8 [6.1] 2.0| 20.6 [6.0] 19.6 [5.8] 2.0| 20.2 [5.9] 18.3 [5.4] 2.0
110 [43.3]| Total BTUH [kW] Sens BTUH [kW] Power| 23.3 [6.8] 14.7 [4.3] 2.2| 22.9 [6.7] 13.7 [4.0] 2.1| 22.5 [6.6] 12.6 [3.7] 2.1| 21.4 [6.3] 18.0 [5.3] 2.2| 21.0 [6.2] 16.8 [4.9] 2.1| 20.6 [6.0] 15.6 [4.6] 2.1| 19.7 [5.8] 19.7 [5.8] 2.2| 19.4 [5.7] 19.1 [5.6] 2.1| 19.0 [5.6] 17.8 [5.2] 2.1
115 [46.1]| Total BTUH [kW] Sens BTUH [kW] Power| 22.1 [6.5] 14.2 [4.2] 2.3| 21.7 [6.4] 13.2 [3.9] 2.3| 21.3 [6.2] 12.2 [3.6] 2.2| 20.2 [5.9] 17.5 [5.1] 2.3| 19.8 [5.8] 16.4 [4.8] 2.3| 19.4 [5.7] 15.2 [4.5] 2.2| 18.5 [5.4] 18.5 [5.4] 2.3| 18.2 [5.3] 18.2 [5.3] 2.3| 17.8 [5.2] 17.4 [5.1] 2.2

DR —Depression ratio
dbE —Entering air dry bulb
wbE —Entering air wet bulb
Total —Total capacity x 1000 BTUH
Sens —Sensible capacity x 1000 BTUH
Power —KW input

NOTES:
When the entering air dry bulb is other than 80°F [27°C], adjust the sensible capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].

HEATING PERFORMANCE DATA—RQPL-025

IDB 60°F [15.5°C] 70°F [21.1°C] 80°F [26.7°C]
CFM [L/s] 930 [439] 850 [401] 760 [359]
[439]** 850 [401] 760 [359] 930 [439]

760 [359]
OUT DOOR
DRY BULB
TEMPERATURE
°F] [°C]| 0 [-17.8]| Total BTUH [kW] Power| 7.3 [2.1] 1.2| 7.2 [2.1] 1.3| 7.2 [2.1] 1.3| 5.9 [1.7] 1.4| 5.9 [1.7] 1.4| 5.9 [1.7] 1.4| 4.6 [1.3] 1.6| 4.5 [1.3] 1.6| 4.5 [1.3] 1.6
5 [-15]| Total BTUH [kW] Power| 9.1 [2.7] 1.3| 9.1 [2.7] 1.3| 9.0 [2.6] 1.3| 7.8 [2.3] 1.4| 7.7 [2.3] 1.5| 7.7 [2.3] 1.5| 6.4 [1.9] 1.6| 6.4 [1.9] 1.6| 6.3 [1.8] 1.7
10 [-12.2]| Total BTUH [kW] Power| 11.0 [3.2] 1.3| 10.9 [3.2] 1.3| 10.8 [3.2] 1.3| 9.6 [2.8]  1.5| 9.5 [2.8] 1.5| 9.5 [2.8] 1.5| 8.2 [2.4] 1.7| 8.2 [2.4] 1.7| 8.1 [2.4] 1.7
15 [-9.4]| Total BTUH [kW] Power| 12.8 [3.8] 1.3| 12.7 [3.7] 1.3| 12.6 [3.7] 1.4| 11.4 [3.3] 1.5| 11.4 [3.3] 1.5| 11.3 [3.3] 1.5| 10.1 [3.0] 1.7| 10.0 [2.9] 1.7| 9.9 [2.9] 1.7
20 [-6.7]| Total BTUH [kW] Power| 14.6 [4.3] 1.4| 14.5 [4.2] 1.4| 14.4 [4.2] 1.4| 13.3 [3.9] 1.5| 13.2 [3.9] 1.6| 13.1 [3.8]  1.6| 11.9 [3.5] 1.7| 11.8 [3.5] 1.7| 11.8 [3.5] 1.8
25 [-3.9]| Total BTUH [kW] Power| 16.5 [4.8] 1.4| 16.4 [4.8] 1.4| 16.2 [4.7] 1.4| 15.1 [4.4] 1.6| 15.0 [4.4] 1.6| 14.9 [4.4]1.6| 13.8 [4.0] 1.7| 13.7 [4.0] 1.8| 13.6 [4.0] 1.8
30 [-1.1]| Total BTUH [kW] Power| 18.3 [5.4] 1.4| 18.2 [5.3] 1.4| 18.0 [5.3] 1.4| 17.0 [5.0] 1.6| 16.8 [4.9] 1.6| 16.7 [4.9] 1.6| 15.6 [4.6] 1.8| 15.5 [4.5] 1.8| 15.4 [4.5] 1.8
35 [1.7]| Total BTUH [kW] Power| 20.1 [5.9] 1.4| 20.0 [5.9] 1.5| 19.9 [5.8] 1.5| 18.8 [5.5] 1.6| 18.7 [5.5] 1.6| 18.5 [5.4] 1.7| 17.4 [5.1] 1.8| 17.3 [5.1] 1.8| 17.2 [5.0] 1.8
40 [4.4]| Total BTUH [kW] Power| 22.0 [6.4] 1.5| 21.8 [6.4] 1.5| 21.7 [6.4] 1.5| 20.6 [6.0]1.6| 20.5 [6.0] 1.7| 20.3 [5.9] 1.7| 19.3 [5.7] 1.8| 19.1 [5.6] 1.9| 19.0 [5.6] 1.9
45 [7.2]| Total BTUH [kW] Power| 23.8 [7.0] 1.5| 23.7 [6.9] 1.5| 23.5 [6.9] 1.5| 22.5 [6.6]  1.7| 22.3 [6.5] 1.7| 22.1 [6.5] 1.7| 21.1 [6.2] 1.9| 21.0 [6.2] 1.9| 20.8 [6.1] 1.9
50 [10]| Total BTUH [kW] Power| 25.7 [7.5] 1.5| 25.5 [7.5] 1.6| 25.3 [7.4] 1.6| 24.3 [7.1] 1.7| 24.1 [7.1] 1.7| 23.9 [7.0] 1.8| 22.9 [6.7] 1.9| 22.8 [6.7] 1.9| 22.6 [6.6] 1.9

COOLING PERFORMANCE DATA—RQPL-030

ENTERING INDOOR AIR @ 80°F [26.7°C] dbE

wbE| 71°F [21.7°C]| 67°F [19.4°C]| 63°F [17.2°C]
CFM [L/s]| 1160 [547]| 1050 [496]| 940 [444]| 1160 [547]| 1050 [496]| 940 [444]| 1160 [547]| 1050 [496]| 940 [444]
DR ➀| .15| .13| .11| .15| .13| .11| .15| .13| .11
OUT DOOR DRY
BULB
TEMPERATURE
°F [°C]| 75 [23.9]| Total BTUH [kW] Sens BTUH [kW] Power| 36.9 [10.81] 23.7 [6.95]  1.9| 36.2 [10.61] 22.6 [6.62] 1.9| 35.5 [10.40] 21.5 [6.30] 1.9| 34.9 [10.23] 26.9 [7.88] 1.9| 34.2 [10.02] 25.7 [7.53] 1.9| 33.6 [9.85] 24.5 [7.18] 1.9| 33.5 [9.82] 28.4 [8.32] 1.9| 32.9 [9.64] 27.1 [7.94] 1.9| 32.3 [9.47] 25.8 [7.56] 1.9
80 [26.7]| Total BTUH [kW] Sens BTUH [kW] Power| 35.7 [10.46] 23.1 [6.77] 2.0| 35.1 [10.29] 22.0 [6.45] 2.0| 34.4 [10.08] 21.0 [6.15] 2.0| 33.7   [9.88] 26.3   [7.71] 2.0| 33.1 [9.70] 25.2 [7.39] 2.0| 32.5 [9.52] 24.0 [7.03] 2.0| 32.3 [9.47] 27.8 [8.15] 2.0| 31.8 [9.32] 26.5 [7.77] 2.0| 31.2 [9.14] 25.3 [7.41] 2.0
85 [29.4]| Total BTUH [kW] Sens BTUH [kW] Power| 34.6 [10.14] 22.5 [6.59] 2.1| 33.9 [9.94] 21.5 [6.30] 2.1| 33.3 [9.76] 20.5 [6.01] 2.1| 32.6 [9.55] 25.8 [7.56] 2.1| 32.0 [9.38] 24.6 [7.21] 2.1| 31.4 [9.20] 23.5 [6.89] 2.1| 31.2 [9.14] 27.2 [7.97] 2.1| 30.6 [8.97] 26.0 [7.62] 2.1| 30.1 [8.82] 24.8 [7.27] 2.1
90 [32.2]| Total BTUH [kW] Sens BTUH [kW] Power| 33.4 [9.79] 21.9 [6.42] 2.2| 32.8 [9.61] 20.9 [6.13] 2.2| 32.2 [9.44] 20.0 [5.86] 2.2| 31.4 [9.20] 25.2 [7.39] 2.2| 30.9 [9.06] 24.1 [7.06] 2.2| 30.3 [8.88] 23.0 [6.74] 2.2| 30.1 [8.82] 26.6 [7.80] 2.2| 29.5 [8.65] 25.4 [7.44] 2.2| 29.0 [8.50] 24.3 [7.12] 2.2
95 [35]| Total BTUH [kW] Sens BTUH [kW] Power| 32.3 [9.47] 21.4 [6.27] 2.3| 31.7 [9.29] 20.4 [5.98] 2.3| 31.1 [9.11] 19.5 [5.71] 2.3| 30.3 [8.88] 24.7 [7.24] 2.3| 29.8 [8.73] 23.6 [6.92] 2.3| 29.2 [8.56] 22.5 [6.59] 2.2| 28.9 [8.47] 26.1 [7.65] 2.3| 28.4 [8.32] 24.9 [7.30] 2.3| 27.9 [8.18] 23.8 [6.98] 2.3
100 [37.8]| Total BTUH [kW] Sens BTUH [kW] Power| 31.1 [9.11] 20.8 [6.10] 2.4| 30.6 [8.97] 19.9 [5.83] 2.4| 30.0 [8.79] 19.0 [5.57] 2.4| 29.1 [8.53] 24.1 [7.06] 2.4| 28.6 [8.38] 23.0 [6.74] 2.4| 28.1 [8.24] 22.0 [6.45] 2.3| 27.8 [8.15] 25.5 [7.47] 2.4| 27.3 [8.00] 24.4 [7.15] 2.4| 26.8 [7.85] 23.3 [6.83] 2.4
105 [40.6]| Total BTUH [kW] Sens BTUH [kW] Power| 30.0 [8.79] 20.3 [5.95] 2.5| 29.4 [8.62] 19.4 [5.69] 2.5| 28.9 [8.47] 18.5 [5.42] 2.5| 28.0 [8.21] 23.6 [6.92] 2.5| 27.5 [8.06] 22.5 [6.59] 2.5| 27.0 [7.91] 21.5 [6.30] 2.4| 26.6 [7.80] 25.0 [7.33] 2.5| 26.1 [7.65] 23.9 [7.00] 2.5| 25.6 [7.50] 22.8 [6.68] 2.5
110 [43.3]| Total BTUH [kW] Sens BTUH [kW] Power| 28.7 [8.41] 19.7 [5.77] 2.6| 28.2 [8.26] 18.8 [5.51] 2.6| 27.7 [8.12] 18.0 [5.28] 2.6| 26.7 [7.83] 23.0 [6.74] 2.6| 26.2 [7.68] 22.0 [6.45] 2.6| 25.8 [7.56] 21.0 [6.15] 2.5| 25.4 [7.44] 24.4 [7.15] 2.6| 24.9 [7.30] 23.4 [6.86] 2.6| 24.5 [7.18] 22.3 [6.54]   2.6
115 [46.1]| Total BTUH [kW] Sens BTUH [kW] Power| 27.4 [8.03] 19.2 [5.63] 2.7| 26.9 [7.88] 18.3 [5.36] 2.7| 26.4 [7.74] 17.5 [5.13] 2.7| 25.4 [7.44] 22.5 [6.59] 2.7| 25.0 [7.33] 21.5 [6.30] 2.6| 24.5 [7.18] 20.5 [6.01] 2.6| 24.1 [7.06] 23.9 [7.00] 2.7| 23.6 [6.92] 22.8 [6.68] 2.7| 23.2 [6.80] 21.8 [6.39] 2.7

DR —Depression ratio
dbE —Entering air dry bulb
wbE —Entering air wet bulb
Total —Total capacity x 1000 BTUH
Sens —Sensible capacity x 1000 BTUH
Power —KW input
NOTES:
When the entering air dry bulb is other than 80°F [27°C], adjust the sensible capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].

