neptronic SM060FNC Actuator Buy or Repair at Radwell Instruction Manual

June 13, 2024
neptronic

neptronic SM060FNC Actuator Buy or Repair at Radwell

SM060FNC Actuator

Specification and Installation Instructions

Models

  • SM060FNC: 70 in.lb. (8 Nm) with fail safe, with FT6 cable

Features

  • 70 in.lb. [8 Nm] at rated voltage
  • 6 seconds torque independent
  • 2 330V ISO 9001 :2015 Certification

Technical Specification
Complies to standards:
UL 60730-1 & UL 60730-2-14, CSA E60730-1 & CSA E60730-2-17, Low Voltage Directive & Electromagnetic Compatibility Directive, Electrical Equipment (Safety) Regulations & Electromagnetic Compatibility Regulations

WARNING: Risk of mechanical failure. Do NOT press clutch when actuator is in operation.

Dimensions

  • A = 1.50 (38mm)
  • B = 3.64 (93mm)
  • C = 6.60(168mm)
  • D = 3.02 (77mm)

Product Usage Instructions

Mechanical Installation
Follow the provided dimensions to properly install the SM060FNC actuator.

Wiring
We strongly recommend that all products be wired to a separate grounded transformer and that the transformer shall service only these products. This precaution will prevent interference with, and/or possible damage to incompatible equipment.

The actuator can be wired using the following methods

  • Analog
  • PWM
  • 3-wire / Digital 2 positions
  • 4-wire / Digital 3-point floating

Auto-Stroke Adjustment
By default, the auto-stroke feature is disabled and can only be activated manually.

To initiate an auto-stroke process

  1. Press and release the push button while the unit is in the normal operating mode (status LED flashes slowly 1Hz).
  2. The actuator will travel in both directions to find its limit and position itself according to the demand.
  3. The LEDs will extinguish when the process is complete. The status LED will then continue flashing slowly (1Hz).

Configuration Instructions

  1. Set all the dip switches to OFF, then press and hold the push button (PB1) for 3 seconds. The red alarm LED will blink with one pulse, meaning that the first menu (Control State) is now accessible.
  2. Select the desired control mode by setting the associated dip switch to ON. In the absence of a selection, the control state menu shall remain unchanged.
  3. To leave the configuration menu and save any changes, press and hold the push button (PB1) for 3 seconds.
  4. To undo changes and reset the settings back to the factory default, press and hold the push button (PB1) for about 15 seconds.

Contact Neptronic for further assistance

Models

  • SM060FNC : 70 in.lb. (8 Nm) with fail safe, with FT6 cable

Features

  • Brushless DC-driven motor (impedance protected)
  • Contactless feedback positioner
  • Mounts easily on round shafts
  • Manual clutch
  • Maintenance-free
  • Position indicator
  • Auto-stroke
  • Cable
  • ½” (16mm) BW BXCON-1 conduit connector (optional)
  • Fail safe by Enerdrive System

Applications

  • Small dampers
  • Unit ventilators
  • 1/4 turn valves
  • VAV box control
  • Fan coils

Technical Specification

Description SM060FNC
Torque 70 in.lb. [8 Nm] at rated voltage
Running Time (for 90° Rotation) 6 seconds torque independent
Fail Safe (Enerdrive) Yes
Fail Safe Runtime (0° to 90°) 6 seconds
Capacitor Charge Time on / Power-up 100 seconds
Power Consumption 32.5VA peak, 15W (during operation), 2W (at rest)
Overload Protection Electronic throughout, 0° to 90° rotation
Power Supply 22 to 26 Vac
Transformer Requirements Class 2; min. 26VA
Cable 5-wire FT6 plenum cable (18AWG) with strain release (NP NEP617-2)
Electrical Connection 18 AWG [0.82mm2], 39.5” (1m) long
Impedance 100 ohms for 2-10Vdc (0.1mA)
Control Signals 2-10Vdc (default) or 4-20mA (DIP switch selectable) / 24VAC

floating
Feedback Signals| 2-10Vdc (default) or 4-20mA (DIP switch selectable)
Angle of Rotation| 0° to 90°, mechanically and electronically adjustable (default: 90° stroke)
Direction of Rotation| Reversible, CW: Clockwise, CCW: Counter Clockwise (default: CW)
Cycles| 100,000 full cycles, 1,500,000 repositions
Noise Produced| 45 dB(A)
Ingress Protection| IP54 equivalent to Nema type 3S
Operating Temperature| 0°F to +122°F [-18°C to +50°C]
Storage Temperature| -22°F to +122°F [-30°C to +50°C]
Relative Humidity| 5 to 95% non-condensing
Weight| 2.5 lb [1.1 kg]
Purpose and Action of Control| Type 1 operating control, electric actuator
Construction of Control| Independently mounted
Pollution Degree| 2
Impulse Voltage| 330V
Quality Management System| ISO 9001: 2015
Certification| Complies to standards: UL 60730-1 & UL 60730-2-14, CSA E60730-1 & CSA E60730-2-17
Complies to Low Voltage Directive & Electromagnetic Compatibility Directive
Complies to Electrical Equipment (Safety) Regulations & Electromagnetic Compatibility Regulations
WARNING: Risk of mechanical failure. Do NOT press clutch when actuator is in operation.

