TRIPP LITE SU10KMBPKX UPS Maintenance Bypass Panel User Manual
- June 13, 2024
- Tripp Lite
Table of Contents
- TRIPP LITE SU10KMBPKX UPS Maintenance Bypass Panel
- Product Information
- Product Usage Instructions
- Introduction
- Important Information About This Manual
- Safety Precautions
- Inspection Upon Receipt of Goods
- System Overview
- System Specifications
- Installation
- System Operation: Configuration 13 Interlocks
- Maintenance
- Reference Materials
- 14 – 1/0
- Warranty
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
TRIPP LITE SU10KMBPKX UPS Maintenance Bypass Panel
Product Information
Product Name | Models |
---|---|
Maintenance Bypass Panel | SU10KMBPKX, SU20KMBPKX |
Product Usage Instructions
Introduction
This manual contains important information that is needed during the
installation and maintenance of the system.
Important Information About This Manual
SAVE THESE INSTRUCTIONS! This manual contains important information that is
needed during the installation and maintenance of the system.
Manual Symbols
- Warning: Indicates information provided to protect the user against personal injury, safety hazards, and/or possible equipment damage.
- Electrical Hazard: Indicates that an electrical hazard exists that will result in personal injury or death if instructions are not followed.
- Important: Indicates information provided as an installation or operating instruction or tip, as well as general important installation and system information.
Safety Precautions
Any modifications to the equipment without authorization by Tripp Lite
could result in equipment damage, personal injury, or death. Never work on
power equipment while it is energized. De-energize equipment and lock off all
power to the equipment before working inside. Inspection and maintenance
should only be performed on equipment that has been de-energized and
electrically isolated so that no accidental contact can be made with energized
parts.
Inspection Upon Receipt of Goods
General
Special precautions and care have been taken to ensure the system arrives
safe and undamaged. However, upon receipt, you should inspect the entire
shipment, including the crate and any boxes, for evidence of damage that may
have occurred during transit.
Visible Damage
It is the responsibility of the person receiving the shipment to inventory
and fully inspect all materials against the bill of lading or waybill
IMMEDIATELY, while the carrier representative is still present. Ensure that
all items are accounted for, including the number of skids and the quantity of
boxes. Also, note any visible external damage that may have occurred during
transit. Make all applicable notations on the delivery receipt before signing
and filing a damage report with the carrier.
Concealed Damage
If there is concealed damage to the equipment, please follow the
instructions provided by Tripp Lite for returning the damaged goods.
Return of Damaged Goods
If the equipment is damaged and requires a return to Tripp Lite for repair,
a representative will provide instructions and an RMA number to expedite the
return. An RMA number must be obtained before returning the equipment to Tripp
Lite.
Introduction
Tripp Lite would like to thank you for choosing our product for your equipment needs. We know there are a lot of choices and we appreciate the opportunity to supply each of our customers with the highest-quality power products manufactured in the United States today. All of our solutions are factory- tested to the highest standards. Sales support for future equipment needs or upgrades is provided by our regional sales staff and qualified representatives. All technical questions and service issues should be directed to our main office by visiting www.tripplite.com/support.
Tripp Lite
www.tripplite.com
Technical Support
www.tripplite.com/support
Important Information About This Manual
SAVE THESE INSTRUCTIONS!
This manual contains important information that is needed during the
installation and maintenance of the system.
Manual Symbols
-
Warning:
Indicates information provided to protect the user against personal injury, safety hazards and/or possible equipment damage. -
Electrical Hazard:
Indicates that an electrical hazard exists that will result in personal injury or death if instructions are not followed. -
Important:
Indicates information provided as an installation or operating instruction or tip, as well as general important installation and system information.
Safety Precautions
- Before installing or maintaining this equipment, it is extremely important to read this manual and be sure that all equipment drawings and schematics are reviewed and clearly understood. If there are any questions concerning this manual or any of the installation or maintenance procedures and/or requirements, please contact a Tripp Lite representative before proceeding.
- Information in this manual is not intended for use as a training manual for nonqualified personnel.
- When installing this equipment, always follow all applicable federal, state and local regulations to ensure safe and proper equipment installation.
- Only qualified persons should attempt to install or service this equipment. A qualified person is one who has skills and knowledge related to the construction and operation of electrical equipment and installations and has received safety training on the hazards involved.