HEATING PERFORMANCE DATA—RQPL-030

IDB 60°F [15.5°C] 70°F [21.1°C] 80°F [26.7°C]
CFM [L/s] 1160 [547] 1050 [496] 940 [444]
[547]** 1050 [496] 940 [444] 1160 [547]

940 [444]
OUT DOOR
DRY BULB
TEMPERATURE
°F [°C]| 0 [-17.8]| Total BTUH [kW] Power| 9.5 [2.78] 1.6| 9.5 [2.78] 1.6| 9.4 [2.75] 1.6| 8.0 [2.34] 1.8| 7.9 [2.32] 1.8| 7.9 [2.32] 1.8| 6.6 [1.93] 2.0| 6.5 [1.90] 2.0| 6.5 [1.90] 2.1
5 [-15]| Total BTUH [kW] Power| 11.5 [3.37] 1.6| 11.4 [3.34] 1.6| 11.3 [3.31] 1.6| 19.9 [2.90] 1.8| 19.8 [2.87] 1.8| 19.8 [2.87] 1.9| 18.5 [2.49] 2.0| 18.4 [2.46] 2.1| 18.4 [2.46] 2.1
10 [-12.2]| Total BTUH [kW] Power| 13.4 [3.93] 1.6| 13.3 [3.90] 1.7| 13.2 [3.87] 1.7| 11.8 [3.46] 1.9| 11.8 [3.46] 1.9| 11.7 [3.43] 1.9| 10.4 [3.05] 2.1| 10.3 [3.02] 2.1| 10.3 [3.02] 2.1
15 [-9.4]| Total BTUH [kW] Power| 15.3 [4.48] 1.7| 15.2 [4.45] 1.7| 15.1 [4.43] 1.7| 13.8 [4.04] 1.9| 13.7 [4.02] 1.9| 13.6 [3.99] 1.9| 12.3 [3.60] 2.1| 12.3 [3.60] 2.1| 12.2 [3.58] 2.2
20 [-6.7]| Total BTUH [kW] Power| 17.2 [5.04] 1.7| 17.1 [5.01] 1.7| 17.0 [4.98] 1.7| 15.7 [4.60] 1.9| 15.6 [4.57] 1.9| 15.5 [4.54] 2.0| 14.3 [4.19] 2.1| 14.2 [4.16] 2.2| 14.1 [4.13] 2.2
25 [-3.9]| Total BTUH [kW] Power| 19.2 [5.63] 1.7| 19.0 [5.57] 1.8| 18.9 [5.54] 1.8| 17.6 [5.16] 1.9| 17.5 [5.13] 2.0| 17.4 [5.10] 2.0| 16.2 [4.75] 2.2| 16.1 [4.72] 2.2| 16.0 [4.69] 2.2
30 [-1.1]| Total BTUH [kW] Power| 21.1 [6.18] 1.8| 20.9 [6.13] 1.8| 20.8 [6.10] 1.8| 19.5 [5.71] 2.0| 19.4 [5.69] 2.0| 19.3 [5.66] 2.0| 18.1 [5.30] 2.2| 18.0 [5.28] 2.2| 17.9 [5.25] 2.3
35 [1.7]| Total BTUH [kW] Power| 23.0 [6.74] 1.8| 22.8 [6.68] 1.8| 22.7 [6.65] 1.8| 21.5 [6.30] 2.0| 21.3 [6.24] 2.0| 21.2 [6.21] 2.1| 20.0 [5.86] 2.2| 19.9 [5.83] 2.3| 19.7 [5.77] 2.3
40 [4.4]| Total BTUH [kW] Power| 24.9 [7.30] 1.8| 24.8 [7.27] 1.8| 24.6 [7.21] 1.9| 23.4 [6.86] 2.0| 23.2 [6.80] 2.1| 23.0 [6.74] 2.1| 22.0 [6.45] 2.3| 21.8 [6.39] 2.3| 21.6 [6.33] 2.3
45 [7.2]| Total BTUH [kW] Power| 26.9 [7.88] 1.9| 26.7 [7.83] 1.9| 26.5 [7.77] 1.9| 25.3 [7.41] 2.1| 25.1 [7.36] 2.1| 24.9 [7.30] 2.1| 23.9 [7.00] 2.3| 23.7 [6.95] 2.3| 23.5 [6.89] 2.4
50 [10]| Total BTUH [kW] Power| 28.8 [8.44] 1.9| 28.6 [8.38] 1.9| 28.4 [8.32] 1.9| 27.2 [7.97] 2.1| 27.0 [7.91] 2.1| 26.8 [7.85] 2.2| 25.8 [7.56] 2.3| 25.6 [7.50] 2.4| 25.4 [7.44] 2.4

COOLING PERFORMANCE DATA—RQPL-036

ENTERING INDOOR AIR @ 80°F [26.7°C] dbE

wbE| 71°F [21.7°C]| 67°F [19.4°C]| 63°F [17.2°C]
CFM [L/s]| 1380 [651]| 1250 [590]| 1120 [528]| 1380 [651]| 1250 [590]| 1120 [528]| 1380 [651]| 1250 [590]| 1120 [528]
DR ➀| .21| .19| .17| .21| .19| .17| .21| .19| .17
OUT DOOR
DRY BULB
TEMPERATURE
°F [°C]| 75 [23.9]| Total BTUH [kW] Sens BTUH [kW] Power| 45.0 [13.19] 27.7 [8.12] 2.3| 44.2 [12.95] 26.5 [7.77] 2.2| 43.4 [12.72] 25.3 [7.41] 2.2| 42.9 [12.57] 31.8 [9.32] 2.2| 42.2 [12.37] 30.4 [8.91] 2.2| 41.4 [12.13] 28.9 [8.47] 2.2| 41.8 [12.25] 34.2 [10.02] 2.2| 41.0 [12.02] 32.6 [9.55] 2.2| 40.3 [11.81] 31.1 [9.11] 2.2
80 [26.7]| Total BTUH [kW] Sens BTUH [kW] Power| 43.9 [12.87] 27.1 [7.94] 2.4| 43.1 [12.63] 25.9 [7.59] 2.4| 42.3 [12.40] 24.7 [7.24] 2.4| 41.8 [12.25] 31.2   [9.14] 2.4| 41.1 [12.05] 29.8 [8.73] 2.4| 40.3 [11.81] 28.4 [8.32] 2.3| 0.7 [11.93] 33.5 [9.82] 2.4| 39.9 [11.69] 32.0 [9.38] 2.3| 39.2 [11.49] 30.5 [8.94] 2.3
85 [29.4]| Total BTUH [kW] Sens BTUH [kW] Power| 42.6 [12.48] 26.5 [7.77] 2.5| 41.8 [12.25] 25.3 [7.41] 2.5| 41.0 [12.02] 24.1 [7.06] 2.5| 40.5 [11.87] 30.5 [8.94] 2.5| 39.8 [11.66] 29.1 [8.53] 2.5| 39.1 [11.46] 27.8 [8.15] 2.5| 39.4 [11.55] 32.9 [9.64] 2.5| 38.7 [11.34] 31.4 [9.20] 2.5| 37.9 [11.11] 29.9 [8.76] 2.5
90 [32.2]| Total BTUH [kW] Sens BTUH [kW] Power| 41.1 [12.05] 25.7 [7.53] 2.7| 40.3 [11.81] 24.6 [7.21] 2.7| 39.6 [11.61] 23.5 [6.89] 2.6| 39.0 [11.43] 29.8 [8.73] 2.7| 38.3 [11.22] 28.5 [8.35] 2.6| 37.6 [11.02] 27.1 [7.94] 2.6| 37.9 [11.11] 32.2 [9.44] 2.6| 37.2 [10.90] 30.7 [9.00] 2.6| 36.5 [10.70] 29.3 [8.59] 2.6
95 [35]| Total BTUH [kW] Sens BTUH [kW] Power| 39.5 [11.58] 25.0 [7.33] 2.8| 38.8 [11.37] 23.9 [7.00] 2.8| 38.1 [11.17] 22.8 [6.68] 2.8| 37.4 [10.96] 29.1 [8.53] 2.8| 36.8 [10.79] 27.8 [8.15] 2.8| 36.1 [10.58] 26.5 [7.77] 2.8| 6.3 [10.64] 31.4 [9.20] 2.8| 35.6 [10.43] 30.0 [8.79] 2.8| 35.0 [10.26] 28.6 [8.38] 2.7
100 [37.8]| Total BTUH [kW] Sens BTUH [kW] Power| 37.8 [11.08] 24.2 [7.09] 3.0| 37.1 [10.87] 23.2 [6.80] 2.9| 36.5 [10.70] 22.1 [6.48] 2.9| 35.8 [10.49] 28.3 [8.29] 2.9| 35.1 [10.29] 27.0 [7.91] 2.9| 34.5 [10.11] 25.8 [7.56] 2.9| 34.6 [10.14] 30.7 [9.00] 2.9| 34.0 [9.96] 29.3 [8.59] 2.9| 33.4 [9.79] 27.9 [8.18] 2.9
105 [40.6]| Total BTUH [kW] Sens BTUH [kW] Power| 36.1 [10.58] 23.4 [6.86] 3.1| 35.5 [10.40] 22.4 [6.56] 3.1| 34.8 [10.20] 21.3 [6.24] 3.1| 34.1 [9.99] 27.5 [8.06] 3.1| 33.5 [9.82] 26.3 [7.71] 3.1| 32.8 [9.61] 25.0 [7.33] 3.0| 32.9 [9.64] 29.9 [8.76] 3.1| 32.3 [9.47] 28.5 [8.35] 3.0| 31.7 [9.29] 27.2 [7.97] 3.0
110 [43.3]| Total BTUH [kW] Sens BTUH [kW] Power| 34.4 [10.08] 22.6 [6.62] 3.3| 33.8 [9.91] 21.6 [6.33] 3.2| 33.2 [9.73] 20.6 [6.04] 3.2| 32.4 [9.50] 26.7 [7.83] 3.2| 31.8 [9.32] 25.5 [7.47] 3.2| 31.2 [9.14] 24.3 [7.12] 3.2| 31.2 [9.14] 29.0 [8.50] 3.2| 30.7 [9.00] 27.7 [8.12] 3.2| 30.1 [8.82] 26.4 [7.74] 3.2
115 [46.1]| Total BTUH [kW] Sens BTUH [kW] Power| 32.8 [9.61] 21.8 [6.39] 3.4| 32.2 [9.44] 20.8 [6.10] 3.4| 31.7 [9.29] 19.8 [5.80] 3.3| 30.8 [9.03] 25.8 [7.56] 3.4| 30.2 [8.85] 24.7 [7.24] 3.3| 29.7 [8.70] 23.5 [6.89] 3.3| 29.6 [8.67] 28.2 [8.26] 3.4| 29.1 [8.53] 26.9 [7.88] 3.3| 28.6 [8.38] 25.7 [7.53] 3.3

DR —Depression ratio
dbE —Entering air dry bulb
wbE —Entering air wet bulb
Total —Total capacity x 1000 BTUH
Sens —Sensible capacity x 1000 BTUH
Power —KW input

NOTES:
When the entering air dry bulb is other than 80°F [27°C], adjust the sensible capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].

HEATING PERFORMANCE DATA—RQPL-036

IDB 60°F [15.5°C] 70°F [21.1°C] 80°F [26.7°C]
CFM [L/s] 1380 [651] 1250 [590] 1120 [528]
[651]** 1250 [590] 1120 [528] 1380 [651]

