FUJITSU FOP1418SJAZNA1 iM Heat Pumps User Manual

June 13, 2024
FUJITSU

FUJITSU FOP1418SJAZNA1 iM Heat Pumps

Product Information

The iM Heat Pumps FOP14 is a series of heat pumps manufacturedby Fujitsu General America, Inc. It offers cooling efficiencies up to 14.3 SEER2/10.4 EER2 and heating efficiency of 7.6 HSPF. The nominal sizes range from 1.5 to 5 tons [5.3 to 17.6 kW], with cooling and heating capacities ranging from 17.1 kBTU to 55.5 kBTU.

Model Number Identification

The model number is composed of various codes that indicate different specifications of the heat pumps:

  • Brand: F – Fujitsu
  • Product Category: O – Outdoor Unit
  • Type : P – HP 14.3 SEER2
  • Capacity: 18, 24, 30, 36, 42, 48, or 60 (in thousands ofBTU/hr)
  • Type: S – Single Stage, T – Two Stage
  • Region: J – 1ph, 208-230/60
  • Refrigerant : A – All, Z – R-410A
  • Controls : N – Non-Communicating
  • Major Series: A – 1st Design
  • Minor Series: 1 – 1st Design

Available Models

  • FOP1418SJAZNA1 – 1.5 ton 14.3 SEER2 1-Stage iM Heat
    Pump-208/230/1/60

  • FOP1418TJAZNA1 – 1.5 ton 14.3 SEER2 2-Stage iM Heat
    Pump-208/230/1/60

  • FOP1424TJAZNA1 – 2 ton 14.3 SEER2 2-Stage iM Heat
    Pump-208/230/1/60

  • FOP1430TJAZNA1 – 2.5 ton 14.3 SEER2 2-Stage iM Heat
    Pump-208/230/1/60

  • FOP1436TJAZNA1 – 3 ton 14.3 SEER2 2-Stage iM Heat
    Pump-208/230/1/60

  • FOP1442TJAZNA1 – 3.5 ton 14.3 SEER2 2-Stage iM Heat
    Pump-208/230/1/60

  • FOP1448TJAZNA1 – 4 ton 14.3 SEER2 2-Stage iM Heat
    Pump-208/230/1/60

  • FOP1460TJAZNA1 – 5 ton 14.3 SEER2 2-Stage iM Heat
    Pump-208/230/1/60

Features and Benefits

  • Swept Wing Fan Technology1: Features quieter operation and improved unit acoustics

  • Two-Stage Scroll Compressor2: Features two speeds
    (high and low) of cooling and heating, providing more precise temperature control, lower humidity and greater efficiency when compared to single stage compressors

  • Inverted Reversing Valve: Allows for faster heat transfer with gravity assist shifting and reduced joint stress for increased reliability

  • Expanded Valve Space: 3 in. – 4 in. – 5 in. service valve space—provides a minimum working area of 27-square inches for easier access

  • Triple Service Access: 15 in. wide, industry leading corner service access, two fastener, removeable corner and individual louver panels—makes repairs easier and faster

Heat Pumps

Designates Metric Conversions

AVAILABLE MODELS DESCRIPTION
FOP1418SJAZNA1 1 1/2 ton 14.3 SEER2 1-Stage iM Heat Pump-208/230/1/60
FOP1418TJAZNA1 1 1/2 ton 14.3 SEER2 2-Stage iM Heat Pump-208/230/1/60
FOP1424TJAZNA1 2 ton 14.3 SEER2 2-Stage Heat iM Pump-208/230/1/60
FOP1430TJAZNA1 2 1/2 ton 14.3 SEER2 2-Stage iM Heat Pump-208/230/1/60
FOP1436TJAZNA1 3 ton 14.3 SEER2 2-Stage iM Heat Pump-208/230/1/60
FOP1442TJAZNA1 3 1/2 ton 14.3 SEER2 2-Stage iM Heat Pump-208/230/1/60
FOP1448TJAZNA1 4 ton 14.3 SEER2 2-Stage iM Heat Pump-208/230/1/60
FOP1460TJAZNA1 5 ton 14.3 SEER2 2-Stage iM Heat Pump-208/230/1/60

