K-RAIN KRC9 Professional Irrigation Controller User Manual
- June 12, 2024
- K-RAIN
Table of Contents
- K-RAIN KRC9 Professional Irrigation Controller
- Product Information
- Product Usage Instructions
- Set Current Time, Day, and Date
- Overview
- Programming
- Manual Operation
- Other Features
- Installation
- Troubleshooting
- Electrical Specifications
- Servicing
- Warranty
- CONTACT
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
K-RAIN KRC9 Professional Irrigation Controller
Product Information
- Max no. ZONES: 9
- Max no. PROGRAMS: 5
- Max no. STARTS per PROGRAM: Not specified
- Looping: Yes
- Max. RUN TIME/DELAY: Not specified
- Scheduling options (per PROGRAM): Not specified
- SEASONAL ADJUSTMENT: Yes
- MANUAL control: Yes
- SYSTEM TEST: Yes
- PUMP/master control: Yes
- Rain sensor connectivity: Yes
- Rain sensor control: Yes
- Rain sensor programming: Yes
- Rain delay: Yes
- Shut off control: Yes
- Contractor programming: Yes
- Clock and calendar: Yes
- Memory backup power: Yes
- Power source: Not specified
- Power spike protection: Yes
- Fault detection: Yes
- Housing: Not specified
Product Usage Instructions
How Programming Works
This controller has been designed with 5 separate programs to allow
different landscape areas to have their own individual watering schedules. A
PROGRAM is a method of grouping zones(valves) with similar characteristics.
Set Automatic Program
To set the automatic PROGRAM for each group of zones (valves), follow these three steps:
- Set watering START TIMES
- Set WATER DAYS
- Set ZONE RUN TIME (durations)
This controller has been designed for quick intuitive programming. Remember these simple tips for hassle-free programming.
Set Current Time, Day, and Date
- Turn the MAIN DIAL to CLOCK-CALENDAR
- Use the arrow buttons to adjust the flashing minutes
- Press the “Enter” button and use the arrow buttons to adjust the flashing hours
- Press the “Enter” button and use the arrow buttons to adjust the flashing days of the week
- Press the “Enter” button repeatedly until the calendar date appears on the display with the year flashing
Overview
Main Components
- LCD display
- LEFT
-
- RIGHT
- –
-
- SENSOR switch
- MAIN DIAL
- Terminal cover
Features
**Max no. ZONES** | **** 9 |
---|---|
Max no. PROGRAMS | 5 |
Max no. STARTS per PROGRAM | 8 |
Looping | PROGRAM 5; max. 99 loops |
**Max. RUN TIME/DELAY** | 12:59 hrs (can be multiplied up to |
200%)
Scheduling options (per PROGRAM)
| 7 Day, Interval Days (up to 15),
Odd, Even, Odd-31
SEASONAL ADJUSTMENT| Per month, 10-200%
MANUAL control| Per ZONE with a savable run time
SYSTEM TEST| Sequential for all ZONES, 2 min default
PUMP/master control| ON/OFF per zone or per program
Rain sensor connectivity| Optically isolated hard-wired input
Rain sensor control| Master ON/OFF slide switch
Rain sensor programming| Per ZONE
Rain delay| Max 9 days
Shut off control| Turn MAIN DIAL to ALL OFF
Contractor programming| Save, recall, and load memory easily
Clock and calendar| RTC; month, year, date, weekday, time
Memory backup power| 9V battery
**Power source| 24VAC low-energy transformer with 30W capacity
Power spike protection| M-205 fuse rated at 1A
Common| 4× common cables
****Fault detection**| Available on LCD display;
no AC power and low battery
**Housing**| Heavy duty with lockable door and IS54 dust and moisture protection
Programming
How Programming Works
This controller has been designed with 5 separate programs to allow different
landscape areas to have their own individual watering schedules
- A PROGRAM is a method of grouping zones (valves) with similar watering requirements to water on the same days. These zones will water in sequential order and on the days selected
- Group the zones (valves) which are watering similar landscape areas together. For example, turf, flower beds, gardens–these different groups may require individual watering schedules, or PROGRAMS
- Set the current time and correct day of the week. If odd or even day watering is going to be used, make sure the current year, month and day of the month is correct
- If left unattended for over 1 minute, the LCD display will return to AUTO no matter the position of the MAIN DIAL. If you were in the process of programming this controller, turn dial to AUTO and then back to the position you were programming to continue
Set Automatic Program
Set the automatic PROGRAM for each group of zones (valves) by completing the following three steps:
- Set watering START TIMES
- For each start time, all the zones (valves) selected for the PROGRAM will come on in sequential order
- If two start times are set, the zones (valves) will come on twice
- Set WATER DAYS
- Set ZONE RUN TIME (durations)
This controller has been designed for quick intuitive programming. Remember these simple tips for hassle free programming:
- One push of a button will increment one unit
- Holding a button down will fast scroll through units
- During the programming, only flashing units are able to be set
- Adjust flashing units using + or –
- Press LEFT or LEFT to scroll through settings as desired
- The MAIN DIAL is the primary device for selecting an operation
- Press to select different PROGRAMS. Each push on this button will increment one PROGRAM number
Set Current Time, Day, and Date
- Turn the MAIN DIAL to CLOCK-CALENDAR
- Use + or – to adjust the flashing minutes [a]
- Press RIGHT and then use + or – to adjust the flashing hours [a]
- AM/PM must be set correctly.
- Press RIGHT and then use + or – adjust the flashing days of the week [b]
- Press LEFT repeatedly until the calendar date appears on the display with the year [c] flashing
- The calendar only needs to be set when selecting odd/even day watering
- Use + or – to adjust the flashing year [c]
- Press LEFT and then use or to adjust the flashing month [d]
- Press+ and – then use or to adjust the flashing date [e]
- To return to the clock, turn the dial back to AUTO
Set Start Times
All zones will run in sequential order for each start time For this example, we will set a START TIME for PROG No. 1
- Turn the dial to START TIMES and ensure that PROG No. 1 is showing
- If not, press to cycle through the PROGRAMS and select PROG No. 1
- START No. 1 [f] will be flashing
- Use + or – to change the START No. if required
- Press RIGHT and the hours [g] for your selected START No. will flash
- Use + or – to adjust if required
- Ensure AM/PM is correct
- Press RIGHT and the minutes [g] will flash
- Use + or – adjust if required
- Each PROGRAM can have up to 8 START TIMES
- To set an additional START TIME, press RIGHT, and START No. 1 [f] will flash
- Advance to START No. 2 by pressing +
- Follow steps 4-7 above to set a START TIME for START No. 2
- To enable or disable a START TIME, use + or – set both the hours and minutes to zero
- To cycle through and change PROGRAMS, press repeatedly
- This unit has individual day, EVEN/ODD date, ODD-31 date and INTERVAL DAYS selection
Individual Day Selection:
- Turn dial to WATER DAYS and PROG No. 1 will show
- If not, use to select PROG No. 1
- MON (Monday) [h]will be flashing
- Use + or – to enable or disable watering for Monday respectively
- Use+ or – to cycle through the days of the week
- Active days will be shown with underneath
- ODD/EVEN Date Selection
- Some regions only allow watering on odd dates if the house number is odd, or likewise for even dates
- Turn dial to WATER DAYS and PROG No. 1 will show
- Press RIGHT repeatedly to cycle past SUN until EVEN DAYS [i] or ODD DAYS is showing accordingly
- Press again for ODD- 31 [j] if necessary
- The 365-day calendar must be set correctly for this feature, (see Set Current Time, Day and Date)
- This controller will take leap years into account
- Interval Day Selection
- Turn dial to WATER DAYS and PROG No. 1 will show
- Press RIGHT repeatedly to cycle past SUN until INTERVAL DAYS is showing accordingly
- INTERVAL DAYS 1 [k] will be flashing
- Use or to select from 1 to 15 day intervals
- Example: INTERVAL DAYS 2 means the controller will run the program every 2 days
- The next active day is always changed to 1, meaning tomorrow is the first active day to run
Set Zone Run Times
ZONE RUN TIME is the length of time each zone (valve) is scheduled to water on a particular PROGRAM Maximum watering time is 12 hrs 59 min for each ZONE A zone can be assigned to any or all of the possible 5 PROGRAMS
- Turn the dial to ZONE RUN TIMES
- ZONE No. 1 [l] will be flashing labelled as OFF, as shown above, meaning it has no RUN TIME programmed in it
- The controller has permanent memory so if there is a power failure, even if the battery is not installed, the programmed values will be restored to the unit
- Press + or – to select a zone (valve)
- Press RIGHT and OFF will flash
- Press + or – to adjust the RUN TIME minutes as desired
- Press RIGHT and the RUN TIME hours will flash
- Press + or – to adjust the RUN TIME hours as desired
- Press RIGHT and the ZONE No. will flash again
- Press + or – to select another zone (valve), and repeat steps 2-7 above to set a RUN TIME
- To turn a ZONE OFF, set both the hours and minutes to 0, and the display will flash OFF [m] as shown
- This completes the setup procedure for PROG No. 1
Set Additional Programs
- Set schedules for up to 5 PROGRAMS by pressing when setting up START TIMES, WATERING DAYS and ZONE RUN TIMES as previously outlined
- Although the controller will run automatic programs with the MAIN DIAL in any position (with the exception of OFF), we recommend to leaving the main dial on AUTO position when not programming or running manually
Manual Operation
Run a Single Zone
The maximum run time is 12 hours 59 minutes
- Turn the dial to MANUAL ZONE
- ZONE No. 1 [l]will be flashing
- The default manual run time [m] is 10 minutes–to edit this, see Edit Manual Run Time
- Use + or – to select the desired zone
- The selected zone will start running and the RUN TIME will decrease accordingly
- If there is a pump or master valve connected, PUMP A [o] will be shown in the display, indicating the pump/master is active
- Press RIGHT and the RUN TIME minutes [p] will flash
- Use + or – to adjust the minutes
- Press RIGHT and the RUN TIME hours [p] will flash
- Use + or – to adjust the hours
- The unit will revert to AUTO after the time has lapsed
- If you forget to turn the dial back to AUTO, the controller will still run programs
- To stop watering immediately, turn the dial to ALL OFF
Edit Manual Run Time
- To edit default MANUAL RUN TIME turn the dial toMANUAL ZONE
- ZONE No. 1 [n] will flash
- Press and the RUN TIME minutes [p] will flash
- Use+ or – to adjust the RUN TIME minutes
- Press and the default RUN TIME hours [p] will flash
- Use or to adjust the RUN TIME hours
- Once the desired RUN TIME is set, press to save this as the default manual RUN TIME
- The new default will now always appear when the dial is turned to MANUAL ZONE
Run a Program
- To manually run a complete program or to stack multiple programs to run, turn the desired PROGRAM
- OFF will flash on the display
- To enable a PROGRAM, press + and the display will change to ON
- If no RUN TIME has been set for the desired PROGRAM, the above step will not work
- To run the desired PROGRAM immediately, press RIGHT
Other Features
Stop Watering
- To stop an automatic or manual watering schedule, turn the dial to ALL OFF
- For automatic watering remember to turn the dial back to AUTO, as ALL OFF will stop any future watering cycles from occurring
Stacking Start Times
- If the same START TIME is set across multiple PROGRAMS, they will run individually in sequential order, starting from PROGRAM 1 through to 5
- If a START TIME runs over another RUN TIME, it will be delayed accordingly
Upload to Contractor Memory
- Turn the MAIN DIAL to ALL OFF
- Press LEFT and RIGHT at the same time, and the display will read LOAD UP and SAVE CONTRACTOR MEMORY
- Press to confirm
Download Contractor Memory
- Turn MAIN DIAL to ALL OFF
- Press and the display will read LOAD and RECALL CONTRACTOR MEMORY
- Press to confirm
Rain Sensor
- When installing a rain sensor, first remove the factory fitted link between the COM and SENS terminals as shown
- Replace with the two wires from the rain sensor into these terminals, polarity NOT required
- A Rain Sensor needs to be connected to the terminal correctly for this feature (for more details, see Zone Valve Installation)
- Toggle the RAIN SENSOR switch to ON
- Turn the dial to RAIN SETTINGS to enable your rain sensor for individual zones
- The default mode is ON for all zones
- If a zone is labelled ON on the display, this means your rain sensor will be able to control the valve in the instance of rain
- Should you have a zone that always needs to be watered, (such as an enclosed greenhouse, or plants that are under cover) the rain sensor can be turned OFF to continue watering during rainy conditions
- To turn a zone OFF, press RIGHT to cycle through and select the desired zone, then press –
- To toggle a zone back ON, press +
- To disable the rain sensor and allow all zones to water, toggle the RAIN SENSOR switch to OFF
Rain Delay
To adjust the timing of your rain sensor, this controller features a RAIN DELAY setting This allows a specific delay time to elapse after the rain sensor has dried out before the zone will water again.
- Turn the dial to RAIN SETTINGS
- Press to access the RAIN DELAY screen
- The INTERVAL DAYS [q]value will now be flashing
- Use + or – to alter the rain delay time in increments of 24 hours at a time
- A maximum delay of 9 days can be set
- This halts any watering and stops all automatic programs until the rain delay expires
Display Contrast
- To adjust the LCD contrast, turn the dial to PUMP SETTINGS
- Press repeatedly until the display reads CON
- CON 3 is the default contrast setting
- Use + or – to adjust the display contrast as desired
- To save your setting, turn the dial back to AUTO
Seasonal Adjustment
Automatic ZONE RUN TIMES can be adjusted by percentage as the seasons change Water budgeting saves valuable water as RUN TIMES can be adjusted quickly to reduce or increase water usage For this function, it is important to set the calendar correctly– see Set Current Time, Day and Date
- Turn dial to SEASONAL ADJUSTMENT–the display will appear as follows:
- This means the RUN TIMES are set to a BUDGET% of 100% [u]
- By default, the display will show the current MONTH
- For example, if ZONE No. 1 is set to 10 minutes then it will run for 10 minutes
- If the BUDGET% changes to 50%, ZONE No. 1 would now run for 5 minutes (50% of 10 minutes)
- The budget calculation is applied to all active ZONES and RUN TIMES
- Use LEFT or RIGHT to cycle through the months 1 to 12
- Use + or – to adjust the BUDGET% in 10% increments for each month
- This can be set for each month from OFF to 200%
- The permanent memory function will retain the information
- To return to the clock, turn the dial to AUTO
- If the BUDGET% [v] for your current month is not 100%, this will be shown in the AUTO clock display
Fuse
Use only 1 amp fuse M-205 If the fuse has blown, or there is none installed, the display will flash FUSE FAULT [w]
System Test
- Turn the dial to SYSTEMS TES
- The system test will begin automatically Your KRC9 will water every zone sequentially for 2 minutes each
- Press to advance to the next zone before the 2 minute period has elapsed
- It is not possible to go backwards to a previous zone
- To restart the system test from ZONE No. 1, turn the dial to OFF, and then back to SYSTEM TEST
Looping Setup
- Turn the MAIN DIAL to ZONE RUN TIMES
- Repeatedly press to access PROGRAM 5 settings
- Set the RUN TIMES as desired for each ZONE (see Set Run Times)
- After setting the RUN TIMES, press repeatedly until the display reads LOOP OFF
- Press to enable looping
- The display will read LOOP ON
- Press to proceed to looping settings, where NO LOOPS [y] (number of loops) will be flashing
- Use + or – to adjust the number of loops
- This controller has a max of 99 loops
- Press RIGHT and Hrs MIN will flash [z]
- Use + or – to toggle between Hrs MIN or MIN SECS
- Press RIGHT to advance to TIME BETWEEN LOOPS
- Use + or – to adjust the MIN or SECS between each loop
- Press RIGHT and use + or – to adjust the Hrs or MIN between each loop.