1120 [528]
OUT DOOR
DRY BULB
TEMPERATURE
°F [°C]| 0 [-17.8]| Total BTUH [kW] Power| 11.7 [3.43] 1.8| 11.6 [3.40] 1.9| 11.5 [3.37] 1.9| 9.6 [2.81] 2.1| 9.6 [2.81] 2.1| 9.5 [2.78] 2.1| 8.3 [2.43] 2.4| 8.2 [2.40] 2.4| 8.1 [2.37] 2.4
5 [-15]| Total BTUH [kW] Power| 14.1 [4.13] 1.9| 14.0 [4.10] 1.9| 13.9 [4.07] 1.9| 12.1 [3.55] 2.1| 12.0 [3.52] 2.2| 11.9 [3.49] 2.2| 10.7 [3.14] 2.4| 10.6 [3.11] 2.5| 10.6 [3.11] 2.5
10 [-12.2]| Total BTUH [kW] Power| 16.6 [4.86] 1.9| 16.5 [4.84] 1.9| 16.3 [4.78] 2.0| 14.5 [4.25] 2.2| 14.4 [4.22]  2.2| 14.3 [4.19] 2.2| 13.2 [3.87]  2.5| 13.1 [3.84] 2.5| 13.0 [3.81]  2.5
15 [-9.4]| Total BTUH [kW] Power| 19.0 [5.57] 2.0| 18.9 [5.54] 2.0| 18.8 [5.51] 2.0| 17.0 [4.98] 2.2| 16.9 [4.95]  2.2| 16.7 [4.89] 2.3| 15.6 [4.57] 2.5| 15.5 [4.54] 2.5| 15.4 [4.51]  2.6
20 [-6.7]| Total BTUH [kW] Power| 21.5 [6.30] 2.0| 21.3 [6.24] 2.0| 21.2 [6.21] 2.1| 19.4 [5.69] 2.3| 19.3 [5.66]  2.3| 19.2 [5.63] 2.3| 18.1 [5.30] 2.5| 17.9 [5.25] 2.6| 17.8 [5.22] 2.6
25 [-3.9]| Total BTUH [kW] Power| 23.9 [7.00] 2.0| 23.8 [6.98] 2.1| 23.6 [6.92] 2.1| 21.9 [6.42] 2.3| 21.7 [6.36] 2.3| 21.6 [6.33] 2.4| 20.5 [6.01]  2.6| 20.4 [5.98]  2.6| 20.2 [5.92]  2.7
30 [-1.1]| Total BTUH [kW] Power| 26.4 [7.74] 2.1| 26.2 [7.68] .1| 26.0 [7.62] 2.1| 24.3 [7.12] 2.3| 24.2 [7.09]  2.4| 24.0 [7.03] 2.4| 23.0 [6.74]  2.6| 22.8 [6.68]  2.7| 22.6 [6.62]  2.7
35 [1.7]| Total BTUH [kW] Power| 28.8 [8.44] 2.1| 28.6 [8.38] 2.1| 28.4 [8.32] 2.2| 26.8 [7.85]2.4| 26.6 [7.80] 2.4| 26.4 [7.74] 2.4| 25.4 [7.44]  2.7| 25.2 [7.39]  2.7| 25.1 [7.36]  2.7
40 [4.4]| Total BTUH [kW] Power| 31.3 [9.17] 2.2| 31.1 [9.11] 2.2| 30.8 [9.03] 2.2| 29.2 [8.56]2.4| 29.0 [8.50]  2.4| 28.8 [8.44] 2.5| 27.9 [8.18]  2.7| 27.7 [8.12] 2.7| 27.5 [8.06]  2.8
45 [7.2]| Total BTUH [kW] Power| 33.7 [9.88] 2.2| 33.5 [9.82] 2.2| 33.3 [9.76] 2.3| 31.7 [9.29] 2.5| 31.5 [9.23]  2.5| 31.2 [9.14] 2.5| 30.3 [8.88]  2.8| 30.1 [8.82]  2.8| 29.9 [8.76]  2.8
50 [10]| Total BTUH [kW] Power| 36.2 [10.61] 2.2| 35.9 [10.52] 2.3| 35.7 [10.46] 2.3| 34.1 [9.99] 2.5| 33.9 [9.94]  2.5| 33.7 [9.88] 2.6| 32.8 [9.61]  2.8| 32.5 [9.52]  2.8| 32.3 [9.47]  2.9

COOLING PERFORMANCE DATA—RQPL-042

ENTERING INDOOR AIR @ 80°F [26.7°C] dbE

wbE| 71°F [21.7°C]| 67°F [19.4°C]| 63°F [17.2°C]
CFM [L/s]| 1540 [727]| 1400 [661]| 1260 [595]| 1540 [727]| 1400 [661]| 1260 [595]| 1540 [727]| 1400 [661]| 1260 [595]
DR| 0.09| 0.11| 0.13| 0.09| 0.11| 0.13| 0.09| 0.11| 0.13
OUT DOOR
DRY  BULB
TEMPEATURE
°F [°C]| 75 [23.9]| Total BTUH [kW] Sens BTUH [kW] Power| 54.1 [15.9] 32.4 [9.5] 2.8| 53.2 [15.6] 30.1 [8.8] 2.8| 52.2 [15.3] 27.7 [8.1] 2.8| 50.3 [14.7] 37.9 [11.1] 2.8| 49.4 [14.5] 35.3 [10.3] 2.8| 48.5 [14.2] 32.8 [9.6] 2.8| 46.8 [13.7] 41.6 [12.2] 2.8| 46.0 [13.5] 38.9 [11.4] 2.8| 45.1 [13.2] 36.2 [10.6] 2.7
80 [26.7]| Total BTUH [kW] Sens BTUH [kW] Power| 49.7 [14.6] 30.5 [8.9] 3.3| 48.8 [14.3] 28.2 [8.3] 3.3| 47.9 [14.0] 26.0 [7.6] 3.3| 45.9 [13.4] 35.8 [10.5] 3.3| 45.1 [13.2] 33.4 [9.8] 3.3| 44.2 [13.0] 31.0 [9.1] 3.3| 42.4 [12.4] 39.5 [11.6] 3.3| 41.6 [12.2] 36.9 [10.8] 3.3| 40.9 [12.0] 34.5 [10.1] 3.2
85 [29.4]| Total BTUH [kW] Sens BTUH [kW] Power| 44.7 [13.1] 27.7 [8.1] 3.9| 43.9 [12.9] 25.7 [7.5] 3.9| 43.1 [12.6] 23.7 [6.9] 3.9| 40.8 [12.0] 33.1 [9.7] 3.9| 40.1 [11.7] 30.9 [9.1] 3.9| 39.4 [11.5] 28.8 [8.4] 3.8| 37.4 [11.0] 36.8 [10.8] 3.9| 36.7 [10.8] 34.5 [10.1] 3.9| 36.0 [10.5] 32.2 [9.4] 3.8
90 [32.2]| Total BTUH [kW] Sens BTUH [kW] Power| 54.2 [15.9] 32.6 [9.6] 3.4| 53.2 [15.6] 31.1 [9.1] 3.4| 52.3 [15.3] 29.7 [8.7] 3.4| 50.1 [14.7] 38.7 [11.3] 3.4| 49.2 [14.4] 36.9 [10.8] 3.4| 48.3 [14.1] 35.2 [10.3] 3.3| 46.2 [13.5] 42.9 [12.6] 3.3| 45.3 [13.3] 41.0 [12.0] 3.3| 44.5 [13.0] 39.1 [11.5] 3.3
95 [35.0]| Total BTUH [kW] Sens BTUH [kW] Power| 52.5 [15.4] 31.8 [9.3] 3.6| 51.6 [15.1] 30.4 [8.9] 3.6| 50.6 [14.8] 28.9 [8.5] 3.6| 48.4 [14.2] 37.8 [11.1] 3.6| 47.5 [13.9] 36.2 [10.6] 3.6| 46.6 [13.7] 34.5 [10.1] 3.5| 44.5 [13.0] 42.1 [12.3] 3.6| 43.7 [12.8] 40.2 [11.8] 3.5| 42.9 [12.6] 38.4 [11.2] 3.5
100 [37.8]| Total BTUH [kW] Sens BTUH [kW] Power| 50.8 [14.9] 31.0 [9.1] 3.8| 49.9 [14.6] 29.6 [8.7] 3.8| 49.0 [14.4] 28.2 [8.3] 3.8| 46.7 [13.7] 37.0 [10.9] 3.8| 45.8 [13.4] 35.4 [10.4] 3.8| 45.0 [13.2] 33.7 [9.9] 3.7| 42.8 [12.5] 41.3 [12.1] 3.8| 42.0 [12.3] 39.5 [11.6] 3.8| 41.2 [12.1] 37.6 [11.0] 3.7
105 [40.6]| Total BTUH [kW] Sens BTUH [kW] Power| 49.1 [14.4] 30.2 [8.8] 4.1| 48.2 [14.1] 28.8 [8.4] 4.0| 47.3 [13.9] 27.5 [8.1] 4.0| 44.9 [13.2] 36.2 [10.6] 4.1| 44.1 [12.9] 34.6 [10.1] 4.0| 43.3 [12.7] 33.0 [9.7] 4.0| 41.0 [12.0] 40.5 [11.9] 4.0| 40.3 [11.8] 38.7 [11.3] 4.0| 39.6 [11.6] 36.9 [10.8] 4.0
110 [43.3]| Total BTUH [kW] Sens BTUH [kW] Power| 47.4 [13.9] 29.4 [8.6] 4.3| 46.5 [13.6] 28.1 [8.2] 4.3| 45.7 [13.4] 26.8 [7.8] 4.3| 43.2 [12.7] 35.4 [10.4] 4.3| 42.5 [12.4] 33.9 [9.9] 4.3| 41.7 [12.2] 32.3 [9.5] 4.2| 39.3 [11.5] 39.3 [11.5] 4.3| 38.6 [11.3] 37.9 [11.1] 4.2| 37.9 [11.1] 36.2 [10.6] 4.2
115 [46.1]| Total BTUH [kW] Sens BTUH [kW] Power| 45.6 [13.4] 28.6 [8.4] 4.6| 44.8 [13.1] 27.3 [8.0] 4.6| 44.0 [12.9] 26.0 [7.6] 4.5| 41.5 [12.2] 34.7 [10.2] 4.6| 40.8 [11.9] 33.1 [9.7] 4.5| 40.0 [11.7] 31.6 [9.2] 4.5| 37.6 [11.0] 37.6 [11.0] 4.5| 36.9 [10.8] 36.9 [10.8] 4.5| 36.2 [10.6] 35.5 [10.4] 4.5

DR —Depression ratio
dbE —Entering air dry bulb
wbE —Entering air wet bulb
Total —Total capacity x 1000 BTUH
Sens —Sensible capacity x 1000 BTUH
Power —KW input

NOTES:
When the entering air dry bulb is other than 80°F [27°C], adjust the sensible capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].

HEATING PERFORMANCE DATA—RQPL-042

IDB 60°F [15.5°C] 70°F [21.1°C] 80°F [26.7°C]
CFM [L/s] 1600 [755] 1375 [649] 1200 [566]
[755]** 1375 [649] 1200 [566] 1600 [755]

1200 [566]
OUT DOOR
DRY BULB
TEMPERATURE
°F [°C]| 0 [-17.8]| Total BTUH [kW] Power| 12.4 [3.6] 2.6| 12.2 [3.6] 2.6| 12.1 [3.5] 2.7| 11.6 [3.4] 2.8| 11.5 [3.4] 2.8| 11.4 [3.3] 2.9| 10.8 [3.2] 3.4| 10.7 [3.1] 3.4| 10.6 [3.1] 3.5
5 [-15]| Total BTUH [kW] Power| 15.3 [4.5] 2.6| 15.2 [4.5] 2.7| 15.0 [4.4] 2.7| 14.6 [4.3] 2.8| 14.4 [4.2] 2.9| 14.3 [4.2] 3.0| 13.8 [4.0] 3.4| 13.6 [4.0] 3.5| 13.5 [4.0] 3.6
10 [-12.2]| Total BTUH [kW] Power| 18.3 [5.4] 2.7| 18.1 [5.3] 2.8| 17.9 [5.2] 2.8| 17.5 [5.1] 2.9| 17.3 [5.1] 3.0| 17.2 [5.0] 3.0| 16.7 [4.9] 3.5| 16.6 [4.9] 3.6| 16.4 [4.8] 3.6
15 [-9.4]| Total BTUH [kW] Power| 21.3 [6.2] 2.8| 21.0 [6.2] 2.8| 20.8 [6.1] 2.9| 20.5 [6.0] 3.0| 20.2 [5.9] 3.0| 20.1 [5.9] 3.1| 19.7 [5.8] 3.6| 19.5 [5.7] 3.6| 19.3 [5.7] 3.7
20 [-6.7]| Total BTUH [kW] Power| 24.2 [7.1] 2.8| 23.9 [7.0] 2.9| 23.7 [6.9] 2.9| 23.4 [6.9] 3.0| 23.2 [6.8] 3.1| 23.0 [6.7] 3.2| 22.7 [6.7] 3.6| 22.4 [6.6] 3.7| 22.2 [6.5]3.8
25 [-3.9]| Total BTUH [kW] Power| 27.2 [8.0] 2.9| 26.9 [7.9] 3.0| 26.6 [7.8] 3.0| 26.4 [7.7] 3.1| 26.1 [7.6] 3.2| 25.9 [7.6] 3.2| 25.6 [7.5] 3.7| 25.3 [7.4] 3.8| 25.1 [7.4] 3.8
30 [-1.1]| Total BTUH [kW] Power| 30.1 [8.8] 3.0| 29.8 [8.7] 3.0| 29.5 [8.6] 3.1| 29.4 [8.6] 3.2| 29.0 [8.5] 3.2| 28.8 [8.4] 3.3| 28.6 [8.4] 3.8| 28.3 [8.3] 3.8| 28.0 [8.2] 3.9
35 [1.7]| Total BTUH [kW] Power| 33.1 [9.7] 3.0| 32.7 [9.6] 3.1| 32.4 [9.5] 3.1| 32.3 [9.5] 3.2| 32.0 [9.4] 3.3| 31.7 [9.3] 3.4| 31.5 [9.2] 3.8| 31.2 [9.1] 3.9| 30.9 [9.1] 4.0
40 [4.4]| Total BTUH [kW] Power| 36.1 [10.6] 3.1| 35.6 [10.4] 3.2| 35.3 [10.3] 3.2| 35.3 [10.3] 3.3| 34.9 [10.2] 3.4| 34.6 [10.1] 3.4| 34.5 [10.1] 3.9| 34.1 [10.0] 4.0| 33.8 [9.9] 4.0
45 [7.2]| Total BTUH [kW] Power| 39.0 [11.4] 3.2| 38.6 [11.3] 3.2| 38.2 [11.2] 3.3| 38.2 [11.2] 3.4| 37.8 [11.1] 3.4| 37.5 [11.0] 3.5| 37.5 [11.0] 3.9| 37.0 [10.8] 4.0| 36.7 [10.8] 4.1
50 [10]| Total BTUH [kW] Power| 42.0 [12.3] 3.2| 41.5 [12.2] 3.3| 41.1 [12.0] 3.3| 41.2 [12.1] 3.4| 40.7 [11.9] 3.5| 40.4 [11.8] 3.6| 40.4 [11.8] 4.0| 40.0 [11.7] 4.1| 39.6 [11.6] 4.2

COOLING PERFORMANCE DATA—RQPL-B049C

ENTERING INDOOR AIR @ 80°F [26.7°C] dbE

wbE| 71°F [21.7°C]| 67°F [19.4°C]| 63°F [17.2°C]| 61°F [16.1°C]| 59°F [15.0°C]
CFM [L/s]| 1760 [831]| 1600 [755]| 1440 [680]| 1760 [831]| 1600 [755]| 1440 [680]| 1760 [831]| 1600 [755]| 1440 [680]| 1760 [831]| 1600 [755]| 1440 [680]| 1760 [831]| 1600 [755]| 1440 [680]
DR| 0.14| 0.12| 0.1| 0.14| 0.12| 0.1| 0.14| 0.12| 0.1| 0.14| 0.12| 0.1| 0.14| 0.12| 0.1
OUT DOOR
DRY BULB
TEMPE R  TURE
°F [°C]| ****

75 [23.9]

| Total BTUH [kW] Sens BTUH [kW] Power| 59.3 [17.4]

35.1 [10.3]

2.9

| 58.2 [17.1] 33.5 [9.8] 2.8| 57.1[16.7] 32.0 [9.4] 2.8| 55.1 [16.1] 41.1 [12.1] 2.8| 54.1 [15.9] 39.3 [11.5] 2.8| 53.1 [15.6] 37.5 [11.0] 2.8| 51.2 [15.0] 45.4 [13.3] 2.8| 50.3 [14.7] 43.4 [12.7] 2.8| 49.4 [14.5] 41.4 [12.1] 2.7| 49.4 [14.5] 46.6 [13.7] 2.8| 48.5 [14.2] 44.6 [13.1] 2.8| 47.6 [14.0] 42.5 [12.4] 2.7| 47.8 [14.0] 47.0 [13.8] 2.8| 46.9 [13.7] 44.9 [13.2] 2.7| 46.0 [13.5] 42.8 [12.6]2.7
80 [26.7]| Total BTUH [kW] Sens BTUH [kW] Power| 57.6[16.9] 34.3 [10.0]  3.0| 56.5 [16.6] 32.7 [9.6] 3.0| 55.5 [16.3] 31.2 [9.1] 3.0| 53.4 [15.7] 40.3 [11.8] 3.0| 52.5 [15.4] 38.5 [11.3] 3.0| 51.5 [15.1] 36.7 [10.8] 2.9| 49.5 [14.5] 44.6 [13.1] 3.0| 48.6 [14.3] 42.6 [12.5] 2.9| 47.8 [14.0] 40.6 [11.9] 2.9| 47.7 [14.0]  45.8 [13.4]3.0| 46.9 [13.7] 43.8 [12.8]  2.9| 46.0 [13.5] 41.7 [12.2] 2.9| 46.1 [13.5] 46.1 [13.5] 2.9| 45.3 [13.3] 44.1 [12.9] 2.9| 44.4 [13.0] 42.1 [12.3] 2.9
85 [29.4]| Total BTUH [kW] Sens BTUH [kW] Power| 55.9 [16.4] 33.4 [9.8] 3.2| 54.9 [16.1] 31.9 [9.4] 3.2| 53.9 [15.8]  30.4 [8.9] 3.2| 51.8 [15.2] 39.5 [11.6] 3.2| 50.8 [14.9] 37.7 [11.1] 3.2| 49.9 [14.6] 36.0 [10.5] 3.1| 47.8 [14.0] 43.8 [12.8] 3.2| 47.0 [13.8] 41.8 [12.3]

3.1

| 46.1 [13.5] 39.9 [11.7]  3.1| 46.0 [13.5] 45.0 [13.2] 3.1| 45.2 [13.3] 43.0 [12.6] 3.1| 44.4 [13.0]41.0 [12.0]3.1| 44.4 [13.0] 44.4 [13.0] 3.1| 43.6 [12.8] 43.3 [12.7]

3.1

| 42.8 [12.5]

41.3 [12.1]

3.1

90 [32.2]| Total BTUH [kW] Sens BTUH [kW] Power| 54.2 [15.9] 32.6 [9.6] 3.4| 53.2[15.6] 31.1 [9.1] 3.4| 52.3 [15.3]  29.7 [8.7] 3.4| 50.1 [14.7] 38.7  11.3] 3.4| 49.2[14.4]  36.9 [10.8] 3.4| 48.3 [14.1]35.2 [10.3]3.3| 46.2 [13.5]42.9 [12.6]3.3| 45.3 [13.3]41.0 [12.0]3.3| 44.5 [13.0]39.1 [11.5]3.3| 44.4 [13.0]44.1 [12.9]3.3| 43.6 [12.8]42.2 [12.4]3.3| 42.8 [12.5]40.2 [11.8]3.3| 42.7 [12.5]42.7 [12.5]3.3| 41.9 [12.3]41.9 [12.3]3.3| 41.2 [12.1]40.6 [11.9]3.3
95 [35.0]| Total BTUH [kW] Sens BTUH [kW] Power| 52.5 [15.4] 31.8 [9.3] 3.6| 51.6 [15.1] 30.4 [8.9]3.6| 50.6 [14.8] 28.9 [8.5] 3.6| 48.4 [14.2] 37.8 [11.1] 3.6| 47.5 [13.9] 36.2 [10.6] 3.6| 46.6 [13.7]34.5 [10.1]3.5| 44.5 [13.0]42.1 [12.3]3.6| 43.7 [12.8]40.2 [11.8]3.5| 42.9 [12.6]38.4 [11.2]3.5| 42.7 [12.5]42.7 [12.5]3.5| 41.9 [12.3]41.4 [12.1]3.5| 41.1 [12.1]39.5 [11.6]3.5| 41.0 [12.0]41.0 [12.0]3.5| 40.3 [11.8]40.3 [11.8]3.5| 39.5 [11.6]39.5 [11.6]3.5
100 [37.8]| Total BTUH [kW] Sens BTUH [kW] Power| 50.8 [14.9] 31.0 [9.1] 3.8| 49.9 [14.6] 29.6 [8.7]  3.8| 49.0 [14.4] 28.2 [8.3] 3.8| 46.7 [13.7] 37.0 [10.9]  3.8| 45.8 [13.4] 35.4 [10.4] 3.8| 45.0 [13.2]33.7 [9.9]3.7| 42.8 [12.5]41.3 [12.1]3.8| 42.0[12.3]39.5 [11.6]3.8| 41.2 [12.1]37.6 [11.0]3.7| 41.0 [12.0]41.0[12.0]3.8| 40.2 [11.8]40.2 [11.8]3.7| 39.5 [11.6]38.7 [11.3]3.7| 39.3 [11.5]39.3 [11.5]3.8| 38.6 [11.3]38.6 [11.3]3.7| 37.9 [11.1]37.9 [11.1]3.7
105 [40.6]| Total BTUH [kW] Sens BTUH [kW] Power| 49.1 [14.4] 30.2 [8.8] 4.1| 48.2 [14.1]  28.8 [8.4] 4.0| 47.3 [13.9] 27.5 [8.1] 4.0| 44.9 [13.2] 36.2 [10.6]  4.1| 44.1 [12.9] 34.6 [10.1] 4.0| 43.3 [12.7]33.0 [9.7]4.0| 41.0 [12.0]40.5 [11.9]4.0| 40.3 [11.8]38.7 [11.3]4.0| 39.6 [11.6]36.9 [10.8]4.0| 39.2 [11.5]39.2 [11.5]4.0| 38.5 [11.3]38.5 [11.3]4.0| 37.8 [11.1]37.8 [11.1]3.9| 37.6 [11.0]37.6 [11.0]4.0| 36.9 [10.8]36.9 [10.8]4.0| 36.2 [10.6]36.2 [10.6]3.9
110 [43.3]| Total BTUH [kW] Sens BTUH [kW] Power| 47.4 [13.9] 29.4 [8.6] 4.3| 46.5 [13.6] 28.1 [8.2] 4.3| 45.7 [13.4] 26.8 [7.8] 4.3| 43.2 [12.7] 35.4 [10.4] 4.3| 42.5 [12.4] 33.9 [9.9]  4.3| 41.7 [12.2]32.3 [9.5]4.2| 39.3 [11.5]39.3 [11.5]4.3| 38.6 [11.3]37.9 [11.1]4.2| 37.9 [11.1]36.2 [10.6]4.2| 37.5 [11.0]37.5 [11.0]4.3| 36.9 [10.8]36.9 [10.8]4.2| 36.2 [10.6]36.2 [10.6]4.2| 35.9 [10.5]35.9 [10.5]4.2| 35.2 [10.3]35.2 [10.3]4.2| 34.6 [10.1]34.6 [10.1]4.2
115 [46.1]| Total BTUH [kW] Sens BTUH [kW] Power| 45.6 [13.4] 28.6 [8.4] 4.6| 44.8 [13.1] 27.3 [8.0] 4.6| 44.0 [12.9] 26.0 [7.6] 4.5| 41.5 [12.2] 34.7 [10.2]  4.6| 40.8 [11.9] 33.1 [9.7] 4.5| 40.0 [11.7]31.6 [9.2]4.5| 37.6 [11.0]37.6 [11.0]4.5| 36.9 [10.8]36.9 [10.8]4.5| 36.2 [10.6]35.5 [10.4]4.5| 35.8 [10.5]35.8 [10.5]4.5| 35.2 [10.3]35.2 [10.3]4.5| 34.5 [10.1]34.5 [10.1]4.4| 34.1 [10.0]34.1 [10.0]4.5| 33.5 [9.8]33.5 [9.8]4.5| 32.9 [9.6]32.9 [9.6]4.4
120 [48.9]| Total BTUH [kW] Sens BTUH [kW] Power| 43.9 [12.9] 27.8 [8.2] 4.9| 43.1 [12.6]  26.6 [7.8] 4.8| 42.3 [12.4] 25.3 [7.4] 4.8| 39.8 [11.7] 33.9 [9.9] 4.8| 39.0 [11.4] 30.9 [9.0] 4.8| 38.3 [11.2]30.9 [9.0]4.8| 35.9 [10.5]35.9 [10.5]4.8| 35.2 [10.3]35.2 [10.3]4.8| 34.6 [10.1]34.6 [10.1]4.7| 34.1 [10.0]34.1 [10.0]4.8| 33.4 [9.8]33.4 [9.8]4.8| 32.8 [9.6]32.8 [9.6]4.7| 32.4 [9.5]32.4 [9.5]4.8| 31.8 [9.3]31.8 [9.3]4.7| 31.2 [9.2]31.2 [9.2]4.7
125 [51.7]| Total BTUH [kW] Sens BTUH [kW] Power| 42.2 [12.4] 27.0 [7.9] 5.2| 41.4 [12.1]  25.8 [7.6] 5.1| 40.7 [11.9] 24.6 [7.2] 5.1| 38.0 [11.1] 33.1 [9.7] 5.1| 37.3 [10.9]31.6 [9.3]5.1| 36.7 [10.7]30.1 [8.8]5.1| 34.1 [10.0]34.1 [10.0]5.1| 33.5 [9.8]33.5 [9.8]5.1| 32.9 [9.6]32.9 [9.6]5.0| 32.3 [9.5]32.3 [9.5]5.1| 31.7 [9.3]31.7 [9.3]5.0| 31.2 [9.1]31.2 [9.1]5.0| 30.7 [9.0]30.7 [9.0]5.1| 30.1 [8.8]30.1 [8.8]5.0| 29.6 [8.7]29.6 [8.7]5.0

DR —Depression ratio
dbE —Entering air dry bulb
wbE —Entering air wet bulb
Total —Total capacity x 1000 BTUH
Sens —Sensible capacity x 1000 BTUH
Power —KW input
NOTES:
When the entering air dry bulb is other than 80°F [27°C], adjust the sensible capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].

HEATING PERFORMANCE DATA—RQPL-B049C

IDB 60°F [15.5°C] 70°F [21.1°C] 80°F [26.7°C]
CFM [L/s] 1760 [831] 1600 [755] 1440 [680]
[831]** 1600 [755] 1440 [680] 1760 [831]

1440 [680]
OUT DOOR
DRY BULB
TEMPERATURE
°F [°C]| 0 [-17.8]| Total BTUH [kW] Power| 15.9 [4.7] 2.5| 15.8 [4.6] 2.5| 15.7 [4.6] 2.5| 14.5 [4.3] 2.9| 14.4 [4.2] 2.9| 14.3 [4.2] 2.9| 13.2 [3.9] 3.2| 13.1 [3.8] 3.3| 13.0 [3.8] 3.3
5 [-15]| Total BTUH [kW] Power| 19.1 [5.6] 2.5| 19.0 [5.6] 2.6| 18.8 [5.5] 2.6| 17.8 [5.2] 2.9| 17.6 [5.2] 3.0| 17.5 [5.1] 3.0| 16.4 [4.8]  3.3| 16.3 [4.8] 3.3| 16.2 [4.7] 3.4
10 [-12.2]| Total BTUH [kW] Power| 22.3 [6.5] 2.6| 22.2 [6.5] 2.6| 22.0 [6.4] 2.7| 21.0 [6.2] 3.0| 20.8 [6.1] 3.0| 20.7 [6.1] 3.0| 19.7 [5.8] 3.4| 19.5 [5.7] 3.4| 19.4 [5.7] 3.4
15 [-9.4]| Total BTUH [kW] Power| 25.5 [7.5] 2.7| 25.4 [7.4] 2.7| 25.2 [7.4] 2.7| 24.2 [7.1] 3.0| 24.0 [7.0] 3.1| 23.9 [7.0] 3.1| 22.9 [6.7] 3.4| 22.7 [6.7] 3.5| 22.5 [6.6] 3.5
20 [-6.7]| Total BTUH [kW] Power| 28.8 [8.4] 2.7| 28.6 [8.4] 2.7| 28.4 [8.3] 2.8| 27.4 [8.0] 3.1| 27.2 [8.0] 3.1| 27.0 [7.9] 3.2| 26.1 [7.6] 3.5| 25.9 [7.6] 3.5| 25.7 [7.5] 3.6
25 [-3.9]| Total BTUH [kW] Power| 32.0 [9.4] 2.8| 31.8 [9.3] 2.8| 31.5 [9.2] 2.8| 30.6 [9.0] 3.1| 30.4 [8.9] 3.2| 30.2 [8.9] 3.2| 29.3 [8.6] 3.5| 29.1 [8.5] 3.6| 28.9 [8.5] 3.6
30 [-1.1]| Total BTUH [kW] Power| 35.2 [10.3] 2.8| 35.0 [10.2] 2.9| 34.7 [10.2] 2.9| 33.9 [9.9] 3.2| 33.6 [9.9] 3.2| 33.4 [9.8] 3.3| 32.5 [9.5] 3.6| 32.3 [9.5] 3.6| 32.1 [9.4] 3.7
35 [1.7]| Total BTUH [kW] Power| 38.4 [11.3] 2.9| 38.2 [11.2] 2.9| 37.9 [11.1] 2.9| 37.1 [10.9] 3.3| 36.8 [10.8] 3.3| 36.6 [10.7] 3.3| 35.8 [10.5] 3.6| 35.5 [10.4] 3.7| 35.2 [10.3] 3.7
40 [4.4]| Total BTUH [kW] Power| 41.6 [12.2] 2.9| 41.4 [12.1] 3.0| 41.1 [12.0] 3.0| 40.3 [11.8] 3.3| 40.0 [11.7] 3.3| 39.7 [11.6] 3.4| 39.0 [11.4] 3.7| 38.7 [11.3] 3.7| 38.4 [11.3] 3.8
45 [7.2]| Total BTUH [kW] Power| 44.9 [13.1] 3.0| 44.5 [13.1] 3.0| 44.2 [13.0] 3.1| 43.5 [12.8] 3.4| 43.2 [12.7] 3.4| 42.9 [12.6] 3.4| 42.2 [12.4] 3.7| 41.9 [12.3] 3.8| 41.6 [12.2] 3.8
50 [10]| Total BTUH [kW] Power| 48.1 [14.1] 3.0| 47.7 [14.0] 3.1| 47.4 [13.9] 3.1| 46.7 [13.7] 3.4| 46.4 [13.6] 3.5| 46.1 [13.5]3.5| 45.4 [13.3] 3.8| 45.1 [13.2] 3.9| 44.8 [13.1] 3.9

COOLING PERFORMANCE DATA—RQPL-B049J

ENTERING INDOOR AIR @ 80°F [26.7°C] dbE

wbE| 71°F [21.7°C]| 67°F [19.4°C]| 63°F [17.2°C]| 61°F [16.1°C]| 59°F [15.0°C]
CFM [L/s]| 1760 [831]| 1600 [755]| 1440 [680]| 1760 [831]| 1600 [755]| 1440 [680]| 1760 [831]| 1600 [755]| 1440 [680]| 1760 [831]| 1600 [755]| 1440 [680]| 1760 [831]| 1600 [755]| 1440 [680]
DR| 0.14| 0.12| 0.1| 0.14| 0.12| 0.1| 0.14| 0.12| 0.1| 0.14| 0.12| 0.1| 0.14| 0.12| 0.1






OUT DOOR
RY BULB
TEMPERATURE
°F [°C]

| ****

75 [23.9]

| Total BTUH [kW] Sens BTUH [kW] Power| 59.3 [17.4] 35.1 [10.3] 2.9| 58.2 [17.1] 33.5 [9.8] 2.8| 57.1 [16.7]  32.0 [9.4]  2.8| 55.1 [16.1]41.1 [12.1]2.8| 54.1 [15.9]39.3 [11.5]2.8| 53.1 [15.6]37.5 [11.0]2.8| 51.2 [15.0]45.4 [13.3]2.8| 50.3 [14.7]43.4 [12.7]2.8| 49.4 [14.5]41.4 [12.1]2.7| 49.4 [14.5]46.6 [13.7]2.8| 48.5 [14.2]44.6 [13.1]2.8| 47.6 [14.0]42.5 [12.4]2.7| 47.8 [14.0]47.0 [13.8]2.8| 46.9 [13.7]44.9 [13.2]2.7| 46.0 [13.5]42.8 [12.6]2.7
80 [26.7]| Total BTUH [kW] Sens BTUH [kW] Power| 57.6 [16.9]34.3 [10.0]3.0| 56.5 [16.6]32.7 [9.6]3.0| 55.5 [16.3]31.2 [9.1]3.0| 53.4 [15.7]40.3 [11.8]3.0| 52.5 [15.4]38.5 [11.3]3.0| 51.5 [15.1]36.7 [10.8]2.9| 49.5 [14.5]44.6 [13.1]3.0| 48.6 [14.3]42.6 [12.5]2.9| 47.8 [14.0]40.6 [11.9]2.9| 47.7 [14.0]45.8 [13.4]3.0| 46.9 [13.7]43.8 [12.8]2.9| 46.0 [13.5]41.7 [12.2]2.9| 46.1 [13.5]46.1 [13.5]2.9| 45.3 [13.3]44.1 [12.9]2.9| 44.4 [13.0]42.1 [12.3]2.9
85 [29.4]| Total BTUH [kW] Sens BTUH [kW] Power| 55.9 [16.4]33.4 [9.8]3.2| 54.9 [16.1]31.9 [9.4]3.2| 53.9 [15.8]30.4 [8.9]3.2| 51.8 [15.2]39.5 [11.6]3.2| 50.8 [14.9]37.7 [11.1]3.2| 49.9 [14.6]36.0 [10.5]3.1| 47.8 [14.0]43.8 [12.8]3.2| 47.0 [13.8]41.8 [12.3]3.1| 46.1 [13.5]39.9 [11.7]3.1| 46.0 [13.5]45.0 [13.2]3.1| 45.2 [13.3]43.0 [12.6]3.1| 44.4 [13.0]41.0 [12.0]3.1| 44.4 [13.0]44.4 [13.0]3.1| 43.6 [12.8]43.3 [12.7]3.1| 42.8 [12.5]41.3 [12.1]3.1
90 [32.2]| Total BTUH [kW] Sens BTUH [kW] Power| 54.2 [15.9]32.6 [9.6]3.4| 53.2 [15.6]31.1 [9.1]3.4| 52.3 [15.3]29.7 [8.7]3.4| 50.1 [14.7]38.7 [11.3]3.4| 49.2 [14.4]36.9 [10.8]3.4| 48.3 [14.1]35.2 [10.3]3.3| 46.2 [13.5]42.9 [12.6]3.3| 45.3 [13.3]41.0 [12.0]3.3| 44.5 [13.0]39.1 [11.5]3.3| 44.4 [13.0]44.1 [12.9]3.3| 43.6 [12.8]42.2 [12.4]3.3| 42.8 [12.5]40.2 [11.8]3.3| 42.7 [12.5]42.7 [12.5]3.3| 41.9 [12.3]41.9 [12.3]3.3| 41.2 [12.1]40.6 [11.9]3.3
95 [35.0]| Total BTUH [kW] Sens BTUH [kW] Power| 52.5 [15.4]31.8 [9.3]3.6| 51.6 [15.1]30.4 [8.9]3.6| 50.6 [14.8]28.9 [8.5]3.6| 48.4 [14.2]37.8 [11.1]3.6| 47.5 [13.9]36.2 [10.6]3.6| 46.6 [13.7]34.5 [10.1]3.5| 44.5 [13.0]42.1 [12.3]3.6| 43.7 [12.8]40.2 [11.8]3.5| 42.9 [12.6]38.4 [11.2]3.5| 42.7 [12.5]42.7 [12.5]3.5| 41.9 [12.3]41.4 [12.1]3.5| 41.1 [12.1]39.5 [11.6]3.5| 41.0 [12.0]41.0 [12.0]3.5| 40.3 [11.8]40.3 [11.8]3.5| 39.5 [11.6]39.5 [11.6]3.5
100 [37.8]| Total BTUH [kW] Sens BTUH [kW] Power| 50.8 [14.9]31.0 [9.1]3.8| 49.9 [14.6]29.6 [8.7]3.8| 49.0 [14.4]28.2 [8.3]3.8| 46.7 [13.7]37.0 [10.9]3.8| 45.8 [13.4]35.4 [10.4]3.8| 45.0 [13.2]33.7 [9.9]3.7| 42.8 [12.5]41.3 [12.1]3.8| 42.0 [12.3]39.5 [11.6]3.8| 41.2 [12.1]37.6 [11.0]3.7| 41.0 [12.0]41.0 [12.0]3.8| 40.2 [11.8]40.2 [11.8]3.7| 39.5 [11.6]38.7 [11.3]3.7| 39.3 [11.5]39.3 [11.5]3.8| 38.6 [11.3]38.6 [11.3]3.7| 37.9 [11.1]37.9 [11.1]3.7
105

[40.6]

| Total BTUH [kW] Sens BTUH [kW] Power| 49.1 [14.4]30.2 [8.8]4.1| 48.2 [14.1]28.8 [8.4]4.0| 47.3 [13.9]27.5 [8.1]4.0| 44.9 [13.2]36.2 [10.6]4.1| 44.1 [12.9]34.6 [10.1]4.0| 43.3 [12.7]33.0 [9.7]4.0| 41.0 [12.0]40.5 [11.9]4.0| 40.3 [11.8]38.7 [11.3]4.0| 39.6 [11.6]36.9 [10.8]4.0| 39.2 [11.5]39.2 [11.5]4.0| 38.5 [11.3]38.5 [11.3]4.0| 37.8 [11.1]37.8 [11.1]3.9| 37.6 [11.0]37.6 [11.0]4.0| 36.9 [10.8]36.9 [10.8]4.0| 36.2 [10.6]36.2 [10.6]3.9
110

[43.3]

| Total BTUH [kW] Sens BTUH [kW] Power| 47.4 [13.9]29.4 [8.6]4.3| 46.5 [13.6]28.1 [8.2]4.3| 45.7 [13.4]26.8 [7.8]4.3| 43.2 [12.7]35.4 [10.4]4.3| 42.5 [12.4]33.9 [9.9]4.3| 41.7 [12.2]32.3[9.5]4.2| 39.3 [11.5]39.3 [11.5]4.3| 38.6[11.3]37.9 [11.1] 4.2| 37.9 [11.1]36.2[10.6] 4.2| 37.5 [11.0]37.5 [11.0]4.3| 36.9 [10.8]36.9[10.8] 4.2| 36.2 [10.6]36.2[10.6] 4.2| 35.9 [10.5]35.9 [10.5]4.2| 35.2 [10.3]35.2 [10.3]4.2| 34.6 [10.1]34.6 [10.1]4.2
115

[46.1]

| Total BTUH [kW] Sens BTUH [kW] Power| 45.6 [13.4]28.6 [8.4]4.6| 44.8 [13.1]27.3 [8.0]4.6| 44.0 [12.9]26.0 [7.6]4.5| 41.5 [12.2]34.7 [10.2]4.6| 40.8 [11.9]33.1 [9.7]4.5| 40.0 [11.7]31.6 [9.2]4.5| 37.6 [11.0]37.6 [11.0]4.5| 36.9 [10.8]36.9 [10.8]4.5| 36.2 [10.6]35.5 [10.4]4.5| 35.8 [10.5]35.8 [10.5]4.5| 35.2 [10.3]35.2 [10.3]4.5| 34.5 [10.1]34.5 [10.1]4.4| 34.1 [10.0]34.1 [10.0]4.5| 33.5 [9.8]33.5 [9.8]4.5| 32.9 [9.6]32.9 [9.6]4.4
120

[48.9]

| Total BTUH [kW] Sens BTUH [kW] Power| 43.9 [12.9]27.8 [8.2]4.9| 43.1 [12.6]26.6 [7.8]4.8| 42.3 [12.4]25.3 [7.4]4.8| 39.8 [11.7]33.9 [9.9]4.8| 39.0 [11.4]30.9 [9.0]4.8| 38.3 [11.2]30.9 [9.0]4.8| 35.9 [10.5]35.9 [10.5]4.8| 35.2 [10.3]35.2 [10.3]4.8| 34.6 [10.1]34.6 [10.1]4.7| 34.1 [10.0]34.1 [10.0]4.8| 33.4 [9.8]33.4 [9.8]4.8| 32.8 [9.6]32.8 [9.6]4.7| 32.4 [9.5]32.4 [9.5]4.8| 31.8 [9.3]31.8 [9.3]4.7| 31.2 [9.2]31.2 [9.2]4.7


125

[51.7]

| Total BTUH [kW] Sens BTUH [kW] Power| 42.2 [12.4]  27.0 [7.9] 5.2| 41.4 [12.1]25.8 [7.6]5.1| 40.7 [11.9]24.6 [7.2]5.1| 38.0 [11.1]33.1 [9.7]5.1| 37.3 [10.9]31.6 [9.3]5.1| 36.7 [10.7]30.1 [8.8]5.1| 34.1 [10.0]34.1 [10.0]5.1| 33.5 [9.8]33.5 [9.8]5.1| 32.9 [9.6]32.9 [9.6]5.0| 32.3 [9.5]32.3 [9.5]5.1| 31.7 [9.3]31.7 [9.3]5.0| 31.2 [9.1]31.2 [9.1]5.0| 30.7 [9.0]30.7 [9.0]5.1| 30.1 [8.8]30.1 [8.8]5.0| 29.6 [8.7]29.6 [8.7]5.0

DR —Depression ratio
dbE —Entering air dry bulb
wbE —Entering air wet bulb
Total —Total capacity x 1000 BTUH
Sens —Sensible capacity x 1000 BTUH
Power —KW input

NOTES:
When the entering air dry bulb is other than 80°F [27°C], adjust the sensible capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].