STANDARD EQUIPMENT

R-410A Refrigerant
Scroll Compressor
Field Installed Filter Drier
Front Seating Service Valves
Internal Pressure Relief Valve
Internal Thermal Overload
Long Line capability
Low Ambient capability with Kit
3-4-5 Expanded Valve Space
Composite Basepan
2 Screw Control Box Access
15″ Access to Internal Components
Quick release louver panel design
No fasteners to remove along bottom
Optimized Venturi Airflow
Single row condenser coil
Powder coated paint
Rust resistant screws
QR code
External gauge ports
Service trays
External gauge ports
Service trays

General Data

GENERAL DATA

MODEL NO.| FOP1418S| FOP1418T| FOP1424T| FOP1430T| FOP1436T| FOP1442T| FOP1448T| FOP1460T
Nominal Tonnage| 1.5| 1.5| 2.0| 2.5| 3.0| 3.5| 4.0| 5.0
Valve Connections|
Liquid Line O.D. – in.| 3/8| 3/8| 3/8| 3/8| 3/8| 3/8| 3/8| 3/8
Suction Line O.D. – in.| 3/4| 3/4| 3/4| 3/4| 3/4| 7/8| 7/8| 7/8
Refrigerant (R410A) furnished oz.¹| 84| 88| 88| 108| 118| 148| 148| 247
Compressor Type| Scroll
Outdoor Coil|
Net face area – Outer Coil| 10.9| 10.9| 10.9| 14.4| 19.5| 19.5| 19.5| 28.4
Net face area – Inner Coil|
Tube diameter – in.| 0.276| 0.276| 0.276| 0.276| 0.276| 0.276| 0.276| 0.375
Number of rows| 1| 1| 1| 1| 1| 1| 1| 1
Fins per inch| 22| 22| 22| 22| 22| 22| 24| 20
Outdoor Fan|
Diameter – in.| 20| 20| 20| 24| 24| 24| 24| 26
Number of blades| 3| 3| 3| 3| 3| 3| 3| 3
Motor hp| 1/7| 1/7| 1/6| 1/5| 1/5| 1/5| 1/5| 1/5
CFM| 2401| 2401| 2620| 3391| 4077| 4077| 4096| 4686
RPM| 1075| 1075| 1075| 850| 850| 850| 850| 850
Watts| 146| 141| 145| 175| 234| 222| 236| 239
Shipping weight lbs.| 157| 157| 158| 196| 209| 239| 245| 285
Operating weight lbs.| 150| 150| 151| 189| 202| 232| 238| 278

Electrical Data

Line Voltage Data (Volts-Phase-Hz)| 208/230-1-60| 208/230-1-60| 208/230-1-60| 208/230-1-60| 208/230-1-60| 208/230-1-60| 208/230-1-60| 208/230-1-60
---|---|---|---|---|---|---|---|---
Maximum overcurrent protection (amps)²| 20| 15| 20| 25| 25| 35| 35| 40
Minimum circuit ampacity³| 11| 11| 15| 18| 21| 26| 29| 31
Compressor|
Rated load amps| 10| 8| 11| 13| 15| 20| 22| 24
Locked rotor amps| 46| 56| 66| 71| 78| 151| 0| 118
Condenser Fan Motor|
Full load amps| 0.75| 0.75| 0.75| 1.0| 1.0| 1.0| 1.0| 1.0
Locked rotor amps| 1.4| 1.4| 1.5| 2.6| 2.56| 2.56| 2.56| 2.6

  1. Refrigerant charge sufficient for 15 ft. length of refrigerant lines. For longer line set requirements see the installation instructions for information about set length and additional refrigerant charge required.
  2. HACR type circuit breaker of fuse.
  3. Refer to National Electrical Code manual to determine wire, fuse and disconnect size requirements.

Accessories

MODEL NO.| FOP1418S| FOP1418T| FOP1424T| FOP1430T| FOP1436T| FOP1442T| FOP1448T| FOP1460T
---|---|---|---|---|---|---|---|---
Compressor crankcase heater*| 44-17402-44| 44-17402-44| 44-17402-44| 44-17402-44| 44-17402-44| 44-17402-45| 44-17402-45| Factory Standard
Low ambient control| RXAD-A08| RXAD-A08| RXAD-A08| RXAD-A08| RXAD-A08| RXAD-A08| RXAD-A08| RXAD-A08
Compressor sound cover| 68-23427-26| 68-23427-26| 68-23427-26| 68-23427-26| 68-23427-26| 68-23427-25| 68-23427-25| 68-23427-25
Compressor hard start kit| SK-A1| SK-A1| SK-A1| SK-A1| SK-A1| SK-A1| SK-A1| SK-A1
Low pressure control| Factory Standard| Factory Standard| Factory Standard| Factory Standard| Factory Standard| Factory Standard| Factory Standard| Factory Standard
High pressure control| Factory Standard| Factory Standard| Factory Standard| Factory Standard| Factory Standard| Factory Standard| Factory Standard| Factory Standard
Liquid Line Solenoid (24 VAC, 50/60 Hz)| Solenoid Valve| 200RD2T3TVLC| 200RD2T3TVLC| 200RD2T3TVLC| 200RD2T3TVLC| 200RD2T3TVLC| 200RD2T3TVLC| 200RD3T3TVLC| 200RD3T3TVLC
Solenoid Coil| 61-AMG24V| 61-AMG24V| 61-AMG24V| 61-AMG24V| 61-AMG24V| 61-AMG24V| 61-AMG24V| 61-AMG24V
Liquid Line Solenoid (120/240 VAC, 50/60 Hz)| Solenoid Valve| 200RD2T3TVLC| 200RD2T3TVLC| 200RD2T3TVLC| 200RD2T3TVLC| 200RD2T3TVLC| 200RD2T3TVLC| 200RD3T3TVLC| 200RD3T3TVLC
Solenoid Coil| 61-AMG120/240V| 61-AMG120/240V| 61-AMG120/240V| 61-AMG120/240V| 61-AMG120/240V| 61-AMG120/240V| 61-AMG120/240V| 61-AMG120/240V
Classic Top Cap w/Label| 91-101123-21| 91-101123-21| 91-101123-21| 91-101123-21| 91-101123-21| 91-101123-21| 91-101123-21| 91-101123-21

Bi-flow kits are required when installing a liquid line solenoid on a heat pump.

Weighted Sound Power Level (dBA)

UNIT SIZE – VOLTAGE, SERIES| STANDARD RATING (DBA)| TYPICAL OCTAVE BAND SPECTRUM (dBA without tone adjustment)
---|---|---
125| 250| 500| 1000| 2000| 4000| 8000
FOP1418| 73| 39.8| 55| 62.1| 67.0| 60.0| 57.4| 51.2
FOP1424| 73| 40.4| 55.4| 62.5| 65.9| 58.7| 56.4| 48.9
FOP1430| 72| 48.9| 55.3| 63.6| 61.0| 59.1| 56.5| 48.7
FOP1436| 72| 50.1| 55.8| 64.4| 61.5| 58.7| 55.1| 50.9
FOP1442| 72| 48.6| 56.2| 63.1| 61.7| 60.0| 56| 50.0
FOP1448| 74| 49.3| 56| 64.5| 64.5| 60.1| 54.9| 47.7
FOP1460| 74| 43.9| 55.2| 63.4| 65.8| 61.7| 57.9| 52.9

NOTE: Tested in accordance dard 270-08 (not listed in AHRI)

Unit Dimensions


MODEL NO.

| OPERATING| SHIPPING
---|---|---
H (Height)| L (Length)| W (Width)| H (Height)| L (Length)| W (Width)
INCHES| mm| INCHES| mm| INCHES| mm| INCHES| mm| INCHES| mm| INCHES| mm
FOP1418S| 25.00| 635| 29.75| 756| 29.75| 756| 27.90| 709| 33.25| 845| 33.25| 845
FOP1418T| 25.00| 635| 29.75| 756| 29.75| 756| 27.90| 709| 33.25| 845| 33.25| 845
FOP1424T| 25.00| 635| 29.75| 756| 29.75| 756| 27.90| 709| 33.25| 845| 33.25| 845
FOP1430T| 27.00| 686| 33.75| 857| 33.75| 857| 30.08| 764| 37.64| 956| 37.64| 956
FOP1436T| 35.00| 889| 33.75| 857| 33.75| 857| 38.35| 974| 37.64| 956| 37.64| 956
FOP1442T| 35.00| 889| 33.75| 857| 33.75| 857| 38.35| 974| 37.64| 956| 37.64| 956
FOP1448T| 35.00| 889| 33.75| 857| 33.75| 857| 38.35| 974| 37.64| 956| 37.64| 956
FOP1460T| 45.00| 1143| 35.75| 908| 35.75| 908| 48.50| 1232| 39.37| 1000| 39.37| 1000

Designates Metric Conversions

CLEARANCES

NOTE: NUMBERS IN () = mm
IMPORTANT : When installing multiple units in an alcove, roof well or partially enclosed area, ensure there is adequate ventillation to prevent re- circulation of discharge air.

Control Wiring

Application Guidelines

  1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01-in. wc.
  2. Minimum outdoor operation air temperature for cooling mode without low-ambient operation accessory is 55°F (12.8°C).
  3. Maximum outdoor operating air temperature is 125°F (51.7°C).
  4. For reliable operation, unit should be level in all horizontal planes.
  5. Use only copper wire for electric connections at unit. Aluminum and clad aluminum are not acceptable for the type of connector provided.
  6. Do not apply capillary tube indoor coils to these units.
  7. Factory-supplied filter drier must be installed

Refrigerant Line Size Information

14.3 SEER2 HEAT PUMPS


UNIT SIZE

| ALLOWABLE LIQUID LINE SIZE| ALLOWABLE SUCTION LINE SIZE| EQUIVALENT LENGTH (FEET)
< 15| 16- 25| 26- 50| 51- 75| 76- 100| 101- 125| 126- 150
MAXIMUM VERTICAL RISE (OUTDOOR UNIT BELOW INDOOR UNIT) *** / CAPACITY MULTIPLIERER**


1.5 Ton Single Stage

| 1/4″| 5/8″| 15 / 1.00| 25 / 1.00| 50 / 0.99| 60 / 0.97| 45 / 0.96| 10 / 0.95| N/A
5/16″| 5/8″| 15 / 1.00| 25 / 1.00| 50 / 0.99| 75 / 0.97| 90 / 0.96| 45 / 0.95| N/A
3/8″| 5/8″| 15 / 1.00| 25 / 1.00| 50 / 0.99| 75 / 0.97| 95 / 0.96| 80 / 0.95| N/A




1.5 Ton Two Stage

| 1/4″| 1/2″| 15 / 0.99| 25 / 0.99| 50 / 0.97| 50 / 0.96| 50 / 0.95| N/A| N/A
5/16″| 1/2″| 15 / 0.99| 25 / 0.99| 50 / 0.97| 50 / 0.96| 50 / 0.95| N/A| N/A
3/8″| 1/2″| 15 / 0.99| 25 / 0.99| 50 / 0.97| 50 / 0.96| 50 / 0.95| N/A| N/A
1/4″| 5/8″| 15 / 0.99| 25 / 0.99| 50 / 0.98| 50 / 0.97| 50 / 0.96| 50 / 0.95| 50 / 0.94
5/16″| 5/8″| 15 / 0.99| 25 / 0.99| 50 / 0.98| 50 / 0.97| 50 / 0.96| 50 / 0.95| 50 / 0.94
3/8″| 5/8″| 15 / 0.99| 25 / 0.99| 50 / 0.98| 50 / 0.97| 50 / 0.96| 50 / 0.95| 50 / 0.94


2 Ton Two Stage

| 1/4″| 5/8″| 15 / 0.99| 25 / 0.99| 50 / 0.99| 31 / 0.97| 3 / 0.97| N/A| N/A
5/16″| 5/8″| 15 / 0.99| 25 / 0.99| 50 / 0.99| 50 / 0.97| 50 / 0.97| 50 / 0.96| 50 / 0.95
3/8″| 5/8″| 15 / 0.99| 25 / 0.99| 50 / 0.99| 50 / 0.97| 50 / 0.97| 50 / 0.96| 50 / 0.95




2.5 Ton Two Stage

| 1/4″| 5/8″| 15 / 0.99| 25 / 0.99| 50 / 0.97| 50 / 0.96| 46 / 0.95| 50 / 0.94| N/A
5/16″| 5/8″| 15 / 0.99| 25 / 0.99| 50 / 0.97| 50 / 0.96| 50 / 0.95| 50 / 0.94| N/A
3/8″| 5/8″| 15 / 0.99| 25 / 0.99| 50 / 0.97| 50 / 0.96| 50 / 0.95| 50 / 0.94| N/A
1/4″| 3/4″| 15 / 1.00| 25 / 0.99| 50 / 0.98| 50 / 0.98| 50 / 0.98| 50 / 0.96| 50 / 0.95
5/16″| 3/4″| 15 / 1.00| 25 / 0.99| 50 / 0.98| 50 / 0.98| 50 / 0.98| 50 / 0.96| 50 / 0.95
3/8″| 3/4″| 15 / 1.00| 25 / 0.99| 50 / 0.98| 50 / 0.98| 50 / 0.98| 50 / 0.96| 50 / 0.95



3 Ton Two Stage

| 5/16″| 5/8″| 15 / 0.99| 25 / 0.99| 50 / 0.97| 50 / 0.95| 50 / 0.93| 50 / 0.91| N/A
3/8″| 5/8″| 15 / 0.99| 25 / 0.99| 50 / 0.97| 50 / 0.95| 50 / 0.93| 50 / 0.91| N/A
5/16″| 3/4″| 15 / 1.00| 25 / 0.99| 50 / 0.98| 50 / 0.98| 50 / 0.98| 50 / 0.97| 50 / 0.96
3/8″| 3/4″| 15 / 1.00| 25 / 0.99| 50 / 0.98| 50 / 0.98| 50 / 0.98| 50 / 0.97| 50 / 0.96
1/2″| 3/4″| 15 / 1.00| 25 / 0.99| 50 / 0.98| 50 / 0.98| 50 / 0.98| 50 / 0.97| 50 / 0.96


3.5 Ton Two Stage

| 3/8″| 3/4″| 15 / 1.00| 25 / 0.99| 50 / 0.98| 50 / 0.97| 50 / 0.97| 50 / 0.96| 50 / 0.96
1/2″| 3/4″| 15 / 1.00| 25 / 0.99| 50 / 0.98| 50 / 0.97| 50 / 0.97| 50 / 0.96| 50 / 0.96
3/8″| 7/8″| 15 / 1.00| 25 / 0.99| 15 / 1.00| 50 / 0.98| 50 / 0.98| 50 / 0.97| 50 / 0.97
1/2″| 7/8″| 15 / 1.00| 25 / 0.99| 15 / 1.00| 50 / 0.98| 50 / 0.98| 50 / 0.97| 50 / 0.97


4 Ton Two Stage

| 3/8″| 3/4″| 15 / 1.00| 25 / 0.99| 50 / 0.98| 50 / 0.97| 50 / 0.95| 50 / 0.94| 50 / 0.93
1/2″| 3/4″| 15 / 1.00| 25 / 0.99| 50 / 0.98| 50 / 0.97| 50 / 0.95| 50 / 0.94| 50 / 0.93
3/8″| 7/8″| 15 / 1.00| 25 / 0.99| 50 / 1.00| 50 / 0.97| 50 / 0.98| 50 / 0.98| 50 / 0.97
1/2″| 7/8″| 15 / 1.00| 25 / 0.99| 50 / 1.00| 50 / 0.97| 50 / 0.98| 50 / 0.98| 50 / 0.97


5 Ton Two Stage

| 3/8″| 3/4″| 15 / 0.99| 25 / 0.99| 50 / 0.97| 50 / 0.95| 50 / 0.93| 50 / 0.91| N/A
1/2″| 3/4″| 15 / 0.99| 25 / 0.99| 50 / 0.97| 50 / 0.95| 50 / 0.93| 50 / 0.91| N/A
3/8″| 7/8″| 15 / 1.00| 25 / 0.99| 40 / 0.99| 15 / 0.99| 50 / 0.98| 50 / 0.97| 50 / 0.96
1/2″| 7/8″| 15 / 1.00| 25 / 0.99| 50 / 1.00| 50 / 0.99| 50 / 0.98| 50 / 0.97| 50 / 0.96

NOTES:

  1. Do not exceed 200 ft linear line length.
  2. Do not exceed 100 ft vertical separation if outdoor unit is above indoor unit.
  3. Always use the smallest liquid line allowable to minimize refrigerant charge.
  4. Applications shaded in light gray indicate capacity multipliers between 0.90 and 0.96 which are not recommended, but are allowed.
  5. Applications shaded in dark gray are not recommended due to excessive liquid or suction pressure drop.

14.3 SEER2 HEAT PUMPS


UNIT SIZE

| ALLOWABLE LIQUID LINE SIZE MM [IN.]| ALLOWABLE SUCTION LINE SIZE MM [IN.]| EQUIVALENT LENGTH (METERS)
0- 4.5| 5- 7.5| 8- 15| 15.5- 23| 23.5- 30| 30.5- 38| 38.5- 46
MAXIMUM VERTICAL RISE (OUTDOOR UNIT BELOW INDOOR UNIT) *** / CAPACITY MULTIPLIER**
5.3 KW [1.5 Ton]

Single Stage

| 6.35 [1/4]| 15.88 [5/8]| 15 / 1.00| 25 / 1.00| 50 / 0.99| 60 / 0.97| 45 / 0.96| 10 / 0.95| N/A
7.94 [5/16]| 15.88 [5/8]| 15 / 1.00| 25 / 1.00| 50 / 0.99| 75 / 0.97| 90 / 0.96| 45 / 0.95| N/A
9.53 [3/8]| 15.88 [5/8]| 15 / 1.00| 25 / 1.00| 50 / 0.99| 75 / 0.97| 95 / 0.96| 80 / 0.95| N/A



5.3 KW [1.5 Ton] Two Stage

| 6.35 [1/4]| 12.7 [1/2]| 15 / 0.99| 25 / 0.99| 50 / 0.97| 50 / 0.96| 50 / 0.95| N/A| N/A
7.94 [5/16]| 12.7 [1/2]| 15 / 0.99| 25 / 0.99| 50 / 0.97| 50 / 0.96| 50 / 0.95| N/A| N/A
9.53 [3/8]| 12.7 [1/2]| 15 / 0.99| 25 / 0.99| 50 / 0.97| 50 / 0.96| 50 / 0.95| N/A| N/A
6.35 [1/4]| 15.88 [5/8]| 15 / 0.99| 25 / 0.99| 50 / 0.98| 50 / 0.97| 50 / 0.96| 50 / 0.95| 50 / 0.94
7.94 [5/16]| 15.88 [5/8]| 15 / 0.99| 25 / 0.99| 50 / 0.98| 50 / 0.97| 50 / 0.96| 50 / 0.95| 50 / 0.94
9.53 [3/8]| 15.88 [5/8]| 15 / 0.99| 25 / 0.99| 50 / 0.98| 50 / 0.97| 50 / 0.96| 50 / 0.95| 50 / 0.94
7.0 KW [2 Ton]

Two Stage

| 6.35 [1/4]| 15.88 [5/8]| 15 / 0.99| 25 / 0.99| 50 / 0.99| 31 / 0.97| 3 / 0.97| N/A| N/A
7.94 [5/16]| 15.88 [5/8]| 15 / 0.99| 25 / 0.99| 50 / 0.99| 50 / 0.97| 50 / 0.97| 50 / 0.96| 50 / 0.95
9.53 [3/8]| 15.88 [5/8]| 15 / 0.99| 25 / 0.99| 50 / 0.99| 50 / 0.97| 50 / 0.97| 50 / 0.96| 50 / 0.95



8.8 KW [2.5 Ton] Two Stage

| 6.35 [1/4]| 15.88 [5/8]| 15 / 0.99| 25 / 0.99| 50 / 0.97| 50 / 0.96| 46 / 0.95| 50 / 0.94| N/A
7.94 [5/16]| 15.88 [5/8]| 15 / 0.99| 25 / 0.99| 50 / 0.97| 50 / 0.96| 50 / 0.95| 50 / 0.94| N/A
9.53 [3/8]| 15.88 [5/8]| 15 / 0.99| 25 / 0.99| 50 / 0.97| 50 / 0.96| 50 / 0.95| 50 / 0.94| N/A
6.35 [1/4]| 19.05 [3/4]| 15 / 1.00| 25 / 0.99| 50 / 0.98| 50 / 0.98| 50 / 0.98| 50 / 0.96| 50 / 0.95
7.94 [5/16]| 19.05 [3/4]| 15 / 1.00| 25 / 0.99| 50 / 0.98| 50 / 0.98| 50 / 0.98| 50 / 0.96| 50 / 0.95
9.53 [3/8]| 19.05 [3/4]| 15 / 1.00| 25 / 0.99| 50 / 0.98| 50 / 0.98| 50 / 0.98| 50 / 0.96| 50 / 0.95