- Equipment installation and maintenance should always be performed with heavily insulated tools. It is also recommended to wear rubber gloves and boots and to use insulating mats to stand on when working on this equipment.
- Always wear eye protection when installing or maintaining power equipment.
- To avoid personal injury, including electrical shock, severe burns and possible death, all jewelry, including bracelets, rings and watches, must be removed prior to installing or servicing this equipment.
- For the safety of others, never leave an open cabinet or panel unattended.
- Any modifications to the equipment without authorization by Tripp Lite could result in equipment damage, personal injury or death.
- Never work on power equipment while it is energized. De-energize equipment and lock off all power to the equipment before working inside.
- Inspection and maintenance should only be performed on equipment that has been de-energized and electrically isolated, so that no accidental contact can be made with energized parts.
Inspection Upon Receipt of Goods
General
- Special precautions and care have been taken to ensure the system arrives safe and undamaged. However, upon receipt, you should inspect the entire shipment, including the crate and any boxes, for evidence of damage that may have occurred during transit.
Visible Damage
- It is the responsibility of the person receiving the shipment to inventory and fully inspect all materials against the bill of lading or waybill IMMEDIATELY, while the carrier representative is still present. Ensure that all items are accounted for, including the number of skids and quantity of boxes. Also, note any visible external damage that may have occurred during transit. Make all applicable notations on the delivery receipt before signing and file a damage report with the carrier.
Concealed Damage
- Within 3 to 30 days of receipt (depending on courier), unpack the system and check for any concealed damage. Check the materials received against the detailed packing list to verify the quantity and the condition as complete and satisfactory.
- Note any damage to the internal packaging. Then, request an inspection by the carrier and file a concealed damage claim. If there is a material shortage, visit www.tripplite.com/support to file a claim.
- Please contact your shipping company for all shipping damage. Tripp Lite is not responsible for any shipping damage.
Return of Damaged Goods
- Should equipment be damaged and require a return to Tripp Lite for repair, a representative will provide instructions and an RMA number to expedite the return.
An RMA number must be obtained before returning equipment to Tripp Lite.
System Overview
- The Tripp Lite SU10KMBPKX or SU20KMBPKX Maintenance Bypass Panel (MBP) is used in conjunction with an Uninterruptible Power Supply (UPS) to maintain total continuity of power to connected load circuits when bypass of the UPS equipment is required for performance of regular service and maintenance.
- The SU10KMBPKX and SU20KMBPKX Series MBPs are available with current capacities ranging from 15 to 225 amperes with multiple input voltage options available.
- The MBP contains two or three Cutler Hammer Series C circuit breakers that are protected by a Kirk Key interlock system.
System Specifications
Always refer to the Ratings Label on the equipment for configuration-specific ratings. Equipment specifications and ratings in this document represent typical equipment and may vary from the equipment provided.
Electrical
- Voltage : 400Y/230VAC, 3-Phase, 4-Wire, plus ground
- Frequency : 60 Hz
- Current: Models available from 40A to 70A
- Short Circuit Rating: up to 10kAIC
- Neutral Bus Current Rating : 450A
Environmental
- Operating Temperature: 32°F to 104°F (0°C to 40°C)
- Relative Humidity: 5% to 95% non-condensing
- Altitude : 0 to 7400 ft. (0 to 2255 m) above sea level
General
- Cabinet Size, H x W x D: 24 x 22 x 9 in. (610 x 559 x 229 mm)
- Weight : 55 lb. (25 kg)
Installation
Preparation
Equipment Inspection
Remove the equipment from the packaging material and inspect for any shipping
damage that may have been overlooked upon receipt of goods. Verify that the
system includes all necessary hardware for installation.
Necessary Equipment and Tools
- Properly insulated tools
- Properly sized and rated mounting hardware
Installation Safety Precautions
- Before proceeding with system installation, be sure to review and understand all of the SAFETY PRECAUTIONS in Section 3 of this manual!
- AC VOLTAGE WARNING
The input/output voltage in this equipment can be up to 480 VAC. Be sure to fully read and understand this manual and verify that all AC connections are correct and properly torqued. Use extreme caution when installing and maintaining the system!