- Press RIGHT again and the display will read LOOP RUN [A] at this stage
- Use + or – to toggle between the Hrs MIN or MIN SECS [A] time settings that were previously set
- This will also change times set for PROGRAM 5 to Hrs MIN or MIN SECS
- Press RIGHT to save your loop settings and return to PROGRAM 5 controls
Running Automatic Looping
- Turn MAIN DIAL to WATERING DAYS and set desired active days for PROGRAM 5 (see Set Watering Days)
- Turn MAIN DIAL to START TIMES and set the desired times for PROGRAM 5 (see Set Start Times)
- Turn the MAIN DIAL to AUTO to complete the process A
Clearing the Programs
As this unit has a permanent memory feature, the best way to clear the PROGRAMS is as follows:
- Turn the dial to ALL OFF
- Press RIGHT twice until the display appears as follows:
- Press to clear all PROGRAMS
- All functions for setting TIME, START TIMES, WATERING DAYS and RUN TIMES will be cleared and returned to the start up settings
- PROGRAMS can also be cleared by manually setting START TIMES, WATERING DAYS and RUN TIMES individually back to their defaults
Program Rescue Feature
- To upload Program Recall Feature turn the dial to ALL OFF and press LEFT and RIGHT simultaneously–LOAD UP will appear on the screen
- Press to complete the process
- To re-install Program Recall Feature turn the dial ALL OFF and press RIGHT
- LOAD will appear on the screen
- Press to return to the original stored program
Installation
Mounting Controller
- Install the controller near a 240VAC outlet–preferably in a house, garage, or exterior electrical cubicle
- For ease of operation, eye level placement is recommended
- Ideally, your controller location should not be exposed to rain or areas prone to flooding or heavy water
- This inbuilt controller comes with an internal transformer and is suitable for outdoor or indoor installation
- The housing is designed for outdoor installation but the plug needs to be installed in a weatherproof socket or under cover
- Fasten the controller using the key hole slot positioned externally on the top centre and the additional holes positioned internally under the terminal cover
Power Supply Connections
- It is recommended that the transformer is not connected to a 240VAC supply also servicing or supplying motors (such as air conditioners, pool pumps, refrigerators)
- Lighting circuits are suitable as power sources
Electrical Hook-up
- Installation must be carried out in accordance with these instructions and all Local, State and Federal codes
- Disconnect all 240VAC power before commencing any wiring or valve connection
- Avoid connecting to a 240VAC supply also servicing motors (ie. pool pumps, refrigerators, etc.)
Field Wiring Connections
- Prepare wire for hook-up by cutting the wires to the correct length and stripping approx. 6mm of insulation from the end to be connected to the controller
- A maximum of 2 solenoid valves can be run off each output
- Ensure terminal block screws are loosened sufficiently to permit easy access for wire ends
- Insert stripped wire ends into the clamp aperture and tighten screws
- Do not over tighten as this may damage the terminal block
- A maximum of 0.75 amps may be supplied by any output
- Check the inrush current of your solenoid coils before connecting more than two valves to any one zone
Terminal Block Layout
- 24VAC—24VAC power supply connection
- COM—Common wire connection to field wiring
- SENS—Input for rain switch
- PUMP 1—Master valve or pump start output
- ST1–ST9—Zone (valve) field connections
- Use a 1 amp fuse
Master Valve Installation
- For a detailed illustration of valve installation, view page 32
- The purpose of the master valve [connected to the PUMP terminal] is to shut off the water supply to the irrigation system when there is a faulty valve or none of the zones are operating correctly
- It is used like a backup valve or fail safe device and is installed at the start of the irrigation system where it is connected to the water supply line
Rain Sensor Connection
- For a detailed illustration of rain sensor connection, view page 32
- A rain sensor detects rainfall and tells the controller to suspend watering, resuming after the sensor dries out
- This is wired between the SENSOR TERMINAL [SENS] and the COMMON [COM] as shown below
Zone Valve Installation
- Up to two 24VAC solenoid valves can be connected to each zone output and wired back to the Common [COM] connector
- With long cable lengths, voltage drop can be significant, especially when more than one coil is wired to a zone
- As a good rule of thumb select your cable as follows:
- 0–50m cable dia 0.5mm
- 50–100m cable dia 1.0mm
- 100–200m cable dia 1.5mm
- 200–400m cable dia 2.0mm
- When using multiple valves per zone, the common wire needs to be larger to carry more current. In these circumstances choose a common cable one or two sizes larger than required
- When making connections in the field, only ever use gel filled or greased filled connectors. Most field failures occur due to poor connections. The better the connection here, and the better the waterproof seal the longer the system will perform without trouble
Pump Relay Connection
- This controller does not provide mains power to drive a pump–a pump must be driven via an external relay and contactor (pump start) setup
- The controller provides a low voltage signal that actuates the relay which in turn enables the contactor and finally the pump
- Although the controller has permanent memory and thus a default program will not cause erroneous valve actuation, it is still good practice when using a system where the water supply comes from a pump to connect unused zones on the unit back to the last used zone
- This in effect, inhibits the chances of the pump ever running against a closed head
Pump Protection
- In some circumstances not all operational zones may be hooked up–for example, if the controller was capable of running 6 zones but there were only 4 field wires and solenoid valves available for connection
- This situation can pose a risk to a pump when the system test routine for the controller is initiated
- The system test routine sequences through all available zones on the controller
- In the above example this would mean zones 5 through to 6 would become active and would cause the pump to operate against a closed head
- This could possibly cause permanent pump, pipe and pressure vessel damage
- It is mandatory if the system test routine is going to be used, that all unused, spare zones, should be linked together and then looped to the last working zone with a valve on it
- Using this example, the connector block should be wired as per the diagram below
Pump Installation
It is recommended to always use a relay between the controller and the pump
starter for single phase pump installation
Troubleshooting
Symptom | Possible Cause | Suggestion |
---|
No display
| ****
Flat battery or
no mains power or
fuse blown
| Install a charged battery. If the display still doesn’t work, then check the transformer or the main power supply. If main power supply is working, check and replace the fuse if necessary
Zone not working
| ****
Faulty solenoid coil
or broken cable
| Swap faulty zone wire on controller terminal block with known working zone wire. If
the faulty valve still does not work on the known working connection then the
solenoid coil is faulty. The panel may need to be repaired or the cable may be broken
Fuse blows| Incorrect wiring or
bad wiring joint
| Check wiring and joints for a short circuit
No automatic start| Incorrect programming or blown fuse| If unit
works manually check settings. Check fuse and field wiring
System watering at random| Too many start times entered| Check
number of start times entered and when they are scheduled to water. Reset the
unit if necessary
Multiple zones running at once
| ****
Looping program active or faulty driver triac
| Check if looping program is active and in multi-zone mode. Check wiring and
swap faulty wires on terminal block with known working zones. If same outputs
are still locked on, contact Customer Service
Pump start chattering| Faulty relay or
pump contactor
| Electrician to check voltage on relay or contactor
Display cracked or missing segments| Display damaged during
transportation| ****
Contact Customer Service for support
Rain Sensor input not working
| ****
RAIN SENSOR
switch is OFF or
faulty wiring
| Ensure RAIN SENSOR switch is ON
Test all wiring and ensure Rain Sensor is a normally closed type
Check programming to ensure Rain Sensor is enabled
Electrical Specifications
Electrical Outputs
Power Supply
- Mains supply: this unit runs off a 240 volt 50 hertz single phase outlet
- The RTC uses a coin cell placed on the back of the board, to get access to the coin cell, remove the screws from the facia, unwire the terminal block and tilt the panel down and swap out the battery
- The controller draws 30 watt at 240VAC
- The internal transformer reduces the 240VAC to an extra low voltage supply of 24VAC
- The internal transformer is fully compliant with AS/NZS 61558-2-6 and has been independently tested and judged to comply
- This unit has a 1.25AMP low energy, high efficient toroidal transformer for long life performance
Electrical Power Supply
-
Input 24 volts 50/60Hz
-
Electrical Outputs
Maximum of 1.0 amp -
To Solenoid Valves
24VAC 50/60Hz 0.75 amps max -
Up to 2 valves per zone on the inbuilt model
-
To the Master Valve/ Pump Start
24VAC 0.25 amps max -
Transformer and fuse capacity must be compatible with output requirements
Overload Protection
- Standard 20mm M-205 1 amp fast blow glass fuse, protects against power surges and electronic fuse rated to 1AMP protects against field faults
- Faulty zone skip function
Wiring
Output circuits should be installed and protected in accordance with wiring
code for your location
Power Failure
- The controller has permanent memory and real time clock, so the data is always backed up even with the absence of all power
- The unit is factory fitted with a 3V CR2032 lithium battery with up to 10 years memory backup
- The 9V alkaline battery maintains the data during power outages, and is recommended to help maintain the life of the lithium battery
- Tampering with the unit will void the warranty
- The batteries do not run the outputs. The internal transformer requires mains power to run the valves
Servicing
Servicing your Controller
The controller should always be serviced by an authorised agent. Follow these steps to return your unit:
- Turn the mains power off to controller
- If controller is hard-wired, a qualified electrician is required to remove the entire unit, depending on the fault
- Proceed to either unplug and return the entire controller with transformer or disconnect the panel assembly only for servicing or repair
- Disconnect 24VAC leads at the controller 24VAC terminals on very left hand side of the terminal block
- Clearly mark or identify all valve wires according to the terminals they are connected to, (1–9)
- This allows you to easily wire them back to the controller and maintain your valve watering scheme
- Disconnect valve wires from the terminal block
- Remove the complete panel from the controller housing by unscrewing the two screws in the lower corners of the fascia (both ends of the terminal block)
- Remove the complete controller from the wall unplugging the lead
- Carefully wrap the panel or controller in protective wrapping and pack in a suitable box and return to your service agent or manufacturer
- Replace your controller panel by reversing this procedure
- Tampering with the unit will void the warranty
Warranty
5 Year Replacement Guarantee
Holman Industries offers a 5 Year replacement guarantee with this product. In Australia our goods come with guarantees that cannot be excluded under the Australian Consumer Law. You are entitled to a replacement or refund for a major failure and compensation for any other reasonably foreseeable loss or damage. You are also entitled to have the goods repaired or replaced if the goods fail to be of acceptable quality and the failure does not amount to a major failure. As well as your statutory rights referred to above and any other rights and remedies you have under any other laws relating to your Holman product, we also provide you with a Holman guarantee. Holman Industries guarantees this product against defects caused by faulty workmanship and materials for 5 Years domestic use from the date of purchase. During this guarantee period Holman Industries will replace any defective product. Packaging and instructions may not be replaced unless faulty. In the event of a product being replaced during the guarantee period, the guarantee on the replacement product will expire 5 Years from the purchase date of the original product, not 5 years from the date of replacement. To the extent permitted by law, this Holman Replacement Guarantee excludes liability for consequential loss or any other loss or damage caused to property of persons arising from any cause whatsoever. It also excludes defects caused by the product not being used in accordance with instructions, accidental damage, misuse, or being tampered with by unauthorised persons, excludes normal wear and tear and does not cover the cost of claiming under the warranty or transporting the goods to and from the place of purchase. Should you suspect your product may be defective and need some clarification or advice please contact us directly: 1300 716 188 support@holmanindustries.com.au. 11 Walters Drive, Osborne Park 6017 WA If you are certain your product is defective and is covered by the terms of this warranty, you will need to present your defective product and your purchase receipt as proof of purchase to the place you purchased it from, where the retailer will replace the product for you on our behalf.
CONTACT
- For support email
- info@k-rain.com.au. or
- contact the friendly
- Customer Service
- team at Holman
- Industries on
- 08 9416 9999
- Supplied and Serviced
- by Holman Industries
- 11 waiters Drive. Osborne Park WA 6017
We really appreciate having you as a customer and would like to say thank you
for choosing us. We recommend registering your new product on our website.
This will ensure we have a copy of your purchase and activate an extended
warranty. Keep up to date to with relevant product information and special
offers available through our new sletter.
Scan here, or visit
k-rain.com.au/register. for more info
WWW.K-RAW.COM.AU. An other content K.Rain Austraia
2022
References
- Product Registration and Extended Warranty - K-Rain Australia
- Rain - Maintaining Web Applications Efficiently - Jason Hendry
- K-Rain Australia - The Landscaper's Choice
- Contact Us - K-Rain
- Product Registration and Extended Warranty - K-Rain Australia
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>