10.6 KW [3 Ton]

Two Stage

| 7.94 [5/16]| 15.88 [5/8]| 15 / 0.99| 25 / 0.99| 50 / 0.97| 50 / 0.95| 50 / 0.93| 50 / 0.91| N/A
9.53 [3/8]| 15.88 [5/8]| 15 / 0.99| 25 / 0.99| 50 / 0.97| 50 / 0.95| 50 / 0.93| 50 / 0.91| N/A
7.94 [5/16]| 19.05 [3/4]| 15 / 1.00| 25 / 0.99| 50 / 0.98| 50 / 0.98| 50 / 0.98| 50 / 0.97| 50 / 0.96
9.53 [3/8]| 19.05 [3/4]| 15 / 1.00| 25 / 0.99| 50 / 0.98| 50 / 0.98| 50 / 0.98| 50 / 0.97| 50 / 0.96
12.7 [1/2]| 19.05 [3/4]| 15 / 1.00| 25 / 0.99| 50 / 0.98| 50 / 0.98| 50 / 0.98| 50 / 0.97| 50 / 0.96


12.3 KW [3.5 Ton] Two Stage

| 9.53 [3/8]| 19.05 [3/4]| 15 / 1.00| 25 / 0.99| 50 / 0.98| 50 / 0.97| 50 / 0.97| 50 / 0.96| 50 / 0.96
12.7 [1/2]| 19.05 [3/4]| 15 / 1.00| 25 / 0.99| 50 / 0.98| 50 / 0.97| 50 / 0.97| 50 / 0.96| 50 / 0.96
9.53 [3/8]| 22.23 [7/8]| 15 / 1.00| 25 / 0.99| 15 / 1.00| 50 / 0.98| 50 / 0.98| 50 / 0.97| 50 / 0.97
12.7 [1/2]| 22.23 [7/8]| 15 / 1.00| 25 / 0.99| 15 / 1.00| 50 / 0.98| 50 / 0.98| 50 / 0.97| 50 / 0.97


14.1 KW [4 Ton]

Two Stage

| 9.53 [3/8]| 19.05 [3/4]| 15 / 1.00| 25 / 0.99| 50 / 0.98| 50 / 0.97| 50 / 0.95| 50 / 0.94| 50 / 0.93
12.7 [1/2]| 19.05 [3/4]| 15 / 1.00| 25 / 0.99| 50 / 0.98| 50 / 0.97| 50 / 0.95| 50 / 0.94| 50 / 0.93
9.53 [3/8]| 22.23 [7/8]| 15 / 1.00| 25 / 0.99| 50 / 1.00| 50 / 0.97| 50 / 0.98| 50 / 0.98| 50 / 0.97
12.7 [1/2]| 22.23 [7/8]| 15 / 1.00| 25 / 0.99| 50 / 1.00| 50 / 0.97| 50 / 0.98| 50 / 0.98| 50 / 0.97


17.6 KW [5 Ton]

Two Stage

| 9.53 [3/8]| 19.05 [3/4]| 15 / 0.99| 25 / 0.99| 50 / 0.97| 50 / 0.95| 50 / 0.93| 50 / 0.91| N/A
12.7 [1/2]| 19.05 [3/4]| 15 / 0.99| 25 / 0.99| 50 / 0.97| 50 / 0.95| 50 / 0.93| 50 / 0.91| N/A
9.53 [3/8]| 22.23 [7/8]| 15 / 1.00| 25 / 0.99| 40 / 0.99| 15 / 0.99| 50 / 0.98| 50 / 0.97| 50 / 0.96
12.7 [1/2]| 22.23 [7/8]| 15 / 1.00| 25 / 0.99| 50 / 1.00| 50 / 0.99| 50 / 0.98| 50 / 0.97| 50 / 0.96

NOTES

  1. Do not exceed 200 ft linear line length.
  2. Do not exceed 100 ft vertical separation if outdoor unit is above indoor unit.
  3. Always use the smallest liquid line allowable to minimize refrigerant charge.
  4. Applications shaded in light gray indicate capacity multipliers between 0.90 and 0.96 which are not recommended, but are allowed.
  5. Applications shaded in dark gray are not recommended due to excessive liquid or suction pressure drop.

Performance Data @ AHRI Standard Conditions – Cooling

DESIGNATED TESTED COMBINATION (DTC)


OUTDOOR UNIT

| ****

AIR HANDLER

| TOTAL CAPACITY BTU/H [kW]| NET SENSIBLE BTU/H [kW]| NET LATENT BTU/H [kW]| ****

SEER2

| ****

EER2

| ****

INDOOR CFM [L/S]

| 47 DEGREE HEATING CAPACITY BTU/H [KW]| 47

DEGREE COP

| 17 DEGREE HEATING CAPACITY BTU/H [KW]| 17

DEGREE COP

| REGION IV HSPF2
FOP1418S| FHRNTT2417SAZTNA| 17,100 [5.0]| 13,100 [3.8]| 4,000 [1.2]| 14.3| 9.0| 575 [271.4]| 17,100 [5.0]| 3.78| 11,100 [3.3]| 2.56| 7.5
FOP1418T| FHRNTT2417SAZTNA| 17,100 [5.0]| 13,100 [3.8]| 4,000 [1.2]| 14.3| 9.0| 550 [259.6]| 17,100 [5.0]| 3.58| 11,000 [3.2]| 2.52| 7.5
FOP1424T| FHRNTT2417SAZTNA| 22,800 [6.7]| 17,500 [5.1]| 5,300 [1.6]| 14.3| 9.0| 775 [365.8]| 22,800 [6.7]| 3.51| 14,600 [4.3]| 2.55| 7.5
FOP1430T| FHRNTT3617SAZTNA| 28,600 [8.4]| 21,900 [6.4]| 6,700 [2.0]| 14.3| 9.0| 950 [448.4]| 28,600 [8.4]| 3.56| 18,200 [5.3]| 2.57| 7.5
FOP1436T| FHRNTT3617SAZTNA| 34,200 [10.0]| 26,200 [7.7]| 8,000 [2.3]| 14.3| 9.0| 1,050 [495.5]| 34,200 [10.0]| 3.27| 23,600 [6.9]| 2.49| 7.5
FOP1442T| FHRNTT4821SAZTNA| 39,500 [11.6]| 30,300 [8.9]| 9,200 [2.7]| 14.3| 9.0| 1,275 [601.7]| 39,500 [11.6]| 3.69| 25,500 [7.5]| 2.67| 7.5
FOP1448T| FHRNTT4821SAZTNA| 45,500 [13.3]| 34,900 [10.2]| 10,600 [3.1]| 14.3| 9.0| 1,450 [684.3]| 45,500 [13.0]| 3.65| 27,500 [8.1]| 2.54| 7.5
FOP1460T| FHRNTT6024SAZTNA| 55,500 [16.3]| 42,600 [12.5]| 12,900 [3.8]| 14.3| 9.0| 1,800 [849.5]| 55,500 [16.3]| 2.66| 34,000 [10.0]| 2.56| 7.5

NOTE: This data includes DTC (Designated Test Combination) ratings and is for reference purposes only. A full listing of official ratings and system match-ups, along with downloadable certificates, will be accessible from the AHRI website: www.ahridirectory.org later this year.

WARRANTY

GENERAL TERMS OF LIMITED WARRANTY
Fujitsu General America, Inc. will furnish a replacement for any part of this product which fails in normal use and service within the applicable period stated, in accordance with the terms of the limited warranty.
For complete details of the Limited and Conditional Warranties, including applicable terms and conditions, contact your local contractor or the Manufacturer for a copy of the product warranty certificate.

Conditional Parts
(Registration Required ) ……………………………Ten (10) Years

Before proceeding with installation, refer to installation instructions packaged with each model, as well as complying with all Federal, State, Provincial, and Local codes, regulations, and practices.
“In keeping with its policy of continuous progress and product improvement, Fujitsu reserves the right to make changes without notice.”

PRINTED IN U.S.A. 4/23 QG FORM NO. PFJ-828 REV. 2

FOP14

  • Cooling Efficiencies up to: 14.3 SEER2/10.4 EER2
  • Heating Efficiency: 7.6 HSPF
  • Nominal Sizes: 1.5 to 5 Tons [5.3 to 17.6 kW] Cooling &
  • Heating Capacities: 17.1 kBTU to 55.5 kBTU

Manufactured for
Fujitsu General America, Inc.
Fairfield, NJ

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

FUJITSU User Manuals

Related Manuals