Storage
If the equipment cannot be immediately installed, it should be stored in a
clean and dry indoor location with adequate air circulation and uniform
temperature to prevent condensation. If the equipment must be stored for any
length of time, it should be covered to protect it from dust, debris and
moisture.
Installation Steps
Before installing or maintaining this system, it is extremely important to
read this manual and be sure that all system drawings and schematics are
reviewed and clearly understood. If there are any questions concerning this
manual or any of the installation or maintenance procedures and/or
requirements, please contact a Tripp Lite representative before proceeding.
Equipment Location
- This equipment is intended to be installed in a restricted access location.
- The permanent location of the equipment must be on a smooth and solid wall surface. Do not locate the equipment against a non-fireproof ceiling. Allow a space of 3 feet between the ceiling and the equipment unless an adequate fireproof shield is provided. Also, verify that the selected location will provide working clearances in compliance with Article 110.26 of the National Electrical Code (NEC). The environmental conditions of the selected location should also be reviewed. Refer to section 6.2 Environmental for environmental specifications.
Equipment Mounting
The equipment should be reliably secured to the mounting surface. Do not
depend on wooden plugs driven into holes in masonry, concrete, plaster or
similar materials in accordance with Article 110.13 of the National Electrical
Code (NEC). Secure the equipment utilizing the four 0.375-inch diameter
mounting holes located in the back of the equipment. A set of equipment
drawings for the specific configuration of the equipment is included inside
the equipment. Reference the equipment drawings or mounting hole size and
locations. (See drawings in the Reference Materials section.)
Equipment Connections
- Never work on power equipment while it is energized. De-energize equipment and lock off all power to the equipment before working inside.
The top and bottom panels of the equipment are the recommended designated areas for landing conduits to the equipment. All conduits must be located to avoid interference with structural members and live bus. A set of drawings for the specific configuration of the equipment is included inside the equipment. Reference the equipment drawings in Section 10 Reference Materials.
- All conductors are to be sized for 167°F (75°C) ampacity. When cable is used with temperature ratings above 167°F/75°C, it shall be sized based on the ampacity of cable rated 167°F (75°C).
- The equipment must be grounded with an appropriately sized conductor in compliance with Article 250 of the National Electrical Code (NEC). The ground conductor should be terminated to the main ground bus bar inside the equipment.
Remove the equipment covers as needed to access the input and output connection points. Where cables enter or exit the equipment or pass through any metal which has magnetic properties, they shall be arranged so all phase and neutral conductors are grouped together and pass through the same opening in compliance with Article 300.20 of the National Electrical Code (NEC). When pulling cable into the equipment, take care not to damage any of the internal components and control wiring. Position the cables inside of the equipment so they are not subject to physical damage and are not forced permanently against the edges of any metal parts. If any cables are in contact with sharp edges, place suitable protective material between the cable and the metal edge to protect the cable insulation. Using the appropriate tools, strip a length of insulation from the end of the cable sufficient to fit into the full length of the mechanical lug for the designated connection point. If using aluminum conductors, apply an appropriate antioxidant compound to the bare aluminum. Insert the bare conductor into the lug so the bare conductor fills the full length of the mechanical lug body. Tighten the set screw on the mechanical lug and torque to the values indicated on the Torque Values Label located on the equipment. Reference the Equipment Schematic Drawing for information on the required connections between the Maintenance Bypass Panel, the UPS and the critical load.
Pre-Energizing Inspection
Inspection and maintenance should only be performed on equipment that has been de-energized and electrically isolated so that no accidental contact can be made with energized parts.
The top and bottom panels of the equipment are the recommended designated
areas for landing conduits to the equipment. All conduits must be located to
avoid interference with structural members and live bus. A set of drawings for
the specific configuration of the equipment is included inside the equipment.
Reference the equipment drawings in Section 10 Reference Materials.
Before energizing the equipment, it must be thoroughly inspected.
- Remove any foreign materials from inside of the equipment including tools, scraps of wire or other debris.
- Visually inspect the equipment for any damage that may have occurred during the installation process. Be sure to inspect all insulators, busbars and other conductors. Do not energize if any damage is found!
- Verify cable phase orientation at all connection points.
- Verify all field cable connections are properly torqued.
- Manually operate all circuit breakers to verify proper operation.
- Verify the circuit breaker trip unit adjustments are set per the end-user requirements.
- Verify equipment ground connections are properly terminated.
- Review the Kirk Key interlock operating sequence and confirm the Kirk Key interlocks are performing properly.
- Verify all covers are installed.
Energizing
- Hazardous voltages in electrical equipment can cause severe injury or death!
- Only qualified persons should attempt to install or service this equipment. A qualified person is one who has skills and knowledge related to the construction and operation of electrical equipment and installations and has received safety training on the hazards involved.
- Ensure maximum continuous loads do not exceed 80% of the overcurrent protective device (circuit breakers and fuses) ratings employed in other than motor circuits, except for those circuits employing circuit breakers marked as suitable for continuous operation at 100% of their ratings.
Extreme hazards can exist when energizing electrical equipment. Take all precautions necessary to protect people and property when energizing this equipment. Before energizing the equipment, open/turn off all circuit breakers and verify the Kirk Key interlocks are in the correct state to allow for proper startup. Refer to the UPS manual for proper startup procedures.
System Operation: Configuration 13 Interlocks
The following user instructions are for a two- or three-circuit breaker MBP configured to be controlled by a 1-interlock, 1-key breaker interlock system.
Do not operate the “SW2” circuit breaker unless the UPS is in BYPASS mode! Failure to follow the operating instructions for this equipment could result in equipment damage, fire, severe injury or death!
Normal Operation (Online Mode)
The “SW1” UPS AC Input Breaker is closed/on. The Maintenance Bypass Breaker
“SW2” breaker is open/off with the interlock locking bolt in the withdrawn
position. The Maintenance Isolation Breaker “SW3” is locked closed/on with the
interlock locking bolt in the extended position. Key A1 is free.
Transfer to Maintenance Bypass
- Transfer the UPS to the Bypass mode before proceeding.
- Insert Key A1 into lock.
- Close/turn on the “SW2” breaker.
- Turn Key A1 to lock the “SW2” breaker in the closed/on position. Key A1 is now free.
- Open/turn off the “SW3” breaker.
- The UPS is now ready for routine maintenance.
- If further maintenance requires a total shutdown of the UPS and isolation from the input, the “SW1” breaker must be opened/turned off and the battery supply to the UPS must be disconnected. Refer to your UPS manual for proper shutdown procedures.
Return the UPS and Bypass Switch to Normal Operation
- If the “SW1” breaker was opened/turned off for maintenance, then follow the UPS manual for proper startup procedures. To restore input power to the UPS, close/turn on the “SW1” breaker. Make sure the UPS is in Bypass mode before proceeding!
- Close/turn on the “SW3” breaker.
- Turn Key A1 to lock the “SW3” breaker in the closed/on position. Key A1 is now free.
- Open/turn off the SW2 breaker.
- Transfer the UPS from Bypass mode to Normal Operation (Online Mode).
Maintenance
- Before installing or maintaining this equipment, it is extremely important to read this manual and be sure that all equipment drawings and schematics are reviewed and clearly understood. If there are any questions concerning this manual or any of the installation or maintenance procedures and/or requirements, please contact a Tripp Lite representative before proceeding.
- Inspection and maintenance should only be performed on equipment that has been de-energized and electrically isolated so that no accidental contact can be made with energized parts.
Short Circuits and Overloads
- Do not attempt to re-energize a circuit breaker after a short circuit or overload until the cause of the event has been identified and corrected. Failure to correct the cause of the event may result in equipment damage, fire, severe injury or death.
Circuit breakers will normally prevent electrical damage except at the point where the short circuit occurred. High mechanical stress developed by short circuit currents may cause damage to conductors, insulation or other components. After a fault, a thorough inspection of the entire system must be made to verify that there is no damage. Circuit breakers that performed the short circuit interruption must be inspected for possible damage. Do not disassemble the breaker or open the breaker trip unit. Replace all damaged insulation materials, conductors and circuit breakers. It is recommended that the equipment be hipot tested prior to being placed back in service.