HEATING PERFORMANCE DATA—RQPL-B049J

IDB 60°F [15.5°C] 70°F [21.1°C] 80°F [26.7°C]
CFM [L/s] 1760 [831] 1600 [755] 1440 [680]
[831]** 1600 [755] 1440 [680] 1760 [831]

1440 [680]
OUT DOOR
DRY BULB
TEMPERATURE
°F [°C]| 0 [-17.8]| Total BTUH [kW] Power| 15.9 [4.7] 2.5| 15.8 [4.6] 2.5| 15.7 [4.6] 2.5| 14.5 [4.3] 2.9| 14.4 [4.2] 2.9| 14.3 [4.2] 2.9| 13.2 [3.9] 3.2| 13.1 [3.8] 3.3| 13.0 [3.8] 3.3
5 [-15]| Total BTUH [kW] Power| 19.1 [5.6] 2.5| 19.0 [5.6] 2.6| 18.8 [5.5] 2.6| 17.8 [5.2] 2.9| 17.6 [5.2] 3.0| 17.5 [5.1] 3.0| 16.4 [4.8] 3.3| 16.3 [4.8] 3.3| 16.2 [4.7] 3.4
10 [-12.2]| Total BTUH [kW] Power| 22.3 [6.5] 2.6| 22.2 [6.5] 2.6| 22.0 [6.4] 2.7| 21.0 [6.2] 3.0| 20.8 [6.1] 3.0| 20.7 [6.1] 3.0| 19.7 [5.8] 3.4| 19.5 [5.7] 3.4| 19.4 [5.7] 3.4
15 [-9.4]| Total BTUH [kW] Power| 25.5 [7.5] 2.7| 25.4 [7.4] 2.7| 25.2 [7.4] 2.7| 24.2 [7.1] 3.0| 24.0 [7.0] 3.1| 23.9 [7.0] 3.1| 22.9 [6.7] 3.4| 22.7 [6.7] 3.5| 22.5 [6.6] 3.5
20 [-6.7]| Total BTUH [kW] Power| 28.8 [8.4] 2.7| 28.6 [8.4] 2.7| 28.4 [8.3] 2.8| 27.4 [8.0] 3.1| 27.2 [8.0] 3.1| 27.0 [7.9] 3.2| 26.1 [7.6] 3.5| 25.9 [7.6] 3.5| 25.7 [7.5] 3.6
25 [-3.9]| Total BTUH [kW] Power| 32.0 [9.4] 2.8| 31.8 [9.3] 2.8| 31.5 [9.2] 2.8| 30.6 [9.0] 3.1| 30.4 [8.9] 3.2| 30.2 [8.9] 3.2| 29.3 [8.6] 3.5| 29.1 [8.5] 3.6| 28.9 [8.5] 3.6
30 [-1.1]| Total BTUH [kW] Power| 35.2 [10.3] 2.8| 35.0 [10.2] 2.9| 34.7 [10.2] 2.9| 33.9 [9.9] 3.2| 33.6 [9.9] 3.2| 33.4 [9.8] 3.3| 32.5 [9.5] 3.6| 32.3 [9.5] 3.6| 32.1 [9.4] 3.7
35 [1.7]| Total BTUH [kW] Power| 38.4 [11.3] 2.9| 38.2 [11.2] 2.9| 37.9 [11.1] 2.9| 37.1 [10.9] 3.3| 36.8 [10.8] 3.3| 36.6 [10.7] 3.3| 35.8 [10.5] 3.6| 35.5 [10.4] 3.7| 35.2 [10.3] 3.7
40 [4.4]| Total BTUH [kW] Power| 41.6 [12.2] 2.9| 41.4 [12.1] 3.0| 41.1 [12.0] 3.0| 40.3 [11.8] 3.3| 40.0 [11.7] 3.3| 39.7 [11.6] 3.4| 39.0 [11.4] 3.7| 38.7 [11.3] 3.7| 38.4 [11.3] 3.8
45 [7.2]| Total BTUH [kW] Power| 44.9 [13.1] 3.0| 44.5 [13.1] 3.0| 44.2 [13.0] 3.1| 43.5 [12.8] 3.4| 43.2 [12.7] 3.4| 42.9 [12.6] 3.4| 42.2 [12.4] 3.7| 41.9 [12.3] 3.8| 41.6 [12.2] 3.8
50 [10]| Total BTUH [kW] Power| 48.1 [14.1] 3.0| 47.7 [14.0] 3.1| 47.4 [13.9] 3.1| 46.7 [13.7] 3.4| 46.4 [13.6] 3.5| 46.1 [13.5] 3.5| 45.4 [13.3] 3.8| 45.1 [13.2] 3.9| 44.8 [13.1] 3.9

Indoor Airflow Performance

INDOOR AIRFLOW PERFORMANCE—208 VOLTS

Nominal Cooling Capacity Tons [kW]| Motor Speed from Factory| Manufacturer Recommended Airflow (Min/Max)| Blower Size/ Motor HP [W] &
# of Speeds| **Motor Speed| | External Static Pressure – Inches W.C. [kPa] (Side Discharge-Wet Coil)
---|---|---|---|---|---|---
0.1 [.02]| 0.2 [.05]| 0.3 [.07]| 0.4 [.10]| 0.5 [.12]| 0.6 [.15]| 0.7 [.17]| 0.8 [.20]
2.0 [7.03]| Low (Tap 1)| 700 CFM /900 CFM| 9 x 7 Blower 1/3 HP [249W] 3 Speed X13 Motor| Low (Tap 1)| CFM [l/s]| 847 [400]| 818 [386]| 788 [372]| 765 [361]| 737 [348]| 695 [328]| 659 [311]| 581 [274]
RPM| 862| 888| 940| 976| 1033| 1066| 1122| 1193
Watts| 145| 147| 156| 157| 164| 167| 167| 155
High (Tap 2)| CFM [l/s]| 914 [431]| 887 [419]| 853 [403]| 824 [389]| 793 [374]| 762 [360]| 717 [338]| 602 [284]
RPM| 934| 971| 1024| 1053| 1083| 1121| 1135| 1155
Watts| 173| 177| 185| 186| 188| 192| 185| 164
2.5 [8.79]| Low (Tap 1)| **
875 CFM / 1125 CFM| 10 x 9 Blower 1/2 HP [373W] 3 Speed X13 Motor| Low (Tap 1)| CFM [l/s]| 1067 [504]| 1034 [488]| 992 [468]| 957 [452]| 912 [430]| 820 [387]| 778 [367]| 729 [344]
RPM| 719| 749| 791| 819| 876| 952| 983| 1024
Watts| 143| 145| 155| 159| 169| 182| 185| 192
Med. (Tap 2)| CFM [l/s]| 1165 [550]| 1132 [534]| 1091 [515]| 1051 [496]| 1009 [476]| 959 [453]| 855 [404]| 819 [387]
RPM| 744| 785| 833| 864| 905| 951| 1020| 1053
Watts| 167| 177| 188| 191| 202| 206| 217| 351
High (Tap 3)| CFM [l/s]| 1252 [591]| 1213 [572]| 1166 [550]| 1137 [537]| 1099 [519]| 1046 [494]| 986 [465]| 892 [421]
RPM| 796| 826| 868| 893| 934| 982| 1026| 1086
Watts| 206| 210| 219| 225| 234| 245| 248| 256
3.0 [10.55]| Low (Tap 1)| 1050 CFM /1350 CFM| 10 x 9 Blower 1/2 HP [373W] 3 Speed X13 Motor| Low (Tap 1)| CFM [l/s]| 1247 [589]| 1220 [576]| 1178 [556]| 1143 [539]| 1099 [519]| 1064 [502]| 998 [471]| 904 [427]
RPM| 784| 819| 863| 890| 932| 957| 1012| 1075
Watts| 200| 208| 219| 224| 233| 236| 246| 256
Med. (Tap 2)| CFM [l/s]| 1307 [617]| 1292 [610]| 1238 [584]| 1214 [573]| 1170 [552]| 1135 [536]| 1087 [513]| 989 [467]
RPM| 820| 850| 889| 918| 944| 981| 1028| 1087
Watts| 233| 242| 248| 255| 262| 268| 277| 284
High (Tap 3)| CFM [l/s]| 1396 [659]| 1357 [640]| 1334 [630]| 1286 [607]| 1253 [591]| 1207 [570]| 1163 [549]| 1103 [521]
RPM| 864| 898| 920| 942| 976| 1010| 1043| 1089
Watts| 268| 280| 288| 292| 299| 304| 310| 316
3.5 [12.31]| Low (Tap 1)| 1225 CFM /1575 CFM| 10 x 9 Blower 3/4 HP [559W] 2 Speed X13 Motor| Low (Tap 1)| CFM [l/s]| 1432 [676]| 1398 [660]| 1367 [645]| 1328 [627]| 1287 [607]| 1252 [591]| 1213 [572]|
RPM| 790| 831| 869| 913| 952| 980| 1016|
Watts| 247| 260| 273| 287| 300| 303| 317|
High (Tap 2)| CFM [l/s]| 1559 [736]| 1530 [722]| 1488 [702]| 1454 [686]| 1417 [669]| 1375 [649]| 1336 [631]|
RPM| 870| 893| 932| 968| 1007| 1036| 1072|
Watts| 321| 327| 338| 351| 364| 371| 381|
4.0 [14.07]| Low (Tap 1)| 1350 CFM /1700 CFM| 10 x 9 Blower 3/4 HP [559W] 2 Speed X13 Motor| Low (Tap 1)| CFM [l/s]| 1675 [791]| 1658 [782]| 1610 [760]| 1580 [746]| 1535 [724]| 1491 [704]| 1422 [671]|
RPM| 923| 944| 979| 1013| 1045| 1077| 1098|
Watts| 390| 401| 412| 425| 433| 440| 432|
High (Tap 2)| CFM [l/s]| 1770 [835]| 1751 [826]| 1706 [805]| 1672 [789]| 1624 [766]| 1555 [734]| 1463 [690]|
RPM| 966| 989| 1018| 1050| 1078| 1100| 1115|
Watts| 454| 466| 473| 486| 490| 481| 460|

NOTE: Italic type indicates airflow outside of manufacturers recommendation.
Do not connect wiring to unspecified speed taps..

DOWN DISCHARGE PRESSURE DROP (ADD TO EXTERNAL STATIC PRESSURE)

CFM [L/s]| 600 [283]| 800 [378]| 1000 [472]| 1200 [566]| 1400 [661]| 1600 [775]| 1800 [849]| 2000 [944]
Pressure Drop—Inches W.C. [kPa]| .00| .02 [.005]| .05 [.012]| .07 [.017]| .1 [.025]| .12 [.030]| .15 [.037]| .17 [.042]

INDOOR AIRFLOW PERFORMANCE—230 VOLTS

Nominal Cooling Capacity Tons [kW]| Motor Speed from Factory| Manufacturer Recommended Airflow (Min/Max)| Blower Size/ Motor HP [W] &  # of Speeds| Motor Speed| | External Static Pressure – Inches W.C. [kPa] (Side Discharge-Wet Coil)
---|---|---|---|---|---|---
0.1 [.02]| 0.2 [.05]| 0.3 [.07]| 0.4 [.10]| 0.5 [.12]| 0.6 [.15]| 0.7 [.17]| 0.8 [.20]
2.0 [7.03]| Low (Tap 1)| 700 CFM /900 CFM| ****

9 x 7 Blower 1/3 HP [249W] 3 Speed X13 Motor

| Low (Tap 1)| CFM [l/s]| 862 [407]| 834 [394]| 819 [387]| 781 [369]| 761 [359]| 729 [344]| 695 [328]| 606 [286]
RPM| 889| 953| 974| 1018| 1065| 1101| 1133| 1156
Watts| 151| 159| 162| 166| 173| 176| 180| 165
High (Tap 2)| CFM [l/s]| 918 [433]| 888 [419]| 874 [412]| 838 [395]| 819 [387]| 781 [369]| 711 [336]| 616 [291]
RPM| 953| 988| 1032| 1060| 1091| 1126| 1146| 1157
Watts| 181| 184| 194| 198| 200| 204| 189| 168
2.5 [8.79]| Low (Tap 1)| 875 CFM /1125 CFM| 10 x 9 Blower 1/2 HP [373W] 3 Speed X13 Motor| Low (Tap 1)| CFM [l/s]| 1076 [508]| 1041 [491]| 1017 [480]| 970 [458]| 928 [438]| 852 [402]| 785 [370]| 745 [352]
RPM| 715| 753| 787| 825| 877| 946| 1005| 1032
Watts| 144| 148| 157| 169| 175| 187| 198| 202
Med. (Tap 2)| CFM [l/s]| 1187 [560]| 1124 [530]| 1096 [517]| 1071 [505]| 1024 [483]| 987 [466]| 896 [423]| 852 [402]
RPM| 762| 799| 832| 859| 914| 940| 1021| 1059
Watts| 176| 182| 191| 196| 209| 212| 227| 235
High (Tap 3)| CFM [l/s]| 1271 [600]| 1223 [577]| 1169 [552]| 1137 [537]| 1104 [521]| 1071 [505]| 1015 [479]| 934 [441]
RPM| 797| 836| 878| 905| 939| 974| 1026| 1089
Watts| 212| 217| 227| 231| 241| 247| 257| 270
3.0 [10.55]| Low (Tap 1)| 1050 CFM /1350 CFM| 10 x 9 Blower 1/2 HP [373W] 3 Speed X13 Motor| Low (Tap 1)| CFM [l/s]| 1258 [594]| 1215 [573]| 1200 [566]| 1160 [547]| 1130 [533]| 1082 [511]| 1026 [484]| 954 [450]
RPM| 802| 829| 861| 894| 933| 971| 1020| 1077
Watts| 210| 217| 225| 230| 239| 245| 259| 268
Med. (Tap 2)| CFM [l/s]| 1336 [631]| 1298 [613]| 1259 [594]| 1229 [580]| 1198 [565]| 1160 [547]| 1116 [527]| 1071 [505]
RPM| 821| 867| 903| 920| 957| 993| 1038| 1071
Watts| 239| 249| 259| 262| 275| 279| 290| 299
High (Tap 3)| CFM [l/s]| 1416 [668]| 1379 [651]| 1342 [633]| 1292 [610]| 1275 [602]| 1240 [585]| 1200 [566]| 1168 [551]
RPM| 874| 898| 933| 952| 993| 1011| 1060| 1091
Watts| 285| 290| 299| 304| 314| 322| 328| 337
3.5 [12.31]| Low (Tap 1)| 1225 CFM /1575 CFM| 10 x 9 Blower 3/4 HP [559W] 2 Speed X13 Motor| Low (Tap 1)| CFM [l/s]| 1441 [680]| 1406 [664]| 1367 [645]| 1338 [631]| 1305 [616]| 1265 [597]| 1229 [580]|
RPM| 790| 832| 874| 914| 950| 988| 1014|
Watts| 252| 266| 279| 292| 305| 318| 323|
High (Tap 2)| CFM [l/s]| 1550 [732]| 1520 [717]| 1486 [701]| 1449 [684]| 1407 [664]| 1382 [652]| 1337 [631]|
RPM| 867| 890| 930| 974| 1003| 1039| 1073|
Watts| 317| 323| 339| 355| 362| 377| 385|
4.0 [14.07]| **** Low (Tap 1)| 1350 CFM /1700 CFM| 10 x 9 Blower 3/4 HP [559W] 2 Speed X13 Motor| Low (Tap 1)| CFM [l/s]| 1692 [799]| 1661 [784]| 1633 [771]| 1589 [750]| 1560 [736]| 1512 [714]| 1442 [681]|
RPM| 931| 950| 982| 1018| 1054| 1082| 1103|
Watts| 404| 409| 424| 434| 450| 453| 443|
High (Tap 2)| CFM [l/s]| 1748 [825]| 1718 [811]| 1686 [796]| 1647 [777]| 1616 [763]| 1543 [728]| 1472 [695]|
RPM| 955| 978| 1010| 1043| 1073| 1096| 1111|
Watts| 440| 446| 462| 475| 484| 473| 459|

NOTE: Italic type indicates airflow outside of manufacturers recommendation.
Do not connect wiring to unspecified speed taps.

DOWN DISCHARGE PRESSURE DROP (ADD TO EXTERNAL STATIC PRESSURE)

CFM [L/s]| 600 [283]| 800 [378]| 1000 [472]| 1200 [566]| 1400 [661]| 1600 [775]| 1800 [849]| 2000 [944]
Pressure Drop—Inches W.C. [kPa]| .00| .02 [.005]| .05 [.012]| .07 [.017]| .1 [.025]| .12 [.030]| .15 [.037]| .17 [.042]

Electrical Data

ELECTRICAL DATA – RQPL SERIES

| | B024JK| B025JK| B030JK| C036CK| C036JK| C042CK| C042JK| B049CK| B049JK
Unit Information| Unit Operating Voltage Range| 187-253| 187-253| 187-253| 187-253| 187-253| 187-253| 187-253| 187-253| 187-253
Volts| 208/230| 208/230| 208/230| 208/230| 208/230| 208/230| 208/230| 208/230| 208/230
Phase| 1| 1| 1| 3| 1| 3| 1| 3| 1
Hz| 60| 60| 60| 60| 60| 60| 60| 60| 60
Minimum Circuit Ampacity| 21| 21| 24| 20| 27| 27| 34| 26| 33
Minimum Overcurrent Protection Device Size| 25| 25| 25| 25| 35| 35| 40| 30| 40
Maximum Overcurrent Protection Device Size| 30| 30| 35| 25| 40| 40| 50| 35| 50
Compressor Motor| No.| 1| 1| 1| 1| 1| 1| 1| 1| 1
Volts| 208/230| 208/230| 208/230| 200/230| 208/230| 200/230| 208/230| 200/230| 208/230
Phase| 1| 1| 1| 3| 1| 3| 1| 3| 1
RPM| 3450| 3450| 3450| 3450| 3450| 3500| 3500| 3500| 3500
HP, Compressor 1| 2| 2| 2 1/2| 3| 3| 3 1/2| 3 1/2| 4| 4
Amps (RLA), Comp. 1| 12.8| 12.8| 14.1| 10.4| 16.7| 13.8| 19.2| 13.7| 19.6
Amps (LRA), Comp. 1| 58.3| 58.3| 73| 73| 79| 83.1| 124| 83.1| 130
Condenser Motor| No.| 1| 1| 1| 1| 1| 1| 1| 1| 1
Volts| 208/230| 208/230| 208/230| 208/230| 208/230| 208/230| 208/230| 208/230| 208/230
Phase| 1| 1| 1| 1| 1| 1| 1| 1| 1
HP| 1/3| 1/3| 1/3| 1/3| 1/3| 1/3| 1/3| 1/3| 1/3
Amps (FLA, each)| 1.3| 1.3| 1.3| 2| 2| 3.5| 3.5| 2| 2
Amps (LRA, each)| 2.2| 2.2| 2.2| 3.9| 3.9| 3.9| 3.9| 3.9| 3.9
Evaporator Fan| No.| 1| 1| 1| 1| 1| 1| 1| 1| 1
Volts| 208/230| 208/230| 208/230| 208/230| 208/230| 208/230| 208/230| 208/230| 208/230
Phase| 1| 1| 1| 1| 1| 1| 1| 1| 1
HP| 1/3| 1/3| 1/2| 1/2| 1/2| 3/4| 3/4| 3/4| 3/4
Amps (FLA, each)| 2.8| 2.8| 4.1| 4.1| 4.1| 6| 6| 6| 6

  1. Horsepower Per Compressor.
  2. Amp Draw Per Motor. Multiply Value By Number of Motors to Determine Total Amps.

Electric Heater Kits

Unit Model Application| **Electric Heater Kit Factory Installed Options***
---|---
RQPL-B024JK & RQPL-B025JK| RXQJ-A05J (208-240 volt, 1-ph, 5kW)
RXQJ-A10J (208-240 volt, 1-ph, 10kW)
RQPL-B030JK| RXQJ-A05J (208-240 volt, 1-ph, 5kW)
RXQJ-A10J (208-240 volt, 1-ph, 10kW)
RQPL-C036JK| RXQJ-A10J (208-240 volt, 1-ph, 10kW)
RXQJ-A15J (208-240 volt, 1-ph, 15kW)
RQPL-C042JK| RXQJ-B10J (208-240 volt, 1-ph, 10kW)
RXQJ-B15J (208-240 volt, 1-ph, 15kW)
RQPL-B049JK| RXQJ-B10J (208-240 volt, 1-ph, 10kW)
RXQJ-B15J (208-240 volt, 1-ph, 15kW)
RQPL-C036JK| RXQJ-A10C (208-240 volt, 3-ph, 10kW)
RXQJ-A15C (208-240 volt, 3-ph, 15kW)
RQPL-C042JK| RXQJ-A10C (208-240 volt, 3-ph, 10kW)
RXQJ-A15C (208-240 volt, 3-ph, 15kW)
RQPL-B049CK| RXQJ-A10C (208-240 volt, 3-ph, 10kW)
RXQJ-A15C (208-240 volt, 3-ph, 15kW)

*Further kits for field installation on following pages.

WARNING
ONLY ELECTRIC HEATER KITS SUPPLIED BY THIS MANUFACTURER AS DESCRIBED IN THIS PUBLICATION HAVE BEEN DESIGNED, TESTED, AND EVALUATED BY A NATIONALLY RECOGNIZED SAFETY TESTING AGENCY FOR USE WITH  THIS UNIT. USE OF ANY OTHER MANUFACTURED ELECTRIC HEATERS INSTALLED WITHIN THIS UNIT MAY CAUSE HAZARDOUS CONDITIONS RESULTING IN PROPERTY DAMAGE, FIRE, BODILY INJURY OR DEATH.

208/240 VOLT, SINGLE PHASE, 60 Hz, AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION

Single Power Supply For Both Unit and Heater Kit| Separate Power Supply For Both Unit and Heater Kit

Unit Model No. RQPL-

| Heater Kit| Heat Pump| Heater Kit| Heat Pump
RXQJ- Heater Kit Nominal kW| No. of Sequence Steps| Rated Heater kW @ 208/240 V| Heater KBTU/Hr

@ 208/240 V

| Heater Amp. @ 208/240 V| Unit Min. Ckt. Ampacity @ 208/240 V| Over Current Protective Device Size| Min. Ckt. Ampacity 208/240 V| Max. Fuse Size 208/240 V| Min. Circuit Ampacity 208/240 V| Over Current Protective Device Size
Min./Max. @ 208 V| Min./Max. @ 240 V| Min./Max. @ 208 V| Min./Max. @ 240 V
B024JK| No Heat| —| —| —| —| 21/21| 25/30| 25/30| —| —| 21/21| 25/30| 25/30
A05J
A08J| 1

1

| 3.6/4.8
5.7/7.6| 12.28/16.38
19.45/25.93| 17.3/20.0
27.4/31.6| 42/46
55/60| 45/50
60/60| 50/50
70/70| 22/25
35/40| 25/25
35/40| 21/21
21/21| 25/30
25/30| 25/30
25/30
A10J| 1| 7.2/9.6| 24.57/32.76| 34.6/40.0| 64/71| 70/70| 80/80| 44/50| 45/50| 21/21| 25/30| 25/30
B025JK| No Heat| —| —| —| —| 21/21| 25/30| 25/30| —| —| 21/21| 25/30| 25/30
A05J
A08J| 1

1

| 3.6/4.8
5.7/7.6| 12.28/16.38
19.45/25.93| 17.3/20.0
27.4/31.6| 42/46
55/60| 45/50
60/60| 50/50
70/70| 22/25
35/40| 25/25
35/40| 21/21
21/21| 25/30
25/30| 25/30
25/30
A10J| 1| 7.2/9.6| 24.57/32.76| 34.6/40.0| 64/71| 70/70| 80/80| 44/50| 45/50| 21/21| 25/30| 25/30
B030JK| No Heat| —| —| —| —| 24/24| 25/35| 25/35| —| —| 24/24| 25/35| 25/35
A05J
A08J| 1

1

| 3.6/4.8
5.7/7.6| 12.28/16.38
19.45/25.93| 17.3/20.0
27.4/31.6| 45/49
58/63| 50/50
60/60| 50/50
70/70| 22/25
35/40| 25/25
35/40| 24/24
24/24| 25/35
25/35| 25/35
25/35
A10J| 1| 7.2/9.6| 24.57/32.76| 34.6/40.0| 67/74| 70/70| 80/80| 44/50| 45/50| 24/24| 25/35| 25/35
C036JK| No Heat| —| —| —| —| 27/27| 35/40| 35/40| —| —| 27/27| 35/40| 35/40
A08J| 1| 5.7/7.6| 19.45/25.93| 27.4/31.6| 62/67| 70/70| 70/70| 35/40| 35/40| 27/27| 35/40| 35/40
A10J| 1| 7.2/9.6| 24.57/32.76| 34.6/40.0| 71/77| 80/80| 80/80| 44/50| 45/50| 27/27| 35/40| 35/40
A15J| 1| 10.8/14.4| 36.85/49.13| 51.9/60.0| 92/102| 100/100| 110/110| 65/75| 70/80| 27/27| 35/40| 35/40
B06J| 1| 4.2/5.6| 14.33/19.11| 20.2/23.3| 53/57| 60/60| 60/60| 26/30| 30/30| 27/27| 35/40| 35/40
C042JK| No Heat| —| —| —| —| 34/34| 40/50| 40/50| —| —| 34/34| 40/50| 40/50
A08J| 1| 5.7/7.6| 19.45/25.93| 27.4/31.6| 68/73| 70/80| 80/80| 35/40| 35/40| 34/34| 40/50| 40/50
B06J| 1| 4.2/5.6| 14.33/19.11| 20.2/23.3| 59/63| 60/70| 70/70| 26/30| 30/30| 34/34| 40/50| 40/50
B10J| 1| 7.2/9.6| 24.57/32.76| 34.6/40.0| 77/84| 80/80| 90/90| 44/50| 45/50| 34/34| 40/50| 40/50
B15J| 1| 10.8/14.4| 36.85/49.13| 51.9/60.0| 99/109| 100/100| 110/110| 65/75| 70/80| 34/34| 40/50| 40/50
B049JK| No Heat| —| —| —| —| 33/33| 40/50| 40/50| —| —| 33/33| 40/50| 40/50
A08J
B10J| 1

1

| 5.7/7.6
7.2/9.6| 19.45/25.93
24.57/32.76| 27.4/31.6

34.6/40.0

| 67/72
76/83| 70/70
80/80| 80/80
90/90| 35/40
44/50| 35/40
45/50| 33/33
33/33| 40/50
40/50| 40/50
40/50
B15J| 1| 10.8/14.4| 36.85/49.13| 51.9/60.0| 98/108| 100/100| 110/110| 65/75| 70/80| 33/33| 40/50| 40/50
208/240 VOLT, THREE PHASE, 60 Hz, AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION

Single Power Supply For Both Unit and Heater Kit| Separate Power Supply For Both Unit and Heater Kit
Unit Model No. RQPL-| Heater Kit| Heat Pump| Heater Kit| Heat Pump
RXQJ- Heater Kit Nominal kW| No. of Sequence Steps| Rated Heater kW @ 208/240 V| Heater KBTU/Hr @ 208/240 V| Heater Amp. @ 208/240 V| Unit Min. Ckt. Ampacity @ 208/240 V| Over Current Protective Device Size| Min. Ckt. Ampacity 208/240 V| Max. Fuse Size 208/240 V| Min. Circuit Ampacity 208/240 V| Over Current Protective Device Size
Min./Max. @ 208 V| Min./Max. @ 240 V| Min./Max. @ 208 V| Min./Max. @ 240 V
C036CK| No Heat| —| —| —| —| 20/20| 25/25| 25/25| —| —| 20/20| 25/25| 25/25
A10C
A15C| 1

1

| 7.2/9.6
10.8/14.4| 24.57/32.76
36.85/49.13| 20.0/23.1
30.1/34.7| 45/48
57/63| 50/50
60/60| 50/50
70/70| 25/29
38/44| 25/30
40/45| 20/20
20/20| 25/25
25/25| 25/25
25/25
C042CK| No Heat| —| —| —| —| 27/27| 35/40| 35/40| —| —| 27/27| 35/40| 35/40
A10C| 1| 7.2/9.6| 24.57/32.76| 20.0/23.1| 52/56| 60/60| 60/60| 25/29| 25/30| 27/27| 35/40| 35/40
A15C| 1| 10.8/14.4| 36.85/49.13| 30.1/34.7| 65/71| 70/70| 80/80| 38/44| 40/45| 27/27| 35/40| 35/40

B049CK

| No Heat
A10C| —
1| —
7.2/9.6| —
24.57/32.76| —
20.0/23.1| 26/26
51/54| 30/35
60/60| 30/35
60/60| —
25/29| —
25/30| 26/26
26/26| 30/35
30/35| 30/35
30/35
A15C| 1| 10.8/14.4| 36.85/49.13| 30.1/34.7| 63/69| 70/70| 80/80| 38/44| 40/45| 26/26| 30/35| 30/35

Dimensional Data

FUJITSU RQPL Package Heat Pump - Fig 1

FUJITSU RQPL Package Heat Pump - Fig 2

Typical Installations

FUJITSU RQPL Package Heat Pump - Fig 3

Accessories

ACCESSORY EQUIPMENT

Accessory Description| Model Application| Accessory Model No.
---|---|---
Roof curb| RQPL-| RXQG-AAA14 (14″ [356 mm] Height)
RXQG-AAA24 (24″ [610 mm] Height)
Supply & Return Diffusers| RQPL-| RXRN-BD15
Economizers (Convertable)| RQPL-| AXRD-01RACAM3
Dual Enthalpy Kit| | RXAX-A04
Fresh Air Damper| RQPL-| AXRF-FAB1 (Motorized-35%) AXRF-FAA1 (Fixed-35%)
Rectangular to Round Transition (Downflow)| RQPL-| RXMC-CA02 (16″ [406 mm] Ducts)
RXMC-CA03 (18″ [457 mm] Ducts)
Filter Kit| RQPL-| RXRY-B01
High Pressure Control| RQPL-| RXAB-D01
Outdoor Thermostat| RQPL-| RXPT-A01
Low Ambient Control| RQPL-| RXPZ-G01
Duct Adapter Side flow Square to Round Transition| RQPL-| AXMC-BA01
Lift Kit| RQPL-| RXML-A01

COMMON SUPPLY/RETURN CONCENTRIC AIR DIFFUSER

FUJITSU RQPL Package Heat Pump - Fig 4

SUPPLY/RETURN DIFFUSER

Designed to convert a side by side or an over and under arrangement into a concentric distribution of air. The diffuser is flush mounted, completely insulated, assembled, and internally baffled to provide four way supply air distribution with a center return. To make the assembly complete and ready to fit into a 2′ [0.61 m] x 4′ [1.22 m] suspended ceiling grid, the diffuser includes adjustable supply louvers, hanging rings, anti-sweat gasket, and round flanges for use with flexible ducts.

Model No. RXRN-| Diameter Inches [mm]| Shipping Wt. Lbs. [kg]| Dimension A Inches [mm]
---|---|---|---
BD15| 16 [406]| 90 [40.82]| 201/2 [521]

NOTE: The location of the combination supply and return diffuser should not exceed 10 feet [3.05 m] above the floor level for units @ 1000 CFM [472 L/s] or less and 12 [3.66 m] to 14 feet [4.27 m] above the floor level for units with CFM greater than 1000 [472 L/s]. If the diffuser is installed with a greater distance than recommended above, the supply air may become stratified above the required comfort area causing uncomfortable conditions.
AIRFLOW/PRESSURE DROP INFORMATION (INCHES W.C. [kPa])

Accessory Appr oximate CFM [L/s]-Supply Air
1300 [614] 1575 [743]
Plenum & Supply/Return Duct .07 [.017]
Diffuser .09 [.022]
Economizer .06 [.015]

SUPPLY AIR/PERFORMANCE

Diffuser Airflow CFM [L/s] Range of Thr ow Ft. [m]
800 [378]-1200 [566] 14 [4.27]-16 [4.88]
1600 [755]-2000 [944] 18 [5.49]-28 [8.53]

DUCT ADAPTERS
RECTANGULAR TO ROUND TRANSITIONS (DOWNFLOW)

FUJITSU RQPL Package Heat Pump - Fig 7

FRESH AIR DAMPER FOR USE ON RQPL- SERIES
AXRF-FAA1 (Fixed – 0-35%)
The 0-35% manual outside Air Damper is designed to replace the unit return air duct cover. No drilling or damper assembly is required. The amount of outside air (0-35%) is controlled by simply adjusting the side damper.
AXRF-FAB1 (Motorized – 0-35%)
The 0-35% motorized outside Air Damper is designed to replace the unit return air duct cover. No drilling or damper assembly is required. The control motor opens the adjustable slide damper when the unit blower motor is energized.

FUJITSU RQPL Package Heat Pump - Fig 8

ECONOMIZERS
AXRD-01RACAM3 (Fully Modulating)
Horizontally and Vertically Applicable

  • LCD Screen for Continuous diagnostic and system status
  • Programmable set points for accurate positioning
  • Simplified wiring and color coded terminals
  • Onboard fault detection and diagnostics (FDD)
  • Operational Checkout to verify installation
  • Enthalpy sensors and actuator that communicate through a Sylk Bus Network with the Jade Controller reducing wiring errors while providing more information
  • CO 2 sensor input for DCV (Demand Control Ventilation) applications
  • RXRX-AV04 Dual Enthalpy kit available for field installation
  • AMCA licensed class 1A low leak Dampers

FUJITSU RQPL Package Heat Pump - Fig 10

FILTER KIT INSTALLATION
RXRY-B01
For use in either vertical or horizontal discharge.

CFM [L/s]

Minimum Airflow| Nominal Airflow| Maximu m Airflow
510 [241]| 600 [283]| 660| [311]
680 [321]| 800 [378]| 880| [415]
850 [401]| 1000 [472]| 1100| [519]
1020 [481]| 1200 [566]| 1320| [623]
1190 [562]| 1400 [661]| 1540| [727]
1275 [602]| 1500 [708]| 1650| [779]
1700 [802]| 2000 [944]| 2200 [1039]
Airflow Pre ssure Drop, Inches W .C. [kPa]

CFM [L/s]| 1″ Filter| 2″ Filter
500 [236]| .02 [.0050]| .03 [.0075]
600 [283]| .02 [.0050]| .03 [.0075]
700 [330]| .03 [.0075]| .04 [.0010]
800 [378]| .04 [.0010]| .05 [.0124]
900 [425]| .05 [.0124]| .06 [.0149]
1000 [472]| .07 [.0174]| .08 [.0199]
1100 [519]| .08 [.0199]| .09 [.0224]
1200 [566]| .10 [.0249]| .12 [.0299]
1300 [614]| .13 [.0324]| .15 [.0373]
1400 [661]| .16 [.0398]| .19 [.0473]
1500 [708]| .19 [.0473]| .21 [.0523]
1600 [755]| .20 [.0498]| .23 [.0572]
1700 [802]| .21 [.0523]| .24 [.0598]
1800 [850]| .22 [.0548]| .25 [.0623]
1900 [897]| .24 [.0598]| .27 [.0672]
2000 [944]| .26 [.0647]| .29 [.0722]

DUCT ADAPTER SIDEFLOW
SQUARE TO ROUND TRANSITION AXMC-BA01
Adapts the side rectangular supply and return openings to 14″ [356 mm] diameter round openings. Adapters provided with same finish as unit and also provided with thermal insulation.
[ ] Designates Metric Conversions

FUJITSU RQPL Package Heat Pump - Fig 12

Roof curb (Sloped)
RXQG-AAA14 & RXQG-AAA24 **for RQPL- Series
Note:** Heat pump models must use sloped curbs. Hinged corners make for fast, easy set-up.

FUJITSU RQPL Package Heat Pump - Fig 13

Packaged Heat Pump

Roof curb Installation (Sloped)

FUJITSU RQPL Package Heat Pump - Fig 14

ROOFCURB ADAPTERS
Fabricated from galvanized steel to adapt the New cabinet to the old style curb. All are furnished with a New gasket.

FUJITSU RQPL Package Heat Pump - Fig 15

BEFORE PURCHASING THIS APPLIANCE, READ IMPORTANT ENERGY COST AND EFFICIENCY INFORMATION AVAILABLE FROM YOUR RETAILER.

GENERAL TERMS OF LIMITED WARRANTY*

Fujitsu General America, Inc. will furnish a replacement for any part of this product which fails in normal use and service within the applicable periods stated, in accordance with the terms of the limited warranty.

  • For complete details of the Limited and Conditional Warranties, including applicable terms and conditions, contact your local contractor or the Manufacturer for a copy of the product warranty certificate.

Conditional Parts (Registration Required)
1 Phase, Residential Applications …………….. Ten (10) Years
Compressor
1 Phase, Residential Applications …………….. Ten (10) Years
1 & 3 Phase, Commercial Applications ………..Five (5) Years
Parts
1 & 3 Phase, Commercial Applications ………… One (1) Year

“In keeping with its policy of continuous progress and product improvement, Fujitsu reserves the right to make changes without notice.”
PRINTED IN U.S.A. 4/22 QG FORM NO. PFJ-791 REV. 2

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

FUJITSU User Manuals

Related Manuals