IMI-Hydronic 322231 TA-Smart BACnet User Manual
- June 4, 2024
- IMI Hydronic
Table of Contents
IMI-Hydronic 322231 TA-Smart BACnet User Manual
TA-Smart BACnet MS/TP
Protocol Implementation Conformance Statement – PICS
General Information
Date: 18/11/2021
Vendor Name: IMI Hydronic Engineering
Vendor ID: 926
Product Name: TA-Smart DN32 to 80
Product Model Number: 322231-XXXXX
Application Software Version: 1.0
BACnet Protocol Revision: 16
Product Description: Digitally configurable connected 2-way control valve
with integrated ultrasonic flow measurement
BACnet Standard Device Profile: BACnet Application Specific Controller
(B-ASC)
BACnet Interoperability Building Blocks (BIBBs) supported:
- Data Sharing – ReadProperty-B (DS-RP-B)
- Data Sharing – ReadPropertyMultiple-B (DS-RPM-B)
- Data Sharing – WriteProperty-B (DS-WP-B)
- Data Sharing – WritePropertyMultiple-B (DS-WPM-B)
- Device Management – DynamicDeviceBinding-B (DM-DDB-B)
- Device Management – DynamicObjectBinding-B (DM-DOB-B)
- Device Management – DeviceCommunicationControl-B (DM-DCC-B)†
- Device Management – TimeSynchronization (DM-TS-B)*
- Device Management – UTCTimeSynchronization (DM-UTC-B)*
Segmentation Capability: Configurable (Tx, Rx, Both, None)
Data Link Layer Options: MS/TP master
Baud rates: Auto, 9600, 19200, 38400, 56700, 76800, 115200
Device Address Binding: Supported
Networking Options: None
Character Sets Supported: ISO 10646 (UTF-8)
†) No password required
*) Valid range for years is 2000 – 2099
**) Default value
BACnet Object Description
Device object
Event Table
Object Processing
The properties Object name, Description and Location of the Device Object
support up to 32 characters (all other character strings are read-only).
The device does not support the CreateObject and DeleteObject service.
RS-485 Termination Resistance
The jumper placed beside the RS-485 A, B and M wire connectors must be closed
(set to ON) for activating the 120 Ohm RS-485 termination resistance.
The termination resistance must be activated if TA-Smart is at the end of a
daisy chain or if it is not part of a daisy chain.
Wiring Diagram
TA-Smart
Note:
- A, B and M terminals are NOT isolated from all other terminals.
- GND (M – 0V) is common to power supply, analog signals and RS 485.
- In case of AC power supply, L24 and M should be connected to the same phase for each TA-Smart.
- GND (0V) of RS 485 should be connected to 0 VAC/VDC on the controller side.
- GND (0V) of analog input/output should be connected to 0 VAC/VDC on the controller side.
We reserve the right to introduce technical alterations without prior
notice.
www.imi-hydronic.com
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>