Reference Materials
CIRCUIT BREAKER SUMMARY
MODEL| BREAKER TYPE| BREAKER MODEL| TRIP|
AIC| WIRE RANGE
SU10KMBPKX| CUTLER HAMMER SERIES C| EHD3040| 40A| 14K @ 480VAC| (1) 14 – 1/0
SU20KMBPKX| EHD3070| 70A
WIRE RANGE & TORQUE VALUE SUMMARY
MECHANICAL LUG CONNECTIONS| WIRE RANGE| TORQUE VALUE
INPUT & OUTPUT
|
14 – 1/0
| (#10 – #14 AWG) 35 IN-LB. (3.9 Nm)
(#8 AWG) 40 IN-LB. (4.5 Nm)
(#4 – #6 AWG) 45 IN-LB. (5.1 Nm)
(#3 – 1/0 AWG) 50 IN-LB. (5.7 Nm)
NEUTRAL| #6 – 350 MCM| 375 IN-LB. (42.4 Nm)
GROUND| #6 – 350 MCM| 375 IN-LB. (42.4 Nm)
Notes:
- APPROXIMATE WEIGHT: 77 LB.
- NEMA 1 WALL-MOUNT ENCLOSURE.
- THE BOX AND TRIM ARE CONSTRUCTED OF GALVANIZED STEEL.
- THE TRIM FINISH IS POWDER-COATED ON ALL EXTERNAL AND VISIBLE SURFACES. BOX AND ALL INTERNAL-MOUNT BRACKETS ARE GALVANIZED FINISH.
- THE PANEL IS PROVIDED WITH A KEY-LOCKING PUSH-TO-CLOSE LATCH ON THE ACCESS COVER.
- THE PANEL IS TO BE MOUNTED THROUGH THE Ø0.375” HOLES IN THE BACK OF THE ENCLOSURE.
Notes:
- “SW1” UPS INPUT BREAKER.
- “SW2” MAINTENANCE BYPASS BREAKER.
- “SW3” MAINTENANCE ISOLATION BREAKER.
- 450A-RATED NEUTRAL BUS PROVIDED WITH MECHANICAL LUGS THAT ACCEPT A TOTAL OF (4) #6 – 350MCM CABLES.
- GROUND LUG ACCEPTS (3) #6 – 350MCM CABLES.
- MECHANICAL LUGS USED FOR THE UTILITY INPUT AND THE OUTPUT TO LOAD HAVE THE SAME WIRE RANGE AS THE CIRCUIT BREAKERS.
- THIS DRAWING IS TO BE USED FOR ELECTRICAL PURPOSES ONLY AND DOES NOT REPRESENT THE ACTUAL MECHANICAL LAYOUT OF THE EQUIPMENT.
Warranty
LIMITED WARRANTY AND EXCLUSIONS
Tripp Lite strives to produce quality products at reasonable prices. If you
are not satisfied with our product because of a defect, we will repair or
replace the defective part or parts free of charge for a period of one year
from the date of purchase. In the event you claim that the product contains a
defect, simply notify Tripp Lite of the defect, and we will arrange for repair
or replacement. The sole and exclusive remedy against Tripp Lite relating in
any way to a product defect shall be the repair or replacement of defective
parts as provided for under this LIMITED WARRANTY. No other remedy, including,
but not limited to, incidental or consequential damages for lost profits, lost
sales, injury to person or property, or any other incidental or consequential
loss, is available. This LIMITED WARRANTY shall not be deemed to have failed
of its essential purpose so long as Tripp Lite is willing and able to repair
or replace defective parts in the manner prescribed in this LIMITED WARRANTY.
Certain integrated products, that are not manufactured by Tripp Lite, will be
warranted by the applicable manufacturer. These warranties shall be between
the manufacturer and the user. Terms and conditions may vary. These integrated
products include, but may not be limited to, the following products:
Batteries, Inverters, and UPS Systems.
Use of this equipment in life support applications where the failure of this equipment can reasonably be expected to cause the failure of the life support equipment or to significantly affect its safety or effectiveness is not recommended. Any action for a breach relating to the sale of a Tripp Lite product must be commenced within one year after the cause of action has been accrued. THIS LIMITED WARRANTY IS IN LIEU OF ANY OTHER WARRANTY, EXPRESS OR IMPLIED, AND ALL SUCH WARRANTIES ARE EXCLUDED, INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Tripp Lite has a policy of continuous improvement. Specifications are subject to change without notice. Photos and illustrations may differ slightly from actual products.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>