Dimensions

  • A = 1.50” (38mm)
  • B = 3.64” (93mm)
  • C = 6.60”(168mm)
  • D = 3.02” (77mm)

Mechanical Installation

  1. Manually close the damper blades and position the actuator to 0º or 90º.

  2. Slide the actuator onto the shaft.

  3. Tighten the nuts on the “U” bolt to the shaft with an 8mm wrench to a torque of 60 in.- lbs [6.7 Nm].

  4. Slide the mounting bracket under the actuator.
    Ensure free movement of the slot at the base of the actuator.
    Place the bracket pin at mid distance of the slot.

  5. Affix the bracket to the ductwork with #8 self-tapping screws.

Wiring
We strongly recommend that all products be wired to a separate grounded transformer and that transformer shall service only these products. This precaution will prevent interference with, and/or possible damage to incompatible equipment.neptronic-SM060FNC-Actuator-Buy-or-Repair-at-Radwell-
\(2\)

neptronic-SM060FNC-Actuator-Buy-or-Repair-at-Radwell-
\(4\)

Settings

DIP Switches

| Feature| OFF| ON

---|---|---|---
1| Rotation| CW | CCW
| Fail-safe return| at 0°
| at 90°
3| Control Input signal| Vdc | mA
4| Feedback| Vdc
| mA

Status LED

State Description
ON Auto-stroke
Flash Normal operation
Rapid flash During charging of capacitors

Alarm LED

State Description
**** Flash ****

**** Error or Configuration mode

    • = default
  • Normal Operation
  • The status LED will indicate the selected control mode:
Control State Number of Status LED Pulses
Analog 1
Digital ON/OFF or floating 2
PWM 5 seconds 3
PWM 25 seconds 4

Auto-Stroke Adjustment

  • As a default, the auto-stroke feature is disabled and can only be activated manually.
  • To initiate an auto-stroke process, press and release the push button while the unit is in the normal operating mode (status LED flashes slowly 1Hz). The status (green) LED will remain lit.
  • The actuator travels in both directions to find its limit and position itself according to the demand. The LEDs will extinguish when the process is complete. The status LED will then continue flashing slowly (1Hz).

Configuration Instructions

  1. Set all the dip switches to OFF, then press and hold the push button (PB1) for 3 seconds. The red alarm LED will blink with one pulse, meaning that the first menu (Control State) is now accessible.
  2. Select the desired control mode by setting the associated dip switch to ON. In the absence of a selection, the control state menu shall remain unchanged.

Menu| Number of Alarm LED Pulses| Dip Switch 1| Dip Switch 2| Dip Switch 3| Dip Switch 4
---|---|---|---|---|---
Control State| 1| Analog (Modulat- ing)*| Digital (On/Off or

floating)

| PWM (5 sec)| PWM (25 sec)
Zero Span| 2| 2-10Vdc*| 0-10Vdc| Minimum value| Maximum value

* Default factory settings

  1. To navigate through the configuration menus, press and release the push button (PB1).
    • Press again to access the second menu (Zero Span). There will be 2 pulses on the alarm LED.
    • Press again to go back to the first menu (Control State).
  2. To change the span range to something other than 2-10Vdc or 0-10Vdc, access the Zero Span menu and do the following
    • Input the desired minimum voltage to the white wire, then set dip switch 3 to ON.
    • Input the desired maximum voltage to the white wire, then set dip switch 4 to ON.
    • The maximum voltage must be at least 3V greater than the minimum voltage, and they must both lie within 0 to 10V.
  3. To leave the configuration menu and save any changes, press and hold the push button (PB1) for 3 seconds.
  4. To undo changes and reset the settings back to the factory default, press and hold the push button (PB1) for about 15 seconds.

List of Alarms

Number of Alarm LED

Pulses

| **Alarm| ****Issues| ****Solution
---|---|---|---
1| **
Power fail| The actuator is not receiving any power and is shutting off.| **** Ensure the actuator is properly connected the power supply source.


2

| ****

Auto-stroke

| The actuator auto-stroke is not at a minimum of 30°.| Press the push button (PB1) and ensure that the span is greater than 30°.


3

| ****

Over-torque

| The actuator over torque has exceeded the torque limit.| Ensure that the actuator is not trying to rotate with more than 25% of its nominal torque. Then, press the push button (PB1) to trigger an auto-stroke and clear the alarm.
**** 4| Hardware|

  1. **** The NVM is corrupt.
  2. There is no magnet installed.
  3. The GMR sensor failed.

|

  1. Visually inspect the NVM IC, remove any dust or debris from it, then perform a power cycle.
  2. Ensure that the magnet is installed at a proper distance not touching the PCB or is not too far from it. It is recommended to keep it 1-2mm away. Once confirmed, perform a power cycle.
  3. Visually inspect the TLI IC, remove any dust or debris from it, then perform a power cycle.

BX Connector Attachment Installation

  1. Remove the strain release NP NEP617-2 by turning it counterclockwise and slide it off the wires.
  2. Insert the conduit attachment and turn it clockwise until it has been properly tightened onto the actuator attachment.neptronic-SM060FNC-Actuator-Buy-or-Repair-at-Radwell- \(5\)

Recycling at end of life : please return this product to your Neptronic local distributor for recycling. If you need to find the nearest Neptronic authorized distributor, please consult www.neptronic.com.
neptronic.com | 514-333-1433 | contact@neptronic.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals